Plan Review Stops For Permit 18090632 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2019-01-15 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2019-01-15 |
Time |
12:14 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2019-01-14 |
Time |
19:05 |
Sent To |
|
|
Notes |
2019-01-15 12:24:56 | SPOKE TO THE ARCHITECT, BRENT WOODS ON THE TELEPHONE. | | HE AGREED TO ALLOW ME TO REDINE THE PRODUCT APPROVAL | | NUMBERS AND PRESSURES FOR THE DOORS TO THE GENERATOR | | ROOM AND THE FIRE COMMAND ROOM TO MATCH THE PRODUCT | | APPROVALS THAT HE APPROVED AND SUBMITTED. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2018-12-10 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2018-12-10 |
Time |
08:45 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2018-12-10 |
Time |
07:40 |
Sent To |
M |
|
Notes |
2018-12-10 08:45:51 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | NEW COMMENTS WERE CREATED BY THE ADDITIONAL DRAWINGS | | THAT WERE SUBMITTED. | | | | 1) PLANS SHOW A DOUBLE OUTSWING DOOR (002) FOR THE | | GENERATOR ROOM AND THE DOOR SCHEDULE ON SHEET A-6.01 | | LISTS DOOR (002) AS A 3' WIDE DOOR. CLARIFY. FBC | | 107.2.1 | | | | 2) DOORS (001) AND (003) TO THE FIRE COMMAND ROOM ARE | | SINGLE DOORS AND ARE SPECIFIED AS TYPE 5 DOORS IN THE | | SCHEDULE ON A-6.01. THE TYPE 5 DOOR IS A DOUBLE DOOR. | | THE REMARKS FOR DOOR (003) IN THE SCHEDULE STATE THAT | | THIS IS THE DOOR TO THE MAINTENANCE ROOM, NOT THE FIRE | | COMMAND ROOM. PLEASE CORRECT. FBC 107.2.1 | | | | 3) PRODUCT APPROVALS ARE REQUIRED TO BE SUBMITTED FOR | | THE DOORS AND LOUVERS IN THE EXTERIOR WALLS. FBC | | 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS FOR | | THOSE PRODUCTS WHICH ARE REGULATED BY FAC 61G20-3.001 | | PER FLORIDA STATUTE 553.842 (5) THAT HAVE BEEN REVIEWED | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH FL OR NOA | | NUMBERS INCLUDING INSTALLATION INSTRUCTIONS AND MAXIMUM | | DESIGN PRESSURES FOR EACH REGULATED PRODUCT. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
2018-09-26 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2018-09-26 |
Time |
18:11 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2018-09-26 |
Time |
18:11 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2018-12-13 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2018-12-13 |
Time |
07:22 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2018-12-13 |
Time |
06:39 |
Sent To |
P |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2018-09-28 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2018-09-28 |
Time |
10:04 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2018-09-28 |
Time |
05:33 |
Sent To |
FIRE |
|
Notes |
2018-09-28 09:23:02 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1. CONDUIT SIZE FROM GENERATOR TO ATS NOT ANNOTATED ON | | PLAN. PLEASE PROVIDE CORRECTION. FBC 107.2.1 | | | | 2. WIRING METHOD AND CONDUIT SIZE FROM GENERATOR TO | | FIRE PUMP CONTROLLER NOT ANNOTATED ON PLAN. WRING | | METHOD MUST COMPLY WITH 695.6A2. PLEASE PROVIDE | | CORRECTION. FBC 107.2.1 | | | | 3. WIRE SIZE FROM GENERATOR TO ATS NOT ANNOTATED ON | | PLAN. PLEASE PROVIDE CORRECTION. FBC 107.2.1 | | | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | CODES IN EFFECT: | | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE 2017 6TH ED. | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | V/R, | | | | FRANK GIAQUINTO | | ELECTRICAL INSPECTOR | | ELECTRICAL PLANS EXAMINER | | CITY OF WPB | | [email protected] | | CELL: 561-657-1653 | | | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
|
|
|
Cont ID |
|
Sent By |
Bwoods |
Date |
2018-12-06 |
Time |
0:00 |
Rev Time |
0.00 |
Received By |
|
Date |
2018-12-03 |
Time |
0:00 |
Sent To |
M |
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2018-10-17 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2018-10-17 |
Time |
00:00 |
Rev Time |
0.00 |
Received By |
bwoods |
Date |
2018-10-17 |
Time |
00;00 |
Sent To |
I |
|
Notes |
2018-10-17 13:00:54 | PER NFPA 110 | | | | 7.2 LOCATION. | | 7.2.1 INDOOR EPS INSTALLATIONS. THE EPS SHALL BE | | INSTALLED IN A | | SEPARATE ROOM FOR LEVEL 1 INSTALLATIONS. | | 7.2.1.1 THE EPS ROOM SHALL BE SEPARATED FROM THE REST | | OF THE | | BUILDING BY CONSTRUCTION WITH A 2-HOUR FIRE RESISTANCE | | RATING. | | | | PLEASE PROVIDE DETAILS OF THE RATING OF THE PROPOSED | | ROOM AND DOOR TO THIS GENERATOR ROOM. | | | | | | | | | | | | THERE IS AN INDICATION OF EXHAUST PIPING, HOWEVER, | | THERE ARE NO DETAILS. | | | | PER NFPA 110 | | | | 7.10 EXHAUST SYSTEM. | | 7.10.1 THE EXHAUST SYSTEM EQUIPMENT AND INSTALLATION, | | INCLUDING | | PIPING, MUFFLER, AND RELATED ACCESSORIES, SHALL BE IN | | ACCORDANCE WITH NFPA37, STANDARD FOR THE INSTALLATION | | AND USE OF | | STATIONARY COMBUSTION ENGINES AND GAS TURBINES, AND | | OTHER APPLICABLE | | STANDARDS. | | 7.10.2 EXHAUST SYSTEM INSTALLATION SHALL BE GASTIGHT TO | | PREVENT | | EXHAUST GAS FUMES FROM ENTERING INHABITED ROOMS OR | | BUILDINGS | | AND TERMINATE IN SUCH A MANNER THAT TOXIC FUMES CANNOT | | REENTER A BUILDING OR STRUCTURE, PARTICULARLY THROUGH | | WINDOWS, | | AIR VENTILATION INLETS, OR THE ENGINE AIR-INTAKE | | SYSTEM. | | 7.10.3* EXHAUST PIPING SHALL BE CONNECTED TO THE PRIME | | MOVER | | BY MEANS OF A FLEXIBLE CONNECTOR AND SHALL BE | | INDEPENDENTLY | | SUPPORTED THEREAFTER SO THAT NO DAMAGING WEIGHT OR | | STRESS IS | | APPLIED TO THE ENGINE EXHAUST MANIFOLD OR TURBOCHARGER. | | | | PLEASE PROVIDE SPECIFIC DETAILS AND SPEC SHEETS. | | | | | | | | | | THERE IS AN INDICATION OF A FUEL TANK INSIDE THE | | GENERATOR ROOM. THERE IS NO INDICATIONS IF IT MEETS THE | | REQUIREMENTS OF NFPA 110 OR OTHER APPLICABLE CODES. | | | | PER NFPA 110 | | | | 7.9.1.1 ALL FUEL TANKS AND SYSTEMS SHALL BE INSTALLED | | AND MAINTAINED | | IN ACCORDANCE WITH NFPA 30, FLAMMABLE AND COMBUSTIBLE | | LIQUIDS CODE; NFPA 37, STANDARD FOR THE INSTALLATION | | AND USE OF | | STATIONARY COMBUSTION ENGINES AND GAS TURBINES; NFPA | | 54, NATIONAL | | FUEL GAS CODE; AND NFPA 58, LIQUEFIED PETROLEUM GAS | | CODE. | | 7.9.3.1* GALVANIZED FUEL LINES SHALL NOT BE USED. | | 7.9.3.2 APPROVED FLEXIBLE FUEL LINES SHALL BE USED | | BETWEEN THE | | PRIME MOVER AND THE FUEL PIPING. | | 7.9.11 ALL MANUAL FUEL SYSTEM VALVES SHALL BE OF THE | | INDICATING | | TYPE. | | 7.9.12.1 A MINIMUM CLEARANCE OF 0.9 M (36 IN.) SHALL BE | | MAINTAINED ON ALL SIDES. | | | | PLEASE PROVIDE DETAILS. | | | | | | | | THERE IS AN INDICATION OF A FUEL TANK WITHIN THE | | GENERATOR ROOM. THERE IS NO INDICATION IF THIS TANK IS | | DOUBLE WALLED OR THERE IS CONTAIMENT. | | | | PER NFPA 30 | | | | 9.13* CONTAINMENT, DRAINAGE, AND SPILL CONTROL. | | 9.13.1 STORAGE AREAS SHALL BE DESIGNED AND OPERATED TO | | PREVENT | | THE DISCHARGE OF LIQUIDS TO PUBLIC WATERWAYS, PUBLIC | | SEWERS, | | OR ADJOINING PROPERTY, UNLESS SUCH DISCHARGE HAS BEEN | | SPECIFICALLY | | APPROVED. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2019-01-28 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2019-01-28 |
Time |
14:13 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2019-01-25 |
Time |
13:50 |
Sent To |
|
|
Notes |
2019-01-28 13:50:57 | 1/28 TO TL DESK | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2019-01-22 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2019-01-22 |
Time |
11:02 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2019-01-11 |
Time |
14:59 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2018-12-17 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2018-12-17 |
Time |
11:07 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2018-11-26 |
Time |
13:34 |
Sent To |
|
|
Notes |
2018-11-28 13:34:18 | RESUB ROUTED TO FIRE INBOX |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2018-10-23 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2018-10-23 |
Time |
14:05 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2018-09-14 |
Time |
11:40 |
Sent To |
|
|
Notes |
2018-09-17 11:40:38 | ROUTED TO ZONING INBOX |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2019-01-28 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2019-01-28 |
Time |
11:51 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2019-01-28 |
Time |
11:51 |
Sent To |
|
|
Notes |
2019-01-28 12:05:47 | MECHANICAL PROVISO: | | | | THE SUBMITTED PLANS, REVISED ARCHITECTURAL AND | | MECHANICAL SKETCHES, AND SPEC SHEETS ARE APPROVED WITH | | EXCEPTION. | | A COMPLETE MATCHING SET OF REVISED ARCHITECTURAL, | | MECHANICAL, AND ELECTRICAL PLANS MUST BE SUBMITTED FOR | | FINAL APPROVAL. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2019-01-16 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2019-01-16 |
Time |
09:09 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2019-01-16 |
Time |
09:09 |
Sent To |
|
|
Notes |
2019-01-16 09:51:15 | 2ND REVIEW FBC-2017 MECHANICAL | | PERMIT #18090632 | | 1/16/19 | | | | CODES IN EFFECT: | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | 2017 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | EDITION 2017 | | NFPA 37-2018 | | NFPA 110- | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) REFER TO SECTIONS 7.7.2,1 &, 7.7.2.3 & 7.7.3 NFPA | | 110: PER THE ENGINEER'S PLAN AND NARRATIVE, THE | | VENTILATION AIR FOR THE GENERATOR IS BEING DRAWN IN | | THROUGH A LOUVERED OPENING IN THE 2HR. FIRE-RATED WALL | | GENERATOR ROOM WALL THAT ADJACENT TO THE PARKING GARAGE | | WHICH IS NOT PERMITTED PER SECTION 7.7.2.1 & 7.7.3. | | THESE SECTIONS STATE THAT VENTILATION AIR MUST BE | | SUPPLIED DIRECTLY FROM A SOURCE OUTSIDE THE BUILDING. | | SECTION 7.7.2.3 PROHIBITS THE USE OF A FIRE DAMPER TO | | PROTECT THE OPENING, THEREFORE THE VENTILATION OPENING | | LOCATION WOULD NOT BE COMPLIANT BECAUSE OPENINGS IN | | FIRE BARRIERS REQUIRE PROTECTION ACCORDING TO SECTION | | 607.5.2 FBC M. | | | | 2) THE SUBMITTED CUT SHEET FOR THE IN LINE FAN (EF-2) | | IN THE GENERATOR/TANK ROOM IS FOR A MODEL THAT IS NOT | | THE SAME AS FAN IN THE SUBMITTED SCHEDULE. THE NEW FAN | | DOES NOT APPEAR TO BE IN COMPLAINCE WITH SECTIONS 503.1 | | AND 503.2 FBC M WHICH REQUIRE THE MOTOR FOR THE FAN TO | | BE OUTSIDE THE DUCT, AND ALL PARTS OF THE FAN IN | | CONTACT WITH FLAMMABLE VAPORS, FUMES, OR DUSTS SHALL BE | | OF NONFERROUS OR NONSPARKING MATERIALS ETC. | | | | 3) THE EXHAUST DUCT WORK FOR EF-2 SHALL BE G90 PER | | SECTIONS 510.9 AND SHALL ALSO BE ENCLOSED IN 2HR, | | FIRE-RESISTANT RATED CONSTRUCTION FROM POINT OF | | PENETRATRION TO THE OUTLET TERMINAL- SECTIONS 510.2 & | | 510.7.3 FBC M, AND 6.3.6.5.1 NFPA 37. | | | | 4) AS PREVIOUSLY REQUESTED SUBMIT THE GENERATOR EXHAUST | | PIPE SPECS. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | KEEP THEM WITH THE SUBMITTALS | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2018-12-12 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2018-12-12 |
Time |
09:08 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2018-12-11 |
Time |
17:44 |
Sent To |
E |
|
Notes |
2018-12-12 10:06:05 | 1ST REVIEW FBC-2017 MECHANICAL | | PERMIT #18090632 | | 12/12/18 | | | | CODES IN EFFECT: | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | 2017 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | EDITION 2017 | | NFPA 37-2018 | | NFPA 110- | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M-401: THE GENERATOR/TANK (EPS) ROOM DRAWINGS | | SHOW THE INTAKE AND EXHAUST AIRFLOW ARROWS REVERSED. | | THE RADIATOR IS EXHAUST AND THE LOUVER BY THE DOORS IN | | ALLEY IS INTAKE- PLEASE CORRECT. | | | | 2) M-401: IT APPEARS THAT THE GENERATOR RADIATOR | | EXHAUST DISCHARGE AND EF-2 ARE BOTH DISCHARGING INTO | | THE PARKING GARAGE. PLEASE REVIEW THE FOLLOWING LIST OF | | CODE SECTIONS AND CORRECT: | | | | A) SECTION 501.3 FBC M: AIR REMOVED BY MECHANICAL | | EXHAUST SYSTEMS SHALL DISCHARGE TO THE OUTDOORS. | | | | B) SECTION 510.6.7 FBC M: HAZARDOUS EXHAUST DUCT | | SYSTEMS SHALL EXTEND DIRECTLY TO THE EXTERIOR OF THE | | BUILDING. | | | | C) SECTION 6.3.6.5.2 NFPA 37- 2015: VENTILATION