Plan Review Details - Permit 18091312
Plan Review Stops For Permit 18091312 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2018-12-04 |
|
|
Cont ID |
|
Sent By |
dbattles |
Date |
2018-12-04 |
Time |
10:36 |
Rev Time |
0.00 |
Received By |
dbattles |
Date |
2018-12-04 |
Time |
10:36 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2018-11-15 |
|
|
Cont ID |
|
Sent By |
dbattles |
Date |
2018-11-15 |
Time |
08:06 |
Rev Time |
0.00 |
Received By |
dbattles |
Date |
2018-11-14 |
Time |
13:13 |
Sent To |
|
|
Notes |
2018-11-15 08:07:37 | ****CORRECTIONS**** | | W.P.B. PERMIT: 18091312 | | REVIEWED: NOVEMBER 14, 2018 | | | | DYLAN BATTLES | | BUILDING PLANS EXAMINER I | | [email protected] | | 561-805-6718 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC ENERGY = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | CURRENT CODES: | | ADOPTED DECEMBER 31, 2017 | | FLORIDA BUILDING CODE(FBC), 6TH EDITION (2017) | | | | 1. [FBC 107.3.5]UPDATE SHEETS LS-101 AND LS102 FOR | | CURRENT DODE EDITIONS. | | | | 2. [FBC 107.3.5]THIS SHOULD BE A LEVEL 3 ALTERARTION | | SINCE IT AFFECTS MORE THAN 50% OF THE BUILDING. | | PLEASE UPDATE LS-101 AND LS102 TO STATE LEVEL 3 | | ALTERATION. | | | | 3. [FBC TABLE 1004.1.2]SHEETS LS-101 AND LS102 SHOW | | FIRST FLOOR OCCUPANT LOAD FOR MERCANTILE AT 30 SQ. FT. | | PER. | | MERCANTILE WOULD BE CALCULATED AT 60 SQ. FT. PER PERSON | | LIKE SHOWN FOR SECOND FLOOR. | | PLEASE REVISE OCCUPANT COUNT TO REFLECT MERCANTILE PER | | TABLE 1004.1.2. | | | | 4. [FBC 1015.7]ROOF ACCESS. GUARDS SHALL BE PROVIDED | | WHERE THE ROOF | | HATCH OPENING IS LOCATED WITHIN 10 FEET (3048 MM) OF A | | ROOF | | EDGE OR OPEN SIDE OF A WALKING SURFACE AND SUCH EDGE OR | | OPEN | | SIDE IS LOCATED MORE THAN 30 INCHES (762 MM) ABOVE THE | | FLOOR, | | ROOF OR GRADE BELOW. THE GUARD SHALL BE CONSTRUCTED SO | | AS TO | | PREVENT THE PASSAGE OF A SPHERE 21 INCHES (533 MM) IN | | DIAMETER. | | VERIFY THAT PARAPET PROVIDES EDGE PROTECTION OR ADD | | RAIL TO MEET FBC 1015. | | -PROVIDE PRODUCT APPROVAL FOR NEW ROOF HATCH. | | | | 5. [FBC 1510.10]MECHANICAL UNITS. ROOF MOUNTED | | MECHANICAL UNITS | | SHALL BE MOUNTED ON CURBS RAISED A MINIMUM OF 8 INCHES | | (203 | | MM) ABOVE THE ROOF SURFACE. | | PROVIDE DETAIL OF NEW HVAC EQUIPMENT CURBS. STRUCTURAL | | SHEET S-201 SAYS SEE MECHANICAL AND MECHANICAL M-103 | | SAYS SEE STRUCTURAL FOR ATTACHMENT. | | | | 6. [FBC 107.3.5]SHEET A-801 AND SHEET A-810 ARE | | REVERSED. | | | | NOTE: | | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW | | EACH COMMENT IS BEING ADDRESSED. | | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW | | OF MATERIALS REQUESTED. | | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS | | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) | | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT | | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER | | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" | | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS | | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE | | NEED "VOID", RENDERING THEM NOT USABLE. | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
P |
Date |
2019-01-09 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2019-01-09 |
Time |
16:53 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2019-01-09 |
Time |
16:53 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
F |
Date |
2018-12-21 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2018-12-21 |
Time |
13:06 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2018-12-21 |
Time |
09:57 |
Sent To |
|
|
Notes |
2018-12-21 13:06:39 | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | 6TH ED, CHAPTER 1. | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED | | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS | | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY | | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW | | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. | | | | 1. CORRECTED. | | 2. CORRECTED. | | 3. CORRECTED. | | 4. CORRECTED. | | 5. CORRECTED. | | 6. CORRECTED. | | 7. CORRECTED. | | 8. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE | | EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE | | IS ADEQUATE. NEC 215.2, 220, 408.30 (NOT PROVIDED. | | SERVICE LOAD FOR THIS PROJECT AND FOR ENTIRE SERVICE, | | AND SIZE OF EXISTING SERVICE MUST BE CONFIRMED FOR | | APPROVAL.)