Plan Review Details - Permit 18091249
Plan Review Stops For Permit 18091249
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-11-21 Cont ID  
Sent By cthroop Date 2018-11-21 Time 16:51 Rev Time 0.00
Received By cthroop Date 2018-11-21 Time 15:33 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-10-29 Cont ID  
Sent By cthroop Date 2018-10-29 Time 13:18 Rev Time 0.00
Received By cthroop Date 2018-10-29 Time 12:13 Sent To  
Notes
2018-10-29 13:30:14BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. INCLUDE ADDRESS OF SITE ON PLANS.
 ADDRESSING:
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED.
  
 2. PROVIDE A DETAILED DESIGN OF THE ROOF TO STANCHION
 CONNECTION FOR BOTH SHINGLE AND TILE ROOF SYSTEMS.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
 3. PROVIDE ROOF PLAN. INDICATE LOCATION OF PROPOSED
 SOLAR PANELS.
 FBC 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 THE EXAMINATION OF THE DOCUMENTS BY THE BUILDING
 OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA
 AND DOCUMENTS: A FLOOR PLAN; SITE PLAN; FOUNDATION
 PLAN; FLOOR/ROOF FRAMING PLAN OR TRUSS LAYOUT; ALL
 FENESTRATION PENETRATIONS; FLASHING; AND ROUGH OPENING
 DIMENSIONS; AND ALL EXTERIOR ELEVATIONS:
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2018-11-21 Cont ID  
Sent By jleahy Date 2018-11-21 Time 11:26 Rev Time 0.00
Received By jleahy Date 2018-11-21 Time 11:26 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-10-04 Cont ID  
Sent By jleahy Date 2018-10-04 Time 09:26 Rev Time 0.00
Received By jleahy Date 2018-10-04 Time 09:26 Sent To P
Notes
2018-10-04 09:27:35NO ELECTRIC SHOWN, SOMETHING HAS TO PUSH THE WATER
 THROUGH THE COLLECTORS ON THE ROOF.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-11-21 Cont ID  
Sent By cthroop Date 2018-11-21 Time 16:52 Rev Time 0.00
Received By cthroop Date 2018-11-08 Time 13:13 Sent To  
Notes
2018-11-09 13:13:38RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-10-29 Cont ID  
Sent By cthroop Date 2018-10-29 Time 13:18 Rev Time 0.00
Received By cthroop Date 2018-09-27 Time 14:08 Sent To  
Notes
2018-10-12 08:49:5210/12 TO ZONING
  
2018-09-28 14:08:31ROUTED TO JLEAHY

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-11-20 Cont ID  
Sent By lcrespo Date 2018-11-20 Time 14:38 Rev Time 0.00
Received By lcrespo Date 2018-11-20 Time 14:38 Sent To  
Notes
2018-11-20 14:39:0311/20/18 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVE PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-10-09 Cont ID  
Sent By lcrespo Date 2018-10-09 Time 06:06 Rev Time 0.00
Received By lcrespo Date 2018-10-09 Time 06:06 Sent To  
Notes
2018-10-09 06:08:5210/09/2018 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. A COMPREHENSIVE PLAN REVIEW HAS NOT BEEN PERFORMED
 AT THIS TIME; PLEASE PROVIDE INFORMATION AS REQUESTED
 BELOW, WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 2. PLEASE PROVIDE A PLUMBING RISER DIAGRAM FORM WATER
 HEATER TO COLLECTOR TACK AND SHOW THERMAL EXPANSION
 WITH TYPE OF INSULATION, WPB AMENDMENTS TO THE FBC SEC.
 107.3.5.3 (11) RESIDENTIAL PLUMBING.
 3. PLEASE PROVIDE APRICUS INSTALLATION MANUAL WHICH IS
 REFERRED ON NOT #5, WPB AMENDMENTS TO THE FBC SEC.
 107.2.1. INFORMATION ON CONSTRUCTION DOCUMENTS.
 4. THERE ARE TWO COLLECTOR SPECIFIED ON PLANS, ETC 20
 AND ETC 30, PLEASE REFLECT CORRECT ONE ON ALL AREAS,
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 5. IS THIS A TILT OR A FLUSH MOUNT UNIT, PLEASE
 CLARIFY, WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
 6. A SUB ELECTRICAL PERMIT MAY BE REQUIRED FOR THIS
 UNIT, WPB AMENDMENTS TO THE FBC SEC. 105.1
 7. THE ADDRESS OF PROJECT OR RESIDENCE MUST BE ON PLAN.
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  

Review Stop Z ZONING
Rev No 2 Status P Date 2018-11-15 Cont ID  
Sent By hmtribou Date 2018-11-15 Time 13:02 Rev Time 0.00
Received By hmtribou Date 2018-11-15 Time 13:02 Sent To P
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2018-10-18 Cont ID  
Sent By hmtribou Date 2018-10-18 Time 15:30 Rev Time 0.00
Received By hmtribou Date 2018-10-18 Time 15:30 Sent To B
Notes
2018-10-18 15:32:35PLEASE PROVIDE PLAN OF LOCATION OF SOLAR PANEL
 COLLECTORS. PANLES MAY NOT EXTEND PAST ROOF. PANELS
 MUST BE PARALLEL TO THE ROOF SURFACE LOCATED NO MORE
 THAN 12" ABOVE THE ROOF'S SURFACE.