Plan Review Details - Permit 18100052
Plan Review Stops For Permit 18100052
Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2019-01-16 Time   Rev Time 0.00
Received By lmarchan Date 2019-01-10 Time 12:32 Sent To  
Notes
2019-01-11 12:33:06RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2018-12-19 Time   Rev Time 0.00
Received By lmarchan Date 2018-12-14 Time 14:30 Sent To  
Notes
2018-12-17 14:30:14RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2018-10-11 Time   Rev Time 0.00
Received By lmarchan Date 2018-10-01 Time 15:24 Sent To  
Notes
2018-10-03 15:24:13REVISION ROUTED TO CCOLE

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2019-01-16 Cont ID  
Sent By ccole Date 2019-01-16 Time 11:20 Rev Time 0.00
Received By ccole Date 2019-01-16 Time 11:20 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-12-19 Cont ID  
Sent By ccole Date 2018-12-19 Time 13:04 Rev Time 0.00
Received By ccole Date 2018-12-19 Time 13:04 Sent To I
Notes
2018-12-19 13:08:062ND REVIEW FBC-2017 MECHANICAL
 REVISION #18100052
 12/18/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) 2ND REQUEST FOR THE ARCHITECT OF RECORD TO PROVIDE
 HIS ORIGINAL SIGNATURE AND SEAL TO THE REVISED M-2 PLAN
 SHEET. THE SUBMITTED REVISED SHEET IS A REDUCED COPY
 THAT HAS PRINT IN MANY PLACES THAT IS TOO SMALL TO READ
 OR FOR SCANNING. PLEAE PROVIDE A FULL-SIZED PLAN SHEET.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-10-11 Cont ID  
Sent By ccole Date 2018-10-11 Time 13:12 Rev Time 0.00
Received By ccole Date 2018-10-11 Time 13:12 Sent To I
Notes
2018-10-11 13:19:231ST REVIEW FBC-2017 MECHANICAL
 REVISION #18100052
 10/12/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE SUBMITTED MARKED UP PLAN IS NOT ACCEPTABLE PER
 SECTION 107.2.1 WPB. THE ARCHITECT OF RECORD SHALL
 PROVIDE A SIGNED AND SEALED REVISED PLAN SHEET WITH
 CLOUDS AND SYMBOLS TO INDICATE ALL CHANGES MADE TO THE
 APPROVED MECHANICAL PLAN- SEE SECTION 61G1-16.0003 FAC.
  
 2) PLEASE NOTE THAT MISSING FROM THE MARKED UP PLAN
 SHEET ARE THE DUCT SMOKE DETECTORS AND MOTORIZED
 DAMPERS FOR O/A INTAKE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  