Plan Review Details - Permit 18090957
Plan Review Stops For Permit 18090957
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2019-02-19 Cont ID  
Sent By pvalenti Date 2019-02-19 Time 14:01 Rev Time 0.00
Received By pvalenti Date 2019-02-19 Time 14:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-01-23 Cont ID  
Sent By pvalenti Date 2019-01-23 Time 10:03 Rev Time 0.00
Received By pvalenti Date 2019-01-23 Time 10:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-01-04 Cont ID  
Sent By shill Date 2019-01-04 Time 17:55 Rev Time 0.00
Received By shill Date 2019-01-04 Time 06:54 Sent To  
Notes
2019-01-04 18:03:29****CORRECTIONS****
 ****REVISED 1/12/19***
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. RAS 117 CALCULATIONS WERE SUBMITTED, BUT ARE
 DESIGNED TO THE WRONG WIND SPEED, SEE MASTER PERMIT
 (170 RATHER THAN 180). A ROOF SUB PERMIT WAS SUBMITTED;
 CAN THIS DOCUMENT BE DELETED?
  
 2. COMMENT FROM FIRST REVIEW: FBC 107, AN INDEX PAGE IS
 SUGGESTED. NOTE THAT, WITHOUT AN INDEX, IT IS VERY
 DIFFICULT TO FIND INFORMATION. FOR INSTANCE, LS001
 WHICH INCLUDES INFORMATION NEEDED FOR REVIEW OF ALL
 OTHER SHEETS, IS AT THE END OF THE FILE DUE TO THE WAY
 THAT IT WAS NAMED; THIS IS TYPICALLY IN THE BEGINNING
 OR RIGHT AFTER CIVILS.
  
 2ND REVIEW - DOCUMENT "101 - GI1000, 102 - GI1001",
 ETC. WERE UPLOADED. AS THE OTHER DOCUMENTS ARE A ZERO
 SERIES (001, 052, 060, ETC.) THE INDEX APPEARS AT THE
 END OF THE DOCUMENT. SINCE THE PURPOSE WAS TO MAKE THE
 PLAN EASIER TO REVIEW AND TO FIND INFORMATION, PLEASE
 RENAME SO IT APPEARS BEFORE THE OTHER SHEETS RATHER
 THAN AT THE END.
  
 3-4. OK
  
 4. COMMENT FROM FIRST REVIEW: DA121, FBC B 1017, SECOND
 TIER LEVEL, EXITING FOR THE STORAGE AREAS IS NOT CLEAR.
 REVISE PLAN TO SHOW EXIT ACCESS TRAVEL DISTANCE.
  
 2ND REVIEW, LS003A & DA131, 209'4" AND 212' ARE NOTED
 AS THE TRAVEL DISTANCE BUT THE LOCATION OF THE EXIT IS
 NOT CLEAR. THE PATH OF EGRESS SHOWN ON THE PLAN APPEARS
 TO END IN THE MIDDLE OF AN OPEN STAIR. CLARIFY EXIT
 LOCATION AND TRAVEL DISTANCE. LS003A DOES NOT APPEAR TO
 SHOW THE EXIT. IF THIS IS COVERED UNDER AN EXCEPTION,
 PLEASE REVISE PLAN TO INCLUDE.
  
 5. COMMENT FROM FIRST REVIEW: DA131, FBC B 1017, THIRD
 TIER LEVEL, EXITING FOR THE STORAGE AREAS IS NOT CLEAR.
 REVISE PLAN TO SHOW EXIT ACCESS TRAVEL DISTANCE.
  
 2ND REVIEW, LS003A, DA131, 209'4" AND 212' ARE NOTED AS
 THE TRAVEL DISTANCES. THIS IS THE SAME AS 2ND FLOOR BUT
 BOTH APPEAR TO TRAVEL THROUGH AN UNPROTECTED STAIR, NOT
 CLEAR WHERE 209'4" ENDS FOR EACH STAIR. IF 209'4" IS
 THE DISTANCE FROM 2ND FLOOR STORAGE ROOM TO AN EXIT,
 AND 3RD FLOOR USES THE SAME TRAVEL PATH BUT IS ONE
 FLOOR HIGHER, IT APPEARS THAT THE 3RD FLOOR NUMBER
 SHOULD BE A LARGER NUMBER.
  
