Plan Review Details - Permit 18090469
Plan Review Stops For Permit 18090469
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-03-23 Cont ID  
Sent By dbattles Date 2019-03-23 Time 10:29 Rev Time 0.00
Received By dbattles Date 2019-03-23 Time 10:02 Sent To  
Notes
2019-03-23 10:30:05PROVISOS:
  
 A. SEPARATE ROOF PERMIT IS REQUIRED. PRIOR TO
 INSTALLATION, SUBMIT ROOF PERMIT APPLICATION WITH
 PRODUCT APPROVALS REVIEWED BY DESIGNER OF RECORD AND
 ENGINEERING (IF APPLICABLE).
  
 B. COMPONENT & CLADDING PRODUCT APPROVALS REVIEWED BY
 DESIGNER OF RECORD ARE TO BE SUBMITTED TO THE BUILDING
 DIVISION, REVIEWED AND ISSUED PRIOR TO INSTALLATION.
  
 C. DEFERRED SUBMITTALS REQUESTED BY ARCHITECT, SEE LIST
 SHEET G10.04 ; DOCUMENTS SHOWING COMPLIANCE ARE TO BE
 REVIEWED BY DESIGNER OF RECORD PRIOR TO SUBMITTAL
 (ARCHITECT OR ENGINEER FOR PRODUCT APPROVALS AND OTHER
 SPECIFICATION DOCUMENTS, STRUCTURAL ENGINEER OF RECORD
 APPROVAL AND REVIEW IS REQUIRED FOR DELEGATED
 ENGINEERING). SUBMITTAL, REVIEW AND APPROVAL ARE
 REQUIRED PRIOR TO INSTALLATION.
  
 D. COMPONENT & CLADDING PRODUCT APPROVALS (COMPLY WITH
 PRESSURES SHOWN ON SHEET S0.05 AND S0.05A)
  
 E. SEPARATE PERMITS (APPLICATIONS, PLANS, AND FEES) ARE
 REQUIRED FOR:
 LIGHT POLES/SITE LIGHTING
 FIRE ALARM
 FIRE SPRINKLER
 LOW VOLTAGE
 ACCESS
 LANDSCAPING
 IRRIGATION
 PARKING LOT
 ALL OTHER ITEMS OTHER THAN BMEP
  
 F. PROVIDE THE RECORDED PLAT WHEN FINALIZED; EITHER A
 PDF VIA EMAIL OR ADVISE BOOK AND PAGE NUMBER VIA EMAIL.
  
 G. AIPP COMPLIANCE REQUIRED (VERIFY WITHIN 90 DAYS OF
 PERMIT ISSUANCE); VERIFICATION REQUIRED PRIOR TO C.O.
  
 F. SHORING/RESHORE ENGINEERING IS REQUIRED TO BE
 SUBMITTED TO THE BUILDING DIVISION FOR REVIEW. THE
 ENGINEERING IS TO BE SUBMITTED, REVIEWED AND ISSUED
 PRIOR TO CONCRETE POUR.
  
 H. A CONSTRUCTION GUARD RAIL ENGINEERED DETAIL IS
 REQUIRED TO BE PROVIDED PRIOR TO INSTALLATION.
  
 I. CONSTRUCTION HOURS - 7AM TO 7PM MON-FRI, 8AM TO 8PM
 SAT-SUN
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2019-02-27 Cont ID  
Sent By dbattles Date 2019-02-27 Time 13:55 Rev Time 0.00
Received By dbattles Date 2019-02-20 Time 14:07 Sent To  
Notes
2019-02-27 13:56:13****CORRECTIONS****
 W.P.B. PERMIT: 18090469
 2 ND REVIEW: FEBRUARY 21, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[B] = FBC BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
  
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18090469
 ADD: 360 ROSEMARY AVE. / PCN: 74-43-43-21-01-022-0040
 CONT: MOSS & ASSOCIATES LLC
 TEL: 954-524-5678
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 1ST REVIEW
 DATE: MONDAY DEC.10TH/ 2018. COMPLETED REVIEW.
 ACTION: DENIED
  
 1) OK.
 2A-B) OK.
 3A-B) OK.
 3C-D) OK.
 4) OK.
 5) OK.
 6) OK.
 7) OK.
  
 8) IN-PROGRESS
 8A-F) IN-PROGRESS
  
 8G) SHORING AND RESHORING WILL NEED TO BE SUPPLIED AS
 SUBMITTAL.
  
 8H-I) OK.
 9) OK.
 10) OK.
 10A-N) OK.
  
