Plan Review Details - Permit 18090657
Plan Review Stops For Permit 18090657
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-12-20 Cont ID  
Sent By cthroop Date 2018-12-20 Time 08:48 Rev Time 0.00
Received By cthroop Date 2018-12-20 Time 06:52 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-11-01 Cont ID  
Sent By cthroop Date 2018-11-01 Time 14:12 Rev Time 0.00
Received By cthroop Date 2018-11-01 Time 09:25 Sent To  
Notes
2018-11-01 14:15:59BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. ROOF FRAMING - PROPOSED ROOF INDICATES A
 PRE-ENGINEERED ROOF SYSTEM. DETAIL - TYP.RIDGE COPING
 DETAIL ON PLAN PAGE A-4 INDICATES A RIDGE BEAM AND
 RAFTER SYSTEM. PLEASE CLARIFY.
 2. WALL INSULATION - ENERGY SUBMITTAL REQUIRES R-19.
 PLANS INDICATE R-15. PLEASE CLARIFY.
 3. CRAWL SPACE INSULATION - ENERGY SUBMITTAL REQUIRED
 R-19. PLANS SHOW NO INSULATION IN CRAWL SPACE. PLEASE
 CLARIFY.
 4. PROVIDE CRAWL SPACE VENTS PER R408.1 AND ACCESS PER
 R408.4.
 5. EGRESS WINDOW - PGT-700 SERIES. WINDOW SIZE FROM
 WINDOW SCHEDULE 3' X 5' DOES NOT PROVIDE THE REQUIRED
 EGRESS OPENING PER R310.2.1. SELECT WINDOW FROM PGT
 CATALOG THAT MEETS EGRESS REQUIREMENTS. CHANGE ROUGH
 OPENING DEMENSIONS FOR NEW WINDOW.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-12-20 Cont ID  
Sent By cthroop Date 2018-12-20 Time 08:48 Rev Time 0.00
Received By cthroop Date 2018-12-20 Time 08:48 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-11-19 Cont ID  
Sent By jpearson Date 2018-10-05 Time 15:52 Rev Time 0.00
Received By jpearson Date 2018-10-05 Time 15:52 Sent To  
Notes
2018-11-19 12:29:29CHANGED VALUE TO $40,000 PER INFORMATION FROM OWNER,
 CHANGED STATUS TO PASS.
  
  
  
2018-10-05 15:52:09CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
 (S)
  
 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. FBC 109.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2018-12-14 Cont ID  
Sent By fmittner Date 2018-12-14 Time 11:02 Rev Time 0.00
Received By fmittner Date 2018-12-14 Time 11:02 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2018-11-14 Cont ID  
Sent By fmittner Date 2018-11-14 Time 08:05 Rev Time 0.00
Received By fmittner Date 2018-11-14 Time 08:05 Sent To  
Notes
2018-11-14 08:08:32PROPERTY LOCATED IN HISTORIC DISTRICT. ADDITIONS
 REQUIRE SUBMITTAL OF CERTIFICATE OF APPROPRIATENESS
 (COA). INITIAL REVIEW INDICATES PROPOSAL DOES NOT MEET
 DESIGN GUIDELINES. NO PRECEDENCE ON HOUSE OR
 ARCHITECTURAL STYLE FOR ARCH OR DOUBLE FRENCH DOORS
 THAT ARE DRAWN AS SOLID DOORS. QUESTIONS, CONTACT
 FRIEDERIKE MITTNER, CITY HSITORIC PRESERVATION PLANNER
 AT (561) 822-1457 OR [email protected].

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-12-20 Cont ID  
Sent By cthroop Date 2018-12-20 Time 08:49 Rev Time 0.00
Received By cthroop Date 2018-11-27 Time 11:50 Sent To  
Notes
2018-11-29 11:50:35R06

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-11-14 Cont ID  
Sent By cpuell Date 2018-11-14 Time 09:15 Rev Time 0.00
Received By cpuell Date 2018-09-14 Time 15:03 Sent To  
Notes
2018-11-06 08:54:5511/6 TO FM
  
2018-09-17 15:03:37R38

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2018-12-20 Cont ID  
Sent By cthroop Date 2018-12-20 Time 07:01 Rev Time 0.00
Received By cthroop Date 2018-12-20 Time 06:52 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-10-30 Cont ID  
Sent By skennedy Date 2018-10-30 Time 14:12 Rev Time 0.00
Received By skennedy Date 2018-10-30 Time 14:12 Sent To  
Notes
2018-10-30 14:14:011ST REVIEW: FBC 2017 6TH ED. RESIDENTIAL
 1ST REVIEW FBC 2017 EXISTING BUILDING
  
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE PLAN AND
 TAKE TO THAT OFFICE FOR REVIEW. PLEASE RETURNED STAMPED
 WITH A COPY OF RECEIPT AS APPLICABLE.
  
  
 STEVEN KENNEDY, CBO
 ASSISTANT BUILDING OFFICIAL
 (561) 805-6710
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-12-20 Cont ID  
Sent By cthroop Date 2018-12-20 Time 08:48 Rev Time 0.00
Received By cthroop Date 2018-12-20 Time 08:48 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-11-01 Cont ID  
Sent By cmontell Date 2018-10-22 Time 14:17 Rev Time 0.00
Received By cmontell Date 2018-11-01 Time 14:04 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-12-20 Cont ID  
Sent By cthroop Date 2018-12-20 Time 08:49 Rev Time 0.00
Received By cthroop Date 2018-12-20 Time 08:49 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-10-18 Cont ID  
Sent By jesmith Date 2018-10-18 Time 12:20 Rev Time 0.00
Received By jesmith Date 2018-10-18 Time 10:47 Sent To  
Notes
2018-10-18 12:10:331ST REVIEW:
 PLUMBING COMMENTS: APPROVED
  
 PROVISO
 1. TUB/SHOWER CONTROL VALVE(S) SHALL BE PRESSURE
 BALANCED PB,THERMOSTATIC MIXING (TM) OR COMBINATION
 PB/TM VALVE TYPES WITH HIGH TEMPERATURE LIMITING STOP.
 FBC RES P2708.4
 2. ACCESSIBLE TEMPERATURE LIMITING DEVICE REQUIRED ON
 HOT WATER TO MASTER BATH BATHTUB(S) IS REQUIRED. FBC
 RES P2713.3
 3. PROVIDE WATER HAMMER ARRESTORS AT WATER SUPPLIES TO
 ICE LINE, DISHWASHER AND CLOTHES WASHER PER FBC RES
 P2903.5
 4. THE VALVES FOR THE STACKABLE WASHING MACHINE(S)
 SHALL BE ACCESSIBLE. FBC RES P2903.9.3
  
 ADDITIONAL NOTE: SEE RED LINE MODIFICATION OF SANITARY
 ISOMETRIC TO MAKE CODE COMPLIANT
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2018-12-20 Cont ID  
Sent By cthroop Date 2018-12-20 Time 08:48 Rev Time 0.00
Received By cthroop Date 2018-12-20 Time 07:01 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2018-12-14 Cont ID  
Sent By fmittner Date 2018-12-14 Time 11:02 Rev Time 0.00
Received By fmittner Date 2018-12-14 Time 11:02 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2018-11-14 Cont ID  
Sent By fmittner Date 2018-11-14 Time 08:05 Rev Time 0.00
Received By fmittner Date 2018-11-14 Time 08:04 Sent To  
Notes
2018-11-14 08:05:44APPLICATION NEEDS TO REFLECT LOT COVERAGE AND SHOW
 DIMENSIONS FOR REAR SETBACK.