(3RD REVIEW: THE TOTAL LOAD CALCULATION FOR | | THE SERVICE HAS NOT BEEN PROVIDED. THIS PROJECT AND THE | | LOAD CALCULATION ON PLAN ARE FOR 539 CLEMATIS. HOWEVER, | | THE SERVICE FEEDERS ALSO FEED 537 CLEMATIS, AND A LOAD | | CALCULATION INCLUDING THOSE LOADS MUST BE PROVIDED. IN | | REFERENCE TO THE LOAD CALCULATION FOR THIS PROJECT, | | PANEL PP1 SHOWS A DEMAND FACTOR OF 80% FOR AC | | EQUIPMENT. PROVIDE CODE SECTION THAT PERMITS THIS | | REDUCTION IN LOAD, OR CORRECT LOAD CALCULATION TO | | INCLUDE 125% OF THE CONTINUOUS LOAD AND 100% OF THE | | NON-CONTINUOUS LOAD PER CODE. ADDITIONALLY, RISER | | DIAGRAM SHOWS PANEL RP-B BEING FED FROM PANEL RP-A. | | HOWEVER, THERE IS NO LOAD SHOWN IN PANEL RP-A FOR PANEL | | RP-B. THERE IS LOAD SHOWN FOR PANEL RP-IG, BUT THE | | RISER DIAGRAM SHOWS THIS FED FROM GUTTER. CLARIFY | | AND/OR CORRECT.) | | 9. CORRECTED. | | 10. PROVIDE CORRECTED RISER DIAGRAM, SHOWING ALL | | DETAILS OF SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD | | SERVICE, WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO | | ANY SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW | | INTERSYSTEM BONDING TERMINATION POINT. RISER PROVIDED | | DOES NOT SHOW WIRE SIZES TO MAIN AND GUTTER AND DOES | | NOT SHOW SIZE OF MAIN. PROVIDE CORRECTION. NEC 215.5, | | 230, 250.50, 250.94, 408.30 (NOT PROVIDED, REQUIRED FOR | | APPROVAL.)(3RD REVIEW: IN ADDITION TO THE ITEMS | | MENTIONED IN COMMENT 8 ABOVE, THERE NEEDS TO BE FURTHER | | CORRECTIONS TO THE RISER DIAGRAM. AFTER SITE VISIT, I | | SEE THAT THERE IS NOT A "EXISTING SERVICE END BOX" AS | | SHOWN ON PLAN. THE FPL FEED GOES DIRECTLY INTO A LINE | | GUTTER. THERE IS A DISCONNECT AND METER FOR 537 | | CLEMATIS MOUNTED AT THE LOCATION OF THIS LINE GUTTER, | | BUT I DID NOT SEE THE 600 AMP MAIN THAT IS STATED IN | | RISER DIAGRAM. WHERE IS THIS MAIN LOCATED? IS IT INSIDE | | THE ELECTRICAL ROOM AND FEEDS ANOTHER GUTTER? ARE | | PANELS RP-A AND RP-B FED AS A TAP FROM THIS GUTTER, OR | | ARE THERE MAINS AHEAD OF THEM? THE PANELS ARE SHOWN AS | | MAIN LUG ONLY. NEED CLARIFICATION AND/OR CORRECTION.) | | 11. AIC DEFERRED SUBMITTAL ACCEPTED. | | 12. CORRECTED. | | 13. CORRECTED. | | | | NEW COMMENT: | | | | 14. PLEASE BE ADVISED THAT SOME OF THESE COMMENTS HAVE | | NOT BEEN ADDRESSED FOR THREE REVIEWS. IF UPON THE NEXT | | REVIEW, IF IT IS NECESSARY TO REJECT THE SUBMITTED PLAN | | AGAIN FOR THE SAME REASONS, AN ADDITIONAL PLAN REVIEW | | IS REQUIRED. FLORIDA STATUTES STATE: WITH RESPECT TO | | EVALUATION OF DESIGN PROFESSIONALS DOCUMENTS, IF A | | LOCAL GOVERNMENT FINDS IT NECESSARY, IN ORDER TO | | ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING CODE AND | | ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS REQUIRED BY | | THE CODE THREE OR MORE TIMES FOR FAILURE TO CORRECT A | | CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY NOTED IN | | EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, EGRESS, | | FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, | | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, | | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER | | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING | | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL | | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH | | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, | | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE | | PERMIT FEE ATTRIBUTED TO PLANS REVIEW. FS 553.80(2)(B) | | THE ADDITIONAL FEE FOR THIS PROJECT WOULD BE | | $20,530.32. | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD | | SHEETS. | | | | SINCERELY, | | | | JOHN PEARSON | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2018-12-06 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2018-12-06 |
Time |
09:05 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2018-12-06 |
Time |
09:05 |
Sent To |
|
|
Notes |
2018-12-06 09:05:03 | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | 6TH ED, CHAPTER 1. | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED | | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS | | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY | | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW | | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. | | | | 1. CORRECTED. | | 2. CORRECTED. | | 3. CORRECTED. | | 4. CORRECTED. | | 5. CORRECTED. | | 6. CORRECTED. | | 7. CORRECTED. | | 8. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE | | EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE | | IS ADEQUATE. NEC 215.2, 220, 408.30 (NOT PROVIDED. | | SERVICE LOAD FOR THIS PROJECT AND FOR ENTIRE SERVICE, | | AND SIZE OF EXISTING SERVICE MUST BE CONFIRMED FOR | | APPROVAL.) | | 9. CORRECTED. | | 10. PROVIDE CORRECTED RISER DIAGRAM, SHOWING ALL | | DETAILS OF SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD | | SERVICE, WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO | | ANY SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW | | INTERSYSTEM BONDING TERMINATION POINT. RISER PROVIDED | | DOES NOT SHOW WIRE SIZES TO MAIN AND GUTTER AND DOES | | NOT SHOW SIZE OF MAIN. PROVIDE CORRECTION. NEC 215.5, | | 230, 250.50, 250.94, 408.30 (NOT PROVIDED, REQUIRED FOR | | APPROVAL.) | | 11. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR | | EACH PANEL INCLUDING INFORMATION FROM THE POWER COMPANY | | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR | | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE | | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. | | NEC 110.9, 110.10 (NOT PROVIDED, REQUIRED FOR APPROVAL. | | A DEFERRED SUBMITTAL IS ACCEPTABLE IF RESPONSE FROM FPL | | IS DELAYED. HOWEVER, BE ADVISED THAT THE CONTRACTOR IS | | PROCEEDING AT HIS OWN RISK. IF THIS IS DESIRED, PROVIDE | | BLOCK NOTE ON PLAN THAT THIS INFORMATION WILL BE | | PROVIDED PRIOR TO FIRST INSPECTION.) | | 12. PROVIDE AIC RATING OF SERVICE DISCONNECTS AND | | PANELS. NEC 110.3, 110.9 (NOT PROVIDED, REQUIRED FOR | | APPROVAL. A DEFERRED SUBMITTAL IS ACCEPTABLE IF | | RESPONSE FROM FPL IS DELAYED. HOWEVER, BE ADVISED THAT | | THE CONTRACTOR IS PROCEEDING AT HIS OWN RISK. IF THIS | | IS DESIRED, PROVIDE BLOCK NOTE ON PLAN THAT THIS | | INFORMATION WILL BE PROVIDED PRIOR TO FIRST | | INSPECTION.) | | 13. CORRECTED. | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD | | SHEETS. | | | | SINCERELY, | | | | JOHN PEARSON | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2018-10-18 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2018-10-18 |
Time |
11:56 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2018-10-18 |
Time |
11:56 |
Sent To |
|
|
Notes |
2018-10-18 11:56:32 | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | 6TH ED, CHAPTER 1. | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND VALUE | | OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS IS | | FOR TOTAL PROJECT, NOT JUST ELECTRICAL. FBC 109.3 | | 2. PROVIDE SHOW WINDOW RECEPTACLE OUTLETS. NEC 210.62 | | 3. PROVIDE DEDICATED CIRCUIT AND CONTROL FOR SIGN. NEC | | 600.5; FBC EC 405.2.4 | | 4. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES | | EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN | | RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR | | LIGHTING PROPOSED TO COMPLY WITH CODE. FBC EC C405.4.2 | | 5. PROVIDE RECEPTACLE CONTROL REQUIRED BY ASHREA 90.1: | | 8.4.2. PER THIS REQUIREMENT, THE FOLLOWING SHALL BE | | AUTOMATICALLY CONTROLLED: 1) AT LEAST 50% OF ALL | | 125-VOLT, 15 AND 20 AMP RECEPTACLES, IN ALL PRIVATE | | OFFICES, CONFERENCE ROOMS, ROOMS USED PRIMARILY FOR | | PRINTING AND/OR COPYING FUNCTIONS, BREAK ROOMS, | | CLASSROOMS, AND INDIVIDUAL WORKSTATIONS. 2) AT LEASE | | 25% OF BRANCH CIRCUIT FEEDERS INSTALLED FOR MODULAR | | FURNITURE NOT SHOWN ON THE CONSTRUCTION DOCUMENTS. FBC | | EC C405.6.1 | | 6. LIGHTING PLAN NOTE 11 ON SHEET E-101 STATE THAT | | LIGHTING WILL BE FED FROM PANEL RP-1, WHICH IS NOT | | SHOWN ON RISER DIAGRAM OR IN PANEL SCHEDULES. CORRECT | | DISCREPANCY. WPB FBC 107.2.1 | | 7. PROVIDE GFCI PROTECTED RECEPTACLE OUTLET FOR | | SERVICING OF A/C EQUIPMENT WITHIN 25 FEET OF THE | | EQUIPMENT PER CODE. NEC 210.63 | | 8. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE | | EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE | | IS ADEQUATE. NEC 215.2, 220, 408.30 | | 9. PROVIDE LOAD CALCULATION FOR PANELS, INCLUDE | | EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE | | TO PANELS IS ADEQUATE. NEC 215.2, 220, 408.30 | | 10. PROVIDE CORRECTED RISER DIAGRAM, SHOWING ALL | | DETAILS OF SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD | | SERVICE, WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO | | ANY SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW | | INTERSYSTEM BONDING TERMINATION POINT. RISER PROVIDED | | DOES NOT SHOW WIRE SIZES TO MAIN AND GUTTER AND DOES | | NOT SHOW SIZE OF MAIN. PROVIDE CORRECTION. NEC 215.5, | | 230, 250.50, 250.94, 408.30 | | 11. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR | | EACH PANEL INCLUDING INFORMATION FROM THE POWER COMPANY | | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR | | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE | | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. | | NEC 110.9, 110.10 | | 12. PROVIDE AIC RATING OF SERVICE DISCONNECTS AND | | PANELS. NEC 110.3, 110.9 | | 13. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS, | | DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD | | SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND | | SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN | | THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE | | INDICATING THE REQUIRED SEPARATE PERMITS AND PLAN | | SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. WPB FBC | | 105.1, 107.2.1 | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD | | SHEETS. | | | | SINCERELY, | | | | JOHN PEARSON | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2018-12-05 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2018-12-05 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2018-11-28 |
Time |
10:29 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2018-10-12 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2018-10-12 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2018-10-12 |
Time |
12:27 |
Sent To |
|
|
Notes |
2018-10-12 12:55:44 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | 1 SHEET LS 101 - THERE IS AN INCORRECT REFERNECE TO THE | | CURRENT FLORIDA FIRE PREVENTION CODE. | | | | THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE | | 6TH EDITION OF FLORIDA FIRE PREVENTION CODE WHICH | | INCLUDES THE 2015 EDITION OF NFPA 1 AND NFPA 101 AND | | ALL OTHER APPLICABLE CODES OR STANDARDS. | | | | PLEASE REVIEW AND ENSURE COMPLIANCE WERE APPLICABLE AND | | PROVIDE A CORRECTION. | | | | | | | | | | 2) SHEET E 101 - THERE DOES NOT APPEAR TO BE AN EXIT | | SIGN AT DOOR 108 INSIDE THE PROCESSING ROOM. | | | | PER NFPA 101, CHAPTER 7 MEANS OF EGRESS | | | | 7.10.1.2 EXITS. | | 7.10.1.2.1* EXITS, OTHER THAN MAIN EXTERIOR EXIT DOORS | | THAT OBVIOUSLY | | AND CLEARLY ARE IDENTIFIABLE AS EXITS, SHALL BE MARKED | | BY AN APPROVED | | SIGN THAT IS READILY VISIBLE FROM ANY DIRECTION OF EXIT | | ACCESS. | | | | | | AN EXIT SIGN IS REQUIRED ABOVE THAT DOOR. | | | | 7.10.1.5 EXIT ACCESS. | | 7.10.1.5.1 ACCESS TO EXITS SHALL BE MARKED BY APPROVED, | | READILY | | VISIBLE SIGNS IN ALL CASES WHERE THE EXIT OR WAY TO | | REACH THE EXIT IS | | NOT READILY APPARENT TO THE OCCUPANTS. | | | | AN EXIT SIGN IS REQUIRED AT THE END WALL LEADING TO THE | | EXIT DOOR. | | | | PLEASE REVIEW AND CORRECT. | | | | | | | | | | 3) SHEET E 101 - THERE DOES NOT APPEAR TO BE AN EXIT | | SIGN AT DOOR 103 ON THE.SALES ROOM SIDE. | | | | PER NFPA 101, CHAPTER 7 MEANS OF EGRESS | | | | 7.10.1.2 EXITS. | | 7.10.1.2.1* EXITS, OTHER THAN MAIN EXTERIOR EXIT DOORS | | THAT OBVIOUSLY | | AND CLEARLY ARE IDENTIFIABLE AS EXITS, SHALL BE MARKED | | BY AN APPROVED | | SIGN THAT IS READILY VISIBLE FROM ANY DIRECTION OF EXIT | | ACCESS. | | | | | | AN EXIT SIGN IS REQUIRED ABOVE THAT DOOR. | | | | 7.10.1.5 EXIT ACCESS. | | 7.10.1.5.1 ACCESS TO EXITS SHALL BE MARKED BY APPROVED, | | READILY | | VISIBLE SIGNS IN ALL CASES WHERE THE EXIT OR WAY TO | | REACH THE EXIT IS | | NOT READILY APPARENT TO THE OCCUPANTS. | | | | AN EXIT SIGN IS REQUIRED IN THE SALES ROOM OPEN AREA | | LEADING TO THE EXIT DOOR. | | | | PLEASE REVIEW AND CORRECT. | | | | | | | | | | 4) SHEET A 101 - DOOR 107 IS INDICATED AS OPENING OUT | | INTO THE EXIT ACCESS CORRIDAR. | | | | PER NFPA 101, CHAPTER 7 MEANS OF EGRESS | | | | 7.2.1.4.3* DOOR LEAF ENCROACHMENT. | | 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS | | OF EGRESS | | SHALL LEAVE NOT LESS THAN ONE-HALF OF THE REQUIRED | | WIDTH OF AN AISLE, | | A CORRIDOR, A PASSAGEWAY, OR A LANDING