Plan Review Details - Permit 18100096
Plan Review Stops For Permit 18100096
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2018-11-05 Cont ID  
Sent By jgomez Date 2018-11-05 Time 12:13 Rev Time 0.00
Received By jgomez Date 2018-11-05 Time 11:04 Sent To  
Notes
2018-11-05 11:06:04SHUTTERS SECOND BUILDING REVIEW CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 ORIGINAL COMMENT:
 FLORIDA PRODUCT APPROVAL FL17080-R2 IS NOT DESIGNED FOR
 STEEL FRAMED APPLICATION. NEED PRODUCT APPROVAL THAT IS
 DESIGNED FOR PROPOSED INSTALLATION. OR SITE SPECIFIC
 PROJECTS USING THIS PRODUCT APPROVAL SHALL BE SUBMITTED
 TO THE PRODUCT APPROVAL ENGINEER FOR REVIEW AS REQUIRED
 BY NOTE 12(D) ON SHEET 1 OF 13. IF USING THIS PRODUCT
 APPROVAL, THEN NEED THE APPROVAL OF THE PRODUCT
 APPROVAL ENGINEER OF RECORD. SEC. 107.2.1 CITY
 AMENDMENTS AND FAC 61G20-3.001.
  
 RESPONSE:
 A) TALKED TO BUILDING OFFICIAL. EVEN THOUGHT IT LOOKS
 LIKE THE NOTE IMPLIES TO SENT DRAWINGS TO THE P.E.D.
 ENGINEER. NO NEED TO SEND DRAWINGS TO PRODUCT APPROVAL
 ENGINEER OF RECORD. ENGINEER OF RECORD WILL BE THE
 ENGINEER PROVIDING THE SITE SPECIFIC INSTALLATION USING
 THIS PRODUCT APPROVAL.
  
 B) SITE SPECIFIC DRAWINGS NEED TO PROVIDE ALL THE SITE
 SPECIFIC INFORMATION, INCLUDING ALL THE INFORMATION
 SHOWN IN THE INSTALLATION SCHEDULE. NEED TO SPECIFY THE
 SPECIFIC SHUTTER MOUNTING CONDITION ("C4" IS NOT A
 MOUNTING CONDITION); SHUTTER GLASS SEPARATION; SHUTTER
 SPAN, EDGE DISTANCE, ANCHOR TYPE AND SPACING (TOP &
 BOTTOM). SEC. 107.2.1 CITY AMENDMENTS.
  
 NOTE: INFORMATION SHOWN ON THE INSTALLATION SCHEDULE
 AND THE SITE SPECIFIC DRAWINGS DON'T MATCH. CHECK
 OPENINGS SIZES, ANCHOR TYPE, ETC.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2018-10-23 Cont ID  
Sent By jgomez Date 2018-10-23 Time 16:13 Rev Time 0.00
Received By jgomez Date 2018-10-23 Time 16:13 Sent To  
Notes
2018-10-23 16:14:06SHUTTERS SECOND BUILDING REVIEW CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 ORIGINAL COMMENT:
 FLORIDA PRODUCT APPROVAL FL17080-R2 IS NOT DESIGNED FOR
 STEEL FRAMED APPLICATION. NEED PRODUCT APPROVAL THAT IS
 DESIGNED FOR PROPOSED INSTALLATION. OR SITE SPECIFIC
 PROJECTS USING THIS PRODUCT APPROVAL SHALL BE SUBMITTED
 TO THE PRODUCT APPROVAL ENGINEER FOR REVIEW AS REQUIRED
 BY NOTE 12(D) ON SHEET 1 OF 13. IF USING THIS PRODUCT
 APPROVAL, THEN NEED THE APPROVAL OF THE PRODUCT
 APPROVAL ENGINEER OF RECORD. SEC. 107.2.1 CITY
 AMENDMENTS AND FAC 61G20-3.001.
  
 RESPONSE:
 A) TALKED TO BUILDING OFFICIAL. EVEN THOUGHT IT LOOKS
 LIKE THE NOTE IMPLIES TO SENT DRAWINGS TO THE P.E.D.
 ENGINEER. NO NEED TO SEND DRAWINGS TO PRODUCT APPROVAL
 ENGINEER OF RECORD. ENGINEER OF RECORD WILL BE THE
 ENGINEER PROVIDING THE SITE SPECIFIC INSTALLATION USING
 THIS PRODUCT APPROVAL.
  
