Plan Review Stops For Permit 18091065 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2019-01-11 |
|
|
Cont ID |
|
Sent By |
skennedy |
Date |
2019-01-11 |
Time |
08:43 |
Rev Time |
0.00 |
Received By |
skennedy |
Date |
2019-01-11 |
Time |
08:43 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2018-11-15 |
|
|
Cont ID |
|
Sent By |
skennedy |
Date |
2018-11-15 |
Time |
10:01 |
Rev Time |
0.00 |
Received By |
skennedy |
Date |
2018-11-15 |
Time |
10:01 |
Sent To |
|
|
Notes |
2018-11-15 11:24:36 | 1ST REVIEW FBC 2017 EXISTING BUILDING | | | | FAILED: | | | | 1) SHEET LS1.1 - THE CODE REFERENCE CITED IS 2014 FBC. | | PLEASE CORRECT TO THE CODE IN EFFECT WHICH IS THE 2017 | | FBC, | | | | 2) SHEET LS1.1 - THE CODE REFERENCE LISTS THE TYPE OF | | CONSTRICTION AS VB AND INDICATES THE BUILDING AS TWO | | STORIES NOT EXCEEDING 9,000 SF PER FLOOR. PLEASE CHECK | | THE BUILDING RECORD FOR ACCURACY AND VERIFY THE | | CONSTRUCTION TYPE CLASSIFICATION PER THE APPLICABLE | | CODE. PLEASE NOTE THE BUILDING APPEARS LARGER THAN | | INDICATED. | | | | 3) SHEET LS1.1 - THE PLAN IS NOT DIMENSIONED. PLEASE | | PROVIDE AT A MINIMUM, OVERALL DIMENSIONS PER FBC 107 | | AND TABULAR DATA FOR VERIFICATION OF THE DETERMINED | | OCCUPANT LOAD PER FBC T1004 | | | | 4) FBC ACCESSIBILITY - 202.4ALTERATIONS AFFECTING | | PRIMARY FUNCTION AREAS. PLEASE INDICATE THE LEVEL OF | | COMPLIANCE WITH ACCESSIBILITY CRITERIA. FOR EXAMPLE IS | | THE ENTRANCE ACCESSIBLE IS THERE ANY NEED TO PROVIDE | | ENHANCEMENTS PURSUANT TO THE FOREGOING SECTION. IT | | APPEARS THAT PART OF THE IMPROVEMENT COST RESULTS IN A | | BREAKROOM AREA THAT IS COMPLIANT. IF THERE IS NO NEED | | TO FURTHER EVALUATE OR PROVIDE ENHANCEMENTS PLEASE | | INDICATE SO. | | | | 5) SUITE NUMBER IDENTIFICATION. THE TITLE BLOCK | | INDICATE THE SPACE IS KNOWN AS OR TO BE KNOWN AS SUITE | | #100. THERE ARE MANY SUITE NUMBERS ON RECORD AT THIS | | ADDRESS HOWEVER NONE PREVIOUSLY AS 100. THE PERMIT | | APPLICATION PROGRAM CAN BE ADJUSTED TO IDENTIFY THE | | IMPROVEMENTS AT THIS SUITE NUMBER. | | | | | | STEVEN KENNEDY, CBO | | ASSISTANT BUILDING OFFICIAL | | (561) 805-6710 | | [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2019-01-15 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2019-01-15 |
Time |
07:10 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2019-01-15 |
Time |
07:10 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2019-01-07 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2019-01-07 |
Time |
11:10 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2019-01-07 |
Time |
10:35 |
Sent To |
|
|
Notes |
2019-01-07 10:45:13 | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | 6TH ED, CHAPTER 1. | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | (S) | | | | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED | | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS | | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY | | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW | | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. | | | | 1. CORRECTED. | | 2. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS | | LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND | | VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS | | IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. FBC 109.3 | | (NOT PROVIDED.) | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD | | SHEETS. | | | | SINCERELY, | | | | JOHN PEARSON | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2018-10-29 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2018-10-29 |
Time |
14:11 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2018-10-29 |
Time |
13:35 |
Sent To |
|
|
Notes |
2018-10-29 14:11:49 | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | 6TH ED, CHAPTER 1. | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1. PER THE WPB AMENDMENTS TO THE FBC, PLAN (EACH SHEET | | OF BOTH COPIES) IS REQUIRED TO BEAR THE NAME AND BE | | SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE | | DESIGN. PROVIDE CORRECTION. WPB FBC 107.1, 107.2; FS | | 471, 481 | | 2. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS | | LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND | | VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS | | IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. FBC 109.3 | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD | | SHEETS. | | | | SINCERELY, | | | | JOHN PEARSON | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2018-09-28 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2018-09-28 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2018-09-28 |
