Plan Review Details - Permit 18091312
Plan Review Stops For Permit 18091312
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-12-04 Cont ID  
Sent By dbattles Date 2018-12-04 Time 10:36 Rev Time 0.00
Received By dbattles Date 2018-12-04 Time 10:36 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-11-15 Cont ID  
Sent By dbattles Date 2018-11-15 Time 08:06 Rev Time 0.00
Received By dbattles Date 2018-11-14 Time 13:13 Sent To  
Notes
2018-11-15 08:07:37****CORRECTIONS****
 W.P.B. PERMIT: 18091312
 REVIEWED: NOVEMBER 14, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC ENERGY = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 CURRENT CODES:
 ADOPTED DECEMBER 31, 2017
 FLORIDA BUILDING CODE(FBC), 6TH EDITION (2017)
  
 1. [FBC 107.3.5]UPDATE SHEETS LS-101 AND LS102 FOR
 CURRENT DODE EDITIONS.
  
 2. [FBC 107.3.5]THIS SHOULD BE A LEVEL 3 ALTERARTION
 SINCE IT AFFECTS MORE THAN 50% OF THE BUILDING.
 PLEASE UPDATE LS-101 AND LS102 TO STATE LEVEL 3
 ALTERATION.
  
 3. [FBC TABLE 1004.1.2]SHEETS LS-101 AND LS102 SHOW
 FIRST FLOOR OCCUPANT LOAD FOR MERCANTILE AT 30 SQ. FT.
 PER.
 MERCANTILE WOULD BE CALCULATED AT 60 SQ. FT. PER PERSON
 LIKE SHOWN FOR SECOND FLOOR.
 PLEASE REVISE OCCUPANT COUNT TO REFLECT MERCANTILE PER
 TABLE 1004.1.2.
  
 4. [FBC 1015.7]ROOF ACCESS. GUARDS SHALL BE PROVIDED
 WHERE THE ROOF
 HATCH OPENING IS LOCATED WITHIN 10 FEET (3048 MM) OF A
 ROOF
 EDGE OR OPEN SIDE OF A WALKING SURFACE AND SUCH EDGE OR
 OPEN
 SIDE IS LOCATED MORE THAN 30 INCHES (762 MM) ABOVE THE
 FLOOR,
 ROOF OR GRADE BELOW. THE GUARD SHALL BE CONSTRUCTED SO
 AS TO
 PREVENT THE PASSAGE OF A SPHERE 21 INCHES (533 MM) IN
 DIAMETER.
 VERIFY THAT PARAPET PROVIDES EDGE PROTECTION OR ADD
 RAIL TO MEET FBC 1015.
 -PROVIDE PRODUCT APPROVAL FOR NEW ROOF HATCH.
  
 5. [FBC 1510.10]MECHANICAL UNITS. ROOF MOUNTED
 MECHANICAL UNITS
 SHALL BE MOUNTED ON CURBS RAISED A MINIMUM OF 8 INCHES
 (203
 MM) ABOVE THE ROOF SURFACE.
 PROVIDE DETAIL OF NEW HVAC EQUIPMENT CURBS. STRUCTURAL
 SHEET S-201 SAYS SEE MECHANICAL AND MECHANICAL M-103
 SAYS SEE STRUCTURAL FOR ATTACHMENT.
  