UNOBSTRUCTED, | | UNLESS BOTH | | OF THE FOLLOWING CONDITIONS ARE MET: | | (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN | | EXISTING | | BUILDING. | | (2) THE DOOR OPENING MEETS THE REQUIREMENT OF | | 7.2.1.4.3.2. | | 7.2.1.4.3.2 WHEN FULLY OPEN, ANY DOOR LEAF IN A MEANS | | OF EGRESS | | SHALL NOT PROJECT MORE THAN 7 IN. (180 MM) INTO THE | | REQUIRED WIDTH | | OF AN AISLE, A CORRIDOR, A PASSAGEWAY, OR A LANDING, | | UNLESS THE DOOR | | LEAF IS EQUIPPED WITH AN APPROVED SELF-CLOSING DEVICE | | AND IS NOT | | REQUIRED BY THE PROVISIONS OF 7.2.1.4.2 TO SWING IN THE | | DIRECTION OF | | EGRESS TRAVEL. | | | | | | PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECFIC CODE | | REFERENCES. | | | | | | | | | | 5) CS 1.00 - THERE IS AN INDICATION UNDER PREFIX 029 | | THAT THE DOOR SCHEDULE AND HARWARE SET ARE ON SHEET A | | 810. | | | | SHEET A 810 DOES NOT DIPLAY THAT INFORMATION AND THE | | DOOR SCHULE AND HARDWARE SET INFORMATION COULD NOT BE | | LOCATED. | | | | THE HARDWARE ON THE EXIT DOES COULD NOT BE VERIFIED OR | | CONFIRMED TO BE CODE COMPLIANT PER NFPA 101, CHAPTER 7 | | MEANS OF EGRESS. | | | | PLEASE REVIEW AND CORRECT. | | | | | | | | | | 6) SHEET A 131 - THERE ARE INDICATIONS OF ACCESS | | CONTROL AT EXIT DOORS. ALL ACCESS CONTROL SHALL COMPLY | | WITH PER NFPA 101, CHAPTER 7 MEANS OF EGRESS | | | | ACCESS CONTROL SHALL BE SUBMITTED UNDER SEPARATE SHOP | | DRAWINGS. | | | | PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF | | ACKNOWLEDGEMENT AND COMPLIANCE. | | | | | | | | | | 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | | | 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | | | | | | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2019-01-09 |
Time |
|
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2019-01-09 |
Time |
12:30 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2018-12-21 |
Time |
|
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2018-12-17 |
Time |
07:55 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2018-12-13 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2018-12-13 |
Time |
09:20 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2018-11-26 |
Time |
11:17 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2018-11-21 |
|
|
Cont ID |
|
Sent By |
skennedy |
Date |
2018-11-21 |
Time |
15:22 |
Rev Time |
0.00 |
Received By |
skennedy |
Date |
2018-10-01 |
Time |
08:29 |
Sent To |
|
|
Notes |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
3 |
Status |
N |
Date |
2018-12-07 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2018-12-07 |
Time |
09:57 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2018-12-07 |
Time |
09:57 |
Sent To |
|
|
Notes |
2018-12-07 09:57:37 | $0.00 OWED PER IMPACT FEE OFFICE. LEM | 2018-12-06 10:55:43 | 12/6/18 EMAILED IMPACT FEE OFFICE PER DBATTLES. LEM |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
2 |
Status |
F |
Date |
2018-12-04 |
|
|
Cont ID |
|
Sent By |
dbattles |
Date |
2018-12-04 |
Time |
10:54 |
Rev Time |
0.00 |
Received By |
dbattles |
Date |
2018-12-04 |
Time |
10:54 |
Sent To |
|
|
Notes |
2018-12-04 10:56:45 | 2ND ROUND NOT YET COMPLETE. | | ONCE ALL REVIEWS APPROVED PROCEED WITH PBC IMPACT FEE | | REVIEW. | | | | [FBC AMENDED 109]PLANS WILL BE REVIEWED BY THE PBC | | IMPACT FEE OFFICE DIGITALLY VIA PROJECTDOX UPON | | NOTIFICATION BY THIS OFFICE. NOTIFICATION MAY OCCUR | | WHEN PLANS ARE NEAREST FINAL FORM. YOU MAY COORDINATE | | WITH THE IMPACT FEE OFFICE AT (561) 233-5025 OR SIMPLY | | UPLOAD THE MUNICIPAL IMPACT FEE QUESTIONNAIRE FORM TO | | YOUR PROJECT AND NAME THE FILE MUNICIPAL IMPACT FEE | | QUESTIONNAIRE. THE FORM CAN BE FOUND AT: HTTP://DISCOVE | | R.PBCGOV.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QU | | ESTIONNAIRE.PDF UPON APPROVAL AND FEE PAYMENT, PLEASE | | UPLOAD THE RECEIPT TO YOUR PROJECT OR EMAIL IT TO | | [email protected] | | | | DYLAN BATTLES | | BUILDING PLANS EXAMINER I | | [email protected] | | 561-805-6718 |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
1 |
Status |
F |
Date |
2018-11-15 |
|
|
Cont ID |
|
Sent By |
dbattles |
Date |
2018-11-15 |
Time |
08:08 |
Rev Time |
0.00 |
Received By |
dbattles |
Date |
2018-11-15 |
Time |
08:08 |
Sent To |
|
|
Notes |
