Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-10-11 Cont ID  
Sent By jgomez Date 2018-10-11 Time 17:50 Rev Time 0.00
Received By jgomez Date 2018-10-11 Time 17:49 Sent To  
Notes
2018-10-11 17:51:3110/11/18 RECEIVED REVISED RAS 117 CALCULATIONS FROM
 ENGINEER VIA E-MAIL. JG.
  
  
 10/11/18 APPROVED. NEED ENGINEER'S CALCULATIONS WITH
 ORIGINAL SEAL & SIGNATURE TO PRINT PERMIT. PERMIT
 PACKAGE UPRONT UNDER "P". JG.
  
 10/11/18 TALKED TO JOHN AVERKAMP (ENGINEER) RAS 117
 CALCS ARE OK. NEED ORIGINAL COPIES SIGNED AND SELAED AS
 REQ'D BY F. S. 471. JG.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-10-10 Cont ID  
Sent By jgomez Date 2018-10-10 Time 12:23 Rev Time 0.00
Received By jgomez Date 2018-10-10 Time 10:37 Sent To  
Notes
2018-10-10 12:23:00RESIDENTIAL (R3) RE-ROOF SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 ORIGINAL COMMENT:
 1- FLAT ROOF: ENGINEER TO REVISE RAS 117 CALCULATIONS
 SUBMITTED. ENGINEER IS ROUNDING UP THE FASTENER
 SPACING. ACCORDING TO SEC. 104.5 OF RAS 117 THE
 FASTENER SPACING SHALL BE ROUNDED DOWN TO THE NEXT
 WHOLE NUMBER NOT ROUNDED UP. REVISE FASTENER SPACING AS
 REQUIRED. NOTE: KEEP IN MIND THAT THE MINIMUM FASTENER
 SEPARATION SHALL NOT BE LESS THAN 4 INCHES O.C.. SEE
 SEC. 8.1 OF RAS 117.
  
 RESPONSE:
 ENGINEER TO REVISE RAS 117 CALCULATIONS.
 (1) NEED TO USE THE ACTUAL NET WIDTH OF THE ANCHOR
 SHEET AS SHOWN ON THE NOA SUBMITTED. IT LOOKS LIKE THE
 ENGINEER IS USING THE NET WIDTH SHOWN ON THE RAS 117
 CALCULATIONS SAMPLE NOT THE ACTUAL WIDTH OF NOA
 SUBMITTED.
 (2) ENGINEER SPECIFIES TWO ROWS OF FASTENERS IN A 6"
 SIDE LAP. TWO ROWS IN A 6" LAP DOESN'T SEEM TO COMPLY
 WITH THE MIN. 4"0.C. FASTENER SPACING REQUIRED BY SEC.
 8.1 OF RAS 117.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-10-04 Cont ID  
Sent By jgomez Date 2018-10-04 Time 16:26 Rev Time 0.00
Received By jgomez Date 2018-10-04 Time 15:42 Sent To  
Notes
2018-10-04 16:26:11RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- FLAT ROOF: ENGINEER TO REVISE RAS 117 CALCULATIONS
 SUBMITTED. ENGINEER IS ROUNDING UP THE FASTENER
 SPACING. ACCORDING TO SEC. 104.5 OF RAS 117 THE
 FASTENER SPACING SHALL BE ROUNDED DOWN TO THE NEXT
 WHOLE NUMBER NOT ROUNDED UP. REVISE FASTENER SPACING AS
 REQUIRED. NOTE: KEEP IN MIND THAT THE MINIMUM FASTENER
 SEPARATION SHALL NOT BE LESS THAN 4 INCHES O.C.. SEE
 SEC. 8.1 OF RAS 117.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-10-11 Cont ID  
Sent By jgomez Date 2018-10-11 Time 17:52 Rev Time 0.00
Received By jgomez Date 2018-10-11 Time 17:49 Sent To  
Notes
2018-10-11 17:50:46RECEIVED REVISED RAS 117 CALCULATIONS FROM ENGINEER VIA
 E-MAIL.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-10-10 Cont ID  
Sent By jgomez Date 2018-10-10 Time 12:23 Rev Time 0.00
Received By jgomez Date 2018-10-10 Time 10:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-10-04 Cont ID  
Sent By jgomez Date 2018-10-04 Time 16:43 Rev Time 0.00
Received By jgomez Date 2018-10-03 Time 15:08 Sent To I
Notes