Plan Review Details - Permit 18091065
Plan Review Stops For Permit 18091065
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-01-11 Cont ID  
Sent By skennedy Date 2019-01-11 Time 08:43 Rev Time 0.00
Received By skennedy Date 2019-01-11 Time 08:43 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-11-15 Cont ID  
Sent By skennedy Date 2018-11-15 Time 10:01 Rev Time 0.00
Received By skennedy Date 2018-11-15 Time 10:01 Sent To  
Notes
2018-11-15 11:24:361ST REVIEW FBC 2017 EXISTING BUILDING
  
 FAILED:
  
 1) SHEET LS1.1 - THE CODE REFERENCE CITED IS 2014 FBC.
 PLEASE CORRECT TO THE CODE IN EFFECT WHICH IS THE 2017
 FBC,
  
 2) SHEET LS1.1 - THE CODE REFERENCE LISTS THE TYPE OF
 CONSTRICTION AS VB AND INDICATES THE BUILDING AS TWO
 STORIES NOT EXCEEDING 9,000 SF PER FLOOR. PLEASE CHECK
 THE BUILDING RECORD FOR ACCURACY AND VERIFY THE
 CONSTRUCTION TYPE CLASSIFICATION PER THE APPLICABLE
 CODE. PLEASE NOTE THE BUILDING APPEARS LARGER THAN
 INDICATED.
  
 3) SHEET LS1.1 - THE PLAN IS NOT DIMENSIONED. PLEASE
 PROVIDE AT A MINIMUM, OVERALL DIMENSIONS PER FBC 107
 AND TABULAR DATA FOR VERIFICATION OF THE DETERMINED
 OCCUPANT LOAD PER FBC T1004
  
 4) FBC ACCESSIBILITY - 202.4ALTERATIONS AFFECTING
 PRIMARY FUNCTION AREAS. PLEASE INDICATE THE LEVEL OF
 COMPLIANCE WITH ACCESSIBILITY CRITERIA. FOR EXAMPLE IS
 THE ENTRANCE ACCESSIBLE IS THERE ANY NEED TO PROVIDE
 ENHANCEMENTS PURSUANT TO THE FOREGOING SECTION. IT
 APPEARS THAT PART OF THE IMPROVEMENT COST RESULTS IN A
 BREAKROOM AREA THAT IS COMPLIANT. IF THERE IS NO NEED
 TO FURTHER EVALUATE OR PROVIDE ENHANCEMENTS PLEASE
 INDICATE SO.
  
 5) SUITE NUMBER IDENTIFICATION. THE TITLE BLOCK
 INDICATE THE SPACE IS KNOWN AS OR TO BE KNOWN AS SUITE
 #100. THERE ARE MANY SUITE NUMBERS ON RECORD AT THIS
 ADDRESS HOWEVER NONE PREVIOUSLY AS 100. THE PERMIT
 APPLICATION PROGRAM CAN BE ADJUSTED TO IDENTIFY THE
 IMPROVEMENTS AT THIS SUITE NUMBER.
  
  
 STEVEN KENNEDY, CBO
 ASSISTANT BUILDING OFFICIAL
 (561) 805-6710
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-01-15 Cont ID  
Sent By jpearson Date 2019-01-15 Time 07:10 Rev Time 0.00
Received By jpearson Date 2019-01-15 Time 07:10 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-01-07 Cont ID  
Sent By jpearson Date 2019-01-07 Time 11:10 Rev Time 0.00
Received By jpearson Date 2019-01-07 Time 10:35 Sent To  
Notes
2019-01-07 10:45:13CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
 (S)
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. FBC 109.3
 (NOT PROVIDED.)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-10-29 Cont ID  
Sent By jpearson Date 2018-10-29 Time 14:11 Rev Time 0.00
Received By jpearson Date 2018-10-29 Time 13:35 Sent To  
Notes
2018-10-29 14:11:49CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PER THE WPB AMENDMENTS TO THE FBC, PLAN (EACH SHEET
 OF BOTH COPIES) IS REQUIRED TO BEAR THE NAME AND BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. PROVIDE CORRECTION. WPB FBC 107.1, 107.2; FS
 471, 481
 2. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. FBC 109.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-09-28 Cont ID  
Sent By pleduc Date 2018-09-28 Time   Rev Time 0.00
Received By pleduc Date 2018-09-28 Time 10:52 Sent To  
Notes
2018-09-28 11:01:57THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THERE ARE NO INDICATIONS OF EXISTING OR NEW EXIT
 SIGNAGE ALONG THE EGRESS TAVEL PATH.
  