 10O) 008-LS1.01. OK.
 NEW COMMENT 2 ND REVIEW:
 10O) 1006.2.1 FBC[B] EGRESS BASED ON OCCUPANT LOAD AND
 COMMON PATH OF EGRESS TRAVEL DISTANCE. TWO EXITS OR
 EXIT ACCESS DOORWAYS FROM ANY SPACE SHALL BE PROVIDED
 WHERE THE DESIGN OCCUPANT LOAD OR THE COMMON PATH OF
 EGRESS TRAVEL DISTANCE EXCEEDS THE VALUES LISTED IN
 TABLE 1006.2.1.
 LOADING DOCK SUPPLIES 1 MARKED EXIT, BUT EXCEEDS TABLE
 1006.2.1 FOR REQUIREMENTS OF SPACE WITH ONE EXIT.
 PLEASE REVIEW LOADING DOCK EGRESS REQUIREMENTS.
  
 NO EXIT SIGNS ARE PROVIDED ON LIFE SAFETY, SO COMMENTS
 ARE USING E SHEETS FOR CROSS REFERENCE. CAN EXIT SIGNS
 BE ADDED TO LIFE SAFETY FOR CLARITY?
  
 10O) 1013.2 FBC[B] EXIT SIGN PLACEMENT SHALL BE SUCH
 THAT NO POINT IN AN EXIT ACCESS CORRIDOR OR EXIT
 PASSAGEWAY IS MORE THAN 100 FEET OR THE LISTED VIEWING
 DISTANCE FOR THE SIGN, WHICHEVER IS LESS, FROM THE
 NEAREST VISIBLE EXIT SIGN.
 VERIFY EXIT SIGN PLACEMENT WITH LS SHEETS.
  
 10P) OK.
 10Q) OK.
  
 10Q)(2) SUBMITTAL NEEDED FOR 6" CMU
  
 10R) OK.
 10R)(1) OK.
 10R)(2) OK.
  
 10S) NEITHER THE LIFE SAFETY FOR LEVEL 1, NOR THE
 ENLARGED LEVEL 1 AREA A NOR SHEET AE4.20 ENLARGED CORE
 PLAN LEVEL 1 SHOW COMPLIANCE FOR:
  
 10S)(1) 2017 FBC-B 403.6.1 FIRE SERVICE ACCESS
 ELEVATOR. NO FEWER THAN TWO FIRE SERVICE ACCESS
 ELEVATORS SHALL BE PROVIDED IN ACCORDANCE WITH SECTION
 3007 IN BUILDINGS WITH AN OCCUPIED FLOOR MORE THAN 120
 FEET MEASURED FROM THE ELEVATION OF THE STREET LEVEL
 ACCESS.
 COMMENT NOT ADDRESSED. SHEET LS1.01 IS SHOWING ONE
 SERVICE ELEVATOR PLEASE SHOW HOW TWO FIRE SERVICE
 ELEVATORS ARE PROVIDED.
  
 10S)(2) 2017 FBC-B 2017 FBC-B 403.6.1 FIRE SERVICE
 ACCESS ELEVATOR. PLEASE SHOW COMPLIANCE WITH EACH FIRE
 SERVICE ACCESS ELEVATOR SHALL HAVE A CAPACITY OF NOT
 LESS THAN 3,500 POUNDS.
  
 10S-T) OK.
  
 THE COMMENT RESONSE SHEETS SKIPS COMMENTS 10T(8)
 THROUGH 11H
 PLEASE PROVIDE MISSING COMMENT RESPONSE SHEETS.
  
 10T)(8) PLEASE NOTE THE STAIRWAY #2 AN INTERIOR EXIT
 STAIRWAY THAT IS CONTINUOUS TO THE EXTERIOR DOES NOT
 SHOW STAIRWELL PRESSURIZATION, SMOKEPROOF ENCLOSURES,
 IN ANY OF THE MECHANICAL PLANS, SEE 2017 FBC-B 1023.11
 SMOKEPROOF ENCLOSURES. WHERE REQUIRED BY SECTION
 403.5.4 OR 405.7.2, INTERIOR EXIT STAIRWAYS AND RAMPS
 SHALL BE SMOKEPROOF ENCLOSURES IN ACCORDANCE WITH
 SECTION 909.20.
 11) LEVEL 2: 09LS1.02, 135-AE1.02, & 190/191 AE4.02 A &
 B:
  
 11A)(1) THE LIFE SAFETY SHEET ANALYSIS, NOR LS1, NOR
 LS2 SHOW AN ANALYSIS OF THE PARKING STRUCTURE, HOW MANY
 TOTAL PARKING SPACES THERE IS OR HOW MANY ACCESSIBLE
 PARKING SPACES THERE IS OR COMPLIANCE WITH THE 2017
 FBC-ACCESSIBLE PARKING SPACES. SHOW ACCESSIBLE MATRIX.
  
 11A)(2) SHEET 135-AE1.02 THE OVERALL FLOOR PLAN FOR
 LEVEL 2 SHOWS 4 ACCESSIBLE PARKING SPACES, 3 ACCESSIBLE
 SPACES. SHOW THE ACCESSIBLE ROUTE FOR A WHEEL CHAIR TO
 BE ABLE TO GET TO AN ELEVATOR WITHOUT HAVING TO GO OUT
 INTO THE VEHICULAR TRAVEL LANE. ACCESSIBILITY CODE
 SECTION 206.2. WHERE REQUIRED. AN
 ACCESSIBLE ROUTE SHALL BE PROVIDED WHERE REQUIRED BY
 206.2.
 206.2.2 WITHIN A SITE. AT LEAST ONE ACCESSIBLE ROUTE
 SHALL CONNECT ACCESSIBLE BUILDINGS, ACCESSIBLE
 FACILITIES, ACCESSIBLE ELEMENTS, AND ACCESSIBLE SPACES
 THAT ARE ON THE SAME SITE.
  
 11B) COMMENT FOR ALL PARKING FLOORS. PLEASE ALSO SHOW
 COMPLIANCE WITH SECTION 208.2.4. VAN PARKING SPACES.
 WHERE VAN PARKING IS PROVIDED PURSUANT TO SECTION
 502.2, FOR EVERY SIX OR FRACTION OF SIX PARKING SPACES
 REQUIRED BY 208.2 TO COMPLY WITH 502, AT LEAST ONE
 SHALL BE A VAN PARKING SPACE COMPLYING WITH 502.
  
 11C) COMMENT FOR ALL PARKING FLOORS. SHEET 182-AE3.18
 BUILDING SECTION. THE PLAN SHOWS ELEVATIONS OF THE
 VARIOUS FLOOR LEVELS AND BY MEASURING BETWEEN FLOOR
 SLABS IT WOULD APPEAR THERE MAYBE ONLY 7 FEET 8 INCHES
 FROM THE BOTTOM OF THE FLOOR PRECAST AND FINISH FLOOR
 BELOW. PLEASE PROVIDE THE CLEAR HEIGHT BETWEEN FLOOR
 SLABS AND THE PRECAST FLOOR JOIST ABOVE, AND ALSO
 PROVIDE FOR THE FIRE SPRINKLERS TO HAVE A TRUE HEIGHT
 FOR THE RAMPS AND FOR THE PARKING AREAS. PLEASE SHOW
 HOW COMPLIANCE WITH 2017 FBC-ACCESSIBILITY CODE SECTION
 502.5 VERTICAL CLEARANCE. PARKING SPACES FOR VANS AND
 ACCESS AISLES AND VEHICULAR ROUTES SERVING THEM SHALL
 PROVIDE A VERTICAL CLEARANCE OF 98 INCHES MINIMUM.
  
 11D) PLEASE REVIEW SHEET 270-AE5.39 PARKING DETAILS.
 PLEASE REFER TO THE 2017 FBC-ACCESSIBILITY CODE SEE THE
 ADVISORY 502.3.3 MARKING.
 2017 ACCESSIBILITY CODE. ADVISORY 502.3.3 MARKING. THE
 METHOD AND COLOR OF MARKING ARE NOT SPECIFIED BY THESE
 REQUIREMENTS BUT MAY BE ADDRESSED BY STATE OR LOCAL
 LAWS OR REGULATIONS. BECAUSE THESE REQUIREMENTS PERMIT
 THE VAN ACCESS AISLE TO BE AS WIDE AS A PARKING SPACE,
 IT IS IMPORTANT THAT THE AISLE BE CLEARLY MARKED.
 FLORIDA LAW, S.553.5041(5)(C)1., REQUIRES DIAGONAL
 STRIPING OF ACCESS AISLES.
 PLEASE REFER TO THE WEST PALM BEACH MUNI CODE 94-485
 FOR STALL PAINTING DETAILS AND REQUIRED DOUBLE LINE
 DIMENSIONS.
  
 11E) THE 2ND LEVEL FLOOR PLAN, : 09LS1.02, 135-AE1.02,
 & 190/191 AE4.02 A & B: WILL NEED TO PROVIDE WHAT THE
 DESIGN FOR THE PARKING FLOORS, IF THESE FLOOR LEVELS
 ARE TO BE CONSIDERED AN OPEN OR ENCLOSED PARKING
 GARAGE? SHOW COMPLIANCE WITH FBC-B 406.5 OPEN PARKING
 GARAGES OR 406.6ENCLOSED PARKING GARAGES.
 IF CONSIDERED OPEN SHOW COMPLIANCE ON THE ELEVATION
 SHEETS AE2.10 THROUGH AE2.22. PLEASE SHOW THE WALL AREA
 IN SQ. FEET. THE OPENING IN SQUARE FEET, PERCENTAGE OF
 OPENING, DEDUCT FOR THE ALUMINUM ARCHITECTURAL SCREEN
 AND TAKE A SECOND DEDUCTION FOR THE BIRD SCREEN AS
 WELL. SHOW COMPLIANCE WITH 406.5.2 OPENINGS OF THE 2017
 FBC-B AND 406.5.6 FIRE SEPARATION DISTANCE CONCERNS
 WITH SOUTH WALL ON GRID LINES F-H SHEET 182AE3.18 SHOWS
 THIS AREA OF THE PARKING GARAGE EXTENDED OVER THE 1ST
 FLOOR LEVEL.
  
 11F) BOTH SHEETS 135-AE1.02 LEVEL 2 AND 190AE4.02 BOTH
 SHOW ATTENDANT BOOTHS AND A GATED ENTRANCE TO THE
 PARKING LEVELS.
  
 11F)(1) PLEASE SHOW CUT SECTIONS FOR THE ATTENDANT
 BOOTHS OF HOW THEY ARE GOING TO BE ANCHORED FOR THE
 WIND, DOES THE WIND TUNNEL TEST HAVE A PRESSURE POINT
 FOR THE BOOTHS, IF NOT HOW ARE PRESSURES TO BE DERIVED?
 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED. FBC-B
 1609.1.1 DETERMINATION OF WIND LOADS.
  
 11F)(2) ADDITIONAL INFORMATION IS REQUIRED FOR THE
 ATTENDANT BOOTHS, ARE THESE BOOTHS PRE-MANUFACTURERED
 (MODULAR) BUILDINGS UNDER FLORIDA S. 553 PART I
 MANUFACTURED BUILDINGS?
  
 11G) THE PLANS ALSO SHOW USE OF VEHICULAR GATES. IF
 THEY USE KEY CARDS THE THEY WOULD ALSO BE CONSIDERED
 AUTOMATIC VEHICULAR GATES HAVING TO COMPLY WITH: FBC-B
 3110.1 AUTOMATIC VEHICULAR GATES SHALL COMPLY WITH THE
 REQUIREMENTS OF SECTIONS 3110.2 THROUGH 3110.4 AND
 OTHER APPLICABLE SECTIONS OF THIS CODE.
  
 11H) OFFICE 202, AREA OF 5,812 SQ. FT. AND FUTURE
 RESTROOMS MAY BE AT THE OWNERS OWN RISK!!!! DEPENDING
 ON IF THE OFFICE AREA IS SUB-DIVIDED IN TO 2 TENANTS
 AND THE LARGER OF THE 2 TENANTS HAS OVER 49 OCCUPANTS
 THEN 2 EXITS WOULD BE REQUIRED. 2017 FBC-B TABLE
 1006.2.1 .SPACES WITH ONE EXIT OR EXIT ACCESS DOORWAY.
  
 THE COMMENT RESONSE SHEETS SKIPS COMMENTS 10T(8)
 THROUGH 11H
 PLEASE PROVIDE MISSING COMMENT RESPONSE SHEETS.
  
 11I) OK.
 11J) OK.
 12) OK.
 12A) OK.
  
 12B) OK. SUBMITTAL FOR SIGNAGE TO BE DEFERRED.
  
 12C) OK.
  
 12D) CONCRETE PEDESTAL PAVER SYSTEMS SPECIALTY
 ENGINEERED SUBMITTAL TO BE DEFERRED.
  
 13) OK.
  
 13A) WASHING EQUIPMENT TIE DOWNS TO BE DEFERRED
 SUBMITTAL.
  
 13B) METAL STAIRS, METAL
 PLATFORM AND GUARDRAIL SYSTEM AT ROOF TO BE A DEFERRED
 SUBMITTAL.
  
 14) OK.
 PLEASE PROVIDE FULL LIST OF DEFERRED SUBMITTALS ON
 CONSTRUCTION DOCUMENTS, OR INDICATE WHICH PAGE THE LIST
 IS CURRENTLY ON.
  
 15A-B) OK.
 15B) OK
  
 16) OK.
  
 17) OK.
 18) OK
 19) OK
  
 20) OK.
 21) OK.
 22) OK.
  
 23) FOR ELECTRONIC REVIEWS. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
 THE COMMENT RESONSE SHEETS SKIPS COMMENTS 10T(8)
 THROUGH 11H
 PLEASE PROVIDE MISSING COMMENT RESPONSE SHEETS
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-12-10 Cont ID  
Sent By jwitmer Date 2018-12-10 Time 13:37 Rev Time 0.00
Received By jwitmer Date 2018-11-26 Time 10:54 Sent To  
Notes
2018-12-05 11:51:512017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18090469
 ADD: 360 ROSEMARY AVE. / PCN: 74-43-43-21-01-022-0040
 CONT: MOSS & ASSOCIATES LLC
 TEL: 954-524-5678
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 1ST REVIEW
 DATE: MONDAY DEC.10TH/ 2018. COMPLETED REVIEW.
 ACTION: DENIED
  