 6. [FBC 107.3.5]SHEET A-801 AND SHEET A-810 ARE
 REVERSED.
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2019-01-09 Cont ID  
Sent By jpearson Date 2019-01-09 Time 16:53 Rev Time 0.00
Received By jpearson Date 2019-01-09 Time 16:53 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2018-12-21 Cont ID  
Sent By jpearson Date 2018-12-21 Time 13:06 Rev Time 0.00
Received By jpearson Date 2018-12-21 Time 09:57 Sent To  
Notes
2018-12-21 13:06:39CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. CORRECTED.
 3. CORRECTED.
 4. CORRECTED.
 5. CORRECTED.
 6. CORRECTED.
 7. CORRECTED.
 8. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30 (NOT PROVIDED.
 SERVICE LOAD FOR THIS PROJECT AND FOR ENTIRE SERVICE,
 AND SIZE OF EXISTING SERVICE MUST BE CONFIRMED FOR
 APPROVAL.)(3RD REVIEW: THE TOTAL LOAD CALCULATION FOR
 THE SERVICE HAS NOT BEEN PROVIDED. THIS PROJECT AND THE
 LOAD CALCULATION ON PLAN ARE FOR 539 CLEMATIS. HOWEVER,
 THE SERVICE FEEDERS ALSO FEED 537 CLEMATIS, AND A LOAD
 CALCULATION INCLUDING THOSE LOADS MUST BE PROVIDED. IN
 REFERENCE TO THE LOAD CALCULATION FOR THIS PROJECT,
 PANEL PP1 SHOWS A DEMAND FACTOR OF 80% FOR AC
 EQUIPMENT. PROVIDE CODE SECTION THAT PERMITS THIS
 REDUCTION IN LOAD, OR CORRECT LOAD CALCULATION TO
 INCLUDE 125% OF THE CONTINUOUS LOAD AND 100% OF THE
 NON-CONTINUOUS LOAD PER CODE. ADDITIONALLY, RISER
 DIAGRAM SHOWS PANEL RP-B BEING FED FROM PANEL RP-A.
 HOWEVER, THERE IS NO LOAD SHOWN IN PANEL RP-A FOR PANEL
 RP-B. THERE IS LOAD SHOWN FOR PANEL RP-IG, BUT THE
 RISER DIAGRAM SHOWS THIS FED FROM GUTTER. CLARIFY
 AND/OR CORRECT.)
 9. CORRECTED.
 10. PROVIDE CORRECTED RISER DIAGRAM, SHOWING ALL
 DETAILS OF SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD
 SERVICE, WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO
 ANY SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. RISER PROVIDED
 DOES NOT SHOW WIRE SIZES TO MAIN AND GUTTER AND DOES
 NOT SHOW SIZE OF MAIN. PROVIDE CORRECTION. NEC 215.5,
 230, 250.50, 250.94, 408.30 (NOT PROVIDED, REQUIRED FOR
 APPROVAL.)(3RD REVIEW: IN ADDITION TO THE ITEMS
 MENTIONED IN COMMENT 8 ABOVE, THERE NEEDS TO BE FURTHER
 CORRECTIONS TO THE RISER DIAGRAM. AFTER SITE VISIT, I
 SEE THAT THERE IS NOT A "EXISTING SERVICE END BOX" AS
 SHOWN ON PLAN. THE FPL FEED GOES DIRECTLY INTO A LINE
 GUTTER. THERE IS A DISCONNECT AND METER FOR 537
 CLEMATIS MOUNTED AT THE LOCATION OF THIS LINE GUTTER,
 BUT I DID NOT SEE THE 600 AMP MAIN THAT IS STATED IN
 RISER DIAGRAM. WHERE IS THIS MAIN LOCATED? IS IT INSIDE
 THE ELECTRICAL ROOM AND FEEDS ANOTHER GUTTER? ARE
 PANELS RP-A AND RP-B FED AS A TAP FROM THIS GUTTER, OR
 ARE THERE MAINS AHEAD OF THEM? THE PANELS ARE SHOWN AS
 MAIN LUG ONLY. NEED CLARIFICATION AND/OR CORRECTION.)
 11. AIC DEFERRED SUBMITTAL ACCEPTED.
 12. CORRECTED.
 13. CORRECTED.
  
 NEW COMMENT:
  