Time |
10:52 |
Sent To |
|
|
Notes |
2018-09-28 11:01:57 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | INSPECTION. | | | | | | 1) THERE ARE NO INDICATIONS OF EXISTING OR NEW EXIT | | SIGNAGE ALONG THE EGRESS TAVEL PATH. | | | | ENSURE PROPER PLACEMENT PER NFPA 101, CHAPTER 7, MEANS | | OF EGRESS. | | | | 7.10.2 DIRECTIONAL SIGNS. | | 7.10.2.1 A SIGN COMPLYING WITH 7.10.3, WITH A | | DIRECTIONAL | | INDICATOR SHOWING THE DIRECTION OF TRAVEL, SHALL BE | | PLACED IN EVERY | | LOCATION WHERE THE DIRECTION OF TRAVEL TO REACH THE | | NEAREST EXIT IS | | NOT APPARENT | | | | | | | | 2) ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR | | CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND | | SPRINKLER SYSTEM FOR CODE COVERAGE AND COMPLIANCE BY | | CERTIFIED LIFE SAFETY CONTRACTORS. | | | | | | 3) ANY AND ALL WORK ON THE FIRE ALARM AND FIRE | | SPRINKLER SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP | | DRAWINGS AND BY CERTIFIED LIFE SAFETY CONTRACTORS. | | | | | | 4) THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE | | SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE | | CONSTRUCTION PERIOD. | | | | | | | | PETER LEDUC | | FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE | | 561-804-4709 | | [email protected] | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2019-01-11 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2019-01-11 |
Time |
14:20 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2018-12-14 |
Time |
10:59 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2018-11-15 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2018-11-15 |
Time |
11:39 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2018-09-25 |
Time |
12:51 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2019-01-02 |
|
|
Cont ID |
|
Sent By |
cmontell |
Date |
2019-01-02 |
Time |
11:49 |
Rev Time |
0.00 |
Received By |
cmontell |
Date |
2019-01-02 |
Time |
11:27 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2018-11-06 |
|
|
Cont ID |
|
Sent By |
cmontell |
Date |
2018-11-06 |
Time |
11:17 |
Rev Time |
0.00 |
Received By |
cmontell |
Date |
2018-11-06 |
Time |
11:00 |
Sent To |
|
|
Notes |
2018-11-06 11:03:56 | MECHANICAL PLAN REVIEW FAIL | | | | | | 1. PER THE WPB AMENDMENTS TO THE FBC, PLAN (EACH SHEET | | OF BOTH COPIES) IS REQUIRED TO BEAR THE NAME AND BE | | SIGNED AND SEALED BY THE PERSON RESPONSIBLE. WPB FBC | | 107.1 | | | | | | CHRIS MONTELLO | | 561-805-6733 | | [email protected] | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2019-01-11 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2019-01-11 |
Time |
14:20 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2019-01-11 |
Time |
14:20 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2018-11-15 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2018-11-15 |
Time |
11:38 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2018-11-15 |
Time |
05:31 |
Sent To |
I |
|
Notes |
2018-11-15 10:53:41 | 1) THE PLUMBING PLANS SHALL BEAR THE SEAL AND SIGNATURE | | OF THE DESIGN PROFESSIONAL OF RECORD PER FL. ADMIN. | | CODE RULE 61G15-23.001. | | 2) THE LEVEL OF ALTERATION SHALL BE LISTED ON THE PLANS | | PER THE 2017 FBC-EXISTING BUILDING CODE SEC.301.1. | | 3) SHT. LS 1.1 - THE EDITION OF CODES IN EFFECT FOR | | THIS PROJECT IS THE 2017 EDITION, NOT THE 2014 AS NOTED | | ON THE PLANS.WPB AMEND. TO FBC SEC. 101.4. | | 4) THE PLANS SHOW A DENTAL OFFICE. DESCRIBE THE TYPE OF | | ACTIVITY THAT WILL TAKE PLACE IN THIS ROOM. WPB AMEND. | | TO FBC SEC. 107.2.1. | | 5) SHT. P 1.0 - THE DRINKING FOUNTAIN IS NOT SHOWN ON | | THE SANITARY OR WATER RISER DIAGRAMS. WPB AMEND. TO FBC | | SEC. 107. 3.5.1.3. | | 6) WHERE IS THE SERVICE SINK? A SERVICE SINK IS | | REQUIRED PER THE 2017 FBC-PLUMBING TABLE 403.1. | | 7) THE "S-1" SINKS ARE INSTALLED ON A VERTICAL WET | | VENT. ONLY FIXTURES WITHIN A BATHROOM GROUP ARE | | PERMITTED TO BE INSTALLED ON A WET VENT PER 2017 | | FBC-PLUMBING SEC.912.1.1. REFER TO THE DEFINITION OF | | ""BATHROOM GROUP" IN SECTION 202 OF THE PLUMBING CODE. | | 8) PLEASE PROVIDE DIMENSIONS OF THE ROOMS INCLUDING THE | | TOILET ROOMS. FBC SEC. 107.2.1. | | | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | | | |
|
|