2018-11-15 08:09:38 | [FBC AMENDED 109]PLANS WILL BE REVIEWED BY THE PBC | | IMPACT FEE OFFICE DIGITALLY VIA PROJECTDOX UPON | | NOTIFICATION BY THIS OFFICE. NOTIFICATION MAY OCCUR | | WHEN PLANS ARE NEAREST FINAL FORM. YOU MAY COORDINATE | | WITH THE IMPACT FEE OFFICE AT (561) 233-5025 OR SIMPLY | | UPLOAD THE MUNICIPAL IMPACT FEE QUESTIONNAIRE FORM TO | | YOUR PROJECT AND NAME THE FILE MUNICIPAL IMPACT FEE | | QUESTIONNAIRE. THE FORM CAN BE FOUND AT: HTTP://DISCOVE | | R.PBCGOV.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QU | | ESTIONNAIRE.PDF UPON APPROVAL AND FEE PAYMENT, PLEASE | | UPLOAD THE RECEIPT TO YOUR PROJECT OR EMAIL IT TO | | [email protected] | | | | DYLAN BATTLES | | BUILDING PLANS EXAMINER I | | [email protected] | | 561-805-6718 | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2018-12-21 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2018-12-21 |
Time |
15:55 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2018-12-21 |
Time |
13:58 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2018-12-06 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2018-12-06 |
Time |
15:46 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2018-12-06 |
Time |
15:31 |
Sent To |
|
|
Notes |
2018-12-06 16:50:44 | 1ST REVIEW FBC-2017 MECHANICAL | | PERMIT #18091312 | | 12/6/18 | | | | CODES IN EFFECT: | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | 2017 | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | 2017 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | EDITION 2017 | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) M101 & M102: SHOW THE LOCATIONS OF ACCESS PANELS FOR | | SERVICE AND REPLACEMENT OF ANY VAV BOXES LOCATED ABOVE | | HARD CEILINGS- SECTION 306.1 FBC M. PLEASE INCLUDE THE | | DIMENSIONS OF THE PANELS | | | | 2) SHEET S103 & M103: A) THE TYP. MECH.UNIT ATTACHMENT | | DETAIL IS MISSING THE RTU ATTACHMENT TO THE 12 GA. | | ANGLE. B) EXHAUST FAN CURB ATTACHMENT DETAIL MISSING | | FAN TO CURB ATTACHMENT. IF THE FAN HAS FLORIDA PRODUCT | | OR MIAMI-DADE NOA APPROVAL, PLEASE PROVIDE THE | | DOCUMENT. C) ENGINEERING FOR INSTALLATION OF THE | | ROOFTOP DUCTWORK NOT PROVIDED. PROVIDE DETAILS | | INDICATING HOW THE DUCTWORK WILL BE SUPPORTED AND | | ATTACHED TO THE ROOF STRUCTURE. D) STEEL DUNNAGE | | ATTACHMENT TO THE ROOF STRUCTURE NOT PROVIDED. | | | | 3) M103: INDICATE THE TYPE AND GAGE OF ROOFTOP DUCTWORK | | TO BE INSTALLED, AND THE INSULATION R-VALUE. | | | | 4) EN-001: THE COMCHECK COMPLIANCE REPORT IS MISSING | | THE DATA FOR THE AC-3 & 4 MITSUBISHI SYSTEMS. | | | | 5) THE SUMMARY AC CALCULATIONS UPLOADED ARE MISSING THE | | PROJECT ADDRESS, THE OUTDOOR WET AND DRY BULB | | TEMPERATURES USED, AND THE INDOOR DRY BULB TEMPERATURE | | USED. | | | | | | ]WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | KEEP THEM WITH THE SUBMITTALS | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2018-10-24 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2018-10-24 |
Time |
17:22 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2018-10-24 |
Time |
17:22 |
Sent To |
|
|
Notes |
2018-10-24 17:45:55 | 1ST REVIEW FBC-2017 MECHANICAL | | PERMIT #18091312 | | 10/24/18 | | | | CODES IN EFFECT: | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | 2017 | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | 2017 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | EDITION 2017 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE | | NEW SYSTEMS IN ACCORDANCE WITH SECTION C403.2.1 FBC EC. | | | | 2) REFER TO SECTION 809.2 FBC-17 EXISTING BUILDING CODE | | AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL | | ROOMS AND SPACES PER TABLE 403.3.1.1 FBC-17 MECHANICAL. | | PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND | | PROVIDED CFMS OF OUTDOOR AIR. | | | | 3) PROVIDE AUTOMATICALLY CONTROLLED SHUTOFF DAMPERS FOR | | THE O/A INTAKE DUCTS- SECTION C403.2.4.3 FBC-17 ENERGY | | CONSERVATION. | | | | 4) SHEET M-501.00: PROVIDE DUCT HANGING AND CONNECTION | | DETAILS PER SMACNA HVAC DUCT CONSTRUCTION | | STANDARDS-2005. THE DUCT DETAILS AND HANGER TABLE SHOWN | | ON THE PLANS ARE NOT IN COMPLIANCE, AND ARE BASED ON A | | NYC CODE. | | | | 5) M501: PROVIDE A HORIZONTAL FIRE DAMPER INSTALLATION | | DETAIL PER MANUFACTURER'S SPECIFICATIONS AND SUBMIT THE | | SPECS FOR THE DEVICE- SECTION 607.5.2 FBC M. INDICATE | | HOW ACCESS WILL BE PROVIDED TO THE DAMPERS IN THE | | SUPPLY AND RETURN RISERS- SECTION 607.4 FBC M. | | | | 6) M101: REQUIRED RETURN AIR FROM THE SECURITY- IT ROOM | | NOT SHOWN. | | | | 7) M102: REQUIRED RETURN AIR FROM THE BREAKROOM NOT | | SHOWN. | | | | 8) M102: CLARIFY IF ANY COOKING APPLIANCES OR EXHAUST | | HOOD SYSTEMS WILL BE INSTALLED IN THE BREAKROOM OR | | STAFF LOUNGE, AND PROVIDE DETAILS, SPECIFICATIONS, AND | | PRODUCT SUBMITTALS IF APPLICABLE. PLEASE NOTE THAT | | SEPARATE PERMITS ARE REQUIRED FOR KITCHEN EXHAUST HOODS | | AND FIR SUPPRESSION SYSTEMS. | | | | 9) M102: THE CONDENSATE DRAINING INTO THE MOP SINK IS | | PROHIBITED PER SECTION 90-126 WPB CODE OF ORDINANCES | | | | 10) M103: COMPLETE WIND LOAD ENGINEERING IS REQUIRED | | FOR THE RTU'S, ROOFTOP CONDENSER UNITS AND STANDS, AND | | THE EXHAUST FAN AND CURB- SECTION 301.15. PLEASE NOTE | | THE RTU DETAIL ON S-400 IS INCOMPLETE- RTU ATTACHMENT | | TO CURB NOT SHOWN AND NO DESIGN CRITERIA HAS BEEN | | PROVIDED. | | | | 11) M103: SHOW HOW ACCESS IS BEING PROVIDED TO THE | | EQUIPMENT ON THE ROOF- SEE SECTION 306.5 FBC M. | | | | 12) M103: VERIFY THE REQUIRED 10' REQUIRED CLEARANCE | | FOR THE SERVICEABLE ROOF TOP MECHANICAL EQUIPMENT TO | | THE ROOF EDGES OR VERIFY 42" GUARD OR PARAPET IN PLACE- | | SECTION 304.11 FBC M. | | | | 13) THE PROPOSED PROJECT IS CLASSIFED AS A"RENOVATED | | BUILDING" PER SECTION 202 FBC EC. PLEASE SUBMIT AN | | ENERGY COM[PLIANCE REPORT IN ACCORDANCE WITH SECTIONS | | C101.5.1 & C101.5.1.1 FBC EC. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | KEEP THEM WITH THE SUBMITTALS | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2018-12-13 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2018-12-13 |
Time |
09:19 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2018-12-13 |
Time |
09:19 |
Sent To |
|
|
Notes |
2018-12-13 09:20:07 | PROVISO: | | 1. PROVIDE FIRE STOPPING SPECIFICATIONS FOR FLOOR | | PENETRATIONS OF PVC AND METALLIC PIPING. PER WPB AMEND | | TO FBC 107.2.1 | | 2. PROVIDE FIRE STOPPING SPECIFICATIONS FOR WALL | | PENETRATIONS OF PVC PIPING. PER WPB AMEND TO FBC | | 107.2.1 | | 3. PROVIDE DETAILS FOR SWAY BRACING PER FBC PL 308.6 | | SWAY BRACING.RIGID SUPPORT SWAY BRACING SHALL BE | | PROVIDED AT CHANGES IN DIRECTION GREATER THAN 45 | | DEGREES FOR PIPE SIZES 4 INCHES AND LARGER. | | | | | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561-805-6711 | | [email protected] | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
|
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2018-11-01 |
Time |
16:51 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2018-11-01 |
Time |
16:51 |
Sent To |
|
|
Notes |
2018-11-01 17:22:38 | 1ST REVIEW: | | 2017 FLORIDA BUILDING CODE 6TH EDITION | | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION | | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH | | EDITION | | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION | | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION | | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH | | EDITION | | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH | | EDITION | | | | PLUMBING COMMENTS: | | | | 1. THE WHEELCHAIR ACCESSIBLE TOILET COMPARTMENT SHALL | | CONTAIN AN ACCESSIBLE LAVATORY WITHIN IT, WHICH MUST BE | | AT LEAST 19 INCHES WIDE BY 17 INCHES DEEP, NOMINAL | | SIZE, AND WALL-MOUNTED. THE LAVATORY SHALL BE MOUNTED | | SO AS NOT TO OVERLAP THE CLEAR FLOOR SPACE AREAS | | REQUIRED BY SECTION 604 FOR THE WHEELCHAIR ACCESSIBLE | | TOILET COMPARTMENT AND SHALL COMPLY WITH SECTION 606. | | SUCH LAVATORIES SHALL BE COUNTED AS PART OF THE | | REQUIRED FIXTURE COUNT FOR THE BUILDING. SEE ALSO | | SECTION 213.3.4. PER FBC ACC 604.8.1.6 | | | | 2. SHOW COMPLIANCE WITH FBC ACC 604.5.1 SIDE WALL.THE | | SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG MINIMUM, | | LOCATED 12 INCHES MAXIMUM FROM THE REAR WALL AND | | EXTENDING 54 INCHES MINIMUM FROM THE REAR WALL. | | | | 3. SHOW COMPLIANCE WITH FBC ACC 604.7 DISPENSERS.TOILET | | PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND SHALL BE 7 | | INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT OF THE | | WATER CLOSET MEASURED TO THE CENTERLINE OF THE | | DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15 | | INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH | | FLOOR. | | | | 4. PROVIDE