Plan Review Stops For Permit 18100167 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2019-02-12 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2019-02-12 |
Time |
11:57 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2019-02-12 |
Time |
11:57 |
Sent To |
|
|
Notes |
2019-02-12 11:59:29 | FINAL INSPECTION PASSED ON 02/04/19 BY TOM MOORE. HE | | RECEIVED THE DRAINAGE CERTIFICATE REQUESTED BY KEN | | CONRAD. JG. | | | | | | RECD DRAINAGE LETTER/FINAL TER |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2019-01-02 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2019-01-02 |
Time |
14:18 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2019-01-02 |
Time |
14:04 |
Sent To |
|
|
Notes |
2019-01-02 14:18:43 | RESIDENTIAL (R3) SECOND BUILDING REVIEW COMMENTS | | CODE: 5TH EDITION (2014) AND CITY AMENDMENTS. | | | | 1- KEN CONRAD (CHIEF BUILDING INSPECTOR) PERFORMED A | | MISCELLANEOUS INSPECTION FOR RETAINING WALL AND PAVER'S | | ON 09/12/18. IT LOOKS LIKE THERE ARE SOME PROBLEMS WITH | | WATER DRAINING INTO NEIGHBOR'S PROPERTY. THEREFORE, KEN | | CONRAD REQUESTED THE FOLLOWING "A DRAINAGE CERTIFICATE | | SHALL BE SUBMITTED AT FINAL". CONTRACTOR TO PROVIDE | | "DRAINAGE CERTIFICATE" AT FINAL INSPECTION AS REQUESTED | | BY KEN CONRAD. | | NOTE: COORDINATE WITH KEN CONRAD (CHIEF BUILDING | | INSPECTOR). | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2018-12-04 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2018-12-04 |
Time |
10:10 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2018-12-04 |
Time |
09:05 |
Sent To |
|
|
Notes |
2018-12-04 09:15:00 | RESIDENTIAL (R3) BUILDING REVIEW COMMENTS | | CODE: 5TH EDITION (2014) AND CITY AMENDMENTS. | | | | 1- KEN CONRAD (CHIEF BUILDING INSPECTOR) PERFORMED A | | MISCELLANEOUS INSPECTION FOR RETAINING WALL AND PAVER'S | | ON 09/12/18. IT LOOKS LIKE THERE ARE SOME PROBLEMS WITH | | WATER DRAINING INTO NEIGHBOR'S PROPERTY. THEREFORE, KEN | | CONRAD REQUESTED THE FOLLOWING "A DRAINAGE CERTIFICATE | | SHALL BE SUBMITED AT FINAL". CONTRACTOR SUBMITTED AN | | "ELEVATION CERTIFICATE" . THIS IS NOT WHAT KEN CONRAD | | REQUESTED. ELEVATION CERTIFICATES ARE ONLY REQUIRED FOR | | PROPERTIES LOCATED IN A SPECIAL FLOOD ZONE. THIS | | PROPERTY IS NO LOCATED IN A FLOOD ZONE. ELEVATION | | CERTIFICATE IS NOT REQUIRED AND WILL NOT BE REVIEWED. | | CONTRACTOR TO SUBMITT "DRAINAGE CERTIFICATE" AS | | REQUESTED BY KEN CONRAD SHOWING THAT THE DRAIN SURFACE | | WATER IS KEPT WITHIN THE LOT AND IS DIVERTED TO AN | | APPROVED POINT OF COLLECTION. SEC. R401.3 | | FBC-RESIDENTIAL. NOTE: COORDINATE WITH KEN CONRAD | | (CHIEF BUILDING INSPECTOR). | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE/VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD | | DRAWINGS/DOCUMENTS FOR REFERENCE. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2019-01-02 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2019-01-02 |
Time |
14:18 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2019-01-02 |
Time |
14:05 |
Sent To |
|
|
Notes |
2019-01-02 14:05:43 | MAX LOPEZ SUBMITTED DRAINAGE CERTIFICATE LETTER. JG |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2018-12-04 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2018-12-04 |