 6-7. OK
  
 8. PRECAST ENGINEERING IN SUPPORTING DOCUMENTS,
 DELEGATED ENGINEERING IS TO BE REVIEWED BY SEOR,
 FAC61G15.
  
 2ND REVIEW, RESPONSE LETTER STATES TO REFER TO REVIEW
 LETTER; UNABLE TO LOCATE. PLEASE PROVIDE OR ADVISE AS
 TO FILE NAME.
  
 9. OK
  
 NEW COMMENT:
  
 10. PER OUR DISCUSSION - SUBMIT THE DELEGATED
 ENGINEERING AND ENGINEERED SHOP DRAWINGS AS A
 SUBMITTAL. SUBMIT THE MISSING PAGE DS502 AS A REVISION
 TO 18060764. IT IS MY UNDERSTANDING THAT THIS IS IN
 PROGRESS (PENDING CITY STAFF GENERATING A PROJECTDOX
 SUBMITTAL AND INVIDATION TO UPLOAD).
  
 11. THIS PERMIT WILL BE ISSUED WITH THE FOLLOWING
 PROVISOS:
  
 A. A SEPARATE ROOF PERMIT IS REQUIRED. PRIOR TO
 INSTALLATION, SUBMIT ROOF PERMIT APPLICATION WITH
 PRODUCT APPROVALS REVIEWED BY DESIGNER OF RECORD AND
 ENGINEERING FOR ENHANCED FASTENING IF APPLICABLE.
  
 B. COMPONENT & CLADDING PRODUCT APPROVALS REVIEWED BY
 DESIGNER OF RECORD ARE TO BE SUBMITTED TO THE BUILDING
 DIVISION, REVIEWED AND ISSUED PRIOR TO INSTALLATION.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-11-02 Cont ID  
Sent By shill Date 2018-11-02 Time 16:33 Rev Time 0.00
Received By shill Date 2018-11-02 Time 06:11 Sent To  
Notes
2018-11-02 16:34:04****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. ROOF PRODUCT APPROVAL WAS SUBMITTED; FBC 107 PRODUCT
 APPROVALS ARE TO BE REVIEWED BY DESIGNER OF RECORD
 PRIOR TO SUBMITTAL TO THE CITY. NOTE THAT THE ASSEMBLY
 DOES NOT MEET THE DESIGN PRESSURES FOR ZONES 2 & 3, SO
 RAS 117 CALCULATIONS ARE REQUIRED.
  
 THIS CAN BE ADDRESSED AT THIS TIME OR WILL BE A PROVISO
 ITEM, SUBMIT WITH ROOF PERMIT APPLICATION, REVIEW
 REQUIRED AT THAT TIME.
  
 2. FBC 107, AN INDEX PAGE IS SUGGESTED. NOTE THAT,
 WITHOUT AN INDEX, IT IS VERY DIFFICULT TO FIND
 INFORMATION. FOR INSTANCE, LS001 WHICH INCLUDES
 INFORMATION NEEDED FOR REVIEW OF ALL OTHER SHEETS, IS
 AT THE END OF THE FILE DUE TO THE WAY THAT IT WAS
 NAMED; THIS IS TYPICALLY IN THE BEGINNING OR RIGHT
 AFTER CIVILS.
  
 3. LS001, LS002, A TEMPORARY LIFE SAFETY PLAN WAS
 PROVIDED FOR TWO LEVELS. PROVIDE A LIFE SAFETY PLAN FOR
 FINISHED CONSTRUCTION, FBC B CHAPTER 10. THIS SHOULD
 INCLUDE THE NEW OCCUPANT LOAD FBC B 1004.
  
 4. LS001, NOTES FOR 508, 508.4 ARE NOT CLEAR AS TO
 DESIGN INTENT AND WHICH NOTE IS APPLICABLE TO THE
 STORAGE AREAS. I COULD NOT FIND OCCUPANCY
 CLASSIFICATION FOR THE STORAGE AREAS; REVISE TO
 INCLUDE. IT APPEARS THAT THE STORAGE MAY BE S2, WHICH
 PER THE NOTE 508.4, SEPARATION IS REQUIRED.
  
 4. DA121, FBC B 1017, SECOND TIER LEVEL, EXITING FOR
 THE STORAGE AREAS IS NOT CLEAR. REVISE PLAN TO SHOW
 EXIT ACCESS TRAVEL DISTANCE.
  
 5. DA131, FBC B 1017, THIRD TIER LEVEL, EXITING FOR THE
 STORAGE AREAS IS NOT CLEAR. REVISE PLAN TO SHOW EXIT
 ACCESS TRAVEL DISTANCE.
  
 6. LS001, REVISE DESCRIPTION OF WORK TO INCLUDE THE 2ND
 AND 3RD TIER STORAGE AREAS, FBC 107.
  
 7. DA121, FBC B 713, 2 HR FIRE RATED CHASE IS SHOWN;
 REVISE PLAN TO INDICATE WHICH ASSEMBLY IS PROPOSED.
  
 8. PRECAST ENGINEERING IN SUPPORTING DOCUMENTS,
 DELEGATED ENGINEERING IS TO BE REVIEWED BY SEOR,
 FAC61G15.
  
 9. PROVIDE A SITE PLAN SHOWING COMPLIANCE WITH FBC B
 TABLES 602, 705.8.
  
 10. THIS PERMIT WILL BE ISSUED WITH THE FOLLOWING
 PROVISOS:
  
 A. A SEPARATE ROOF PERMIT IS REQUIRED. PRIOR TO
 INSTALLATION, SUBMIT ROOF PERMIT APPLICATION WITH
 PRODUCT APPROVALS REVIEWED BY DESIGNER OF RECORD AND
 ENGINEERING FOR ENHANCED FASTENING IF APPLICABLE.
  
 B. COMPONENT & CLADDING PRODUCT APPROVALS REVIEWED BY
 DESIGNER OF RECORD ARE TO BE SUBMITTED TO THE BUILDING
 DIVISION, REVIEWED AND ISSUED PRIOR TO INSTALLATION.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-12-23 Cont ID  
Sent By jpearson Date 2018-12-23 Time 11:47 Rev Time 0.00
Received By jpearson Date 2018-12-23 Time 11:47 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-10-15 Cont ID  
Sent By jpearson Date 2018-10-15 Time 10:23 Rev Time 0.00
Received By jpearson Date 2018-10-15 Time 10:23 Sent To  
Notes
2018-10-15 10:23:27CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE COMPLETED LIGHT FIXTURE SCHEDULE. WPB FBC
 107.2.1
 2. IT APPEARS LOAD IS BEING ADDED TO PANEL SEBB AND
 SWBB FOR THE NEW PANELS. PROVIDE LOAD CALCULATION FOR
 THESE PANELS, INCLUDE EXISTING AND NEW LOADS TO CONFIRM
 CAPACITY IS ADEQUATE. NEC 215.2, 220, 408.30
 3. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND
 SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN
 THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE
 INDICATING THE REQUIRED SEPARATE PERMITS AND PLAN
 SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. WPB FBC
 105.1, 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2018-11-05 Cont ID  
Sent By rrossano Date 2018-11-05 Time   Rev Time  
Received By rrossano Date 2018-11-05 Time   Sent To I
Notes
2018-11-05 09:10:08PASSED PER MANNY GONZALEZ.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-01-04 Cont ID  
Sent By pleduc Date 2019-01-04 Time   Rev Time 0.00
Received By pleduc Date 2018-12-17 Time 14:50 Sent To  
Notes
2019-01-04 09:55:13THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THE SUBMITTED PLANS SHALL REQUIRE THE APPLICABLE
 REVISIONS TO REFLECT THE PERFORMANCE BASED DESIGN AS
 OUTLINED IN THE REVISED THORTON TOMASETTI ENGINEERS
 REPORT SUBMITTED BY EMAIL ON 12/11/18.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-10-15 Cont ID  
Sent By pleduc Date 2018-10-15 Time   Rev Time 0.00
Received By pleduc Date 2018-10-10 Time 09:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-02-21 Cont ID  
Sent By lmarchan Date 2019-02-21 Time 15:02 Rev Time 0.00
Received By lmarchan Date 2019-02-14 Time 08:08 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-01-31 Cont ID  
Sent By lmarchan Date 2019-01-31 Time 15:54 Rev Time 0.00
Received By lmarchan Date 2019-01-22 Time 17:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-01-04 Cont ID  
Sent By shill Date 2019-01-04 Time 18:03 Rev Time 0.00
Received By shill Date 2018-12-12 Time 08:16 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-12-02 Cont ID  
Sent By cpuell Date 2018-12-02 Time 11:24 Rev Time 0.00
Received By cpuell Date 2018-09-26 Time 08:00 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status P Date 2018-11-02 Cont ID  
Sent By shill Date 2018-11-02 Time 06:12 Rev Time 0.00
Received By shill Date 2018-11-02 Time 06:12 Sent To  
Notes
2018-11-02 06:12:41REVIEWED UNDER FOUNDATION PERMIT 18060764
  