 14. PLEASE BE ADVISED THAT SOME OF THESE COMMENTS HAVE
 NOT BEEN ADDRESSED FOR THREE REVIEWS. IF UPON THE NEXT
 REVIEW, IF IT IS NECESSARY TO REJECT THE SUBMITTED PLAN
 AGAIN FOR THE SAME REASONS, AN ADDITIONAL PLAN REVIEW
 IS REQUIRED. FLORIDA STATUTES STATE: WITH RESPECT TO
 EVALUATION OF DESIGN PROFESSIONALS DOCUMENTS, IF A
 LOCAL GOVERNMENT FINDS IT NECESSARY, IN ORDER TO
 ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING CODE AND
 ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS REQUIRED BY
 THE CODE THREE OR MORE TIMES FOR FAILURE TO CORRECT A
 CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY NOTED IN
 EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, EGRESS,
 FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW. FS 553.80(2)(B)
 THE ADDITIONAL FEE FOR THIS PROJECT WOULD BE
 $20,530.32.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-12-06 Cont ID  
Sent By jpearson Date 2018-12-06 Time 09:05 Rev Time 0.00
Received By jpearson Date 2018-12-06 Time 09:05 Sent To  
Notes
2018-12-06 09:05:03CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. CORRECTED.
 3. CORRECTED.
 4. CORRECTED.
 5. CORRECTED.
 6. CORRECTED.
 7. CORRECTED.
 8. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30 (NOT PROVIDED.
 SERVICE LOAD FOR THIS PROJECT AND FOR ENTIRE SERVICE,
 AND SIZE OF EXISTING SERVICE MUST BE CONFIRMED FOR
 APPROVAL.)
 9. CORRECTED.
 10. PROVIDE CORRECTED RISER DIAGRAM, SHOWING ALL
 DETAILS OF SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD
 SERVICE, WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO
 ANY SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. RISER PROVIDED
 DOES NOT SHOW WIRE SIZES TO MAIN AND GUTTER AND DOES
 NOT SHOW SIZE OF MAIN. PROVIDE CORRECTION. NEC 215.5,
 230, 250.50, 250.94, 408.30 (NOT PROVIDED, REQUIRED FOR
 APPROVAL.)
 11. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 EACH PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10 (NOT PROVIDED, REQUIRED FOR APPROVAL.
 A DEFERRED SUBMITTAL IS ACCEPTABLE IF RESPONSE FROM FPL
 IS DELAYED. HOWEVER, BE ADVISED THAT THE CONTRACTOR IS
 PROCEEDING AT HIS OWN RISK. IF THIS IS DESIRED, PROVIDE
 BLOCK NOTE ON PLAN THAT THIS INFORMATION WILL BE
 PROVIDED PRIOR TO FIRST INSPECTION.)
 12. PROVIDE AIC RATING OF SERVICE DISCONNECTS AND
 PANELS. NEC 110.3, 110.9 (NOT PROVIDED, REQUIRED FOR
 APPROVAL. A DEFERRED SUBMITTAL IS ACCEPTABLE IF
 RESPONSE FROM FPL IS DELAYED. HOWEVER, BE ADVISED THAT
 THE CONTRACTOR IS PROCEEDING AT HIS OWN RISK. IF THIS
 IS DESIRED, PROVIDE BLOCK NOTE ON PLAN THAT THIS
 INFORMATION WILL BE PROVIDED PRIOR TO FIRST
 INSPECTION.)
 13. CORRECTED.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-10-18 Cont ID  
Sent By jpearson Date 2018-10-18 Time 11:56 Rev Time 0.00
Received By jpearson Date 2018-10-18 Time 11:56 Sent To  
Notes
2018-10-18 11:56:32CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND VALUE
 OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS IS
 FOR TOTAL PROJECT, NOT JUST ELECTRICAL. FBC 109.3
 2. PROVIDE SHOW WINDOW RECEPTACLE OUTLETS. NEC 210.62
 3. PROVIDE DEDICATED CIRCUIT AND CONTROL FOR SIGN. NEC
 600.5; FBC EC 405.2.4
 4. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES
 EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN
 RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR
 LIGHTING PROPOSED TO COMPLY WITH CODE. FBC EC C405.4.2
 5. PROVIDE RECEPTACLE CONTROL REQUIRED BY ASHREA 90.1:
 8.4.2. PER THIS REQUIREMENT, THE FOLLOWING SHALL BE
 AUTOMATICALLY CONTROLLED: 1) AT LEAST 50% OF ALL
 125-VOLT, 15 AND 20 AMP RECEPTACLES, IN ALL PRIVATE
 OFFICES, CONFERENCE ROOMS, ROOMS USED PRIMARILY FOR
 PRINTING AND/OR COPYING FUNCTIONS, BREAK ROOMS,
 CLASSROOMS, AND INDIVIDUAL WORKSTATIONS. 2) AT LEASE
 25% OF BRANCH CIRCUIT FEEDERS INSTALLED FOR MODULAR
 FURNITURE NOT SHOWN ON THE CONSTRUCTION DOCUMENTS. FBC
 EC C405.6.1
 6. LIGHTING PLAN NOTE 11 ON SHEET E-101 STATE THAT
 LIGHTING WILL BE FED FROM PANEL RP-1, WHICH IS NOT
 SHOWN ON RISER DIAGRAM OR IN PANEL SCHEDULES. CORRECT
 DISCREPANCY. WPB FBC 107.2.1
 7. PROVIDE GFCI PROTECTED RECEPTACLE OUTLET FOR
 SERVICING OF A/C EQUIPMENT WITHIN 25 FEET OF THE
 EQUIPMENT PER CODE. NEC 210.63
 8. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30
 9. PROVIDE LOAD CALCULATION FOR PANELS, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 TO PANELS IS ADEQUATE. NEC 215.2, 220, 408.30
 10. PROVIDE CORRECTED RISER DIAGRAM, SHOWING ALL
 DETAILS OF SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD
 SERVICE, WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO
 ANY SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. RISER PROVIDED
 DOES NOT SHOW WIRE SIZES TO MAIN AND GUTTER AND DOES
 NOT SHOW SIZE OF MAIN. PROVIDE CORRECTION. NEC 215.5,
 230, 250.50, 250.94, 408.30
 11. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR
 EACH PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
 12. PROVIDE AIC RATING OF SERVICE DISCONNECTS AND
 PANELS. NEC 110.3, 110.9
 13. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND
 SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN
 THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE
 INDICATING THE REQUIRED SEPARATE PERMITS AND PLAN
 SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. WPB FBC
 105.1, 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-12-05 Cont ID  
Sent By pleduc Date 2018-12-05 Time   Rev Time 0.00
Received By pleduc Date 2018-11-28 Time 10:29 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-10-12 Cont ID  
Sent By pleduc Date 2018-10-12 Time   Rev Time 0.00
Received By pleduc Date 2018-10-12 Time 12:27 Sent To  
Notes
2018-10-12 12:55:44THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1 SHEET LS 101 - THERE IS AN INCORRECT REFERNECE TO THE
 CURRENT FLORIDA FIRE PREVENTION CODE.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 6TH EDITION OF FLORIDA FIRE PREVENTION CODE WHICH
 INCLUDES THE 2015 EDITION OF NFPA 1 AND NFPA 101 AND
 ALL OTHER APPLICABLE CODES OR STANDARDS.
  
