Plan Review Details - Permit 18090558
Plan Review Stops For Permit 18090558
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-12-12 Cont ID  
Sent By cthroop Date 2018-12-12 Time 12:59 Rev Time 0.00
Received By cthroop Date 2018-12-11 Time 16:54 Sent To  
Notes
2018-12-12 13:00:28PROVISOS ADDRESSED AND REMOVED FROM PLAN. CT

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-11-14 Cont ID  
Sent By shill Date 2018-11-14 Time 12:18 Rev Time 0.00
Received By shill Date 2018-11-05 Time 07:50 Sent To  
Notes
2018-11-14 12:26:21****PROVISOS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC B 1603.1.4, REVISE PLAN TO INCLUDE WIND DESIGN
 CRITERIA, INCLUDING DESIGN PRESSURES FOR THE NEW DOORS.
  
 2. PRIOR TO INSTALLATION, DOOR ENGINEERING REVIEWED BY
 DESIGNER OF RECORD IS TO BE SUBMITTED AND ISSUED PRIOR
 TO INSTALLATION. A SEPARATE SUBMITTAL HAS BEEN
 GENERATED FOR THE DOOR ENGINEERING TO FACILITATE
 ISSUANCE OF THIS PERMIT.
  
 3. REVISE THE LIFE SAFETY PLAN; OCCUPANT LOAD IS OVER
 50 SO REQUIRES TWO REMOTELY LOCATED EXITS. THE THREE
 FRENCH DOORS ARE SHOWN AS NON-EGRESS, BUT ONE IS
 REQUIRED. BUILDING OFFICIAL HAS AGREED TO APPLICANT'S
 PROPOSAL OF DOOR SIGNAGE INDICATING "OPEN" OR "CLOSED"
 AND AGREEMENT THAT THE DOORS WILL REMAIN UNLOCKED AT
 ALL TIMES THAT THE RESTAURANT IS OPEN.
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-10-11 Cont ID  
Sent By shill Date 2018-10-11 Time 06:13 Rev Time 0.00
Received By shill Date 2018-10-10 Time 18:25 Sent To  
Notes
2018-10-11 06:26:13****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC A 226, 902.1, IT APPEARS THAT THERE ARE TWO
 DINING BAR AREAS; REVISE PLAN TO SHOW COMPLIANCE. BAR
 HEIGHT IS NOT CLEAR, AND NO ACCESSIBLE PORTION SHOWN.
  
 2. FBC A 227, SALES AND SERVICE A POS AND PICK UP AREA
 IS SHOWN. REVISE PLAN TO SHOW COMPLIANCE.
  
 3. FBC A TABLE 404.2.41(C), THE TWO BATHROOM DOORS SHOW
 12" CLEARANCE ON THE PULL SIDE, BUT IT APPEARS THAT 18"
 IS REQUIRED. ALTHOUGH THIS IS EXISTING, PLEASE SEE FBC
 A 202.4. IT APPEARS THAT THERE IS ROOM TO MOVE THE LAV
 AND MAINTAIN ALL REQUIRED CLEAR FLOOR SPACES. NOTE
 THAT, AS INSTALLED, A WHEELCHAIR USER COULD ENTER AND
 USE THE BATHROOM BUT MAY BE UNABLE TO EXIT.
  
 4. A.04, DOOR SCHEDULE SHOWS "NA" FOR ALL DOORS. FLOOR
 PLAN SHOWS THREE NEW DOUBLE DOORS PROPOSED AS WELL AS
 EXISTING DOORS AND REFERS TO STRUCTURAL DRAWINGS FOR
 THE NEW DOORS. NO STRUCTURAL SHEETS WERE SUBMITTED,
 PLEASE PROVIDE. LIFE SAFETY/FLOOR PLAN SHOULD SHOW THE
 SIZE OF THE NEW DOORS PROPOSED AS WELL AS PROVIDE
 INFORMATION REGARDING EXISTING DOORS, FBC 107, FBC B
 1609, FBC B CHAPTER 10.
  