 MU-2018-24860
 $1,376.91 PAID
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-12-28 Cont ID  
Sent By ccole Date 2018-12-28 Time 13:25 Rev Time 0.00
Received By ccole Date 2018-12-28 Time 07:37 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-10-29 Cont ID  
Sent By ccole Date 2018-10-29 Time 10:16 Rev Time 0.00
Received By ccole Date 2018-10-18 Time 11:33 Sent To  
Notes
2018-10-29 11:13:271ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18090957
 10/29/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET DM201: REFER TO SECTION 1101.1 FBC-17 EXISTING
 BUILDING CODE AND PROVIDE MINIMUM VENTILATION
 CALCULATIONS FOR ALL ROOMS AND SPACES PER TABLE
 403.3.1.1 FBC-17 MECHANICAL. PROVIDE A SCHEDULE THAT
 INDICATES THE REQUIRED AND PROVIDED CFMS OF OUTDOOR
 AIR.
  
 2) DM202: A) SEE NOTES M09 AND M11 AND CLARIFY THE TYPE
 OF EXHAUST THAT IS BEING EXTENDED TO THE NEW
 TERMINATION LOCATION. B) SUBMIT MANUFACTURER'S
 SPECIFICATIONS AND THE MIAMI-DADE NOA FOR THE EXHAUST
 AND OUTSIDE AIR LOUVERS. C) DUCT SMOKE DETECTORS ARE
 REQUIRED FOR THE NEW FAN COIL UNITS IF THESE UNITS ARE
 SHARING THE COMMON OUTDOOR AIR SUPPLY OR COMMON PLENUM-
 SECTION 606.2.2 FBC M. C) PLACE A NOTE TO INDICATING
 THAT NO MORE THAN 10% OF AIR SUPPLIED INTO THE TOILET
 ROOMS WILL BE RECIRCULATED VIA RETURNS INTO THE PLENUM
 OR TO ADJACENT SPACES- TABLE 403.3.1.1 FOOTNOTE G. D)
 PROVIDE NOTES INDICATING THE LOCATION OF THE RISERS
 INTO THE UPPER LEVELS.
  
 3) DM204, 206, 208, 210, 212: THE PLANS SHOW NUMEROUS
 DUCT RISERS PENETRATING FLOORS AND ALSO WHAT APPEARS TO
 BE CHASES OR SHAFT. PLEASE SHOW THE REQUIRED FIRE
 DAMPERS AT THESE LOCATIONS- SECTIONS 607.5.2, 607.5.5,
 & 607.6 FBC M.
  
 4) DM302: PROVIDE A DUCT PENETRATION FIRESTOPPING
 DETAIL- SECTION 714.1.1 FBC B.
  
 5) DM401: PROVIDE A SEQUENCE OF OPERATION FOR FAN SHUT
 DOWN RELATING TO ACTIVATION OF AN AREA OR DUCT SMOKE
 DETECTOR- SECTIONS 606.4 AND 606.4.1 FBC M.
  