 PLEASE REVIEW AND ENSURE COMPLIANCE WERE APPLICABLE AND
 PROVIDE A CORRECTION.
  
  
  
  
 2) SHEET E 101 - THERE DOES NOT APPEAR TO BE AN EXIT
 SIGN AT DOOR 108 INSIDE THE PROCESSING ROOM.
  
 PER NFPA 101, CHAPTER 7 MEANS OF EGRESS
  
 7.10.1.2 EXITS.
 7.10.1.2.1* EXITS, OTHER THAN MAIN EXTERIOR EXIT DOORS
 THAT OBVIOUSLY
 AND CLEARLY ARE IDENTIFIABLE AS EXITS, SHALL BE MARKED
 BY AN APPROVED
 SIGN THAT IS READILY VISIBLE FROM ANY DIRECTION OF EXIT
 ACCESS.
  
  
 AN EXIT SIGN IS REQUIRED ABOVE THAT DOOR.
  
 7.10.1.5 EXIT ACCESS.
 7.10.1.5.1 ACCESS TO EXITS SHALL BE MARKED BY APPROVED,
 READILY
 VISIBLE SIGNS IN ALL CASES WHERE THE EXIT OR WAY TO
 REACH THE EXIT IS
 NOT READILY APPARENT TO THE OCCUPANTS.
  
 AN EXIT SIGN IS REQUIRED AT THE END WALL LEADING TO THE
 EXIT DOOR.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
  
 3) SHEET E 101 - THERE DOES NOT APPEAR TO BE AN EXIT
 SIGN AT DOOR 103 ON THE.SALES ROOM SIDE.
  
 PER NFPA 101, CHAPTER 7 MEANS OF EGRESS
  
 7.10.1.2 EXITS.
 7.10.1.2.1* EXITS, OTHER THAN MAIN EXTERIOR EXIT DOORS
 THAT OBVIOUSLY
 AND CLEARLY ARE IDENTIFIABLE AS EXITS, SHALL BE MARKED
 BY AN APPROVED
 SIGN THAT IS READILY VISIBLE FROM ANY DIRECTION OF EXIT
 ACCESS.
  
  
 AN EXIT SIGN IS REQUIRED ABOVE THAT DOOR.
  
 7.10.1.5 EXIT ACCESS.
 7.10.1.5.1 ACCESS TO EXITS SHALL BE MARKED BY APPROVED,
 READILY
 VISIBLE SIGNS IN ALL CASES WHERE THE EXIT OR WAY TO
 REACH THE EXIT IS
 NOT READILY APPARENT TO THE OCCUPANTS.
  
 AN EXIT SIGN IS REQUIRED IN THE SALES ROOM OPEN AREA
 LEADING TO THE EXIT DOOR.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
  
 4) SHEET A 101 - DOOR 107 IS INDICATED AS OPENING OUT
 INTO THE EXIT ACCESS CORRIDAR.
  
 PER NFPA 101, CHAPTER 7 MEANS OF EGRESS
  
 7.2.1.4.3* DOOR LEAF ENCROACHMENT.
 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS
 OF EGRESS
 SHALL LEAVE NOT LESS THAN ONE-HALF OF THE REQUIRED
 WIDTH OF AN AISLE,
 A CORRIDOR, A PASSAGEWAY, OR A LANDING UNOBSTRUCTED,
 UNLESS BOTH
 OF THE FOLLOWING CONDITIONS ARE MET:
 (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN
 EXISTING
 BUILDING.
 (2) THE DOOR OPENING MEETS THE REQUIREMENT OF
 7.2.1.4.3.2.
 7.2.1.4.3.2 WHEN FULLY OPEN, ANY DOOR LEAF IN A MEANS
 OF EGRESS
 SHALL NOT PROJECT MORE THAN 7 IN. (180 MM) INTO THE
 REQUIRED WIDTH
 OF AN AISLE, A CORRIDOR, A PASSAGEWAY, OR A LANDING,
 UNLESS THE DOOR
 LEAF IS EQUIPPED WITH AN APPROVED SELF-CLOSING DEVICE
 AND IS NOT
 REQUIRED BY THE PROVISIONS OF 7.2.1.4.2 TO SWING IN THE
 DIRECTION OF
 EGRESS TRAVEL.
  