 5. FBC B 1603.1.4, REVISE PLAN TO INCLUDE WIND DESIGN
 CRITERIA, INCLUDING DESIGN PRESSURES FOR THE NEW DOORS.
  
 6. TO AVOID ANY FIELD CONFLICTS, REVISE THE DOOR
 SCHEDULE TO INCLUDE THE PANIC BARS REQUIRED BY FBC B
 1010.1.10 (PER FBC EB 801.3.
  
 7. FLORIDA STATUTE 481, DOCUMENTS PREPARED BY AN
 ARCHITECT AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 SIGNED, SEALED DATED ORIGINALS. AT LEAST ONE PAGE WAS
 SEALED BUT NOT SIGNED AND DATED. PLEASE CONFIRM ALL
 PAGES PRIOR TO RESUBMITTAL.
  
 8. THIS PERMIT WILL BE ISSUED WITH PROVISO; PRIOR TO
 INSTALLATION, DOOR PRODUCT APPROVALS REVIEWED BY
 DESIGNER OF RECORD ARE TO BE SUBMITTED AND ISSUED PRIOR
 TO REVIEW. ON THE PRODUCT APPROVAL, INDICATE ADA
 THRESHOLD AND PANIC BARS. IF YOU DO NOT AGREE WITH THIS
 PROVISO, CONTACT ME PRIOR TO ISSUANCE.
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-11-09 Cont ID  
Sent By jpearson Date 2018-11-09 Time 12:50 Rev Time 0.00
Received By jpearson Date 2018-11-09 Time 12:50 Sent To  
Notes
2018-11-09 12:50:36NO CHANGES TO PREVIOUSLY APPROVED PLANS.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-09-17 Cont ID  
Sent By jpearson Date 2018-09-16 Time 15:39 Rev Time 0.00
Received By jpearson Date 2018-09-16 Time 15:39 Sent To  
Notes
2018-09-17 10:17:52CHANGED VALUE TO $85,000 PER EMAIL FROM CONTRACTOR.
 CHANGED STATUS TO PASS.
  
  
  
2018-09-16 15:38:32CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
 (S)
  
 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. FBC 109.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED "OLD
 SHEETS".
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  
  
  
  

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2018-11-09 Cont ID  
Sent By jpearson Date 2018-11-09 Time 12:57 Rev Time 0.00
Received By jpearson Date 2018-11-09 Time 12:57 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2018-12-14 Cont ID  
Sent By pleduc Date 2018-12-14 Time   Rev Time 0.00
Received By pleduc Date 2018-12-14 Time 13:48 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2018-10-24 Cont ID  
Sent By pleduc Date 2018-10-24 Time   Rev Time 0.00
Received By pleduc Date 2018-10-24 Time 11:34 Sent To  
Notes
2018-10-24 11:38:48THE PREVIOUS COMMENTS FROM FIRE DO NOT APPEAR TO BE
 ADDRESSED EITHER IN CLOUD REVISIONS NOR NARRATIVE AND
 ARE RESTATED BELOW.
  
 PLEASE ADDRESS FIRE COMMENTS SPECIFICALLY:
  
 THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET A 03 - THE OCCUPANCY LOAD CALCULATIONS DO NOT
 INDICATE NUMBERS FOR THE KITCHEN OR BAR SERVICE AREA.
  
 PLEASE REVIEW AND PROVIDE DETAILS
  
  
  
  
 2) THERE ARE NO DIMENSIONS INDICATED TO VERIFY THE
 OCCUPANCY LOAD OF THE SEATING AREA. THE BATHROOMS
 SHOULD NO BE INCLUDED WITH THE SEATING AREA.
  
 ADDITIONALLY, THERE ARE NO DIMENSIONS INDCATED BETWEEN
 THE SEATS OR EACH AISLE TO ENSURE REQUIRED WIDTHS OR
 PASSAGE.
  