 1) ART IN PUBLIC PLACES. THE CITY OF WEST PALM BEACH
 ART IN PUBLIC PLACES ORDINANCE REQUIREMENT THAT APPLIES
 TO ANY REMODEL OR NEW CONSTRUCTION PROJECT FOR WHICH
 THE PERMIT APPLICATION WAS SUBMITTED AFTER 6/29/14, AND
 THE TOTAL PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR
 GREATER THAN $750,000 WILL NEED TO COMPLY WITH THIS
 ORDINANCE.
 PER CITY OF WEST PALM BEACH ORDINANCE NO. 4504-14, AND
 CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V,
 ART IN PUBLIC PLACES, SECTION 78-123(A) AND SECTION
 78-126(A), THE ART ASSESSMENT IS 1% OF THE TOTAL
 PROJECT CONSTRUCTION COST.
 PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE
 V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND
 NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO
 THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE
 PROJECTS.
 SEC. 78-129. - PUBLIC ART ASSESSMENT FOR PRIVATE
 DEVELOPMENT.
 (A) APPLICABILITY. THE PROVISIONS OF THIS ARTICLE AND
 THE PUBLIC ART ASSESSMENT SECTION SHALL APPLY TO ALL
 PRIVATE DEVELOPMENT PROJECTS, INCLUDING NEW
 CONSTRUCTION, OR THE RENOVATION OR IMPROVEMENT OF AN
 EXISTING BUILDING, WHERE TOTAL CONSTRUCTION COSTS ARE
 EQUAL TO OR GREATER THAN $750,000.00. ALL BUILDINGS
 WITHIN NEW PLANNED DEVELOPMENTS SHALL BE ASSESSED
 CUMULATIVELY TOWARDS THIS ART IN PUBLIC PLACES
 REQUIREMENT, EVEN IF THE BUILDINGS ARE PERMITTED
 SEPARATELY OR DEVELOPED IN PHASES. THE PROVISIONS OF
 THIS SECTION APPLY TO NEW DEVELOPMENT OR NEW
 CONSTRUCTION WITHIN EXISTING PLANNED DEVELOPMENTS.
 FOR CONTACT INFORMATION PLEASE CONTACT:
 MS. SYBILLE WELTER ART IN PUBLIC PLACES COORDINATOR
 822-1515 E-MAIL: [email protected].
  
 2A) PLEASE NOTE SHEET 002-G10.02 SHEET INDEX-VOLUME 1
 IS MISSING THE STRUCTURAL SHEETS S0.01 THROUGH S4.05,
 THERE ARE 57 STRUCTURAL SHEETS MISSING FROM THE INDEX
 OF DRAWINGS. 107.2.1.2. ADDITIONAL INFORMATION IS
 REQUIRED.
  
 2B) PLEASE NOTE SHEET 002-G10.02 SHEET INDEX-VOLUME 1
 IS MISSING THE SHEET 274-AE6.00. 107.2.1.2. ADDITIONAL
 INFORMATION IS REQUIRED.
  
 3A) SHEET 007-LS0.01 THE LIFE SAFETY ANALYSIS SHEET NOR
 ANY OF THE LIFE SAFETY SHEETS FOR EACH FLOOR SHOW A
 CHART PER FLOOR FOR THE SQUARE FOOTAGE PER FLOOR PER
 OCCUPANCY, NOR THE OCCUPANCY LOADS PER FLOOR, NOR THE A
 MENTIONED ABOVE FOR THE WHOLE BUILDING. THE CLOSEST IS
 A PLUMBING FIXTURE CALCULATION THAT SHOW A ZERO
 OCCUPANT LOAD FOR LEVELS 2 THROUGH 8? PLEASE REVIEW THE
 2017 FBC-B TABLE 1004.1.2 PARKING GARAGES 200 GROSS
 OCCUPANT LOAD FACTOR. 107.2.1.2 ADDITIONAL INFORMATION
 IS REQUIRED.
  
 3B) PLEASE NOTE THE DOLLAR AMOUNT STATED IN THE PERMIT
 APPLICATION CANNOT BE CALCULATED AS TO THE VALUE OF THE
 BUILDING SINCE AS STATED ABOVE THERE IS NO CHART PER
 FLOOR FOR THE SQUARE FOOTAGE PER FLOOR PER OCCUPANCY,
 NOR THE OCCUPANCY LOADS PER FLOOR, NOR THE A MENTIONED
 ABOVE FOR THE WHOLE BUILDING.
  
 3C) SHEET 007-LS0.01 THE LIFE SAFETY PLAN ANALYSIS.
 THIS SHEET LIST CODE REFERENCES TO CHAPTER 4,9, 10 WITH
 VARIOUS CODE SECTIONS. EXAMPLES:
 403.4.7 SMOKE REMOVAL 909.16 FIRE FIGHTERS SMOKE
 CONTROL PANEL, 909.16.1 SMOKE CONTROL SYSTEMS, 909.16.2
 SMOKE CONTROL PANEL AND 909.16.3 CONTROL PANEL AND
 PROPERTIES. PLEASE NOTE LISTING THESE CODE SECTIONS
 DOES NOT MEAN CODE COMPLIANCE.
  