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECFIC CODE
 REFERENCES.
  
  
  
  
 5) CS 1.00 - THERE IS AN INDICATION UNDER PREFIX 029
 THAT THE DOOR SCHEDULE AND HARWARE SET ARE ON SHEET A
 810.
  
 SHEET A 810 DOES NOT DIPLAY THAT INFORMATION AND THE
 DOOR SCHULE AND HARDWARE SET INFORMATION COULD NOT BE
 LOCATED.
  
 THE HARDWARE ON THE EXIT DOES COULD NOT BE VERIFIED OR
 CONFIRMED TO BE CODE COMPLIANT PER NFPA 101, CHAPTER 7
 MEANS OF EGRESS.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
  
 6) SHEET A 131 - THERE ARE INDICATIONS OF ACCESS
 CONTROL AT EXIT DOORS. ALL ACCESS CONTROL SHALL COMPLY
 WITH PER NFPA 101, CHAPTER 7 MEANS OF EGRESS
  
 ACCESS CONTROL SHALL BE SUBMITTED UNDER SEPARATE SHOP
 DRAWINGS.
  
 PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF
 ACKNOWLEDGEMENT AND COMPLIANCE.
  
  
  
  
 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2019-01-09 Time   Rev Time 0.00
Received By lmarchan Date 2019-01-09 Time 12:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2018-12-21 Time   Rev Time 0.00
Received By lmarchan Date 2018-12-17 Time 07:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-12-13 Cont ID  
Sent By gjohnson Date 2018-12-13 Time 09:20 Rev Time 0.00
Received By gjohnson Date 2018-11-26 Time 11:17 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-11-21 Cont ID  
Sent By skennedy Date 2018-11-21 Time 15:22 Rev Time 0.00
Received By skennedy Date 2018-10-01 Time 08:29 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status N Date 2018-12-07 Cont ID  
Sent By lmarchan Date 2018-12-07 Time 09:57 Rev Time 0.00
Received By lmarchan Date 2018-12-07 Time 09:57 Sent To  
Notes
2018-12-07 09:57:37$0.00 OWED PER IMPACT FEE OFFICE. LEM
2018-12-06 10:55:4312/6/18 EMAILED IMPACT FEE OFFICE PER DBATTLES. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2018-12-04 Cont ID  
Sent By dbattles Date 2018-12-04 Time 10:54 Rev Time 0.00
Received By dbattles Date 2018-12-04 Time 10:54 Sent To  
Notes
2018-12-04 10:56:452ND ROUND NOT YET COMPLETE.
 ONCE ALL REVIEWS APPROVED PROCEED WITH PBC IMPACT FEE
 REVIEW.
  
 [FBC AMENDED 109]PLANS WILL BE REVIEWED BY THE PBC
 IMPACT FEE OFFICE DIGITALLY VIA PROJECTDOX UPON
 NOTIFICATION BY THIS OFFICE. NOTIFICATION MAY OCCUR
 WHEN PLANS ARE NEAREST FINAL FORM. YOU MAY COORDINATE
 WITH THE IMPACT FEE OFFICE AT (561) 233-5025 OR SIMPLY
 UPLOAD THE MUNICIPAL IMPACT FEE QUESTIONNAIRE FORM TO
 YOUR PROJECT AND NAME THE FILE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE. THE FORM CAN BE FOUND AT: HTTP://DISCOVE
 R.PBCGOV.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QU
 ESTIONNAIRE.PDF UPON APPROVAL AND FEE PAYMENT, PLEASE
 UPLOAD THE RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected]
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-11-15 Cont ID  
Sent By dbattles Date 2018-11-15 Time 08:08 Rev Time 0.00
Received By dbattles Date 2018-11-15 Time 08:08 Sent To  
Notes
2018-11-15 08:09:38[FBC AMENDED 109]PLANS WILL BE REVIEWED BY THE PBC
 IMPACT FEE OFFICE DIGITALLY VIA PROJECTDOX UPON
 NOTIFICATION BY THIS OFFICE. NOTIFICATION MAY OCCUR
 WHEN PLANS ARE NEAREST FINAL FORM. YOU MAY COORDINATE
 WITH THE IMPACT FEE OFFICE AT (561) 233-5025 OR SIMPLY
 UPLOAD THE MUNICIPAL IMPACT FEE QUESTIONNAIRE FORM TO
 YOUR PROJECT AND NAME THE FILE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE. THE FORM CAN BE FOUND AT: HTTP://DISCOVE
 R.PBCGOV.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QU
 ESTIONNAIRE.PDF UPON APPROVAL AND FEE PAYMENT, PLEASE
 UPLOAD THE RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected]
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2018-12-21 Cont ID  
Sent By ccole Date 2018-12-21 Time 15:55 Rev Time 0.00
Received By ccole Date 2018-12-21 Time 13:58 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-12-06 Cont ID  
Sent By ccole Date 2018-12-06 Time 15:46 Rev Time 0.00
Received By ccole Date 2018-12-06 Time 15:31 Sent To  
Notes
2018-12-06 16:50:441ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18091312
 12/6/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
  