 ENSURE PROPER PLACEMENT PER NFPA 101, CHAPTER 7, MEANS
 OF EGRESS.
  
 7.10.2 DIRECTIONAL SIGNS.
 7.10.2.1 A SIGN COMPLYING WITH 7.10.3, WITH A
 DIRECTIONAL
 INDICATOR SHOWING THE DIRECTION OF TRAVEL, SHALL BE
 PLACED IN EVERY
 LOCATION WHERE THE DIRECTION OF TRAVEL TO REACH THE
 NEAREST EXIT IS
 NOT APPARENT
  
  
  
 2) ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR
 CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND
 SPRINKLER SYSTEM FOR CODE COVERAGE AND COMPLIANCE BY
 CERTIFIED LIFE SAFETY CONTRACTORS.
  
  
 3) ANY AND ALL WORK ON THE FIRE ALARM AND FIRE
 SPRINKLER SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP
 DRAWINGS AND BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
  
 4) THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-01-11 Cont ID  
Sent By gjohnson Date 2019-01-11 Time 14:20 Rev Time 0.00
Received By gjohnson Date 2018-12-14 Time 10:59 Sent To  
Notes
2018-12-18 10:59:40C22

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-11-15 Cont ID  
Sent By tklarge Date 2018-11-15 Time 11:39 Rev Time 0.00
Received By tklarge Date 2018-09-25 Time 12:51 Sent To  
Notes
2018-09-27 12:51:41C12

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2019-01-02 Cont ID  
Sent By cmontell Date 2019-01-02 Time 11:49 Rev Time 0.00
Received By cmontell Date 2019-01-02 Time 11:27 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-11-06 Cont ID  
Sent By cmontell Date 2018-11-06 Time 11:17 Rev Time 0.00
Received By cmontell Date 2018-11-06 Time 11:00 Sent To  
Notes
2018-11-06 11:03:56MECHANICAL PLAN REVIEW FAIL
  
  
 1. PER THE WPB AMENDMENTS TO THE FBC, PLAN (EACH SHEET
 OF BOTH COPIES) IS REQUIRED TO BEAR THE NAME AND BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE. WPB FBC
 107.1
  
  
 CHRIS MONTELLO
 561-805-6733
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-01-11 Cont ID  
Sent By gjohnson Date 2019-01-11 Time 14:20 Rev Time 0.00
Received By gjohnson Date 2019-01-11 Time 14:20 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-11-15 Cont ID  
Sent By tklarge Date 2018-11-15 Time 11:38 Rev Time 0.00
Received By tklarge Date 2018-11-15 Time 05:31 Sent To I
Notes
2018-11-15 10:53:411) THE PLUMBING PLANS SHALL BEAR THE SEAL AND SIGNATURE
 OF THE DESIGN PROFESSIONAL OF RECORD PER FL. ADMIN.
 CODE RULE 61G15-23.001.
 2) THE LEVEL OF ALTERATION SHALL BE LISTED ON THE PLANS
 PER THE 2017 FBC-EXISTING BUILDING CODE SEC.301.1.
 3) SHT. LS 1.1 - THE EDITION OF CODES IN EFFECT FOR
 THIS PROJECT IS THE 2017 EDITION, NOT THE 2014 AS NOTED
 ON THE PLANS.WPB AMEND. TO FBC SEC. 101.4.
 4) THE PLANS SHOW A DENTAL OFFICE. DESCRIBE THE TYPE OF
 ACTIVITY THAT WILL TAKE PLACE IN THIS ROOM. WPB AMEND.
 TO FBC SEC. 107.2.1.
 5) SHT. P 1.0 - THE DRINKING FOUNTAIN IS NOT SHOWN ON
 THE SANITARY OR WATER RISER DIAGRAMS. WPB AMEND. TO FBC
 SEC. 107. 3.5.1.3.
 6) WHERE IS THE SERVICE SINK? A SERVICE SINK IS
 REQUIRED PER THE 2017 FBC-PLUMBING TABLE 403.1.
 7) THE "S-1" SINKS ARE INSTALLED ON A VERTICAL WET
 VENT. ONLY FIXTURES WITHIN A BATHROOM GROUP ARE
 PERMITTED TO BE INSTALLED ON A WET VENT PER 2017
 FBC-PLUMBING SEC.912.1.1. REFER TO THE DEFINITION OF
 ""BATHROOM GROUP" IN SECTION 202 OF THE PLUMBING CODE.
 8) PLEASE PROVIDE DIMENSIONS OF THE ROOMS INCLUDING THE
 TOILET ROOMS. FBC SEC. 107.2.1.
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  