Plan Review Details - Permit 18100170
Plan Review Stops For Permit 18100170
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-12-12 Cont ID  
Sent By jgomez Date 2018-12-12 Time 09:22 Rev Time 0.00
Received By jgomez Date 2018-12-10 Time 14:39 Sent To I
Notes
2018-12-11 14:39:39RESUB ROUTED TO JGOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-10-10 Cont ID  
Sent By jgomez Date 2018-10-10 Time 15:57 Rev Time 0.00
Received By jgomez Date 2018-10-03 Time 09:56 Sent To I
Notes
2018-10-05 09:56:52REVISION ROUTED TO JGOMEZ

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-12-12 Cont ID  
Sent By jgomez Date 2018-12-12 Time 09:21 Rev Time 0.00
Received By jgomez Date 2018-12-12 Time 09:08 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-10-10 Cont ID  
Sent By jgomez Date 2018-10-10 Time 15:56 Rev Time 0.00
Received By jgomez Date 2018-10-10 Time 15:56 Sent To  
Notes
2018-10-10 15:57:22RESIDENTIAL (R3) REVISION MECHANICAL REVIEW COMMENTS
 CODE: FBC 5TH EDITION (2014) AND CITY AMENDMENTS.
  
 1- THERE IS AN ENGINEER OF RECORD ON APPROVED
 MECHANICAL PLAN M-1. ENGINEER OF RECORD NEEDS TO SIGN
 AND SEAL REVISED MECHANICAL PLAN. NEED TO HAVE THE
 ORIGINAL SEAL AND SIGNATURE OF THE ENGINEER OF RECORD
 AS REQUIRED BY SEC. 61G15-23.003 FAC AND CHAPTER 471
 F.S. WHEN SUBMITTING PLANS/DOCUMENTS FOR PUBLIC
 RECORDS.
  
 2- THE REVISED TRANSFER DUCT IN THE MASTER BEDROOM
 DOESN'T COMPLY WITH THE BALANCED RETURN AIR SEC.
 M1602.4 FBC-RESIDENTIAL. NEED AT LEAST 13" DUCT.
 ORIGINAL APPROVED PLAN CALLED FOR 14" TRANSFER DUCT AND
 14"X14" RAG. REVISE AS REQUIRED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved