Plan Review Details - Permit 18100063
Plan Review Stops For Permit 18100063
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-12-18 Cont ID  
Sent By jduprey Date 2018-12-18 Time 15:08 Rev Time 0.00
Received By jduprey Date 2018-12-14 Time 09:17 Sent To  
Notes
2018-12-18 15:03:54*PROVISO*
  
 1.PRIOR TO INSTALLATION, SUBMIT PRODUCT APPROVALS
 REVIEWED BY DESIGNER OF RECORD, FOR REVIEW:
 A. METAL ROOF (WITH ROOF PERMIT APPLICATION)
 D. LAP SIDING & SHINGLE SIDING
 2. PRE-ENGINEERED WOOD TRUSS ENGINEERING TO BE PROVIDED
 AT INSPECTION
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-11-07 Cont ID  
Sent By dbattles Date 2018-11-07 Time 14:10 Rev Time 0.00
Received By dbattles Date 2018-11-07 Time 08:49 Sent To  
Notes
2018-11-07 14:12:13****CORRECTIONS****
 W.P.B. PERMIT: 18100063
 REVIEWED: NOVEMBER 7, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC A = FBC ACCESSIBILITY
 FBC ENERGY = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. [FBC 107.3.5.3]PROVIDE SEDIMENT CONTROL PLAN TO KEEP
 CONSTRUCTION DEBRIS FROM ENTERING ADJACENT PROPERTIES
 AND STORM DRAINS DURING CONSTRUCTION. YOU CAN FIND
 ENGINEERING STANDARD DETAILS FROM WPB WEBSITE-POLLUTION
 CONTROL
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
 -ADD DETAIL OF SILT FENCE AND WHERE TO INSTALL IT.
  
 2. [FBC R403.1.7.3] FOUNDATION ELEVATION.
 ON GRADED SITES, THE TOP OF ANY EXTERIOR FOUNDATION
 SHALL EXTEND ABOVE THE ELEVATION OF THE STREET GUTTER
 AT POINT OF DISCHARGE OR THE INLET OF AN APPROVED
 DRAINAGE DEVICE A MINIMUM OF 12 INCHES (305 MM) PLUS 2
 PERCENT. ALTERNATE ELEVATIONS ARE PERMITTED SUBJECT TO
 THE APPROVAL OF THE BUILDING OFFICIAL, PROVIDED IT CAN
 BE DEMONSTRATED THAT REQUIRED DRAINAGE TO THE POINT OF
 DISCHARGE AND AWAY FROM THE STRUCTURE IS PROVIDED AT
 ALL LOCATIONS ON THE SITE.
 -PROVIDE DRAINAGE PLAN OR ADD DRAINAGE DETAILS TO SITE
 PLAN. SHOW ELEVATION CANGES AND HOW WATER IS MAINTAINED
 ON SITE AND DEPOSITED TO STREET DRAIN.
  
 3. [FBC 107.2.5]PROVIDE SURVEY OF PROPERTY SHOWING
 EASEMENTS.
 [FL. STATUTE 472]SURVEY TO BE SIGNED AND SEALED BY THE
 SURVEYOR OF RECORD.
  
 4. [FBC R807] THE ROUGH-FRAMED OPENING SHALL BE NOT
 LESS THAN 22 INCHES
 BY 30 INCHES (559 MM BY 762 MM) AND SHALL BE LOCATED IN
 A
 HALLWAY OR OTHER READILY ACCESSIBLE LOCATION. WHERE
 LOCATED IN
 A WALL, THE OPENING SHALL BE NOT LESS THAN 22 INCHES
 WIDE BY
 30 INCHES HIGH (559 MM WIDE BY 762 MM HIGH). WHERE THE
 ACCESS IS LOCATED IN A CEILING, MINIMUM UNOBSTRUCTED
 HEADROOM
 IN THE ATTIC SPACE SHALL BE 30 INCHES (762 MM) AT SOME
 POINT ABOVE THE ACCESS MEASURED VERTICALLY FROM THE
 BOTTOM
 OF CEILING FRAMING MEMBERS.
  
 5. [FBC AMENDED 107.3.4.1]PROVIDE PRODUCT APPROVAL,
 ATTACHMENT AND INSTALLATION INSTRUCTIONS FOR HARDIE
 BOARD OVER MASONRY.
 THERE IS NO DIRECT ATTACHMENT OF HARDIE SIDING TO
 MASONRY, SO PLEASE PROVIDE DETAIL OF
 FURRING/ATTACHMENT, BARRIER AND SIDING ATTACHMENT.
  
 6. [FBC AMENDED 107.3.4.1]PROVIDE PRODUCT APPROVALS FOR
 ROOFING, OR INDICATE THAT YOU WOULD LIKE THEM DEFERED.
  
 7. [FBC AMENDED 107.3.4.1]SUBMIT TRUSS SHOP DRAWINGS TO
 THE BUILDING INSPECTOR PRIOR TO INSTALLATION.(THIS WILL
 BE A PROVISO)
  
 8. [FBC ENERGY R401.3]PROVIDE ENERGY PERFORMANCE LEVEL
 (EPL)DISPLAY CARD WITH THE ENEGRY CALCULATIONS TO SHOW
 ESTIMATED ENERGY PERFORMANCE LEVEL. THIS CARD IS TO BE
 AVAILABLE FOR INSPECTOR TO REVIEW FOR BUILDING FINAL.
 ALSO, INCLUDE CHECKLISTS WITH ENERGY CALCULATIONS.
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-12-23 Cont ID  
Sent By jpearson Date 2018-12-23 Time 10:58 Rev Time 0.00
Received By jpearson Date 2018-12-23 Time 10:58 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-10-16 Cont ID  
Sent By jpearson Date 2018-10-16 Time 14:59 Rev Time 0.00
Received By jpearson Date 2018-10-16 Time 10:40 Sent To  
Notes
2018-10-16 14:59:37CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. AFCI PROTECTION SHOWN IN NOT CODE COMPLIANT. ALL
 BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15-
 AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND
 POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH
 AFCI AND GFCI PROTECTION. PROVIDE CORRECTION TO AFCI
 NOTE. NEC 210.8, 210.12; FBC RE E3902
 2. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10; FBC RE E3606.3
 3. PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANEL.
 NEC 110.3, 110.9; FBC RE E3603.3
 4. PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE.
 CURRENT NOTE NEEDS TO BE CORRECTED. FBC EC C405.1,
 R404.1
 5. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10
 6. KEYNOTE 8 STATES THAT A PULL CHAIN FIXTURE SHALL BE
 INSTALLED IN CLOSET. IT APPEARS THAT THE CLEARANCE
 BETWEEN THE LIGHT FIXTURE AND THE CLOSET STORAGE SPACE
 IS NOT CODE COMPLIANT. PROVIDE CLARIFICATION AND/OR
 CORRECTION. NEC 410.16; FBC RE E4003.12
 7. A GFCI PROTECTED RECEPTACLE OUTLET ON A 20 AMP
 CIRCUIT IS REQUIRED WITHIN 3 FEET OF EACH BASIN.
 PROVIDE CORRECTION FOR MASTER BATH. NEC 210.11(C)(3),
 210.52(D); FBC RE E3703.4, E3901.6
 8. PANEL SCHEDULE SHOWS THE BATHROOM RECEPTACLE CIRCUIT
 ON 14 GAUGE WIRE AND A 15 AMP BREAKER. PROVIDE
 CORRECTION. NEC 210.11(C)(3), 210.52(D); FBC RE
 E3703.4, E3901.6
 9. PLAN SHOWS BATHROOM LIGHTING AND RECEPTACLES ON THE
 SAME CIRCUIT FEEDING 2 BATHROOM, WHICH IS A CODE
 VIOLATION. PROVIDE CORRECTION. NEC 210.11(C)(3),
 210.52(D); FBC RE E3703.4, E3901.6
 10. ELECTRICAL NOTE 8 STATES ONLY 20 AMP RECEPTACLES
 ARE TO BE TAMPER RESISTANT, AND THIS CONFLICTS WITH
 OTHER NOTE THAT STATES ALL PER CODE SHALL BE TR.
 CORRECT DISCREPANCY. NEC 406.12; FBC RE E4002.14
 11. SMOKE ALARMS MUST BE INSTALLED AT LEAST 3 FEET FROM
 BATHROOM DOOR, 3 FEET FROM CEILING FANS, AND 3 FEET
 FROM ANY MECHANICAL DUCT. PROVIDE CORRECTIONS. FBC RE
 R314.3(4), NFPA 72:29.8.3.4
 12. PROVIDE CARBON MONOXIDE ALARMS WITHIN 10 FEET OF
 EACH ROOM USED FOR SLEEPING PURPOSES. FBC RE R315.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2018-11-01 Cont ID  
Sent By gjohnson Date 2018-11-01 Time 09:33 Rev Time 0.00
Received By gjohnson Date 2018-11-01 Time 09:33 Sent To  
Notes
2018-11-01 09:34:44GAS PLAN REVIEW
 A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE
 REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK.
 PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT
 SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE
 SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1.
  
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL
 GAS SEC. 301.3.
  
 A SEPARATE PERMIT AND PLANS IS REQUIRED FOR THE GAS
 INSTALLATION OR MODIFICATION OF SYSTEM.
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 GAS PERMIT APPLICATION REQUIREMENTS
  
 EFFECTIVE IMMEDIATELY THE FOLLOWING INFORMATION SHALL
 BE SHOWN ON ALL GAS DRAWINGS SUBMITTED FOR PERMITTING
 IN THE CITY OF WEST PALM BEACH:
  
 1. SUBMIT TWO COPIES OF AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS THE LENGTH OF ALL CUT SECTIONS OF PIPE
 PER 2017 FBC-FUEL GAS, SECS. 402.4.1, 402.4.2. OR 2017
 FBC-R SEC. G2413.4.1, G2413.4.2.
  
