Plan Review Details - Permit 18090744
Plan Review Stops For Permit 18090744
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-05-14 Cont ID  
Sent By jgomez Date 2019-05-14 Time 11:47 Rev Time 0.00
Received By jgomez Date 2019-05-14 Time 11:31 Sent To  
Notes
2019-05-14 11:38:0505/14/19 REVISED PROVISO FOR CLARIFICATION. (PER
 SAMANTHA).
  
 BUILDING REVIEW APPROVED WITH PROVISO (SUBMIT
 INFORMATION PRIOR TO INSPECTIONS TO AVOID
 CONFLICTS/DELAYS):
 1-REVISE PLANS AND RESUBMIT FOR REVIEW. SHOW ATTIC
 ACCESS SIZE/LOCATION IN ALL ROOF AREAS IN THE 1ST & 2ND
 FLOOR.
 2-SUBMIT PRODUCT APPROVALS FOR REVIEW: A)WINDOW
 MULLIONS AND SPECIFY MULLION SIZE. B)DOORS PRODUCT
 APPROVAL FL10765-R6 IS FOR NON-IMPACT DOORS. PROVIDE
 SHUTTERS PRODUCT APPROVAL AND COMPLETE INSTALLATION
 SCHEDULE. C)POLYGLASS ROOF UNDERLAYMENT FL5259-R28:
 CLEARLY MARK WHICH ASSEMBLY L IS GOING TO BE USED. D)
 SHUTTERS SHOWN ON EXTERIOR ELEVATIONS AND PROVIDE
 COMPLETE INSTALLATION SCHEDULE. E) WATER PROOFING AT
 TERRACE. PROVIDE PRODUCT APPROVAL THAT IS DESIGNED TO
 RECEIVE MATERIAL SPECIFIED BY THE DESIGNER OF RECORD.
 F) DESIGNER OF RECORD TO REVIEW/APPROVE ALL PRODUCT
 APPROVALS.
 3-SUBMIT COMPLETE INFORMATION FOR ALUMINUM TRELLIS
 UNDER SEPARATE PERMIT PER ARCHITECT'S RESPONSE LETTER.
 4-REVISE PLANS AND RE-SUBMIT FOR REVIEW: ENTRY FOYER
 FINISH ELEVATION IN ALL PLANS. PER JOHN MELHORN, THE
 ELEVATION WILL BE 9'-0" (NAVD OF 1988) NOT 8'-6".
 5-PER JOHN MELHORN, GARAGE WILL HAVE FLOOD VENTS.
 PROVIDE PRODUCT APPROVAL AND REVISE PLANS FOR REVIEW
 SHOWING LOCATION. ALSO, POWDER ROOM LOCATED IN THE
 GARAGE NEEDS TO BE ELEVATED TO 9'-0".
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-12-19 Cont ID  
Sent By jgomez Date 2018-12-19 Time 16:35 Rev Time 0.00
Received By jgomez Date 2018-12-18 Time 17:58 Sent To  
Notes
2018-12-18 18:01:43BUILDING REVIEW APPROVED WITH PROVISO:
 1-SHOW ATTIC ACCESS SIZE/LOCATION IN ALL ROOF AREAS IN
 THE 1ST & 2ND FLOOR.
 2-PROVIDE PRODUCT APPROVAL FOR: A)WINDOW MULLIONS AND
 SPECIFY MULLION SIZE. B)DOORS PRODUCT APPROVAL
 FL10765-R6 IS FOR NON-IMPACT DOORS. PROVIDE SHUTTERS
 PRODUCT APPROVAL AND COMPLETE INSTALLATION SCHEDULE.
 C)POLYGLASS ROOF UNDERLAYMENT FL5259-R28: CLEARLY MARK
 WHICH ASSEMBLY L IS GOING TO BE USED. D) SHUTTERS SHOWN
 ON EXTERIOR ELEVATIONS AND PROVIDE COMPLETE
 INSTALLATION SCHEDULE. E) WATER PROOFING AT TERRACE.
 PROVIDE PRODUCT APPROVAL THAT IS DESIGNED TO RECEIVE
 MATERIAL SPECIFIED BY THE DESIGNER OF RECORD. F)
 DESIGNER OF RECORD TO REVIEW/APPROVE ALL PRODUCT
 APPROVALS.
 3-ALUMINUM TRELLIS UNDER SEPARATE PERMIT PER
 ARCHITECT'S RESPONSE LETTER.
 4-REVISE ENTRY FOYER FINISH ELEVATION IN ALL PLANS. PER
 JOHN MELHORN, THE ELEVATION WILL BE 9'-0" (NAVD OF
 1988) NOT 8'-6".
 5-PER JOHN MELHORN, GARAGE WILL HAVE FLOOD VENTS.
 PROVIDE PRODUCT APPROVAL AND REVISE PLANS SHOWING
 LOCATION. ALSO, POWDER ROOM LOCATED IN THE GARAGE NEEDS
 TO BE ELEVATED TO 9'-0".
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-11-06 Cont ID  
Sent By jgomez Date 2018-11-06 Time 12:29 Rev Time 0.00
Received By jgomez Date 2018-11-05 Time 12:28 Sent To  
Notes
2018-11-06 12:30:39NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1-IMPACT FEES - DIGITAL SUBMITTALS
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected]
  