 PER NFPA 101, CHAPTER 12 OR 13, NEW OR EXISTING
 ASSEMBLY OCCUPANCIES
  
 12.2.5.8 AISLES SERVING SEATING AT TABLES.
  
 12.2.5.8.2* THE WIDTH OF AISLES SERVING SEATING AT
 TABLES SHALL BE
 NOT LESS THAN 44 IN. (1120 MM) WHERE SERVING AN
 OCCUPANT LOAD
 EXCEEDING 50, AND 36 IN. (915 MM) WHERE SERVING AN
 OCCUPANT
 LOAD OF 50 OR FEWER.
 12.2.5.8.3* WHERE NONFIXED SEATING IS LOCATED BETWEEN A
 TABLE AND
 AN AISLE, THE MEASUREMENT OF REQUIRED CLEAR WIDTH OF
 THE AISLE SHALL
 BE MADE TO A LINE 19 IN. (485 MM), MEASURED
 PERPENDICULARLY TO
 THE EDGE OF THE TABLE, AWAY FROM THE EDGE OF SAID
 TABLE.
 12.2.5.9 APPROVAL OF LAYOUTS.
 12.2.5.9.1 WHERE REQUIRED BY THE AUTHORITY HAVING
 JURISDICTION,
 PLANS DRAWN TO SCALE SHOWING THE ARRANGEMENT OF
 FURNISHINGS OR
 EQUIPMENT SHALL BE SUBMITTED TO THE AUTHORITY BY THE
 BUILDING
 OWNER, MANAGER, OR AUTHORIZED AGENT TO SUBSTANTIATE
 CONFORMANCE
 WITH THE PROVISIONS OF 12.2.5.
 12.2.5.9.2 THE LAYOUT PLANS SHALL CONSTITUTE THE ONLY
 ACCEPTABLE
 ARRANGEMENT, UNLESS ONE OF THE FOLLOWING CRITERIA IS
 MET:
 (1) THE PLANS ARE REVISED.
 (2) ADDITIONAL PLANS ARE SUBMITTED AND APPROVED.
 (3) TEMPORARY DEVIATIONS FROM THE SPECIFICATIONS OF THE
 APPROVED PLANS ARE USED, PROVIDED THAT THE OCCUPANT
 LOAD IS
 NOT INCREASED AND THE INTENT OF 12.2.5.9 IS MAINTAINED.
  
 PLEASE REVIEW AND PROVIDE.
  
  
  
 3) SHEET A 04 - 8 SEATS ARE INDCATED ON THE FLOOR PLAN
 BY THE LEFT SIDE DOUBLE DOORS. 4 OF THE SEAT ENCROACH
 INTO THE PATH OF EGRESS.
  
 THOSE DOORS ARE NOT REQUIRED TO MEET YOUR EGRESS
 DEMAND; HOWEVER, EITHER THOSE DOOR CAN NOT BE INDICATED
 AS AN EXIT OR THE CHAIRS AND TABLES WILL NEED TO BE
 REMOVED.
  
 PER NFPA 101, CHAPTER 7, MEANS OF EGRESS.
  
 7.1.10 MEANS OF EGRESS RELIABILITY.
 7.1.10.1* MAINTENANCE. MEANS OF EGRESS SHALL BE
 CONTINUOUSLY
 MAINTAINED FREE OF ALL OBSTRUCTIONS OR IMPEDIMENTS TO
 FULL INSTANT
 USE IN THE CASE OF FIRE OR OTHER EMERGENCY.
  
  
  
 4) SHEET A 06 - THERE IS KITCHEN COOKING AND HOOD
 EQUIPMENT INDICATED. THERE ARE NO INDICATIONS IF THE
 NOTED EQUIPMENT IS NEW OR EXISTING.
  
 PER NFPA 101, CHAPTER 12 OR 13, NEW OR EXISTING
 ASSEMBLY OCCUPANCIES
  
 12.3.2.2 COOKING EQUIPMENT. COOKING EQUIPMENT SHALL BE
 PROTECTED IN ACCORDANCE WITH 9.2.3, UNLESS THE COOKING
 EQUIPMENT
 IS ONE OF THE FOLLOWING TYPES:
 (1) OUTDOOR EQUIPMENT
 (2) PORTABLE EQUIPMENT NOT FLUE-CONNECTED
 (3) EQUIPMENT USED ONLY FOR FOOD WARMING
  
 ALL COOKING AND HOOD EQUIPMENT NEW OR EXISTING SHALL BE
 INSPECTED AND TESTED FOR COMPLIANCE WITH THE APPLICABLE
 CODE.
  
 PLEASE REVIEW AND PROVIDE DETAILS
  
  
  
  
 5) FIRE SPRINKLER DOCUMENTS ARE INDICATED WITH THE
 BACK-UP INFORMATION PACKET . THESE DOCUMENTS ARE
 ACCEPTED AS INFORMATIONAL PURPOSES ONLY.
  
 FIRE SPRINKLER SHOP DRAWINGS SHALL BE SUBMITTED
 SEPARATELY FOR APPROVAL.
  
  
  
 6) DOOR INFORMATION DOCUMENTS ARE INDICATED WITH THE
 BACK-UP INFORMATION PACKET. THOSE DOCUMENTS ARE
 INDICATED WITH HELLBENT CUSTOM GARAGE IN THE TITLE
 BLOCKS
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-09-19 Cont ID  
Sent By pleduc Date 2018-09-19 Time   Rev Time 0.00
Received By pleduc Date 2018-09-18 Time 15:10 Sent To I
Notes
2018-09-18 16:54:29THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET A 03 - THE OCCUPANCY LOAD CALCULATIONS DO NOT
 INDICATE NUMBERS FOR THE KITCHEN OR BAR SERVICE AREA.
  
 PLEASE REVIEW AND PROVIDE DETAILS
  
  
  
  
 2) THERE ARE NO DIMENSIONS INDICATED TO VERIFY THE
 OCCUPANCY LOAD OF THE SEATING AREA. THE BATHROOMS
 SHOULD NO BE INCLUDED WITH THE SEATING AREA.
  
 ADDITIONALLY, THERE ARE NO DIMENSIONS INDCATED BETWEEN
 THE SEATS OR EACH AISLE TO ENSURE REQUIRED WIDTHS OR
 PASSAGE.
  
 PER NFPA 101, CHAPTER 12 OR 13, NEW OR EXISTING
 ASSEMBLY OCCUPANCIES
  
 12.2.5.8 AISLES SERVING SEATING AT TABLES.
  
 12.2.5.8.2* THE WIDTH OF AISLES SERVING SEATING AT
 TABLES SHALL BE
 NOT LESS THAN 44 IN. (1120 MM) WHERE SERVING AN
 OCCUPANT LOAD
 EXCEEDING 50, AND 36 IN. (915 MM) WHERE SERVING AN
 OCCUPANT
 LOAD OF 50 OR FEWER.
 12.2.5.8.3* WHERE NONFIXED SEATING IS LOCATED BETWEEN A
 TABLE AND
 AN AISLE, THE MEASUREMENT OF REQUIRED CLEAR WIDTH OF
 THE AISLE SHALL
 BE MADE TO A LINE 19 IN. (485 MM), MEASURED
 PERPENDICULARLY TO
 THE EDGE OF THE TABLE, AWAY FROM THE EDGE OF SAID
 TABLE.
 12.2.5.9 APPROVAL OF LAYOUTS.
 12.2.5.9.1 WHERE REQUIRED BY THE AUTHORITY HAVING
 JURISDICTION,
 PLANS DRAWN TO SCALE SHOWING THE ARRANGEMENT OF
 FURNISHINGS OR
 EQUIPMENT SHALL BE SUBMITTED TO THE AUTHORITY BY THE
 BUILDING
 OWNER, MANAGER, OR AUTHORIZED AGENT TO SUBSTANTIATE
 CONFORMANCE
 WITH THE PROVISIONS OF 12.2.5.
 12.2.5.9.2 THE LAYOUT PLANS SHALL CONSTITUTE THE ONLY
 ACCEPTABLE
 ARRANGEMENT, UNLESS ONE OF THE FOLLOWING CRITERIA IS
 MET:
 (1) THE PLANS ARE REVISED.
 (2) ADDITIONAL PLANS ARE SUBMITTED AND APPROVED.
 (3) TEMPORARY DEVIATIONS FROM THE SPECIFICATIONS OF THE
 APPROVED PLANS ARE USED, PROVIDED THAT THE OCCUPANT
 LOAD IS
 NOT INCREASED AND THE INTENT OF 12.2.5.9 IS MAINTAINED.
  
 PLEASE REVIEW AND PROVIDE.
  
  
  
 3) SHEET A 04 - 8 SEATS ARE INDCATED ON THE FLOOR PLAN
 BY THE LEFT SIDE DOUBLE DOORS. 4 OF THE SEAT ENCROACH
 INTO THE PATH OF EGRESS.
  
 THOSE DOORS ARE NOT REQUIRED TO MEET YOUR EGRESS
 DEMAND; HOWEVER, EITHER THOSE DOOR CAN NOT BE INDICATED
 AS AN EXIT OR THE CHAIRS AND TABLES WILL NEED TO BE
 REMOVED.
  
 PER NFPA 101, CHAPTER 7, MEANS OF EGRESS.
  
 7.1.10 MEANS OF EGRESS RELIABILITY.
 7.1.10.1* MAINTENANCE. MEANS OF EGRESS SHALL BE
 CONTINUOUSLY
 MAINTAINED FREE OF ALL OBSTRUCTIONS OR IMPEDIMENTS TO
 FULL INSTANT
 USE IN THE CASE OF FIRE OR OTHER EMERGENCY.
  
  
  
 4) SHEET A 06 - THERE IS KITCHEN COOKING AND HOOD
 EQUIPMENT INDICATED. THERE ARE NO INDICATIONS IF THE
 NOTED EQUIPMENT IS NEW OR EXISTING.
  
 PER NFPA 101, CHAPTER 12 OR 13, NEW OR EXISTING
 ASSEMBLY OCCUPANCIES
  
 12.3.2.2 COOKING EQUIPMENT. COOKING EQUIPMENT SHALL BE
 PROTECTED IN ACCORDANCE WITH 9.2.3, UNLESS THE COOKING
 EQUIPMENT
 IS ONE OF THE FOLLOWING TYPES:
 (1) OUTDOOR EQUIPMENT
 (2) PORTABLE EQUIPMENT NOT FLUE-CONNECTED
 (3) EQUIPMENT USED ONLY FOR FOOD WARMING
  
 ALL COOKING AND HOOD EQUIPMENT NEW OR EXISTING SHALL BE
 INSPECTED AND TESTED FOR COMPLIANCE WITH THE APPLICABLE
 CODE.
  
 PLEASE REVIEW AND PROVIDE DETAILS
  
  
  
  
 5) FIRE SPRINKLER DOCUMENTS ARE INDICATED WITH THE
 BACK-UP INFORMATION PACKET . THESE DOCUMENTS ARE
 ACCEPTED AS INFORMATIONAL PURPOSES ONLY.
  
 FIRE SPRINKLER SHOP DRAWINGS SHALL BE SUBMITTED
 SEPARATELY FOR APPROVAL.
  
  
  
 6) DOOR INFORMATION DOCUMENTS ARE INDICATED WITH THE
 BACK-UP INFORMATION PACKET. THOSE DOCUMENTS ARE
 INDICATED WITH HELLBENT CUSTOM GARAGE IN THE TITLE
 BLOCKS
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2019-01-16 Cont ID  
Sent By tklarge Date 2019-01-16 Time 06:53 Rev Time 0.00
Received By tklarge Date 2019-01-16 Time 06:46 Sent To I
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2018-12-20 Cont ID  
Sent By tklarge Date 2018-12-20 Time 06:05 Rev Time 0.00
Received By tklarge Date 2018-12-18 Time 13:41 Sent To  
Notes
2018-12-20 05:09:441) SUBMIT MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION MANUALS FOR ALL GAS EQQUIPMENT.A NOTE ON
 SHT.P-3 FOR THE TANKLESS WATER HEATER IS INSUFFICIENT.
 EQUIPMENT SHALL BE LISTED AND LABELED PER 2017 FBC-FUEL
 GAS SEC.301.3, WPB AMEND. TO FBC SEC.. 107.2.1. 2ND
 REQUEST.
 2) SHOW THE DISTANCE FROM THE TANKLESS WATER HEATER TO
 THE REAR DOOR AND ALL OTHER OPENINGS INTO THE BUILDING.
 THE TANKLESS WATER HEATER SHALL BE LOCATED IN
 ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION MANUAL.
 2017 FBC-FUEL GAS SEC.305.1.
 3) THE COMBUSTION AIR CALCULATIONS THAT HAVE BEEN
 SUBMITTED DO NOT CORRELATE WITH THE EQUATION IN THE
 CODE ALTHOUGH THE FINAL TOTAL CFM IS CORRECT. REVISE
 THE EQUATION NUMBERS TO COMPLY WITH THE CODE. PLEASE
 REFER TO 2017 FBC-FUEL GAS SEC.304.9.
 4) EACH OF THE APPLIANCES SERVED SHALL BE INTERLOCKED
 WITH THE MECHANICAL AIR SUPPLY SYSTEM TO PREVENT MAIN
 BURNER OPERATION WHEN THE MECHANICAL AIR SUPPLY SYSTEM
 IS NOT IN OPERATION. 2017 FBC- FUEL GAS SEC. 304.9.2.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2018-11-28 Cont ID  
Sent By tklarge Date 2018-11-28 Time 09:28 Rev Time 0.00
Received By tklarge Date 2018-11-28 Time 06:16 Sent To I
Notes
2018-11-28 07:03:52CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 GAS COMMENTS: DENIED
  
