Plan Review Details - Permit 18090535
Plan Review Stops For Permit 18090535
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-11-05 Cont ID  
Sent By shill Date 2018-11-05 Time 06:23 Rev Time 0.00
Received By shill Date 2018-11-05 Time 06:23 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-10-24 Cont ID  
Sent By fgiaquin Date 2018-10-24 Time 11:40 Rev Time 0.00
Received By fgiaquin Date 2018-10-24 Time 08:59 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-09-24 Cont ID  
Sent By pleduc Date 2018-09-24 Time   Rev Time 0.00
Received By pleduc Date 2018-09-24 Time 14:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-12-14 Cont ID  
Sent By lmarchan Date 2018-12-14 Time 13:01 Rev Time 0.00
Received By lmarchan Date 2018-11-15 Time 08:42 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-11-07 Cont ID  
Sent By shill Date 2018-11-07 Time 12:56 Rev Time 0.00
Received By shill Date 2018-09-21 Time 14:57 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-12-13 Cont ID  
Sent By ccole Date 2018-12-13 Time 17:22 Rev Time 0.00
Received By ccole Date 2018-12-13 Time 16:34 Sent To  
Notes
2018-12-13 17:23:44MECHANICAL PROVISOS ARE LISTED ON THE APPROVED PLAN
 SHEET M-1.01.
 CCOLE

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-11-06 Cont ID  
Sent By ccole Date 2018-11-06 Time 14:48 Rev Time 0.00
Received By ccole Date 2018-11-06 Time 14:19 Sent To  
Notes
2018-11-06 15:19:381ST REVIEW FBC-2010 MECHANICAL
 PERMIT #18090535
 11/6/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE 2010
 FBC M- FLORIDA MECHANICAL CODE 2010
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 2010
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2010
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2010
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE AC COOLING AND HEATING CALCULATIONS IN
 ACCORDANCE WITH SECTION 503.2.1 FBC EC.
  
 2) SUBMIT AN ENERGY COMPLIANCE REPORT- SEE SECTION
 101.4.9 FBC EC.
  
 3) PROVIDE MINIMUM VENTILATION CALCULATIONS AND SHOW
 THE LOCATION OF THE O/A OUTLET INTO THE SPACE- TABLE
 403.3 FBC M.
  
 4) SHEET M101: PROVIDE DUCT SMOKE DETECTORS IN BOTH THE
 SUPPLY AND RETURN SYSTEMS OF THE HP'S- SECTION 606.2.2
 FBC M
  
 5) M101: INDICATE THE SIZE OF THE RETURN OPENINGS AT
 THE HP CLOSETS- SECTION 601.4 FBC M.
  
 6) M101: THE PLAN APPEARS TO SHOW THE DRYER EXHAUST
 DUCT RUNNING THROUGH THE PLENUM WHICH IS PROHIBITED PER
 SECTION 504.4 FBC M.
  
 7) M101: SHOW THE LOCATIONS OF THE THERMOSTATS FOR THE
 HP'S- SECTION 503.2.4.1 FBC EC.
  
 8) SUBMIT MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS FOR THE DRYER, COOKING
 APPLIANCES, AND THE KITCHEN EXHAUST HOOD AND DUCT-
 SECTION 304.1 FBC M.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-11-29 Cont ID  
Sent By gjohnson Date 2018-11-29 Time 14:41 Rev Time 0.00
Received By gjohnson Date 2018-11-29 Time 14:41 Sent To  
Notes
2018-11-29 14:42:10PROVISO COMPLIED/ GPJ

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-11-05 Cont ID  
Sent By gjohnson Date 2018-11-05 Time 07:16 Rev Time 0.00
Received By gjohnson Date 2018-11-05 Time 07:16 Sent To  
Notes
2018-11-05 07:17:35PROVISO:
 1. INDICATE ON THE PLAN WHICH BATHROOM COMPLIES WITH
 THE FHA REQUIREMENTS AND WHICH DESIGN SPECIFICATION A
 OR B. PER FAIR HOUSING DESIGN MANUAL
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2018-12-13 Cont ID  
Sent By ccole Date 2018-12-13 Time 17:31 Rev Time 0.00
Received By ccole Date 2018-12-13 Time 17:30 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2018-11-07 Cont ID  
Sent By shill Date 2018-11-07 Time 12:57 Rev Time 0.00
Received By shill Date 2018-11-05 Time 06:25 Sent To  
Notes
2018-11-06 15:21:56MECH SHEETS OK
 CCOLE/11/6/18