 2- PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
 FOLLOWING:
 FBC R 401.3 (DRAINAGE)
 FBC 107.2.5 (SITE PLAN)
 FBC 110.9 (IMPACT OF CONSTRUCTION)
  
 SEC. R401.3 FBC_RESIDENTIAL:
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT
 DOES NOT CREATE A HAZARD. LOTS SHALL BE GRADED TO DRAIN
 SURFACE WATER AWAY FROM FOUNDATION WALLS. THE GRADE
 SHALL FALL A MINIMUM OF 6 INCHES (152 MM) WITHIN THE
 FIRST 10 FEET (3048 MM).
 EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER
 PHYSICAL BARRIERS PROHIBIT 6 INCHES (152 MM) OF FALL
 WITHIN 10 FEET (3048 MM), DRAINS OR SWALES SHALL BE
 CONSTRUCTED TO ENSURE DRAINAGE AWAY FROM THE STRUCTURE.
 IMPERVIOUS SURFACES WITHIN 10 FEET (3048 MM) OF THE
 BUILDING FOUNDATION SHALL BE SLOPED A MINIMUM OF 2
 PERCENT AWAY FROM THE BUILDING.
  
 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED
 WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY
 A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF
 NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE,
 DISTANCES FROM LOT LINES, THE ESTABLISHED STREET GRADES
 AND THE PROPOSED FINISHED GRADES, DEPICTING THE
 PROPOSED LOT DRAINAGE AND, AS APPLICABLE, FLOOD HAZARD
 AREAS, FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT
 SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND
 INCLUDED ON A BOUNDARY LINE SURVEY. IN THE CASE OF
 DEMOLITION, THE SITE PLAN SHALL SHOW CONSTRUCTION TO BE
 DEMOLISHED AND THE LOCATION AND SIZE OF EXISTING
 STRUCTURES AND CONSTRUCTION THAT ARE TO REMAIN ON THE
 SITE OR PLOT. THE BUILDING OFFICIAL IS AUTHORIZED TO
 WAIVE OR MODIFY THE REQUIREMENT FOR A SITE PLAN WHEN
 THE
 APPLICATION FOR PERMIT IS FOR ALTERATION OR REPAIR OR
 WHEN OTHERWISE WARRANTED.
  
 SEC. 110.9 CITY AMENDMENTS: IMPACT OF CONSTRUCTION. ALL
 CONSTRUCTION ACTIVITY REGULATED BY THIS CODE SHALL BE
 PERFORMED IN A MANNER SO AS NOT TO ADVERSELY IMPACT THE
 CONDITION OF ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS
 PERMITTED TO AFFECT SAID PROPERTY PURSUANT TO A CONSENT
 GRANTED BY THE APPLICABLE PROPERTY OWNER, UNDER TERMS
 OR CONDITIONS AGREEABLE TO THE APPLICABLE PROPERTY
 OWNER. THIS INCLUDES, BUT IS NOT LIMITED TO, THE
 CONTROL OF DUST, NOISE, WATER OR DRAINAGE RUN-OFFS,
 DEBRIS, AND THE STORAGE OF CONSTRUCTION MATERIALS. NEW
 CONSTRUCTION ACTIVITY SHALL NOT ADVERSELY IMPACT LEGAL
 HISTORIC SURFACE WATER DRAINAGE FLOWS SERVING ADJACENT
 PROPERTIES, AND MAY REQUIRE SPECIAL DRAINAGE DESIGN
 COMPLYING WITH ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE DRAINAGE PATTERNS OF THE AFFECTED SITES.
 ACCORDINGLY, DEVELOPERS, CONTRACTORS AND OWNERS OF ALL
 NEW RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS,
 POOLS, PATIOS, DRIVEWAYS, DECKS
 OR SIMILAR ITEMS, ON EXISTING PROPERTIES RESULTING IN A
 SIGNIFICANT DECREASE OF PERMEABLE LAND AREA ON ANY
 PARCEL OR HAS ALTERED THE DRAINAGE FLOW ON THE
 DEVELOPED PROPERTY SHALL, AS A PERMIT CONDITION,
 PROVIDE A PROFESSIONALLY PREPARED DRAINAGE PLAN CLEARLY
 INDICATING COMPLIANCE WITH THIS PARAGRAPH. UPON
 COMPLETION OF THE IMPROVEMENT, A CERTIFICATION FROM A
 LICENSED PROFESSIONAL SHALL BE SUBMITTED TO THE
 INSPECTOR IN ORDER TO RECEIVE APPROVAL OF THE FINAL
 INSPECTION.
  
  
 3- SURVEY: SURVEY IS NOT SIGNED AND SEALED. NEED TO
 PROVIDE HARD COPY OF SURVEY WITH ORIGINAL SEAL AND
 SIGNATURE AS REQUIRED BY CHAPTER 472 F. S. OR SUBMIT
 DIGITALLY SIGNED SURVEY. COORDINATE WITH CITY LIBRARIAN
 (LAURA MARCHANT (561)805-6658 OR CAROLINE PUELL
 (561)805-6659) FOR PROPER UPLOADING.
  
 4- PROPERTY IS LOCATED IN FLOOD ZONE AE WITH BASED
 FLOOR ELEVATIONS 6 AND 7. ELEVATION CERTIFICATES ARE
 REQUIRED BASED ON CONSTRUCTION DRAWINGS, BUILDING UNDER
 CONSTRUCTION AND FINISHED CONSTRUCTION. PROVIDE THE
 CONSTRUCTION DRAWINGS ELEVATION CERTIFICATE. SEC.
 18-284 CITY ORDINANCE NO. 4729-17.
  
 5- SIZE OF ENTRY DOOR E.01 DOESN'T COMPLY WITH SEC.
 R311.2 FBC-RESIDENTIAL. NEED DOOR THAT PROVIDE 32" MIN.
 CLEAR OPENING. DOOR SPECIFIED IS 30" WIDTH. REVISE AS
 REQUIRED.
  
 6- CLARIFY SIZE AND CONFIGURATION OF SECOND FLOOR
 BEDROOM CASEMENT EGRESS WINDOW (40"X57") TO VERIFY
 COMPLIANCE WITH EGRESS SEC. R310.2.1 FBC-RESIDENTIAL.
 IS THERE A WINDOW MULLION IN THE MIDDLE OF THE
 WINDOWS?. IF SO, WHAT'S THE MINIMUM CLEAR WIDTH?.
 PROVIDE MANUFACTURER'S CUT SHEETS SHOWING THE CLEAR
 OPENINGS TO VERIFY EGRESS.
  
 7- A) FLOOR PLANS ARE INCOMPLETE. PROVIDE FLOOR PLANS
 WITH COMPLETE DIMENSIONS. DOOR SCHEDULE DOESN'T MATCH
 DOORS KEYED ON PLANS. REVISE AS REQUIRED AND PROVIDE
 COMPLETE INFORMATION FOR ALL INTERIOR DOORS. SEC.
 107.2.1 CITY AMENDMENTS.
  
 B) SPECIFY SIZE OF BATHROOM DOORS ON FIRST FLOOR TO
 VERIFY COMPLIANCE WITH SEC. R320 FBC-RESIDENTIAL.
  
 C) PROVIDE SPECIFICATIONS FOR GARAGE DOOR LEADING TO
 THE INTERIOR OF THE HOUSE TO COMPLY WITH SEC. R302.5.1
 FBC-RESIDENTIAL.
  
  
 D) PROVIDE DETAILS AND SPECIFICATIONS FOR INTERIOR
 WALLS FRAMING AND SPECIFY INSULATION BETWEEN GARAGE AND
 MAIN HOUSE. SEC. R103.2 FBC-ENERGY CONSERVATION.
  