 6) DM212: CLARIFY IF THE STAIRWELL WALL THAT THE DUCT
 IS PENETRATING IS A WALL THAT IS ENCLOSING AN INTERIOR
 EXIT STAIRWAY- SEESECTION 1023.5 FBC B.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-01-04 Cont ID  
Sent By gjohnson Date 2019-01-04 Time 16:19 Rev Time 0.00
Received By gjohnson Date 2019-01-04 Time 15:31 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-10-31 Cont ID  
Sent By gjohnson Date 2018-10-31 Time 11:11 Rev Time 0.00
Received By gjohnson Date 2018-10-30 Time 10:37 Sent To  
Notes
2018-10-31 12:02:331ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. THE NEW BATHROOM FIXTURE COUNT SHALL COMPLY WITH FBC
 PL 403.1.3 POTTY PARITY. IN ASSEMBLY OCCUPANCIES,
 RESTROOMS WHICH ARE OPEN TO THE PUBLIC MUST HAVE A
 RATIO OF 3:2 WATER CLOSETS PROVIDED FOR WOMEN AS THE
 COMBINED TOTAL OF WATER CLOSETS AND URINALS PROVIDED
 FOR MEN, UNLESS THESE ARE TWO OR FEWER SUCH FIXTURES
 FOR MEN, IN ACCORDANCE WITH ?553.86, FLORIDA STATUTES.
  
 2. THE GRAB BARS SHALL SHOWN TO BE MEASURED TO THE TOP
 OF THE GRIPPING SURFACE FROM FINISHED FLOOR . PER FBC
 ACC 609.4
  
 3. PLEASE SHOW COMPLIANCE OF THE AMBULATORY STALL PER
 FBC ACC 604.8.2.1 SIZE.
 AMBULATORY ACCESSIBLE COMPARTMENTS SHALL HAVE A DEPTH
 OF 60 INCHES (1525 MM) MINIMUM AND A WIDTH OF 35 INCHES
 (890 MM) MINIMUM AND 37 INCHES (940 MM) MAXIMUM.
 604.8.2.2 DOORS. TOILET COMPARTMENT DOORS, INCLUDING
 DOOR HARDWARE, SHALL COMPLY WITH 404, EXCEPT THAT IF
 THE APPROACH IS TO THE LATCH SIDE OF THE COMPARTMENT
 DOOR, CLEARANCE BETWEEN THE DOOR SIDE OF THE
 COMPARTMENT AND ANY OBSTRUCTION SHALL BE 42 INCHES
 (1065 MM) MINIMUM. THE DOOR SHALL BE SELF-CLOSING. A
 DOOR PULL COMPLYING WITH 404.2.7 SHALL BE PLACED ON
 BOTH SIDES OF THE DOOR NEAR THE LATCH. TOILET
 COMPARTMENT DOORS SHALL NOT SWING INTO THE MINIMUM
 REQUIRED COMPARTMENT AREA.
 604.8.2.3 GRAB BARS. GRAB BARS SHALL COMPLY WITH 609. A
 SIDE-WALL GRAB BAR COMPLYING WITH 604.5.1 SHALL BE
 PROVIDED ON BOTH SIDES OF THE COMPARTMENT.
  
 4.PLEASE ENLARGE THE ISOMETRIC DRAWING FOR THE WATER
 SANITARY AND STORM DRAIN THEY ARE TO CONGESTED TO
 DETERMINE CODE COMPLIANCE. PER WPB AMEND TO FBC
 107.2.1.3
  
  
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2019-01-12 Cont ID  
Sent By shill Date 2019-01-12 Time 11:19 Rev Time 0.00
Received By shill Date 2019-01-12 Time 11:19 Sent To  
Notes
2019-01-12 11:25:30GAF MODIFIED NOA 15-1008.01 SUBMITTED, APPROVED BY
 DESIGNER OF RECORD
 RAS117 CALCULATIONS REQUIRED TO BE SUBMITTED WITH ROOF
 PERMIT APPLICATION
  