 1) M101 & M102: SHOW THE LOCATIONS OF ACCESS PANELS FOR
 SERVICE AND REPLACEMENT OF ANY VAV BOXES LOCATED ABOVE
 HARD CEILINGS- SECTION 306.1 FBC M. PLEASE INCLUDE THE
 DIMENSIONS OF THE PANELS
  
 2) SHEET S103 & M103: A) THE TYP. MECH.UNIT ATTACHMENT
 DETAIL IS MISSING THE RTU ATTACHMENT TO THE 12 GA.
 ANGLE. B) EXHAUST FAN CURB ATTACHMENT DETAIL MISSING
 FAN TO CURB ATTACHMENT. IF THE FAN HAS FLORIDA PRODUCT
 OR MIAMI-DADE NOA APPROVAL, PLEASE PROVIDE THE
 DOCUMENT. C) ENGINEERING FOR INSTALLATION OF THE
 ROOFTOP DUCTWORK NOT PROVIDED. PROVIDE DETAILS
 INDICATING HOW THE DUCTWORK WILL BE SUPPORTED AND
 ATTACHED TO THE ROOF STRUCTURE. D) STEEL DUNNAGE
 ATTACHMENT TO THE ROOF STRUCTURE NOT PROVIDED.
  
 3) M103: INDICATE THE TYPE AND GAGE OF ROOFTOP DUCTWORK
 TO BE INSTALLED, AND THE INSULATION R-VALUE.
  
 4) EN-001: THE COMCHECK COMPLIANCE REPORT IS MISSING
 THE DATA FOR THE AC-3 & 4 MITSUBISHI SYSTEMS.
  
 5) THE SUMMARY AC CALCULATIONS UPLOADED ARE MISSING THE
 PROJECT ADDRESS, THE OUTDOOR WET AND DRY BULB
 TEMPERATURES USED, AND THE INDOOR DRY BULB TEMPERATURE
 USED.
  
  
 ]WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-10-24 Cont ID  
Sent By ccole Date 2018-10-24 Time 17:22 Rev Time 0.00
Received By ccole Date 2018-10-24 Time 17:22 Sent To  
Notes
2018-10-24 17:45:551ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18091312
 10/24/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE
 NEW SYSTEMS IN ACCORDANCE WITH SECTION C403.2.1 FBC EC.
  
 2) REFER TO SECTION 809.2 FBC-17 EXISTING BUILDING CODE
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3.1.1 FBC-17 MECHANICAL.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR.
  
 3) PROVIDE AUTOMATICALLY CONTROLLED SHUTOFF DAMPERS FOR
 THE O/A INTAKE DUCTS- SECTION C403.2.4.3 FBC-17 ENERGY
 CONSERVATION.
  
 4) SHEET M-501.00: PROVIDE DUCT HANGING AND CONNECTION
 DETAILS PER SMACNA HVAC DUCT CONSTRUCTION
 STANDARDS-2005. THE DUCT DETAILS AND HANGER TABLE SHOWN
 ON THE PLANS ARE NOT IN COMPLIANCE, AND ARE BASED ON A
 NYC CODE.
  
 5) M501: PROVIDE A HORIZONTAL FIRE DAMPER INSTALLATION
 DETAIL PER MANUFACTURER'S SPECIFICATIONS AND SUBMIT THE
 SPECS FOR THE DEVICE- SECTION 607.5.2 FBC M. INDICATE
 HOW ACCESS WILL BE PROVIDED TO THE DAMPERS IN THE
 SUPPLY AND RETURN RISERS- SECTION 607.4 FBC M.
  
 6) M101: REQUIRED RETURN AIR FROM THE SECURITY- IT ROOM
 NOT SHOWN.
  
 7) M102: REQUIRED RETURN AIR FROM THE BREAKROOM NOT
 SHOWN.
  
 8) M102: CLARIFY IF ANY COOKING APPLIANCES OR EXHAUST
 HOOD SYSTEMS WILL BE INSTALLED IN THE BREAKROOM OR
 STAFF LOUNGE, AND PROVIDE DETAILS, SPECIFICATIONS, AND
 PRODUCT SUBMITTALS IF APPLICABLE. PLEASE NOTE THAT
 SEPARATE PERMITS ARE REQUIRED FOR KITCHEN EXHAUST HOODS
 AND FIR SUPPRESSION SYSTEMS.
  