 8- SPECIFY ATTIC ACCESS SIZE AND LOCATION IN ALL ROOF
 AREAS IN THE FIRST FLOOR AND SECOND FLOOR AS REQUIRED
 BY SEC. R807 FBC-RESIDENTIAL.
  
 9- PROVIDE SOIL TEST REPORT. SEC. R401.4
 FBC-RESIDENTIAL.
  
 10- REVISE ENERGY CALCULATIONS. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION. COORDINATE WITH ARCHITECTURAL
 PLANS TO AVOID CONFLICTS/DELAYS:
  
 SEPARATE GYM STRUCTURE:
 A) PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING OWNER'S NAME, CORRECT BUILDER'S NAME, PERMIT
 OFFICE, ETC.
 B) REVISE ITEM #4. THERE ARE NO BEDROOMS IN THE GYM.
 C) ARCHITECTURAL PLANS DON'T SPECIFY INSULATION ON SLAB
 ON GRADE. REVISE ITEM #8.
 D) WALL INSULATION SPECIFIED ON ITEM #9 DOESN'T MATCH
 PLANS.
 E) CEILING INSULATION SPECIFIED ON ITEM #10 DOESN'T
 MATCH ARCHITECTURAL PLANS.
 F) THERE IS NO KITCHEN IN THE GYM. REVISE SPACES
 INFORMATION ON PAGE 2 OF 4.
 G) WALLS INFORMATION ON PAGE 3 OF 4 IS MISSING THE EAST
 WALL.
 H) REVISE DOOR INFORMATION PAGE 3 OF 4. THERE IS NOT
 INSULATED DOOR IN THE SOUTH WALL. SEE PLANS AND PRODUCT
 APPROVAL AND REVISE AS REQUIRED. NOTE: GLAZING IN THIS
 DOOR NEEDS TO BE INCLUDED IN THE WINDOW GLAZING AREA.
 SEE SEC. R405.5.3 FBC-ENERGY CONSERVATION.
 I)REVISE WINDOWS OVERHANG DEPTH AND SEPARATION TO MATCH
 PLANS.
 J) NEED TO PROVIDE HARD COPY OF ENERGY CALCULATIONS
 WITH ORIGINAL SEAL AND SIGNATURE AS REQUIRED BY CHAPTER
 472 F. S. OR SUBMIT REPORT DIGITALLY SIGNED. COORDINATE
 WITH CITY LIBRARIAN (LAURA MARCHANT (561)805-6658 OR
 CAROLINE PUELL (561)805-6659) FOR PROPER UPLOADING.
  
 MAIN HOUSE:
 A) PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING OWNER'S NAME, CORRECT BUILDER'S NAME, PERMIT
 OFFICE, ETC.
 B) REVISE ITEM #4. NUMBER OF BEDROOMS DON'T MATCH
 PLANS.
 C) ARCHITECTURAL PLANS DON'T SPECIFY INSULATION ON SLAB
 ON GRADE OR FLOOR OVER OTHER SPACE. . REVISE ITEM #8.
 D) WALL INSULATION SPECIFIED ON ITEM #9 DOESN'T MATCH
 PLANS AND IS MISSING THE INFORMATION FOR ADJACENT WALL
 BETWEEN GARAGE AND MAIN HOUSE.
 E) CEILING INSULATION SPECIFIED ON ITEM #10 DOESN'T
 MATCH ARCHITECTURAL PLANS.
 F) REVISE NUMBER OF PEOPLE IN THE SPACES INFORMATION ON
 PAGE 2 OF 6. COORDINATE WITH NUMBER OF BEDROOMS SHOWN
 ON PLANS.
 G) REVISE DOOR INFORMATION PAGE 3 OF 6. THERE ARE NOT
 INSULATED DOORS. SEE PLANS AND PRODUCT APPROVALS AND
 REVISE AS REQUIRED. NOTE: GLAZING IN THIS DOORS NEEDS
 TO BE INCLUDED IN THE WINDOW GLAZING AREA. SEE SEC.
 R405.5.3 FBC-ENERGY CONSERVATION.
 H)REVISE WINDOWS OVERHANG DEPTH AND SEPARATION TO MATCH
 PLANS.
 I)NEED TO PROVIDE HARD COPY OF ENERGY CALCULATIONS WITH
 ORIGINAL SEAL AND SIGNATURE AS REQUIRED BY CHAPTER 472
 F. S. OR SUBMIT REPORT DIGITALLY SIGNED. COORDINATE
 WITH CITY LIBRARIAN (LAURA MARCHANT (561)805-6658 OR
 CAROLINE PUELL (561)805-6659) FOR PROPER UPLOADING.
  
 NOTE:
 LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR AND
 SHGC FACTOR IS REQUIRED WHEN THE ENERGY CALCULATIONS
 ARE NOT USING THE DEFAULT FACTOR.
  
 11- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL)
  
 A) PRECAST LINTELS AS SPECIFIED ON PLANS.
  
 B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS. NOTE: PROVIDE ONLY THE FLORIDA PRODUCT
 APPROVAL COVER PAGE AND PAGE SHOWING THE SPECIFIED
 CONNECTOR OR DESIGN PROFESSIONAL TO LIST THE FLORIDA
 PRODUCT APPROVAL NUMBER NEXT TO EACH SPECIFIED
 CONNECTOR.
  
 C)WINDOW MULLIONS AS SHOWN ON PLANS. REQUIRED: CLEARLY
 SPECIFY MULLION SIZE TO BE USED TO VERIFY COMPLIANCE
 WITH THE CALCULATED DESIGN PRESSURES.
  
 D) DRAWINGS SUBMITTED WITH FLORIDA PRODUCT APPROVAL
 FL10765.1-R6 FOR FRENCH DOORS DON'T HAVE IMPACT GLASS.
 THEREFORE, HURRICANE SHUTTERS ARE REQUIRED. PROVIDE
 HURRICANE SHUTTERS PRODUCT APPROVAL AND COMPLETE
 INSTALLATION SCHEDULE.
  
 E) PROVIDE PRODUCT APPROVAL FOR MASTER BEDROOM CASEMENT
 WINDOW #107 SPECIFIED SIZE 36"X99".
  
 F) DESIGN PRESSURES FOR EXTERIOR DOORS FLORIDA PRODUCT
 APPROVAL FL18657-R1 DON'T SEEM TO COMPLY WITH THE
 CALCULATED DESIGN PRESSURES. CLARIFY WHERE ARE THESE
 DOORS GOING TO BE INSTALLED AND PROVIDE PRODUCT
 APPROVAL THAT METS THE CALCULATED DESIGN PRESSURES.
  
 G) PROVIDE PRODUCT APPROVAL FOR INSWING ENTRY DOOR AS
 SHOWN ON PLANS.
  
 H) CLAY TILE NOA 17-0626.03: PROVIDE PRODUCT APPROVAL
 FOR ADHESIVE TO BE USED. SEE LISTED ADHESIVES ON NOA.
  
 I) POLYGLASS ROOF UNDERLAYMENT FL5259-R28: CLEARLY MARK
 WHICH ASSEMBLY FROM SEC. 5.6.4 OF FLORIDA PRODUCT
 APPROVAL IS GOING TO BE USED TO VERIFY COMPLIANCE WITH
 THE CALCULATED DESIGN PRESSURES.
  
 J) OPERABLE SHUTTERS AS SHOWN ON EXTERIOR ELEVATIONS
 AND PROVIDE COMPLETE INSTALLATION SCHEDULE. SEE CITY
 SAMPLE OR PROVIDE COMPLETE INFORMATION ON A DIFFERENT
 FORMAT THAT WILL PROVIDE ALL THE REQUIRED INFORMATION.
  
 K) WATER PROOFING AT TERRACE. PROVIDE PRODUCT APPROVAL
 THAT IS DESIGN TO RECEIVE MATERIAL SPECIFIED BY THE
 DESIGNER OF RECORD.
  
 12- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 13- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 INSTALLATION OF THE ALUMINUM TRELLIS. SEC. R301.1
 FBC_RESIDENTIAL.
 NOTE: THIS MAY BE SUBMITTED LATER A A DEFERRED
 SUBMITTAL OR UNDER A SEPARATE PERMIT.
  
 14- FINISH FLOOR ELEVATION AT ENTRY FOYER DOESN'T
 COMPLY WITH THE 2 FEET FREE BOARD REQUIRED BY SEC.
 18-284 CITY ORDINANCE NO. 4729-17 FOR FLOOD ZONE AREAS.
 NOTE: SAME APPLIES FOR ELEVATOR PIT.
  