 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.2.1.
 W.P.B. ADMINISTRATIVE CODE/2017. DRAWINGS &
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC TO
 THE TECHNICAL CODES "SHALL NOT BE CITED AS A WHOLE OR
 IN PART? PLEASE PROVIDE THE SMOKE CONTROL RATIONAL
 ANALYSIS.
  
 3D) SHEET 007-LS0.01 THE LIFE SAFETY PLAN ANALYSIS.
 THIS SHEET LIST CODE REFERENCES TO CHAPTER 9 OF THE
 FBC-B THE SECTION DEALING WITH THE FIRE COMMAND CENTER
 911.1 THROUGH 911.1.5.
  
 W.P.B. ADMINISTRATIVE CODE/2017. DRAWINGS &
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC TO
 THE TECHNICAL CODES "SHALL NOT BE CITED AS A WHOLE OR
 IN PART? PLEASE SHOW HOW COMPLIANCE WILL BE ACHIEVED.
  
  
 4) 2017 W. P. B. AMENDMENTS TO CHAPTER 1
 ADMINISTRATION. 109.3* BUILDING PERMIT VALUATION. IF,
 IN THE OPINION OF THE BUILDING OFFICIAL, THE CLAIMED
 VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS. 2017 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 107.2.1.
 THIS MAIN BUILDING PERMIT WILL INCLUDE THE FEES FOR THE
 MECHANICAL, ELECTRICAL, PLUMBING & ROOFING PERMITS.
 WHEN THE GENERAL CONTRACTOR COMES IN FOR A BUILDING
 PERMIT WITH THE SIGNED PERMIT APPLICATION FORM BY THE
 QUALIFIER AND OWNER AND BRINGS IN THE LISTED
 SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY THE
 QUALIFIER OF EACH COMPANY, THEIR INSURANCES AND
 LICENSURE UP TO DATE, THE M-E-P AND ROOFING PERMITS ARE
 FREE OF CHARGE. IF THE M-E-P & ROOFING PERMITS COME IN
 LATER THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR
 EACH PERMIT.
 ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, RACK
 STORAGE, EXHAUST HOODS, ANSUL SYSTEMS OR ALTERNATIVE
 AUTOMATIC FIRE-EXTINGUISHING SYSTEMS, WALK IN COOLERS &
 FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL
 TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED
 SUB-PERMITS, AWNING, SCREEN ENCLOSURES, CANOPY, FENCE,
 LANDSCAPE, IRRIGATION, AUGER CAST PILE AND OR
 FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE SEPARATE
 REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT.
 PLEASE PROVIDE AN ITEMIZED LIST AND SUBTRACT THESE LINE
 ITEMS AND THEIR VALUE FROM THE OVERALL BUILDING VALUE
 STATED ON THE PERMIT APPLICATION FOR THIS PROJECT. THE
 REMAINING BALANCE WILL BE AFFECTIVELY THE VALUE OF THE
 BUILDING YOU WILL BE PAYING FOR THIS PERMIT. THE
 BUILDING DEPARTMENT DOES NOT WANT TO COLLECT TWICE FOR
 THE VALUE OF THESE SUB-PERMITS NOT COVERED UNDER THE
 PRIME OR MASTER PERMIT.
 5) SUPPORTING DOCUMENT FOLDER. WITHIN THE SUPPORTING
 DOCUMENT FOLDER THERE IS LISTED SPECIFICATION MANUAL.
 PLEASE NOTE THIS DOCUMENT IS NOT TO BE REVIEWED AND NOT
 PART OF THE PLAN REVIEW DOCUMENTS, IT SHOULD BE REMOVED
 OR MARKED VOID/ NOT REVIEWED. THIS DOCUMENT IS FROM THE
 DESIGNERS OF RECORD AND DIRECTED TO THE CONTRACTORS OF
 RECORD FOR SPECIFICATIONS. 107.2.1.3 QUALITY OF PLANS.
 THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE,
 SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO
 RECORDS MANAGEMENT. ELECTRONIC MEDIA MUST BE COMPATIBLE
 WITH THE ARCHIVE REQUIREMENTS OF FLORIDA STATUTES.
 6) SHEET 059-S0.05 INDICATES WIND TUNNEL AND CLADDING
 PRESSURES. THIS REVIEW CYCLE NO WIND TUNNEL TEST REPORT
 WAS SUBMITTED. PLEASE SUBMIT THE WIND TUNNEL TEST IN
 ELECTRONIC VERSION WITH AN ELECTRONIC SIGNATURE OR
 PAPER WITH ORIGINAL SIGNATURE AND SEAL. WIND TUNNEL
 TESTING IS TO COMPLY WITH: 2017 FBC-B 1609.1.1
 EXCEPTION 6.WIND TUNNEL TESTS IN ACCORDANCE WITH ASCE
 49 AND SECTIONS 31.4 AND 31.5 OF ASCE 7.
 SHEET 059-S0.05 WIND TUNNEL COMPONENTS AND CLADDING
 PRESSURES CANNOT BE VERIFIED, NO PRESSURES ARE GIVEN ON
 THE ELEVATIONS. PLEASE ALSO SPECIFY IF THE PRESSURES
 WHEN ADDED ARE IN VULT OR VASD. THE PRESSURES FOR
 PRODUCT APPROVALS ARE IN VASD.
 7) MISSING ENERGY REPORT 2017 FBC-ENERGY C101.5
 COMPLIANCE. COMMERCIAL BUILDINGS SHALL MEET THE
 PROVISIONS OF FLORIDA BUILDING CODE, ENERGY
 CONSERVATION?COMMERCIAL PROVISIONS.
 C401.2 APPLICATION. COMMERCIAL BUILDINGS SHALL COMPLY
 WITH ONE OF THE FOLLOWING:
  