AN ENLARGE DETAIL OF BATHROOMS AND SHOW THE | | REQUIRED CLEAR FLOOR SPACE FOR THE TOILET AND THE | | LAVATORY PLEASE INCLUDE THE DIMENSIONS ON THE CLEAR | | FLOOR SPACES. PER FBC ACC 604.8.1.1 , 606.2 | | | | 5. PROVIDE UL APPROVED DETAILS FOR THE FIRE STOPPING ON | | ALL THE PIPES. PER WPB AMEND TO FBC 107.2.1 | | | | 6. SHT. P-801.00 THE TEXT IS NOT LEGIBLE I CAN NOT | | DETERMINE CODE COMPLIANCE ALL SHEETS SHALL COMPLY WITH | | WPB AMEND TO FBC 107.2.1.3 | | | | 7. THE VENTS ON THE WATER CLOSETS ARE NOT CODE | | COMPLIANT DRY VENTS SHALL NOT RUN HORIZONTAL BELOW THE | | FLOOD LEVEL RIM OF THE FIXTURES THEY SHALL COMPLY WITH | | FBC PL 905.3 , 905.4 | | | | 8. PLEASE ENLARGE WATER AND SANITARY ISOMETRIC DRAWING | | THEY SHALL COMPLY WITH WPB AMEND TO FBC 107.2.1.3 | | | | 9. FBC PL 416.5 TEMPERED WATER SHALL BE DELIVERED FROM | | LAVATORIES AND GROUP WASH FIXTURES LOCATED IN PUBLIC | | TOILET FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND | | VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN | | APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT | | CONFORMS TO ASSE 1070 OR CSA B125.3. | | THE NOTE ON THE WATER HEATER DETAIL STATE 140- 120 DEG. | | DOES NOT COMPLY FOR THE LAVATORIES IN THE BATHROOMS. | | TEMPERED WATER. WATER HAVING A TEMPERATURE RANGE | | BETWEEN 85?F (29?C) AND 110?F (43?C). UNDER 110 DEG. | | | | 10. PLEASE PROVIDE MANUFACTURE SIZING FOR THE 1GAL | | WATER HEATER CAN SUPPLY THE REQUIRED TEMPERATURE WATER | | FOR 2 LAVATORIES THE BREAK ROOM SINK AND A SERVICE SINK | | SIMULTANEOUSLY. PER WPB AMEND TO FBC 107.2.1 | | | | 11. PROVIDE MANUFACTURE SPEC FOR URINAL FLUSHVALVE SHOW | | THAT 1/2" SUPPLY PIPING IS ADEQUATE AS SHOWN ON THE | | WATER ISOMETRIC DRAWING. PER WPB AMEND TO FBC 107.2.1 | | | | 12. SHT. P001 ON THE MAXIMUM FLOW RATE TABLE IT LIST | | THE MIAMI DADE CODE AND RESIDENTIAL THE PROJECT SHALL | | BE DESIGNED AND BUILT UNDER THE FBC PL AND FBC ACC 2017 | | 6TH EDITION PLEASE SHOW ON PLAN. PER WPB AMEND TO FBC | | 107.2.1 | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | THE PREVIOUSLY REVIEWED SHEETS. | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561-805-6711 | | [email protected] | | |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
3 |
Status |
P |
Date |
2018-12-21 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2018-12-21 |
Time |
13:17 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2018-12-21 |
Time |
13:17 |
Sent To |
|
|
Notes |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
2 |
Status |
F |
Date |
2018-12-04 |
|
|
Cont ID |
|
Sent By |
dbattles |
Date |
2018-12-04 |
Time |
10:50 |
Rev Time |
0.00 |
Received By |
dbattles |
Date |
2018-12-04 |
Time |
10:50 |
Sent To |
|
|
Notes |
2018-12-04 10:52:46 | SHEET 027 A-611.00 NOT DIGITALLY SIGNED | | | | ALL OTHER GOOD FOR SECOND REIVIEW. | | NEW SHEETS WILL NEED TO BE CHECKED IF THIRD ROUND OF | | COMMENTS NEEDED. | | | | DYLAN BATTLES | | [email protected] | | 561-805-6718 | | |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
F |
Date |
2018-10-18 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2018-10-18 |
Time |
09:27 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2018-10-18 |
Time |
09:27 |
Sent To |
|
|
Notes |
2018-10-18 09:27:44 | PLAN IS REQUIRED TO BE SIGNED AND SEALED BY THE PERSON | | RESPONSIBLE FOR THE DESIGN. SHEET DE-103 HAS NO | | SIGNATURE. SHEETS S-001, S-100, S-101, S-102, S-200, | | S-201, S-300, S-301, AND S-400 HAVE A CORRUPTED | | SIGNATURE. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE. | | PROVIDE CORRECTION. WPB FBC 107.1; FS 471/481 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2018-12-06 |
|
|
Cont ID |
|
Sent By |
aaponte |
Date |
2018-12-06 |
Time |
10:54 |
Rev Time |
0.00 |
Received By |
aaponte |
Date |
2018-12-06 |
Time |
10:54 |
Sent To |
|
|
Notes |
2019-01-09 10:48:31 | PROVISO: IF NEW MECHANICHAL EQUIPMENT IS BEING | | INSTALLED IN THE ROOF, UNITS SHALL BE SCREENED WITH | | WALL OR LOUVERS AS TALL AS THE UNIT. | | FOR ADDITIONAL INFORMAITON PLEASE CONTACT ANA MARIA | | APONTE AT 561-822-1439. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2018-11-16 |
|
|
Cont ID |
|
Sent By |
aaponte |
Date |
2018-11-16 |
Time |
12:19 |
Rev Time |
0.00 |
Received By |
aaponte |
Date |
2018-11-16 |
Time |
12:19 |
Sent To |
|
|
Notes |
|
|
|