 1.PLAN SHEET P-2; GAS ISOMETRIC. GAS PIPING DOES NOT GO
 THROUGH THE ANSUL SYSTEM. ACCESSIBLE EMERGENCY VALVE TO
 BE INSTALLED IN LINE TO KITCHEN COOKING LINE.
 A. EMERGENCY GAS VALVE PIPING IS SHOWN GOING TO A DEAD
 END. ACCESSIBLE EMERGENCY GAS VALVE TO BE INSTALLED IN
 LINE TO KITCHEN COOKING APPLIANCES AND CONTROLLED BY
 THE ANSUL SYSTEM TO COMPLY.
 2. SUBMIT MANUFACTURER'S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT INCLUDING THE
 TANKLESS WATER HEATER TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND FBC FG 402.2, AND 301.3
 GAS APPLIANCES SHALL BE LISTED AND LABELED. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES / EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION. FBC FG 305.1
 3. SHT. P-2 - THERE IS A NOTE AT THE GAS RISER THAT
 REFERS TO THE 2014 FUEL GAS CODE. THE GAS CODE IN
 EFFECT IS THE 2017 CODE. REVISE THE NOTE.
 4) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE GAS
 EQUIPMENT PER 2017 FBC-FUEL GAS SEC. 304.1.WHERE
 COMBUSTION AIR IS PROVIDED BY THE BUILDING'S MECHANICAL
 VENTILATION SYSTEM,THE SYSTEM SHALL PROVIDE THE
 SPECIFIED COMBUSTION AIR RATE IN ADDITION TO THE
 REQUIRED VENTILATION AIR. 2017 FBC-FUEL GAS
 SEC.304.9.3.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED "VOID".
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-10-02 Cont ID  
Sent By jesmith Date 2018-10-02 Time 16:15 Rev Time 0.00
Received By jesmith Date 2018-10-04 Time 08:28 Sent To  
Notes
2018-10-04 08:28:21CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 1ST REVIEW:
 GAS COMMENTS: DENIED
  
 1. RE: PLAN SHEET P-2; GAS ISOMETRIC. EMERGENCY HOOD
 SHUT DOWN SHUT OFF VALVE SHALL BE BELOW THE CEILING.
 THE MANUAL SHUTOFF VALVE SHALL BE UPSTREAM OF KITCHEN
 EQUIPMENT. UNION TO BE DOWN STREAM OF MANUAL VALVE.
 SECS. 10.4, 10.5 OF NFPA 96-08.
 A. EMERGENCY GAS VALVE PIPING IS SHOWN GOING TO A DEAD
 END. ACCESSIBLE EMERGENCY GAS VALVE TO BE INSTALLED IN
 LINE TO KITCHEN COOKING APPLIANCES AND CONTROLLED BY
 THE ANSUL SYSTEM TO COMPLY.
 2. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT INCLUDING
 REGULATORS TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54,
 NFPA 58, AND FBC FG 402.2, AND 301.3 GAS APPLIANCES
 SHALL BE LISTED AND LABELED. THE INSTALLATION MANUALS
 FOR ALL GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT
 THE TIME OF INSPECTION. FBC FG 305.1
 3. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE,
 TERMINATION POINT, HEIGHT ABOVE THE ROOF AND ANCHORING
 DETAILS FOR GAS REGULATOR VENTS IF APPLICABLE (SEE NOTE
 2 AND FBC FG 410.3) PER FBC-FG SECS. 502 THRU 505 WPB
 FBC 107.2.1
  
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED "VOID".
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
2018-10-02 16:14:48CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 1ST REVIEW:
 PLUMBING COMMENTS: DENIED
  
 1. RE: PLAN SHEET P-2; GAS ISOMETRIC. GAS PIPING DOES
 NOT GO THROUGH THE ANSUL SYSTEM. ACCESSIBLE EMERGENCY
 VALVE TO BE INSTALLED IN LINE TO KITCHEN COOKING LINE.
 2. PROVIDE MANUFACTURER"S SPECS FOR ALL GAS FIRED
 EQUIPMENT INCLUDING THE TANKLESS WATER HEATER. WPB FBC
 107.2.1
  
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED "VOID".
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-01-16 Cont ID  
Sent By tklarge Date 2019-01-16 Time 06:49 Rev Time 0.00
Received By tklarge Date 2019-01-11 Time 14:53 Sent To  
Notes
2019-01-14 14:53:41RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-12-20 Cont ID  
Sent By tklarge Date 2018-12-20 Time 06:27 Rev Time 0.00
Received By tklarge Date 2018-12-06 Time 14:57 Sent To  
Notes
2018-12-10 11:37:40B09
2018-12-07 14:57:09LIBRARY

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-11-16 Cont ID  
Sent By tklarge Date 2018-11-16 Time 15:05 Rev Time 0.00
Received By tklarge Date 2018-10-22 Time 15:46 Sent To  
Notes
2018-11-14 12:58:13TO CC DESK
2018-10-23 15:46:46B23

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-10-11 Cont ID  
Sent By shill Date 2018-10-11 Time 06:55 Rev Time 0.00
Received By shill Date 2018-09-13 Time 16:01 Sent To  
Notes
2018-09-14 16:01:52B06

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-11-15 Cont ID  
Sent By ccole Date 2018-11-15 Time 15:15 Rev Time 0.00
Received By ccole Date 2018-11-15 Time 07:45 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-09-25 Cont ID  
Sent By ccole Date 2018-09-25 Time 10:20 Rev Time 0.00
Received By ccole Date 2018-09-25 Time 09:18 Sent To  
Notes
2018-09-25 10:49:231ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18090558
 9/25/18
  
 CODES IN EFFECT:
  
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-1: RECIRCULATION OF AIR FROM THE KITCHEN
 INTO THE BAR AREAS VIA AHU'S 1 & 3 IS PROHIBITED PER
 TABLE 403.3.1.1 FOOTNOTE B FBC M.
  
 2) M-1: DUCT SMOKE DETECTORS ARE REQUIRED IN THE SUPPLY
 AIR SYSTEMS OF THE 5-TON AC-1 & 3 SYSTEMS PER SECTION
 606.2.1. PLEASE NOTE THAT AN EXEMPTION CAN BE APPLIED
 IF THE MANUFACTURER'S SPECIFICATIONS INDICATE THE
 SYSTEMS ARE NOT CAPABLE OF PRODUCING OVER 2000 CFMS OF
 SUPPLY AIR.
  
 3) M-1: THE LOCATION OF THE O/A INTAKE APPEARS TO BE
 WITHIN THE MINIMUM 10' REQUIRED CLEARANCE TO THE ALLEY
 AND THE PROPERTY LINE- SECTION 401.4 FBC M.
  
 4) M-1: PROVIDE WIND LOAD ENGINEERING FOR TIE DOWN OF
 THE NEW CONDENSER ON THE EXITING STAND- SECTION 301.15
 FBC M.
  
 5) P-1: PROVIDE COMBUSTION AIR CALCULATIONS FOR THE NEW
 GAS-FIRED COOKING APPLIANCES- SECTION 304 FBC FG.
  
 6) P-1: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 GAS-FIRE COOKING APPLIANCES- SECTION 623.1 FBC FG.
  
