2018-10-16 12:51:02 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. PER THE WPB AMENDMENTS TO THE FBC, PLAN (EACH SHEET |
| OF BOTH COPIES) IS REQUIRED TO BEAR THE NAME AND BE |
| SIGNED AND SEALED(WHERE APPLICABLE) BY THE PERSON |
| RESPONSIBLE FOR THE DESIGN. PROVIDE CORRECTION. WPB FBC |
| 107.1, 107.2; FS 471, 481 |
| 2. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS |
| LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND |
| VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS |
| IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. FBC 109.3 |
| 3. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT, |
| SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN |
| KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, |
| PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS, |
| RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND |
| SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. THIS |
| INCLUDES LIGHTING AND POWER OUTLETS AND RECEPTACLES. |
| SOME AREAS REQUIRE BOTH AFCI AND GFCI PROTECTION. |
| PROVIDE CORRECTION. NEC 210.8, 210.12; FBC RE E3902; |
| FBC EX 607.1.1 OR 801.1, 801.2, OR 901.2 AS APPLICABLE. |
| 4. PERMIT APPLICATION MENTIONS MOVING THE ELECTRICAL |
| PANEL FROM OUTSIDE TO INSIDE. PROVIDE RISER DIAGRAM OF |
| EXISTING AND PROPOSED SERVICE TO DETERMINE CODE |
| COMPLIANCE. FOR RISER DIAGRAM, SHOW ALL DETAILS OF |
| SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, |
| WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY |
| SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW |
| INTERSYSTEM BONDING TERMINATION POINT. BE ADVISED THAT |
| CONDUCTORS THAT ARE NOT PROTECTED BY A MAIN BREAKER OR |
| DISCONNECT ARE NOT PERMITTED TO RUN THROUGH THE HOUSE |
| UNPROTECTED. NEC 230.70, 250.6, 215.5, 230, 250.50, |
| 250.94, 408.30; FBC RE E3601.6, E3706.1, E3608.1, |
| E3609.3; WPB FBC 107.2.1 |
| 5. IF SERVICE IS BEING REPLACED TO ACCOMPLISH THIS, |
| PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH |
| PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| ALSO PROVIDE AIC RATING OF NEW PANEL. NEC 110.9, |
| 110.10; FBC RE E3606.3 |
| 6. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC |
| 210.8(D); FBC RE E3902.10 |
| 7. PROVIDE GFCI PROTECTION FOR RECEPTACLE OULTETS IN |
| BATHROOMS. NEC 210.11(C)(3), 210.52(D); FBC RE E3703.4, |
| E3901.6 |
| 8. LIGHTING IN BATHTUB OR SHOWER AREAS SHALL BE |
| SUITABLE FOR DAMP LOCATIONS. PROVIDE CORRECTION. NEC |
| 410.10(D); FBC RE E4003.11 |
| 9. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A |
| NOTE WILL SUFFICE. NEC 406.12; FBC RE E4002.14 |
| 10. PROVIDE GFCI PROTECTED OUTLET ON THE KITCHEN |
| ISLAND. NEC 210.8, 210.52(C)(3); FBC RE E3901.4.3 |
| 11. LIGHT FIXTURE SHOWN IN CLOSET DOES NOT APPEAR TO |
| HAVE THE PROPER CLEARANCE FROM THE CLOSET STORAGE |
| SPACE. PROVIDE CLARIFICATION AND/OR CORRECTION. NEC |
| 410.16; FBC RE E4003.12 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| SHEETS. |
| |
| SINCERELY, |
| |
| JOHN PEARSON |
| ELECTRICAL PLANS EXAMINER |
| 561-805-6746 |