 B) SITE SPECIFIC DRAWINGS NEED TO PROVIDE ALL THE SITE
 SPECIFIC INFORMATION, INCLUDING ALL THE INFORMATION
 SHOWN IN THE INSTALLATION SCHEDULE. NEED TO SPECIFY THE
 SPECIFIC SHUTTER MOUNTING CONDITION ("C4" IS NOT A
 MOUNTING CONDITION); SHUTTER GLASS SEPARATION; SHUTTER
 SPAN, EDGE DISTANCE, ANCHOR TYPE AND SPACING (TOP &
 BOTTOM). SEC. 107.2.1 CITY AMENDMENTS.
  
 NOTE: INFORMATION SHOWN ON THE INSTALLATION SCHEDULE
 AND THE SITE SPECIFIC DRAWINGS DON'T MATCH. CHECK
 OPENINGS SIZES, ANCHOR TYPE, ETC.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-10-23 Cont ID  
Sent By jgomez Date 2018-10-23 Time 09:30 Rev Time 0.00
Received By jgomez Date 2018-10-23 Time 09:01 Sent To  
Notes
2018-10-23 10:03:28SHUTTERS SECOND BUILDING REVIEW CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 ORIGINAL COMMENT:
 1- THE SUBSTRATE FOR THE PROPOSED INSTALLATION IS STEEL
 FRAME. ACCORDING TO NOTE #8 ON SHEET 1 OF 13 OF
 ACCORDION SHUTTERS FLORIDA PRODUCT APPROVAL FL17080-R2
 SUBMITTED "THIS SHUTTER SHALL ONLY BE ATTACHED TO
 CONCRETE, BLOCK OR WOOD FRAME BUILDINGS." THEREFORE,
 THIS PRODUCT APPROVAL CAN NOT BE USED. PROVIDE PRODUCT
 APPROVAL THAT COVERS EXISTING SUBSTRATE ATTACHMENT.
 NOTE: REVISE SHUTTERS INSTALLATION SCHEDULE
 ACCORDINGLY.
 SEC. 107.2.1 CITY AMENDMENTS AND FAC 61G20-3.001
  
 RESPONSE:
 FLORIDA PRODUCT APPROVAL FL17080-R2 IS NOT DESIGNED FOR
 STEEL FRAMED APPLICATION. NEED PRODUCT APPROVAL THAT IS
 DESIGNED FOR PROPOSED INSTALLATION. OR SITE SPECIFIC
 PROJECTS USING THIS PRODUCT APPROVAL SHALL BE SUBMITTED
 TO THE PRODUCT APPROVAL ENGINEER FOR REVIEW AS REQUIRED
 BY NOTE 12(D) ON SHEET 1 OF 13. IF USING THIS PRODUCT
 APPROVAL, THEN NEED THE APPROVAL OF THE PRODUCT
 APPROVAL ENGINEER OF RECORD.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-10-04 Cont ID  
Sent By jgomez Date 2018-10-04 Time 13:54 Rev Time 0.00
Received By jgomez Date 2018-10-04 Time 13:38 Sent To  
Notes
2018-10-04 14:02:36SHUTTERS BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- THE SUBSTRATE FOR THE PROPOSED INSTALLATION IS STEEL
 FRAME. ACCORDING TO NOTE #8 ON SHEET 1 OF 13 OF
 ACCORDION SHUTTERS FLORIDA PRODUCT APPROVAL FL17080-R2
 SUBMITTED "THIS SHUTTER SHALL ONLY BE ATTACHED TO
 CONCRETE, BLOCK OR WOOD FRAME BUILDINGS." THEREFORE,
 THIS PRODUCT APPROVAL CAN NOT BE USED. PROVIDE PRODUCT
 APPROVAL THAT COVERS EXISTING SUBSTRATE ATTACHMENT.
 NOTE: REVISE SHUTTERS INSTALLATION SCHEDULE
 ACCORDINGLY.
 SEC. 107.2.1 CITY AMENDMENTS AND FAC 61G20-3.001
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2018-11-05 Cont ID  
Sent By jgomez Date 2018-11-05 Time 12:13 Rev Time 0.00
Received By jgomez Date 2018-10-31 Time 15:31 Sent To I
Notes
2018-11-01 15:31:33RESUB ROUTED TO JGOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-10-23 Cont ID  
Sent By jgomez Date 2018-10-23 Time 16:37 Rev Time 0.00
Received By jgomez Date 2018-10-23 Time 16:12 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-10-23 Cont ID  
Sent By jgomez Date 2018-10-23 Time 10:03 Rev Time 0.00
Received By jgomez Date 2018-10-17 Time 15:38 Sent To I
Notes
2018-10-18 15:38:41RESUB ROUTED TO JGOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-10-04 Cont ID  
Sent By jgomez Date 2018-10-04 Time 14:05 Rev Time 0.00
Received By jgomez Date 2018-10-02 Time 15:27 Sent To I
Notes
2018-10-03 15:28:02BLDG <5K