 NOTE THAT NOA IS NOW EXPIRED, BUT FOUNDATION PERMIT
 18060764 WAS APPLIED FOR ON 6/15/2018 (NOA NOT EXPIRED
 AT THAT TIME)
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2019-01-23 Cont ID  
Sent By pvalenti Date 2019-01-23 Time 10:03 Rev Time 0.00
Received By pvalenti Date 2019-01-23 Time 10:03 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2018-12-23 Cont ID  
Sent By jpearson Date 2018-12-23 Time 11:43 Rev Time 0.00
Received By jpearson Date 2018-12-23 Time 11:43 Sent To  
Notes
2018-12-23 11:43:49SHEET DA-102 AND LS-003 ARE MISSING THE THIRD PARTY
 VERIFICATION REQUIRED FOR DIGITAL SIGNATURES. ALL OTHER
 SHEETS OK. PROVIDE CORRECTION. WPB FBC 107.1; FS
 471/481

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2018-10-15 Cont ID  
Sent By jpearson Date 2018-10-15 Time 09:57 Rev Time 0.00
Received By jpearson Date 2018-10-15 Time 09:57 Sent To  
Notes
2018-10-15 09:57:07SHEET DA-102 HAS A CORRUPTED SIGNATURE. ALL OTHER
 SHEETS OK. PLAN IS REQUIRED TO BE SIGNED AND SEALED BY
 THE PERSON RESPONSIBLE FOR THE DESIGN. A DIGITAL PLAN
 REQUIRES A DIGITAL SIGNATURE. PROVIDE CORRECTION. WPB
 FBC 107.1; FS 471/481

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status P Date 2018-11-02 Cont ID  
Sent By shill Date 2018-11-02 Time 06:12 Rev Time 0.00
Received By shill Date 2018-11-02 Time 06:12 Sent To  
Notes
2018-11-02 06:29:36**THRESHOLD** ASSEMBLY OCCUPANCY >5000 SF, >500
 OCCUPANTS
  
 SI AGREEMENT AND PRIVATE PROVIDER DOCUMENTS REVIEWED
 UNDER FOUNDATION PERMIT 18091159
  
 ADDITION OF ANOTHER INSPECTOR IS RECOMMENDED (MAY BE
 ADDED AFTER PERMIT ISSUANCE) - PLEASE CONTACT ME IF YOU
 WISH TO DISCUSS
  
 THRESHOLD STATEMENT FOR ARCHITECT ON MOST PAGES
 (WILLIAM A HANSER, AR7110)
 THRESHOLD STATEMENT FOR ENGINEER ON EACH PAGE (DEREK A
 WASSINK, PE 55303, THORNTON THOMASETTI)
  
 THRESHOLD INSPECTION PLAN ON SHEET DS004 & DS005
  
 PRIVATE PROVIDER (MEP STRUCTURAL ENGINEERING AND
 INSPECTIONS) IS ALSO SI FOR THE PROJECT
  
 SI AGREEMENT SIGNED BY:
  
 OTTO J LETZELTER, PE, SI 54716
 MEP STRUCTURAL ENGINEERING AND INSPECTIONS
 GARY HENNINGS, CGC1509819
 KRAVIS REP
 JACK BOTHE, BN5957
  
  
  
  
  
  
  

Review Stop Z ZONING
Rev No 4 Status P Date 2019-02-21 Cont ID  
Sent By eschneid Date 2019-02-21 Time 14:23 Rev Time 0.50
Received By eschneid Date 2019-02-21 Time 13:41 Sent To  
Notes
2019-02-21 14:24:34PASSED W/PROVISOS
  
 1) IN ACCORDANCE WITH RES. NO. 68-18: PRIOR TO THE
 ISSUANCE OF THE CERTIFICATE OF OCCUPANCY (PASS FINAL
 BUILDING INSPECTION) FOR THE EXPANDED DREYFOOS HALL
 LOBBY THE KRAVIS CENTER MUST:
  