 7.1.THE REQUIREMENTS OF ANSI/ASHRAE/IESNA 90.1,
 EXCLUDING SECTION 9.4.1.1(G) OF THE STANDARD.
  
 7.2.THE REQUIREMENTS OF SECTIONS C402 THROUGH C405. IN
 ADDITION, COMMERCIAL BUILDINGS SHALL COMPLY WITH
 SECTION C406 AND TENANT SPACES SHALL COMPLY WITH
 SECTION C406.1.1.
  
 7.3.THE REQUIREMENTS OF SECTIONS C402.5, C403.2, C404,
 C405.2, C405.3, C405.5, C405.6 AND C407. THE BUILDING
 ENERGY COST SHALL BE EQUAL TO OR LESS THAN 85 PERCENT
 OF THE STANDARD REFERENCE DESIGN BUILDING.
  
 8) THIS HIGH-RISE PROJECT QUALIFIES AS A THRESHOLD
 BUILDING / FL S. S. 553.71(7) ?THRESHOLD BUILDING"
 MEANING ANY BUILDING WHICH IS GREATER THAN (3) STORIES
 OR 50 FT. IN HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPANCY
 CLASSIFICATION AS DENIED IN THE FLORIDA BUILDING CODE
 WHICH EXCEEDS 5,000 SQ. FT. IN AREA AND AN OCCUPANT
 CONTENT OF GREATER THAN 500 PERSONS.
  
 8A) 109.3.6.1 THRESHOLD INSPECTION PLAN. COMPLETED,
 SHEET 060-S0.06. THE ENFORCING AGENCY SHALL REQUIRE A
 (WRITTEN/ TYPED) SPECIAL INSPECTOR TO PERFORM
 STRUCTURAL INSPECTIONS ON A THRESHOLD BUILDING PURSUANT
 TO A STRUCTURAL INSPECTION PLAN PREPARED BY THE
 ENGINEER OF RECORD. THE STRUCTURAL INSPECTION PLAN MUST
 BE SUBMITTED TO THE ENFORCING AGENCY PRIOR TO THE
 ISSUANCE OF A BUILDING PERMIT FOR THE CONSTRUCTION OF A
 THRESHOLD BUILDING. THE PURPOSE OF THE STRUCTURAL
 INSPECTION PLAN IS TO PROVIDE SPECIFIC INSPECTION
 PROCEDURES AND SCHEDULES SO THAT THE BUILDING CAN BE
 ADEQUATELY INSPECTED FOR COMPLIANCE WITH THE PERMITTED
 DOCUMENTS.
  
 8B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS
 ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH
 INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND
 REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE
 PLACE.
  
 FORMS SENT TO [email protected] SAT. DEC. 01/2018 12:48
 PM/
 REPLIED: MON. DEC. 03/2018 8:37 AM
  
 8C) THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B.
 AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH
 ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT
 OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 8D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
 NOTE: SHEET 060-S0.06 THRESHOLD NOTES. GENERAL NOTE K
 INDICATES THE SPECIAL INSPECTOR IS TO HAVE 10 YEARS
 EXPERIENCE IN INSPECTION, DESIGN OF SIMILAR STRUCTURES.
  
 8E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION.
  
 8F) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE
 REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE,
 PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING
 ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE
 APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR
 PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN
 COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR
 THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE
 IN BLACK & WHITE..
 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD
 BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS
 CONCERNING SPECIAL INSPECTORS.
  
 8G) 110.3.7.4.3 ALL SHORING AND RESHORING PROCEDURES,
 PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT
 AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING
 INSTALLATION SHALL BE SUPERVISED, INSPECTED AND
 CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
  
 8H) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR ALL
 BUILDING INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6
 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 8I) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES
 FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER
 HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE
 MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR
 WALLS AND CEILINGS.
  