 15- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 STAIRWAY CONSTRUCTION, INCLUDING RISER, TREADS,
 HANDRAILS AND GUARDRAILS SHOWING COMPLIANCE WITH SEC.
 R311.7 FBC-RESIDENTIAL.
  
 16- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 CONSTRUCTION/INSTALLATION OF THE STAINED WOOD BRACKETS
 AND ROOF AT THE ENTRY OF THE GYM. SPECIFY ALL FRAMING
 MEMBERS AND CONNECTORS. SEC. R301.1 FBC-RESIDENTIAL.
  
 17- PROVIDE COMPLETE SECOND FLOOR FRAMING
  
 18- BUILDING SEC. 2/306 ON SHEET A-306.0 SHOWS
 2'-10-1/4" LANDING. NEED 3'-0" MIN. SEC. R311.3
 FBC-RESIDENTIAL.
  
 19- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 PROPOSED FIREPLACE SHOWING COMPLIANCE WITH CHAPTER 10
 FBC-RESIDENTIAL.
  
 20- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 WATERPROOFING AND FINISH MATERIAL AT THE PROPOSED
 TERRACE. SEC. 107.2.1 CITY AMENDMENTS.
  
 21- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 PROPOSED ELEVATOR SHOWING COMPLIANCE WITH SEC. R321
 FBC-RESIDENTIAL.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-12-12 Cont ID  
Sent By jleahy Date 2018-12-12 Time 13:19 Rev Time 0.00
Received By jleahy Date 2018-12-12 Time 13:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-10-03 Cont ID  
Sent By jleahy Date 2018-10-03 Time 11:14 Rev Time 0.00
Received By jleahy Date 2018-10-03 Time 08:21 Sent To  
Notes
2018-10-03 11:47:16FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 PAGE E-0
  
 1) ARC FAULT NOTE #1 TO INCLUDE KITCHEN AND LAUNDRY
 AREAS 201,12 (A), FBC RE3902.16
  
 2)RISER DIAGRAM SHOWS NO GROUNDING AT GYM BUILDING.
 250.32 BUILDINGS OR STRUCTURES SUPPLIED BY A FEEDER(S)
 OR BRANCH CIRCUIT
 A GROUNDING ELECTRODE SYSTEM IS REQUIRED TO BE
 ESTABLISHED AT EACH SEPARATE BUILDING OR STRUCTURE AND
 CONNECTED TOGETHER. PROVIDE
 DETAILS ON PLAN OF GROUNDING ELECTRODE SYSTEM AND
 WIRING. NEC 250.32; FBC RE3607.3
  
 3) LOAD CALCULATION FOR DP USES DEMANDED LOADS FROM
 PANEL "A"?
 PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL LOADS.
 NEC 220; FBC RE3602.3
  
 4) PANEL "A" ON LOAD CALCULATION SHOWS 39.4 KW OF AC
 LOAD BUT USES ONLY 16KW LOAD IN THE CALCULATION?
 PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL LOADS.
 NEC 220; FBC RE3602.3
  
 5) PANEL DB USES 41.4KW OF LOAD FOR PANEL "A" WHICH HAS
 BEEN DEMANDED DOWN TO 41.4KW
  
 PAGE E-1
  
 6) NO OUTLETS SHOWN FOR GARAGE DOOR OPENERS? (NOT
 REQUIRED)
  
 7) ALL AIR HANDLERS IN ATTIC NEED LIGHTING OUTLET
 INSTALLED PER 210.70(A)(3)
  
 8) GROUNDING AT GYM BUILDING TO BE PER 250.32 BUILDINGS
 OR STRUCTURES SUPPLIED BY A FEEDER(S) OR BRANCH CIRCUIT
 A GROUNDING ELECTRODE SYSTEM IS REQUIRED TO BE
 ESTABLISHED AT EACH SEPARATE BUILDING OR STRUCTURE AND
 CONNECTED TOGETHER.
 PROVIDE DETAILS ON PLAN OF GROUNDING ELECTRODE SYSTEM
 AND WIRING. NEC 250.32; FBC RE3607.3
  
 9) DISHWASHER TO BE GFCI PROTECTED PER 210.8(D)< FBC
 RE3902.10
  
 10) OUTLET FOR WASHER IN GARAGE NOT SHOWN TO BE GFCI,
 210.8; FBC RE3902.2

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2018-12-12 Cont ID  
Sent By jleahy Date 2018-12-12 Time 13:22 Rev Time 0.00
Received By jleahy Date 2018-12-12 Time 13:22 Sent To  
Notes
2018-12-12 13:22:44LOW VOLTAGE IS FOR TELEPHONE AND DATA ONLY JLEAHY