SHALL | | DISCHARGE TO A SAFE LOCATION OUTSIDE OF THE BUILDING. | | | | D) SECTION 7.7.4.2 NFPA 110- 2016: RADIATOR AIR SHALL | | DISCHARGE BE DUCTED OUTDOORS. | | | | 3) M-401: PLEASE CORRECT KEYED NOTE #3. THE EXHAUST | | SYSTEM IN THE GENERATOR/TANK (EPS) ROOM (EF-2) SHALL | | RUN CONTINUOUSLY- SECTIONS 4.1.2.1.3 & 6.3.6.5.1 NFPA | | 37, AND SECTION 502.4.2 FBC M. | | | | 4) M-401: PROVIDE EXHAUST VENTILATION CALCULATIONS FOR | | THE GENERATOR/TANK (EPS) ROOM, AND PROVIDE AN EQUIPMENT | | SCHEDULE FOR EF-2- SECTION 502.4.2 FBC M. | | | | 5) M-401: INDICATE THE TYPE AND GAGE OF THE EXHAUST | | DUCTWORK- SECTION 510.9 FBC M. | | | | 6) M-401: THE OUTSIDE AIR INTAKE FOR THE GENERATOR/TAN | | K (EPS) ROOM SHALL BE 10' FROM THE ALLEY IN ACCORDANCE | | WITH SECTION 510.6.5 AND 401.4 (1) & (2) FBC M. | | | | 7) M-401: REFER TO SECTION 7.7.1 NFPA 110- 2016 AND | | VERIFY THAT THE VENTILATION AIRFLOW IN THE | | GENERATOR/TANK (EPS) ROOM IS DESIGNED TO LIMIT THE | | MAXIMUM AIR TEMPERATURE IN THE ROOM TO THE MAXIMUM | | AMBIENT AIR TEMPERATURE REQUIRED BY THE GENERATOR | | MANUFACTURER. CONSIDERATION SHALL BE GIVEN TO ALL THE | | HEAT EMITTED TO THE ROOM BY THE ENERGY CONVERTER, | | EXHAUST PIPES, AND ALL OTHER HEAT PRODUCING EQUIPMENT- | | SECTION 7.7.1.1. DESIGN OF THE HEATING, COOLING, AND | | VENTILATION SYSTEM SHALL AMONG OTHER THINGS, INCLUDE | | PROVISONS FOR FACTORS SUCH AS HEAT, COLD, HUMIDITY, | | LOUVERS, ETC.- SECTION 7.7.7. | | | | 8)1SUBMIT THE GENERATOR EXHAUST PIPE SPECIFICATIONS, | | AND PROVIDE AN EXHAUST PIPE DIAGRAM SHOWING THE TOTAL | | SYSTEM RUN AND LENGTH MEASUREMENT. PLEASE INCLUDE ALL | | COMPONENTS OF THE SYSTEM INCLUDING THE SILENCER, AND | | ANY CONTRACTOR SUPPLIED PIPING. | | | | 9) THE MAXIMUM BACKPRESSURE FOR THE EXHAUST SYSTEM PER | | THE MANUFACTURER'S SPECS IS 10 KPA PLEASE PROVIDE A | | BACKPRESSURE CALCULATION TO SHOW COMPLIANCE. THE CALC | | MUST INCLUDE ALL COMPONENTS OF THE EXHAUST SYSTEM, | | INCLUDING THE SILENCER AND ALL FACTORY OR CONTRACTOR | | SUPPLIED PIPING. | | | | 10) PROVIDE THE UL CERTIFICATES FOR THE GENERATOR AND | | THE FUEL TANK- SECTION 304.1 FBC M. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | KEEP THEM WITH THE SUBMITTALS | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
4 |
Status |
P |
Date |
2019-01-28 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2019-01-28 |
Time |
14:13 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2019-01-28 |
Time |
14:12 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
F |
Date |
2019-01-22 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2019-01-22 |
Time |
11:02 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2019-01-16 |
Time |
13:29 |
Sent To |
I |
|
Notes |