 A. RECORD AN ACCESS AND MAINTENANCE EASEMENT FOR ANY
 PUBLIC SIDEWALKS OR UTILITIES ON THE SITE. THE EASEMENT
 LANGUAGE SHALL BE APPROVED BY THE CITY ATTORNEY?S
 OFFICE.
 B. PROVIDE THE CITY WITH ALL THE DOCUMENTATION REQUIRED
 BY THE FLORIDA DEPARTMENT OF TRANSPORTATION (FDOT) TO
 PERMIT THE OKEECHOBEE BOULEVARD RIGHT-OF-WAY
 IMPROVEMENTS, INCLUDING CURBING, APRONS, STREET TREES,
 TREE GRATES, LANDSCAPING, IRRIGATION AND LIGHTING.
 C. COMPLETE AND PASS INSPECTIONS FOR ALL THE OKEECHOBEE
 BOULEVARD RIGHT-OF-WAY IMPROVEMENTS.
 D. EXECUTE TO A RIGHT-OF-WAY MAINTENANCE AGREEMENT WITH
 THE CITY FOR ALL THE OKEECHOBEE BOULEVARD RIGHT-OF-WAY
 IMPROVEMENTS.
 E. DO ALL ITEMS NECESSARY WITH PALM BEACH COUNTY TO
 RELOCATE THE TRAFFIC SIGNAL POLE AT THE CORNER OF
 SAPODILLA AVENUE AND OKEECHOBEE BOULEVARD TO INCLUDE
 BEARING ALL COSTS FOR THE RELOCATION, TO INCLUDE
 PERMITTING.
  
 2) THE PLANS HAVE CHANGED SINCE THE ONES APPROVED BY
 THE CITY COMMISSION, SO A MINOR PLANNED DEVELOPMENT
 AMENDMENT SHOWING ALL CHANGES MUST BE SUBMITTED PRIOR
 TO THE FINAL INSPECTION FOR THE BUILDING.

Review Stop Z ZONING
Rev No 3 Status F Date 2019-01-31 Cont ID  
Sent By eschneid Date 2019-01-31 Time 15:48 Rev Time 2.00
Received By eschneid Date 2019-01-31 Time 13:52 Sent To  
Notes
2019-01-31 15:49:07FAILED
  
 PROVIDE WRITTEN RESPONSES TO COMMENTS.
  
 1) THANK YOU FOR PROVIDING THE ROOFING MATERIAL
 EXTENDING DOWN THE FACADE OF THE BUILDING TO THE ROOF.
 HOWEVER, AT THE MEETING BETWEEN DESIGN PROFESSIONALS
 AND STAFF AGREEMENT WAS REACHED TO HAVE THE COPPER ROOF
 MATERIAL EXTEND DOWN TO COVER ALL THE NEW HORIZONTAL
 AREAS THAT REPLACED THE SLOPED ROOF ON THE CITY
 COMMISSION APPROVED PLANS. THE DESIGN TEAM STATED THAT
 THE HORIZONTAL AREAS AT THE ALUMINUM LOUVER SYSTEM
 WOULD NOT BE VISIBLE, BUT HAVE PROVIDED NO PROOF TO
 THIS STATEMENT, SO THIS AREA (THE BUILT UP FRAMED CURB)
 MUST INCLUDE THE COOPER ROOF MATERIAL. SEE STAFF
 MARK-UP OF THE ELEVATION DRAWINGS.
  
 2) DETAIL 4 ON SHEET DA311 DOES NOT CORRESPOND TO THE
 DETAIL TAG ON SHEET DA310. IT IS SUPPOSED TO BE THE
 AREA ABOVE THE LOUVER, BUT IS INSTEAD THE ACCESS
 LADDER.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  
  

Review Stop Z ZONING
Rev No 2 Status F Date 2018-12-31 Cont ID  
Sent By eschneid Date 2018-12-31 Time 16:27 Rev Time 2.00
Received By eschneid Date 2018-12-31 Time 12:01 Sent To  
Notes
2018-12-31 16:27:52FAILED
  
 1) REPEAT COMMENT: PROVIDE A SITE PLAN OR SURVEY
 SHOWING THE BUILDING SETBACKS. --- CONTRARY TO THE
 COMMENT RESPONSES, NOT SITE PLAN OR SURVEY SHOWING
 BUILDING SETBACKS WAS PROVIDED WITH THE RESUBMITTAL.
  