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2018-10-16 Cont ID  
Sent By gjohnson Date 2018-10-16 Time 18:06 Rev Time 0.00
Received By gjohnson Date 2018-10-16 Time 18:06 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2018-12-20 Cont ID  
Sent By fmittner Date 2018-12-20 Time 09:48 Rev Time 0.00
Received By fmittner Date 2018-12-20 Time 09:48 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2018-10-12 Cont ID  
Sent By fmittner Date 2018-10-12 Time 16:50 Rev Time 0.00
Received By fmittner Date 2018-10-12 Time 16:50 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-12-21 Cont ID  
Sent By jgomez Date 2018-12-21 Time 13:40 Rev Time 0.00
Received By jgomez Date 2018-12-21 Time 13:34 Sent To I
Notes
2018-12-21 13:35:44CATHERINE SUBMITTED HARD COPIES WITH ORIGINAL SEAL AND
 SIGNATURE OF ENERGY CALCULATIONS AND LOAD CALCULATIONS.
 JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-12-20 Cont ID  
Sent By jgomez Date 2018-12-20 Time 10:43 Rev Time 0.00
Received By jgomez Date 2018-12-03 Time 15:16 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-11-06 Cont ID  
Sent By jgomez Date 2018-11-06 Time 12:35 Rev Time 0.00
Received By jgomez Date 2018-09-18 Time 12:38 Sent To I
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2018-12-18 Cont ID  
Sent By jgomez Date 2018-12-18 Time 18:22 Rev Time 0.00
Received By jgomez Date 2018-12-18 Time 18:22 Sent To  
Notes
2018-12-18 09:54:3612/18/18 STAMPED SET OF PLANS BY IMPACT FEE OFFICE IN
 PROJECTDOX. $0 AMOUNT DUE. MU18-37645

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-11-06 Cont ID  
Sent By jgomez Date 2018-11-06 Time 12:34 Rev Time 0.00
Received By jgomez Date 2018-11-06 Time 12:33 Sent To  
Notes
2018-11-06 12:34:58IMPACT FEES - DIGITAL SUBMITTALS
  
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-10-23 Cont ID  
Sent By cmontell Date 2018-10-23 Time 09:15 Rev Time 0.00
Received By cmontell Date 2018-10-23 Time 09:15 Sent To  
Notes
***NONE***

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 2 Status P Date 2018-12-19 Cont ID  
Sent By jgomez Date 2018-12-19 Time 16:38 Rev Time 0.00
Received By jgomez Date 2018-12-19 Time 16:37 Sent To  
Notes
2018-12-19 16:38:40 
 1-ELEVATION CERTIFICATES ARE REC'D DURING CONSTRUCTION.

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status F Date 2018-11-06 Cont ID  
Sent By jgomez Date 2018-11-06 Time 14:36 Rev Time 0.00
Received By jgomez Date 2018-11-06 Time 14:33 Sent To  
Notes
2018-11-06 14:37:071- PROPERTY IS LOCATED IN FLOOD ZONE AE WITH BASED
 FLOOR ELEVATIONS 6 AND 7. ELEVATION CERTIFICATES ARE
 REQUIRED BASED ON CONSTRUCTION DRAWINGS, BUILDING UNDER
 CONSTRUCTION AND FINISHED CONSTRUCTION. PROVIDE THE
 CONSTRUCTION DRAWINGS ELEVATION CERTIFICATE. SEC.
 18-284 CITY ORDINANCE NO. 4729-17.

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-10-16 Cont ID  
Sent By gjohnson Date 2018-10-16 Time 18:06 Rev Time 0.00
Received By gjohnson Date 2018-10-16 Time 18:06 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2018-12-19 Cont ID  
Sent By jgomez Date 2018-12-19 Time 16:44 Rev Time 0.00
Received By jgomez Date 2018-12-19 Time 16:36 Sent To  
Notes
2018-12-19 16:51:53PRODUCT APPROVALS SUBMITTED:
  
 1-TAMKO UNDERLAYMENT FL12328-R8
 2- ROOF TILE ADHESIVE FL6332-R8
 3-SANTA FE MISSION BARREL TILE NOA 17-0626.03
 4-POLYGLASS UNDERLAYMENT FL5259-R28

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2018-11-06 Cont ID  
Sent By jgomez Date 2018-11-06 Time 12:30 Rev Time 0.00
Received By jgomez Date 2018-11-06 Time 12:30 Sent To  
Notes
2018-11-06 12:32:301- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL)
  
 A) CLAY TILE NOA 17-0626.03: PROVIDE PRODUCT APPROVAL
 FOR ADHESIVE TO BE USED. SEE LISTED ADHESIVES ON NOA.
  