2019-01-18 13:25:23 | 1) SUBMIT THE GENERATOR EXHAUST PIPE SPECIFICATIONS. | | WPB AMEND. TO FBC SEC. 107.2.1. 2ND REQUEST. | | 2) THE GENERATOR SHALL MEET THE REQUIREMENTS OF NFPA 37 | | PER NFPA 37 SEC. 1.3 & 2017 FBC MECH. SEC. 915. THE | | NARRATIVE STATES THAT THE GENERATOR WILL MEET THE | | REQUIREMENTS OF NFPA 37 BUT DOCUMENTATION HAS NOT BEEN | | PROVIDED TO SUPPORT SUCH STATEMENT. PROVIDE | | DOCUMENTATION FROM THE MANUFACTURER THAT CONFIRMS | | COMPLIANCE. WPB AMEND. TO FBC SEC. 107.2.1.2ND REQUEST. | | 3) INDICATE ON THE PLANS THE CLASS OF LIQUID OF THE | | FUEL IN ACCORDANCE WITH NFPA 30 SEC. 4.3.2. 2ND | | REQUEST. | | 4) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE FUEL | | STORAGE TANK. THE STORAGE TANK SHALL MEET THE | | REQUIREMENTS OF NFPA 37 SEC. 22.11.4.1 THROUGH | | SECS.22.11.4.10. SUBMIT A SECTION DETAIL AND PLAN VIEW | | OF THE TANK SHOW THE SIZE OF ALL TANK OPENINGS, VENTS | | AND IDENTIFY EACH OPENING. 2ND REQUEST. | | 5) THE GENERATOR EXHAUST BACKPRESSURE CALCULATION SHEET | | SHOWS THE DIAMETER OF THE EXHAUST AS 5 INCHES BUT | | SHT.SK-M401-2 SHOWS THE EXXHAUST AS 6 INCH. CLARIFY AND | | SUBMIT A REVISED CALCULATION SHEET. | | 6) THE GENERATOR EXHAUST BACKPRESSURE CALCULATION SHEET | | NOTES TWO SHORT RADIUS ELBOWS BUT SHT. SK-M401-2 | | APPEARS TO SHOW THREE ELBOWS: ONE AT THE GENERATOR, ON | | AT THE HORIZONTAL TURN AND GOING VERTICAL. CLARIFY AND | | SUBMIT A REVISED CALCULATION SHEET. | | 7) A SIGN OR MARKING THAT MEETS THE REQUIREMENTS OF | | NFPA 704 OR ANOTHER APPROVED SYSTEM SHALL BE APPLIED TO | | STORAGE TANKS CONTAINING LIQUIDS PER NFPA 30 SEC. | | 21.7.2.1. PLACE A NOTE ON THE PLAN THAT THIS WILL BE | | DONE. | | 8) EMERGENCY RELIEF VENTING IS REQUIRED FOR THE FUEL | | TANK PER NFPA 30 SEC. 22.7. THIS SHALL INCLUDE THE | | INTERSTITIAL SPACE.REFER TO NFPA 30 SEC. 22.7.3 AND | | TABLE 22.7.3.2. SUBMIT SPECIFICATIONS FOR THE EMERGENCY | | VENT. THIS IS NOT SHOWN ON THE PLAN. | | 9) SHOW ON THE PLAN HOW THE VENT PIPES AND FILL PIPE | | WILL BE PROTECTED WHERE PASSING THROUGH THE WALLS OF | | THE STRUCTURE. GROUTING IN PLACE AS NOTED IN THE | | NARRATIVE IS UNACCEPTABLE AND DOES NOT MEET CODE. | | PIPING THAT PASSES THROUGH THE WALL OF A STRUCTURE | | SHALL BE DESIGNED TO PREVENT DAMAGING STRESSES AND | | LEAKAGE DUE TO SETTLEMENT OR FIRE EXPOSURE.NFPA 30 | | SEC.27.6.3. 2ND REQUEST. | | 10) SUBMIT THE UL APPROVAL/ CERTIFICATE/ CERTIFICATION | | FOR THE FUEL TANK.SECTION 304.1 2017 FBC-MECH. 2ND | | REQUEST. | | 11) NORMAL VENTS FROM THE FUEL STORAGE TANK SHALL | | COMPLY WITH NFPA 30 SEC.21.4.3.3 NORMAL VENTS SHALL BE | | SIZED IN ACCORDANCE WITH EITHER API STANDARD 2000, | | VENTING ATMOSPHERIC AND LOW-PRESSURE STORAGE TANKS, OR | | ANOTHER APPROVED STANDARD. ALTERNATIVELY, THE NORMAL | | VENT SHALL BE AT LEAST AS LARGE AS THE LARGEST FILLING | | OR WITHDRAWAL CONNECTION, BUT IN NO CASE SHALL IT BE | | LESS THAN 1.25 IN. (32 MM) NOMINAL INSIDE DIAMETER. | | 12) THE DOCUMENT FROM EMC ( ENGINEERED MANUFACTURING | | CORP.) IS UNACCEPTABLE. WHO IS CERTIFYING THE TANK? | | THERE IS NO NAME ON THIS DOCUMENT OR THE TITLE OF SUCH | | PERSON. WHO IS THE PERSON AND WHAT IS THEIR RANKING IN | | THE COMPANY? IN ADDITION, THIS DOCUMENT SHOWS THE | | RESULTS