 7) ADVISORY: PLEASE REFER TO SECTION 508.1.1 FBC M.
 ALTHOUGH THE KITCHEN HOOD IS UNDER A SEPARATE, THE
 REQUIREMENT CONCERNING THE TEMPERATURE OF THE MAKEUP
 AIR MAY EFFECT THE MAIN HVAC DESIGN.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2019-01-16 Cont ID  
Sent By tklarge Date 2019-01-16 Time 06:45 Rev Time 0.00
Received By tklarge Date 2019-01-16 Time 05:44 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date   Cont ID  
Sent By   Date 2018-12-20 Time   Rev Time 0.00
Received By tklarge Date 2018-12-20 Time 06:05 Sent To I
Notes
2018-12-20 06:26:231) SHT. P-1 - THE SAMPLING PORT SHOWN FOR THE GREASE
 TRAP IS UNACCEPTABLE .THE SAMPLING PORT SHALL BE
 MINIMUM 4 INCH TWO WAY CLEANOUT PER THE CITY OF WEST
 PALM BEACH UTILITIES DEPT.YOU HAVE REVISED THE PLAN
 VIEW BUT HAVE NOT REMOVED THIS DETAIL FROM THE
 PLANS.2ND REQUEST.
 2) THE PLUMBING SANITARY RISER AND PLAN VIEW FOR THE
 BAR AREA STILL SHOWS THE ICE BINS DISCHARGING TO THE
 INTERCEPTOR. THE CLEAR WATER WASTE SHALL NOT DISCHARGE
 TO THE INTERCEPTOR. 2017 FBC-PLUMBING. SEC. 1003.2. 2ND
 REQUEST.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-11-16 Cont ID  
Sent By tklarge Date 2018-11-16 Time 15:04 Rev Time 0.00
Received By tklarge Date 2018-11-16 Time 14:38 Sent To I
Notes
2018-11-16 15:00:341) THE SAMPLING PORT SHOWN FOR THE GREASE TRAP IS
 UNACCEPTABLE. THE SAMPLING PORT SHALL BE A MINIMUM 4
 INCH TWO WAY CLEANOUT PER THE CITY OF WEST PALM BEACH
 UTILITIES DEPT.
 2) THE CLEAR WATER WASTE FROM THE ICE BIN, ICE MAKER
 AND ANY OTHER CLEAR WATER WASTE SHALL NOT DISCHARGE
 INTO THE GREASE INTERCEPTOR. 2017 FBC-PLUMBING
 SEC.1003.2.
 3) THE HOT WATER LINES SHALL BE INSULATED IN ACCORDANCE
 WITH THE 2017 FBC-ENERGY SEC.C404.4 & IN THE THICKNESS
 REQUIRED BY TABLE C403.2.10.
 4) THE LOCATION OF THE TANKLESS WATTER HEATER SHALL BE
 LOCATED A MINIMUM OF 4 FEET FROM OPERABLE DOORS AND
 WINDOWS PER THE MANUFACTURER'S INSTALLATION
 INSTRUCTIONS.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-10-02 Cont ID  
Sent By jesmith Date 2018-10-02 Time 16:01 Rev Time 0.00
Received By jesmith Date 2018-10-02 Time 16:01 Sent To  
Notes
2018-10-02 16:01:45CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 1ST REVIEW:
 PLUMBING COMMENTS: DENIED
  
 1. RE: PLAN SHEET P-2; WATER ISOMETRIC. PROVIDE
 INFORMATION FOR TYPICAL BACKFLOW PREVENTOR(S) SHOWN ON
 WATER SUPPLY(S). INCLUDE TYPE, MODEL NUMBER AND ASSE
 STANDARD FOR COMPLIANCE. IF THERE IS A RELIEF OPENING
 ON THE DEVICE THEN PROVIDE DETAILS FOR DISCHARGE
 PIPING. WPB FBC 107.2.1
 2. RE: PLAN SHEET P-3; TANKLESS WATER HEATER. PROVIDE
 MANUFACTURER, MODEL # AND SPECS FOR THE WATER HEATER.
 WPB FBC 107.2.1
  
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED "VOID".
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715