 2. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING
  
 (IF APPLICABLE) FOR EACH PIPE SIZE. WPB AMENDMENTS TO
 FBC SEC.107.2.1.
  
 3. TYPE OF GAS (LP OR NATURAL).WPB AMEND. TO FBC SEC.
 107.2.1.
  
 4. LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE 2017 FBC-FUEL GAS
 SECS.401.8, 402.2, AND TABLES 402.4 (1) THRU 402.4 (37)
 OR 2017 FBC-RES. SEC. G2413.3, G2413.4 AND TABLES
 G2413.4 (1 ) THROUGH G2413.4 (21).
  
 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND / OR SYSTEM PER THE 2017
 FBC-FUEL GAS SEC.402.4.1, 402.4.2, OR 2017 FBC-RES.
 SEC. G 2413.4.1, G2413.4.2.
  
  
 7. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2017 FBC-FUEL GAS SEC.402.1, 402.4.3
 THRU 402.6 OR 2017 FBC RES. SEC. G2413.2, G2413.4.3.
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2018-11-20 Cont ID  
Sent By fmittner Date 2018-11-20 Time 16:20 Rev Time 0.00
Received By fmittner Date 2018-11-20 Time 16:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-01-10 Cont ID  
Sent By cpuell Date 2019-01-10 Time 12:54 Rev Time 0.00
Received By cpuell Date 2019-01-08 Time 14:48 Sent To  
Notes
2019-01-08 14:48:28IMPACT FEES ROUTED TO JDUPREY

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-01-03 Cont ID  
Sent By cpuell Date 2019-01-03 Time 16:46 Rev Time 0.00
Received By cpuell Date 2018-12-10 Time 15:08 Sent To  
Notes
2018-12-11 15:08:55R15

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-12-08 Cont ID  
Sent By shill Date 2018-12-08 Time 09:43 Rev Time 0.00
Received By shill Date 2018-10-02 Time 15:19 Sent To  
Notes
2018-10-11 16:26:48R19
2018-10-03 15:19:18LIBRARY

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2019-01-09 Cont ID  
Sent By jduprey Date 2019-01-09 Time 10:22 Rev Time 0.00
Received By jduprey Date 2019-01-09 Time 10:22 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-11-07 Cont ID  
Sent By dbattles Date 2018-11-07 Time 08:49 Rev Time 0.00
Received By dbattles Date 2018-11-07 Time 08:49 Sent To  
Notes
2018-11-07 08:50:24[FBC AMENDED 109]PLANS REQUIRE REVIEW BY THE PBC IMPACT
 FEE OFFICE. CALL (561) 233-5025. UPON APPROVAL, YOU MAY
 CHECK OUT ONE PLAN SET AND TAKE TO THAT OFFICE FOR
 REVIEW. PLEASE RETURNED STAMPED AND WITH A COPY OF THE
 RECEIPT AS APPLICABLE. PLEASE PROVIDE THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO THE PBC IMPACT FEE
 OFFICE. THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGO
 V.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONN
 AIRE.PDF

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-10-27 Cont ID  
Sent By cmontell Date 2018-10-27 Time 05:32 Rev Time 0.00
Received By cmontell Date 2018-10-27 Time 05:31 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-11-01 Cont ID  
Sent By gjohnson Date 2018-11-01 Time 09:32 Rev Time 0.00
Received By gjohnson Date 2018-10-31 Time 17:32 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status N Date 2018-12-18 Cont ID  
Sent By shill Date 2018-12-18 Time 13:52 Rev Time 0.00
Received By shill Date 2018-12-18 Time 13:52 Sent To  
Notes
2018-12-18 13:53:00PROVISO: PRODUCT APPROVALS REVIEWED BY DESIGNER OF
 RECORD ARE TO BE SUBMITTED WITH ROOF PERMIT APPLICATION
 PRIOR TO INSTALLATION
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2018-11-07 Cont ID  
Sent By dbattles Date 2018-11-07 Time 14:12 Rev Time 0.00
Received By dbattles Date 2018-11-07 Time 14:12 Sent To  
Notes
2018-11-07 14:13:33SEE BLDG. COMMENT #6

Review Stop Z ZONING
Rev No 2 Status P Date 2019-01-02 Cont ID  
Sent By fmittner Date 2019-01-02 Time 13:04 Rev Time 0.00
Received By fmittner Date 2019-01-02 Time 13:04 Sent To  
Notes
2019-01-02 13:04:32REQUIRES SEPARATE LANDSCAPE AND DRIVEWAY PERMIT.

Review Stop Z ZONING
Rev No 1 Status P Date 2018-11-20 Cont ID  
Sent By fmittner Date 2018-11-20 Time 16:20 Rev Time 0.00
Received By fmittner Date 2018-11-20 Time 16:20 Sent To  
Notes
***NONE***