OF A LEAKAGE TEST, NOT A UL CERTIFICATION FOR | | THE TANK. THE TANK SHALL BE IN COMPLIANCE WITH UL 2085 | | PER THE SPECIFICATIONS ON SHT. E-002. | | 13) SHT. E-002 - 2.4 - FUEL OIL STORAGE SPECIFICATIONS | | REFER TO A SUB-BASE TANK BUT THAT IS NOT WHAT IS BEING | | INSTALLED. CLARIFY. | | 14) NFPA 30-12 SEC. 22.11.4. - WHERE A SECONDARY | | CONTAINMENT- TYPE TANK IS USED TO PROVIDE SPILL | | CONTROL, THE TANK SHALL MEET ALL OF THE REQUIREMENTS OF | | NFPA 30-12 SECS. 22.11.4.1 THROUGH 22.22.4.10. | | 15) IF A NARRRATIVE RESPONSE IS SUBMITTED UPON REVIEW | | OF THESE PLAN REVIEW COMMENTS, THE NARRATIVE SHALL BE | | ON THE LETTERHEAD OF THE ENGINEERING FIRM OF RECORD WHO | | IS ELLIS & GRITTER, NOT STRATICON WHO IS THE | | CONTRACTOR.WPB AMEND TO FBC SEC.107.2. | | | | THE FOLLOWING ITEMS WILL BE PROVISOS AND ARE TO BE | | CHECKED IN THE FIELD BY THE FIELD INSPECTOR: | | | | 1) THE RETURN LINE TO THE DAY TANK SHALL BE BELOW THE | | FUEL RETURN ELEVATION PER NFPA 110SEC.7.9.4.1. | | 2) APPROVED FLEXIBLE FUEL LINES SHALL BE USED | | BETWEENTHE PRIME MOVER AND THE FUEL PIPING. NFPA 110 | | SEC.7.9.3.2. | | | | | | | | | | | | | | | | | | | | | | | | | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | | | | | | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2018-12-17 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2018-12-17 |
Time |
11:07 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2018-12-14 |
Time |
06:08 |
Sent To |
I |
|
Notes |
2018-12-14 11:17:57 | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) SUBMIT THE GENERATOR EXHAUST PIPE SPECIFICATIONS, | | AND PROVIDE AN EXHAUST PIPE DRAWING SHOWING THE TOTAL | | SYSTEM RUN AND LENGTH MEASUREMENT. PLEASE INCLUDE ALL | | COMPONENTS OF THE SYSTEM INCLUDING THE SILENCER, ANY | | CONTRACTOR SUPPLIED PIPING, AND PIPE SUPPORT AND | | SPACING. | | 2) THE GENERATOR SPECIFICATIONS NOTE THAT THE GENERATOR | | OFFERS A UL 2200 LISTING. SUBMIT A COPY OF THE | | CERTIFICATE OF COMPLIANCE SHOWING THE UL 2200 LISTING. | | 2017 FBC-MECH. SEC.915. | | 3) THE GENERATOR SHALL MEET THE REQUIREMENTS OF NFPA 37 | | PER 2017 FBC-MECH. SEC. 915. I COULD NOT FIND THIS | | INFORMATION IN THE SPECIFICATIONS. | | 4) SPILL CONTROL, CONTAINMENT AND DRAINAGE MAY BE | | REQUIRED FOR THE FUEL TANK DEPENDING ON THE CLASS OF | | LIQUID OF THE FUEL. NFPA 30 SEC. 9.13. IT APPEARS THE | | FUEL IS A II COMBUSTIBLE LIQUID PER NFPA 30. CLARIF ON | | THE PLANS.. | | 5) IN ADDITION TO THE TANK PLANS THAT HAVE BEEN | | SUBMITTED, SUPPLY ANY ADDITIONAL MANUFACTURER'S | | SPECIFICATIONS FOR THE FUEL TANK.WPB AMEND. TO FBC SEC. | | 107.2.1. | | 6) THE MAXIMUM BACKPRESSURE FOR THE EXHAUST SYSTEMVPER | | THE MANUFACTURER'S SPECS IS 10 KPA PLEASE PROVIDE A | | BACKPRESSURE CALCULATION TO SHOW COMPLIANCE. THE | | CALCULATION MUST INCLUDE ALL COMPONENTS OF THE EXHAUST | | SYSTEM, INCLUDING THE SILENCER AND ALL FACTORY OR | | CONTRACTOR SUPPLIED PIPING. | | 7) THE FUEL TANK VENTS SHALL BE 5 FEET FROM BUILDING | | OPENINGS AND 15 FEET FROM POWERED VENTILATION AIR | | INTAKES PER NFPA 30-12 SEC.19.5.3.2. | | 8) A SIGN OR MARKING THAT MEETS THE REQUIREMENTS OF | | NFPA 704, OR ANOTHER APPROVED SYSTEM, SHALL BE APPLIED | | TO STORAGE TANKS CONTAINING LIQUIDS PER NFPA 30 | | SEC.21.7.2.1. | | 9) EMERGENCY RELIEF VENTING IS REQUIRED FOR THE FUEL | | TANK PER NFPA 30 SEC.22.7. | | 10) SHOW ON THE PLAN HOW THE VENT PIPES FROM THE FUEL | | TANK WILL BE PROTECTED WHERE PASSING THROUGH THE WALLS | | OF THE STRUCTURE. | | 11) THE FILL PORT FOR THE FUEL TANK SHALL BE PROVIDED | | ON AN EXTERIOR WALL OF THE ROOM OR STRUCTURE ENCLOSING | | THE TANK AT A POINT AT LEAST 24 INCHES FROM ANY | | BUILDING OPENING AT THE SAME OR LOWER LEVEL PER NFPA | | 37-15 SEC. 6.6.3.3. SHOW THE LOCATION OF THE FILL PORT | | ON THE PLANS. | | 12) THE MAXIMUM BACKPRESSURE FOR THE EXHAUST SYSTEMVPER | | THE MANUFACTURER'S SPECS IS 10 KPA PLEASE PROVIDE A | | BACKPRESSURE CALCULATION TO SHOW COMPLIANCE. THE CALC | | MUST INCLUDE ALL COMPONENTS OF THE EXHAUST SYSTEM, | | INCLUDING THE SILENCER AND ALL FACTORY OR CONTRACTOR | | SUPPLIED PIPING. | | 13) PROVIDE THE UL CERTIFICATE FOR THE FUEL TANK- | | SECTION 304.1 FBC M | | 14) SUBMIT A FUEL PIPING RISER DIAGRAM. DAY TANKS ON | | DIESEL SYSTEMS SHALL BE INSTALLED BELOW THE ENGINE FUEL | | RETURN ELEVATION PER NFPA 110-13 SEC.7.9.4. | | 15) THE RETURN LINE TO THE DAY TANK SHALL BE BELOW THE | | FUEL RETURN ELEVATION PER NFPA 110 SEC. 7.9.4.1. | | 16) APPROVED FLEXIBLE FUEL LINES SHALL BE USED BETWEEN | | THE PRIME MOVER AND THE FUEL PIPING. NFPA 110 SEC. | | 7.9.3.2. | | 17) NORMAL VENTS FROM THE FUEL STORAGE TANK SHALL | | COMPLY WITH.NFPA 30 SEC. 21.4.3.3. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | | | | | | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2018-09-25 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2018-09-25 |
Time |
05:48 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2018-09-25 |
Time |
05:30 |
Sent To |
|
|
Notes |
2018-09-25 05:47:59 | 1) PROVIDE A COMPLETE DESCRIPTION OF THE WORK ON THE | | PERMIT APPLICATION. THE DESCRIPTION OF WORK ON THE | | APPLICATION JUST NOTES "GENERATOR". IS THIS GENERATOR | | REPLACING AN EXISTING? THE PLANS ARE VAGUE. 2017 FBC | | SEC. 107.2.1. | | 2) THE PLANS SHOW A FUEL TANK. IS THE TANK NEW OR | | ESISTING? WHAT IS THE CAPACITY? WHAT TYPE OF TANK IS | | IT? SUBMIT 2 COPIES OF THE MANUFACTURER'S | | SPECIFICATIONS FOR THE FUEL TANK. 2017 FBC SEC. | | 107.2.1. | | 3) THE TANK INSTALLATION SHALL COMPLY WITH THE | | APPLICABLE REQUIREMENTS OF NFPA 30. | | 4) SUBMIT TWO COPIES OF THE MSDS SHEETS FOR THE FUEL. | | 2017 FBC SEC. 107.2.1. | | 5) SUBMIT A FUEL PIPING RISER DIAGRAM FOR ANY NEW FUEL | | PIPING THAT WILL BE INSTALLED. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2018-09-20 |
|
|
Cont ID |
|
Sent By |
mcruz |
Date |
2018-09-20 |
Time |
15:26 |
Rev Time |
0.00 |
Received By |
mcruz |
Date |
2018-09-20 |
Time |
15:26 |
Sent To |
B |
|
Notes |
|
|