Plan Review Details - Permit 18091158
Plan Review Stops For Permit 18091158
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-10-18 Cont ID  
Sent By shill Date 2018-10-18 Time 18:02 Rev Time 0.00
Received By shill Date 2018-10-18 Time 18:00 Sent To  
Notes
2018-10-18 18:08:18PROVIDE EVIDENCE OF SEOR REVIEW OF DELEGATED
 ENGINEERING
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-10-06 Cont ID  
Sent By shill Date 2018-10-06 Time 13:14 Rev Time 0.00
Received By shill Date 2018-10-06 Time 13:11 Sent To  
Notes
2018-10-06 13:08:30****CORRECTIONS****
 REVISED 10/11
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. DELEGATED ENGINEERING IS TO BE REVIEWED BY
 STRUCTURAL ENGINEER OF RECORD, FAC61G15-23.
  
 2. PRECAST CALCS SHOW A DESIGN OF 170MPH, SEE COMMENT
 #4 AND CORRELATE IF NECESSARY.
  
 3. PRECAST SHORING IS NOT DIGITALLY SIGNED. AS THE
 ENGINEER HAS A DIGITAL SIGNATURE, PLEASE SEND THE
 ORIGINAL TO ME VIA EMAIL (NO MARKUPS AFTER SIGNING AS
 THAT WILL INVALIDATE THE SEAL).
  
 4. GS001, WIND DESIGN CRITERIA IS IMPORTANCE FACTOR
 III, 170MPH; SHOULDN'T THIS BE 180MPH? SEE FBC B 1609,
 ALSO THE FOLLOWING WEBSITE:
  
 HTTP://WINDSPEED.ATCOUNCIL.ORG/
  
 170MPH IS OK FOR IMPORTANCE FACTOR II. EITHER REVISE
 WIND SPEED OR IMPORTANCE FACTOR TO CORRELATE, MAKE SURE
 THAT PRECAST MATCHES.
  
 5. NA
  
 6. FS553, PROVIDE PRIVATE PROVIDER STAMP AND AFFIDAVIT.
  
  
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-10-19 Cont ID  
Sent By pleduc Date 2018-10-19 Time   Rev Time 0.00
Received By pleduc Date 2018-10-19 Time 10:07 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-10-10 Cont ID  
Sent By pleduc Date 2018-10-10 Time   Rev Time 0.00
Received By pleduc Date 2018-10-09 Time 10:21 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-10-22 Cont ID  
Sent By lmarchan Date 2018-10-22 Time 08:12 Rev Time 0.00
Received By lmarchan Date 2018-10-18 Time 11:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-10-12 Cont ID  
Sent By lmarchan Date 2018-10-12 Time 16:48 Rev Time 0.00
Received By lmarchan Date 2018-09-28 Time 12:53 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2018-12-20 Cont ID  
Sent By shill Date 2018-12-20 Time 10:45 Rev Time 0.00
Received By shill Date 2018-12-20 Time 10:45 Sent To  
Notes
2018-12-20 10:45:42ORIGINAL PAPER DOCUMENTS RECEIVED; ROUTED TO RECORDS SH

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2018-10-18 Cont ID  
Sent By shill Date 2018-10-18 Time 18:03 Rev Time 0.00
Received By shill Date 2018-10-18 Time 18:03 Sent To  
Notes
2018-10-18 18:04:06PROVISO:
 PRIOR TO ISSUANCE OF THIS REVISION, SUBMIT THE ORIGINAL
 SIGNED AND SEALED CALCS
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2018-10-06 Cont ID  
Sent By shill Date 2018-10-06 Time 13:11 Rev Time 0.00
Received By shill Date 2018-10-06 Time 13:11 Sent To  
Notes
2018-10-06 13:02:11****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. SHORING CALCS ARE NOT DIGITALLY SIGNED; PLEASE SEND
 TO ME VIA EMAIL.
  
 2. THE PRECAST DESIGN CALCS SIGNATURE IS OK BUT SEE
 BUILDING COMMENTS (WILL BE REPLACED AFTER CORRECTION).
  
 3. PLAN PAGES DIGITAL SIGNATURE OK, ANY NEW SHEETS
 SUBMITTED NEXT REVIEW CYCLE REQUIRED REVIEW.
  
  
  
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2018-10-19 Cont ID  
Sent By eschneid Date 2018-10-19 Time 15:46 Rev Time 0.25
Received By eschneid Date 2018-10-19 Time 15:46 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2018-10-12 Cont ID  
Sent By eschneid Date 2018-10-12 Time 16:21 Rev Time 1.00
Received By eschneid Date 2018-10-12 Time 16:21 Sent To  
Notes
2018-10-12 16:42:53FAILED
  
 PROVIDE WRITTEN RESPONSES TO COMMENTS.
  
 1) IN ACCORDANCE WITH THE APPROVED ELEVATIONS (AND TO
 MATCH THE EXISTING DREYFOOS HALL), THE BANDING AT THE
 CORNERS OF THE GARAGE NEEDS TO BE RAISED OFF THE PLANE
 OF THE FACADE. THIS IS NOT CLEARLY DEMONSTRATED FOR ALL
 OF THE BANDING REQUIRED.
  
 2) THE NORTH ELEVATION (OVER THE VEHICLE EGRESS POINT)
 IS DIFFERENT FROM THE CITY COMMISSION APPROVED PLANS.
 THE PERMIT SET SHOWS OPENINGS IN THE WALL. THE APPROVED
 PLANS SHOW BOTH OF THESE AREAS AS SOLID STUCCO FINISHED
 WALLS.
  
 3) THE WEST ELEVATION SHOWS A SOLID WALL WHERE THE
 APPROVED PLANS SHOW THE SCREEN WALL. THIS AREA IS
 REQUIRED TO HAVE THE SCREENING APPLIED PER THE CITY
 COMMISSION APPROVAL.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]