Plan Review Details - Permit 18090893
Plan Review Stops For Permit 18090893
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-10-29 Cont ID  
Sent By aclange Date 2018-10-29 Time 17:26 Rev Time 0.00
Received By jgomez Date 2018-10-29 Time 08:06 Sent To  
Notes
2018-10-29 18:04:55PHONE CONVERSATION WITH CONTRACTOR (MR. CHANDLER) AND
 RICHARD GATHRIGHT. MR. CHANDLER SAID THAT THERE WERE
 NOT CHANGES TO THE STOREFRONT. CLOUDED AREAS BY THE
 STOREFRONT SHOW NO DOORS. ORIGINAL PLANS WERE APPROVED
 WITH DOORS. PER CONTRACTOR, DOORS WERE NOT INSTALLED.
 JG.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-09-22 Cont ID  
Sent By jpearson Date 2018-09-22 Time 14:26 Rev Time 0.00
Received By jpearson Date 2018-09-22 Time 14:26 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-09-25 Cont ID  
Sent By pleduc Date 2018-09-25 Time   Rev Time 0.00
Received By pleduc Date 2018-09-25 Time 12:24 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-10-29 Cont ID  
Sent By jgomez Date 2018-10-29 Time 17:26 Rev Time 0.00
Received By jgomez Date 2018-09-20 Time 12:16 Sent To I
Notes
2018-09-21 12:16:18C11

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-10-24 Cont ID  
Sent By hmoser Date 2018-10-24 Time 15:16 Rev Time 0.00
Received By hmoser Date 2018-10-24 Time 15:16 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-10-05 Cont ID  
Sent By ccole Date 2018-10-05 Time 13:42 Rev Time 0.00
Received By ccole Date 2018-10-05 Time 13:42 Sent To  
Notes
2018-10-05 14:06:341ST REVIEW FBC-2017 MECHANICAL
 REVISION #18090893
 10/5/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE NEW
 CLOTHES DRYERS INCLUDING INSTALLATION INSTRUCTIONS FOR
 THE DRYER EXHAUST- SEE SECTIONS 504.1 AND 504.8.4.2 FBC
 M.
  
 2) SHEET M2.1: PROVIDE DRYER EXHAUST DUCT DIAGRAMS
 INDICATING THE TOTAL RUN LENGTHS OF THE DUCTS FROM THE
 EXHAUST OUTLETS TO THE TERMINATION LOCATIONS.
  
 3) M2.1: INDICATE HOW MAKE UP AIR IS BEING PROVIDED FOR
 THE DRYERS AND PROVIDE AN AIR BALANCE CALCULATION FOR
 THE ROOM.
  
 4) M2.1: PLEASE LABEL THE O/A INTAKE AND EXHAUST OUTLET
 FOR THE ERV AND VERIFY COMPLIANCE WITH REQUIRED
 CLEARANCE DISTANCES AS REQUIRED BY SECTION 401.4(1-4)
 AND 501.3.1(3) FBC M
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-10-12 Cont ID  
Sent By gjohnson Date 2018-10-12 Time 14:00 Rev Time 0.00
Received By gjohnson Date 2018-10-12 Time 14:00 Sent To  
Notes
***NONE***