 9) M102: THE CONDENSATE DRAINING INTO THE MOP SINK IS
 PROHIBITED PER SECTION 90-126 WPB CODE OF ORDINANCES
  
 10) M103: COMPLETE WIND LOAD ENGINEERING IS REQUIRED
 FOR THE RTU'S, ROOFTOP CONDENSER UNITS AND STANDS, AND
 THE EXHAUST FAN AND CURB- SECTION 301.15. PLEASE NOTE
 THE RTU DETAIL ON S-400 IS INCOMPLETE- RTU ATTACHMENT
 TO CURB NOT SHOWN AND NO DESIGN CRITERIA HAS BEEN
 PROVIDED.
  
 11) M103: SHOW HOW ACCESS IS BEING PROVIDED TO THE
 EQUIPMENT ON THE ROOF- SEE SECTION 306.5 FBC M.
  
 12) M103: VERIFY THE REQUIRED 10' REQUIRED CLEARANCE
 FOR THE SERVICEABLE ROOF TOP MECHANICAL EQUIPMENT TO
 THE ROOF EDGES OR VERIFY 42" GUARD OR PARAPET IN PLACE-
 SECTION 304.11 FBC M.
  
 13) THE PROPOSED PROJECT IS CLASSIFED AS A"RENOVATED
 BUILDING" PER SECTION 202 FBC EC. PLEASE SUBMIT AN
 ENERGY COM[PLIANCE REPORT IN ACCORDANCE WITH SECTIONS
 C101.5.1 & C101.5.1.1 FBC EC.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-12-13 Cont ID  
Sent By gjohnson Date 2018-12-13 Time 09:19 Rev Time 0.00
Received By gjohnson Date 2018-12-13 Time 09:19 Sent To  
Notes
2018-12-13 09:20:07PROVISO:
 1. PROVIDE FIRE STOPPING SPECIFICATIONS FOR FLOOR
 PENETRATIONS OF PVC AND METALLIC PIPING. PER WPB AMEND
 TO FBC 107.2.1
 2. PROVIDE FIRE STOPPING SPECIFICATIONS FOR WALL
 PENETRATIONS OF PVC PIPING. PER WPB AMEND TO FBC
 107.2.1
 3. PROVIDE DETAILS FOR SWAY BRACING PER FBC PL 308.6
 SWAY BRACING.RIGID SUPPORT SWAY BRACING SHALL BE
 PROVIDED AT CHANGES IN DIRECTION GREATER THAN 45
 DEGREES FOR PIPE SIZES 4 INCHES AND LARGER.
  
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date   Cont ID  
Sent By gjohnson Date 2018-11-01 Time 16:51 Rev Time 0.00
Received By gjohnson Date 2018-11-01 Time 16:51 Sent To  
Notes
2018-11-01 17:22:381ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. THE WHEELCHAIR ACCESSIBLE TOILET COMPARTMENT SHALL
 CONTAIN AN ACCESSIBLE LAVATORY WITHIN IT, WHICH MUST BE
 AT LEAST 19 INCHES WIDE BY 17 INCHES DEEP, NOMINAL
 SIZE, AND WALL-MOUNTED. THE LAVATORY SHALL BE MOUNTED
 SO AS NOT TO OVERLAP THE CLEAR FLOOR SPACE AREAS
 REQUIRED BY SECTION 604 FOR THE WHEELCHAIR ACCESSIBLE
 TOILET COMPARTMENT AND SHALL COMPLY WITH SECTION 606.
 SUCH LAVATORIES SHALL BE COUNTED AS PART OF THE
 REQUIRED FIXTURE COUNT FOR THE BUILDING. SEE ALSO
 SECTION 213.3.4. PER FBC ACC 604.8.1.6
  
 2. SHOW COMPLIANCE WITH FBC ACC 604.5.1 SIDE WALL.THE
 SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG MINIMUM,
 LOCATED 12 INCHES MAXIMUM FROM THE REAR WALL AND
 EXTENDING 54 INCHES MINIMUM FROM THE REAR WALL.
  
 3. SHOW COMPLIANCE WITH FBC ACC 604.7 DISPENSERS.TOILET
 PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND SHALL BE 7
 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT OF THE
 WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15
 INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR.
  
