Plan Review Details - Permit 18090573
Plan Review Stops For Permit 18090573
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-10-24 Cont ID  
Sent By jwitmer Date 2018-10-24 Time 13:35 Rev Time  
Received By jwitmer Date 2018-10-24 Time 13:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-10-26 Cont ID  
Sent By jpearson Date 2018-10-26 Time 15:42 Rev Time 0.00
Received By jpearson Date 2018-10-26 Time 15:42 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-10-01 Cont ID  
Sent By jpearson Date 2018-10-01 Time 15:22 Rev Time 0.00
Received By jpearson Date 2018-10-01 Time 15:22 Sent To  
Notes
2018-10-01 15:21:16CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY A LICENSED DESIGN PROFESSIONAL OR SIGNED BY
 THE ELECTRICAL CONTRACTOR QUALIFIER. FS 471.003(2)(H);
 471.025; WPB FBC 107.2.1, 107.3.5
 2. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. FBC 109.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-09-18 Cont ID  
Sent By pleduc Date 2018-09-18 Time   Rev Time 0.00
Received By pleduc Date 2018-09-18 Time 11:59 Sent To I
Notes
2018-09-18 13:02:27THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) ANY REMOVAL OF WALLS, NEW WALLS OR A RECONSTRUCTION
 OF AREAS REQUIRES A REVIEW OF THE FIRE SPRINKLER
 PROTECTION.
  
 ANY AND ALL WORK ON THE FIRE SPRINKLER SYSTEM SHALL BE
 DONE UNDER SEPARATE SHOP DRAWINGS AND BY CERTIFIED LIFE
 SAFETY CONTRACTORS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2018-10-26 Time   Rev Time 0.00
Received By lmarchan Date 2018-10-25 Time 12:45 Sent To  
Notes
2018-10-26 12:45:52RESUB ROUTED TO JPEARSON

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-10-24 Cont ID  
Sent By pleduc Date 2018-10-24 Time 13:40 Rev Time 0.00
Received By cpuell Date 2018-09-13 Time 15:41 Sent To  
Notes
2018-09-14 15:41:28B04

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-10-09 Cont ID  
Sent By jesmith Date 2018-10-09 Time 11:13 Rev Time 0.00
Received By jesmith Date 2018-10-09 Time 11:13 Sent To  
Notes
2018-10-09 11:13:50CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 1ST REVIEW:
 PLUMBING COMMENTS: APPROVED
  
 PROVISO
 PROVIDE WATER HAMMER ARRESTORS AT WATER SUPPLIES TO ICE
 LINE AND DISHWASHER PER FPC PL 604.9
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715