 B) POLYGLASS ROOF UNDERLAYMENT FL5259-R28: CLEARLY MARK
 WHICH ASSEMBLY FROM SEC. 5.6.4 OF FLORIDA PRODUCT
 APPROVAL IS GOING TO BE USED TO VERIFY COMPLIANCE WITH
 THE CALCULATED DESIGN PRESSURES.
  
 C) WATER PROOFING AT TERRACE. PROVIDE PRODUCT APPROVAL
 THAT IS DESIGN TO RECEIVE MATERIAL SPECIFIED BY THE
 DESIGNER OF RECORD.
  
 2- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2018-12-21 Cont ID  
Sent By jgomez Date 2018-12-21 Time 13:36 Rev Time 0.00
Received By jgomez Date 2018-12-21 Time 13:35 Sent To  
Notes
2018-12-21 13:36:25CATHERINE SUBMITTED HARD COPIES WITH ORIGINAL SEAL AND
 SIGNATURE OF ENERGY CALCULATIONS AND LOAD CALCULATIONS.
 JG.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2018-12-21 Cont ID  
Sent By shill Date 2018-12-21 Time 13:07 Rev Time 0.00
Received By shill Date 2018-12-21 Time 13:07 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2018-12-21 Cont ID  
Sent By jgomez Date 2018-12-21 Time 10:23 Rev Time 0.00
Received By jgomez Date 2018-12-21 Time 09:19 Sent To  
Notes
2018-12-21 10:33:00 
 DOCUMENTS SUBMITTED ARE NOT DIGITALLY SIGNED. AFTER ALL
 PLAN REVIEWS HAVE PASSED, SUBMIT ONE PAPER ORIGINAL AT
 THE BUILDING DIVISION. THIS INCLUDES THE FOLLOWING
 DOCUMENTS:
  
 1. ENERGY CALCS FOR MAIN HOUSE (ONLY CALCULATIONS FOR
 THE GYM WERE SUBMITTED) AND ALL LOAD CALCS
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2018-12-19 Cont ID  
Sent By jgomez Date 2018-12-19 Time 16:41 Rev Time 0.00
Received By jgomez Date 2018-12-19 Time 16:41 Sent To  
Notes
2018-12-19 16:42:57 
 DOCUMENTS SUBMITTED ARE NOT DIGITALLY SIGNED. AFTER ALL
 PLAN REVIEWS HAVE PASSED, SUBMIT ONE PAPER ORIGINAL AT
 THE BUILDING DIVISION. THIS INCLUDES THE FOLLOWING
 DOCUMENTS:
  
 1. ENERGY CALCS, LOAD CALCS
  
 2- SOIL TEST REPORT.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2018-11-06 Cont ID  
Sent By shill Date 2018-11-06 Time 06:20 Rev Time 0.00
Received By shill Date 2018-11-06 Time 06:20 Sent To  
Notes
2018-11-06 06:20:26SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 DOCUMENTS SUBMITTED ARE NOT DIGITALLY SIGNED. AFTER ALL
 PLAN REVIEWS HAVE PASSED, SUBMIT ONE PAPER ORIGINAL AT
 THE BUILDING DIVISION. THIS INCLUDES THE FOLLOWING
 DOCUMENTS:
  
 1. SURVEY
  
 2. ENERGY CALCS, LOAD CALCS
  
 3. PLAN PAGES
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2018-12-20 Cont ID  
Sent By fmittner Date 2018-12-20 Time 09:48 Rev Time 0.00
Received By fmittner Date 2018-12-20 Time 09:48 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2018-10-12 Cont ID  
Sent By fmittner Date 2018-10-12 Time 16:50 Rev Time 0.00
Received By fmittner Date 2018-10-12 Time 16:50 Sent To  
Notes
***NONE***