 2) REVISED COMMENT: THE ROOF DOES NOT MATCH THE PLANS
 APPROVED BY THE CITY COMMISSION. THE LOWEST LEVEL OF
 ROOF HAS BEEN REMOVED FROM THE PERMIT PLANS. --- AT THE
 MEETING BETWEEN DESIGN PROFESSIONALS AND STAFF
 AGREEMENT WAS REACHED TO HAVE THE COPPER ROOF MATERIAL
 EXTEND DOWN TO COVER ALL THE NEW HORIZONTAL AREAS THAT
 REPLACED THE SLOPED ROOF ON THE CITY COMMISSION
 APPROVED PLANS. NO NEW ELEVATION DRAWINGS WERE
 SUBMITTED TO VERIFY THIS (SHEETS DA201 THROUGH DA203).
  
 3) REPEAT COMMENT: THE PLANS ARE UNCLEAR TO THE DEPTH
 OF THE HORIZONTAL AND VERTICAL MULLIONS. THE APPROVED
 PLANS WERE TO EXPAND THE LOBBY WITH THE SAME DEPTH OF
 THE MULLIONS. SHEET DA303 SEEMS TO INDICATE HORIZONTAL
 MULLION DEPTH, BUT DOES NOT GIVE DETAILS ON THE DEPTH,
 NOR HOW IT COMPARES TO THE EXISTING MULLION DEPTH.
 PROVIDE INFORMATION TO VERIFY THAT THE HORIZONTAL AND
 VERTICAL MULLIONS ARE THE SAME AS EXISTING. ------ THE
 COMMENT RESPONSES REFERENCE DETAILS 8 AND 9 ON SHEET
 DA603 AS WELL AS AN ATTACHED PHOTO TO ADDRESS THIS
 COMMENT. NEITHER SHEET DA603 NOR THE PHOTO WAS INCLUDED
 IN THE RESUBMITTAL.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2018-11-05 Cont ID  
Sent By eschneid Date 2018-11-05 Time 17:14 Rev Time 3.00
Received By eschneid Date 2018-11-05 Time 17:14 Sent To  
Notes
2018-11-05 17:26:04FAILED
  
 1) PROVIDE A SITE PLAN OR SURVEY SHOWING THE BUILDING
 SETBACKS.
  
 2) THE ROOF DOES NOT MATCH THE PLANS APPROVED BY THE
 CITY COMMISSION. THE LOWEST LEVEL OF ROOF HAS BEEN
 REMOVED FROM THE PERMIT PLANS. IN ORDER TO REMOVE THIS
 FEATURE, THE CITY COMMISSION IS REQUIRED TO APPROVE AS
 PART OF A REVISED LEVEL III SITE PLAN REVIEW.
  
 3) THE PLANS ARE UNCLEAR TO THE DEPTH OF THE HORIZONTAL
 AND VERTICAL MULLIONS. THE APPROVED PLANS WERE TO
 EXPAND THE LOBBY WITH THE SAME DEPTH OF THE MULLIONS.
 SHEET DA303 SEEMS TO INDICATE HORIZONTAL MULLION DEPTH,
 BUT DOES NOT GIVE DETAILS ON THE DEPTH, NOR HOW IT
 COMPARES TO THE EXISTING MULLION DEPTH. PROVIDE
 INFORMATION TO VERIFY THAT THE HORIZONTAL AND VERTICAL
 MULLIONS ARE THE SAME AS EXISTING.
  
 4) THE MECHANICAL PLANS SHOW NEW ROOFTOP EQUIPMENT. IN
 ACCORDANCE WITH THE CITYPLACE DRI, PLEASE PROVIDE
 VERIFICATION THAT ALL ROOFTOP MECHANICAL EQUIPMENT,
 INCLUDING BUT NOT LIMITED TO SUCH ITEMS AS PUBLIC AND
 PRIVATE UTILITY SERVICE CONNECTIONS; HEATING,
 VENTILATING, AND AIR CONDITIONING SYSTEMS;
 COMMUNICATIONS DEVICES; AND RELATED EQUIPMENT, SHALL BE
 SCREENED FROM PUBLIC VIEW THROUGH ANY COMBINATION OF
 LANDSCAPING, WALLS AND EQUIPMENT LOCATION. PLEASE
 PROVIDE PLANS OR OTHER EVIDENCE THAT THE NEW ROOFTOP
 MECHANICAL EQUIPMENT WILL BE SCREENED FROM PUBLIC VIEW.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]