Time |
10:10 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2018-11-20 |
Time |
16:53 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2018-10-10 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2018-10-10 |
Time |
15:45 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2018-10-03 |
Time |
09:55 |
Sent To |
I |
|
Notes |
2018-10-05 09:55:35 | REVISION ROUTED TO JGOMEZ |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2018-12-04 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2018-12-04 |
Time |
09:05 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2018-12-03 |
Time |
16:27 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2018-10-10 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2018-10-10 |
Time |
15:44 |
Rev Time |
0.00 |
Received By |
jgomez |
Date |
2018-10-10 |
Time |
14:09 |
Sent To |
Z |
|
Notes |
2018-10-10 15:44:48 | RESIDENTIAL (R3) REVISION MECHANICAL REVIEW COMMENTS | | CODE: FBC 5TH EDITION (2014) AND CITY AMENDMENTS. | | | | 1- THERE IS AN ENGINEER OF RECORD ON APPROVED | | MECHANICAL PLAN M-1. ENGINEER OF RECORD NEEDS TO SIGN | | AND SEAL REVISED MECHANICAL PLAN. NEED TO HAVE THE | | ORIGINAL SEAL AND SIGNATURE OF THE ENGINEER OF RECORD | | AS REQUIRED BY SEC. 61G15-23.003 FAC AND CHAPTER 471 | | F.S. WHEN SUBMITTING PLANS/DOCUMENTS FOR PUBLIC | | RECORDS. | | | | 2- THE REVISED TRANSFER DUCT IN THE MASTER BEDROOM | | DOESN'T COMPLY WITH THE BALANCED RETURN AIR SEC. | | M1602.4 FBC-RESIDENTIAL. NEED AT LEAST 13" DUCT. | | ORIGINAL APPROVED PLAN CALLED FOR 14" TRANSFER DUCT AND | | 14"X14" RAG. REVISE AS REQUIRED. | | | | 3- CLARIFY LOCATION OF A/C COMPRESSOR. THERE IS A | | HANDWRITTEN NOTE STATING THAT COMPRESSOR "MOVED TO WEST | | SIDE". SHOW ACTUAL LOCATION OF COMPRESSOR. HANDWRITTEN | | NOTES ARE NOT ALLOWED. SEC. 107.2.1 CITY AMENDMENTS. | | NOTE: NEED ZONING APPROVAL FOR LOCATION OF A/C | | EQUIPMENT. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2018-11-30 |
|
|
Cont ID |
|
Sent By |
jgomez |
Date |
2018-12-04 |
Time |
10:10 |
Rev Time |
0.00 |
Received By |
mcruz |
Date |
2018-11-30 |
Time |
09:39 |
Sent To |
M |
|
Notes |
2018-11-30 09:39:46 | ZONING PASSED WITH PROVISO: A/C EQUIMENT SHALL BE AT | | LEAST 1' FROM WEST PROPERTY LINE. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2018-10-16 |
|
|
Cont ID |
|
Sent By |
mcruz |
Date |
2018-10-16 |
Time |
16:24 |
Rev Time |
0.00 |
Received By |
mcruz |
Date |
2018-10-16 |
Time |
16:08 |
Sent To |
PC |
|
Notes |
2018-10-16 16:24:05 | ZONING REVIEW FAILED, DUE TO THE FOLLOWING: | | | | 1) PROVIDE 2 COPIES OF THE PROPERTY SURVEY. | | 2) INDICATE THE SETBACK DIMENSION FROM THE A/C | | EQUIPMENT TO THE WEST PROPERTY LINE. | | | | FOR ADDITIONAL INFORMATION, THE ZONING AND LAND | | DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT | | WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH | | PLANNING DEPARTMENT WEBSITE AT | | WWW.CITYOFWPB.COM/PLAN/INDEX.HTM. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO | | CONTACT ME. | | | | MAGGIE CRUZ | | ASSOCIATE PLANNER | | PLANNING AND ZONING DEPARTMENT | | TEL: 561-822-1442 | | E-MAIL: [email protected] | 2018-10-10 15:54:09 | CHANGE OF A/C EQUIPMENT LOCATION. |
|
|