 4. PROVIDE AN ENLARGE DETAIL OF BATHROOMS AND SHOW THE
 REQUIRED CLEAR FLOOR SPACE FOR THE TOILET AND THE
 LAVATORY PLEASE INCLUDE THE DIMENSIONS ON THE CLEAR
 FLOOR SPACES. PER FBC ACC 604.8.1.1 , 606.2
  
 5. PROVIDE UL APPROVED DETAILS FOR THE FIRE STOPPING ON
 ALL THE PIPES. PER WPB AMEND TO FBC 107.2.1
  
 6. SHT. P-801.00 THE TEXT IS NOT LEGIBLE I CAN NOT
 DETERMINE CODE COMPLIANCE ALL SHEETS SHALL COMPLY WITH
 WPB AMEND TO FBC 107.2.1.3
  
 7. THE VENTS ON THE WATER CLOSETS ARE NOT CODE
 COMPLIANT DRY VENTS SHALL NOT RUN HORIZONTAL BELOW THE
 FLOOD LEVEL RIM OF THE FIXTURES THEY SHALL COMPLY WITH
 FBC PL 905.3 , 905.4
  
 8. PLEASE ENLARGE WATER AND SANITARY ISOMETRIC DRAWING
 THEY SHALL COMPLY WITH WPB AMEND TO FBC 107.2.1.3
  
 9. FBC PL 416.5 TEMPERED WATER SHALL BE DELIVERED FROM
 LAVATORIES AND GROUP WASH FIXTURES LOCATED IN PUBLIC
 TOILET FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3.
 THE NOTE ON THE WATER HEATER DETAIL STATE 140- 120 DEG.
 DOES NOT COMPLY FOR THE LAVATORIES IN THE BATHROOMS.
 TEMPERED WATER. WATER HAVING A TEMPERATURE RANGE
 BETWEEN 85?F (29?C) AND 110?F (43?C). UNDER 110 DEG.
  
 10. PLEASE PROVIDE MANUFACTURE SIZING FOR THE 1GAL
 WATER HEATER CAN SUPPLY THE REQUIRED TEMPERATURE WATER
 FOR 2 LAVATORIES THE BREAK ROOM SINK AND A SERVICE SINK
 SIMULTANEOUSLY. PER WPB AMEND TO FBC 107.2.1
  
 11. PROVIDE MANUFACTURE SPEC FOR URINAL FLUSHVALVE SHOW
 THAT 1/2" SUPPLY PIPING IS ADEQUATE AS SHOWN ON THE
 WATER ISOMETRIC DRAWING. PER WPB AMEND TO FBC 107.2.1
  
 12. SHT. P001 ON THE MAXIMUM FLOW RATE TABLE IT LIST
 THE MIAMI DADE CODE AND RESIDENTIAL THE PROJECT SHALL
 BE DESIGNED AND BUILT UNDER THE FBC PL AND FBC ACC 2017
 6TH EDITION PLEASE SHOW ON PLAN. PER WPB AMEND TO FBC
 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2018-12-21 Cont ID  
Sent By jpearson Date 2018-12-21 Time 13:17 Rev Time 0.00
Received By jpearson Date 2018-12-21 Time 13:17 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2018-12-04 Cont ID  
Sent By dbattles Date 2018-12-04 Time 10:50 Rev Time 0.00
Received By dbattles Date 2018-12-04 Time 10:50 Sent To  
Notes
2018-12-04 10:52:46SHEET 027 A-611.00 NOT DIGITALLY SIGNED
  
 ALL OTHER GOOD FOR SECOND REIVIEW.
 NEW SHEETS WILL NEED TO BE CHECKED IF THIRD ROUND OF
 COMMENTS NEEDED.
  
 DYLAN BATTLES
 [email protected]
 561-805-6718
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2018-10-18 Cont ID  
Sent By jpearson Date 2018-10-18 Time 09:27 Rev Time 0.00
Received By jpearson Date 2018-10-18 Time 09:27 Sent To  
Notes
2018-10-18 09:27:44PLAN IS REQUIRED TO BE SIGNED AND SEALED BY THE PERSON
 RESPONSIBLE FOR THE DESIGN. SHEET DE-103 HAS NO
 SIGNATURE. SHEETS S-001, S-100, S-101, S-102, S-200,
 S-201, S-300, S-301, AND S-400 HAVE A CORRUPTED
 SIGNATURE. A DIGITAL PLAN REQUIRES A DIGITAL SIGNATURE.
 PROVIDE CORRECTION. WPB FBC 107.1; FS 471/481

Review Stop Z ZONING
Rev No 2 Status P Date 2018-12-06 Cont ID  
Sent By aaponte Date 2018-12-06 Time 10:54 Rev Time 0.00
Received By aaponte Date 2018-12-06 Time 10:54 Sent To  
Notes
2019-01-09 10:48:31PROVISO: IF NEW MECHANICHAL EQUIPMENT IS BEING
 INSTALLED IN THE ROOF, UNITS SHALL BE SCREENED WITH
 WALL OR LOUVERS AS TALL AS THE UNIT.
 FOR ADDITIONAL INFORMAITON PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.

Review Stop Z ZONING
Rev No 1 Status P Date 2018-11-16 Cont ID  
Sent By aaponte Date 2018-11-16 Time 12:19 Rev Time 0.00
Received By aaponte Date 2018-11-16 Time 12:19 Sent To  
Notes
***NONE***