 9) SHEET 005-AS0.01 SITE PLAN VERSES 006-AS0.02. IT
 APPEARS THE SITE PLAN INCLUDES 360 S. ROSEMARY, 370 S.
 ROSEMARY AND 352 EVERNIA ST. PLUS CITY OF W. P. B.
 ABANDONMENT OF A PORTION OF THE ALLEY. PLEASE NOTE A
 NEW PLAT WILL NEED TO BE RECORDED AND DOCUMENTATION OF
 THE CITY OF WEST PALM BEACH ABANDONING A PORTION OF THE
 ALLEY AND THE RELOCATION OF UTILITIES. PLEASE ALSO NOTE
 THE ALLEYWAY BEHIND 352 EVERNIA ST. IT WOULD APPEAR THE
 PROPERTY LINE IS DRAWN TO THE CENTERLINE OF THE ALLEY
 WHEREAS THE CORNERS OF THE LOT ARE DESIGNATED AS THE
 SOUTH SIDE OF THE ALLEY. PLEASE PROVIDE A SURVEY AND
 OVERLAY OF THE NEW PROPOSED LOT LINES (SEE 005-AS0.01).
 2017 FBC-B SECTION 503 & 602, BUILDINGS CANNOT GO
 BEYOND THE LOT LINES, THEY HAVE TO SIT ON ONE LOT.
  
 10) BOTH SHEETS LS1.01 LIFE SAFETY PLAN LEVEL 1 &
 134-AE1.01:
  
 10A) BOTH SHOW WHAT APPEARS TO BE A STRUCTURE JUST EAST
 OF THE NEWLY CREATED PROPERTY LINE. PLEASE IDENTIFY IF
 THIS LINE REPRESENTS THE WALL LINE OR ROOF LINE? PLEASE
 ALSO SHOW THE EXTERIOR STAIR LOCATED ON THE WEST SIDE
 OF THIS EXISTING BUILDING AND THE WIDTH OF THE
 UNPROTECTED EXTERIOR STAIR. PLEASE ALSO PROVIDE HOW
 MANY WINDOWS ARE WITHIN THIS WALL PER STORY AND SQ. FT.
 AREA OF UNPROTECTED OPENINGS. PLEASE PROVIDE THE
 DISTANCE FROM THE WALL LINE OF THIS EXISTING BUILDING
 TO THE PROPERTY LINE.
  
 THE CREATION OF NEW LOT LINES/ AND OR PLAT ARE NOT TO
 CREATE NEW NONCONFORMITIES TO EXISTING BUILDINGS. THE
 2017 FBC-B DEALS WITH:
  
 10A)(1). LIGHT FRAME CONSTRUCTION IN 704.4.1.
 LIGHT-FRAME CONSTRUCTION. STUDS AND BOUNDARY ELEMENTS
 THAT ARE INTEGRAL ELEMENTS IN LOAD-BEARING WALLS OF
 LIGHT-FRAME CONSTRUCTION SHALL BE PERMITTED TO HAVE
 REQUIRED FIRE-RESISTANCE RATINGS PROVIDED BY THE
 MEMBRANE PROTECTION PROVIDED FOR THE LOAD-BEARING WALL.
  
 10A)(2). 704.10 EXTERIOR STRUCTURAL MEMBERS.
 LOAD-BEARING STRUCTURAL MEMBERS LOCATED WITHIN THE
 EXTERIOR WALLS OR ON THE OUTSIDE OF A BUILDING (
 EXTERIOR STAIRS) OR STRUCTURE SHALL BE PROVIDED WITH
 THE HIGHEST FIRE-RESISTANCE RATING AS DETERMINED IN
 ACCORDANCE WITH THE FOLLOWING:
 1.AS REQUIRED BY TABLE 601 FOR THE TYPE OF BUILDING
 ELEMENT BASED ON THE TYPE OF CONSTRUCTION OF THE
 BUILDING;
 2.AS REQUIRED BY TABLE 601 FOR EXTERIOR BEARING WALLS
 BASED ON THE TYPE OF CONSTRUCTION; AND
 3.AS REQUIRED BY TABLE 602 FOR EXTERIOR WALLS BASED ON
 THE FIRE SEPARATION DISTANCE.
  
 10A)(3). TABLE 705.8 MAXIMUM AREA OF EXTERIOR WALL
 OPENINGS.
  
 10B) DISCREPANCY IN PLANS. SHEETS LS1.01 LIFE SAFETY
 PLAN LEVEL VERSES 134-AE1.01 OVERALL FLOOR PLAN LEVEL
 1. THE LIFE SAFETY PLAN SHOWS A 2 HOUR FIRE RATED WALL
 VERSES THE ARCHITECTURAL SHEET 1ST FLOOR SHOWS A 1 HOUR
 FIRE RATING. SEE FBC-B TABLE 601, 602 AND 704.10.
 PLEASE NOTE THIS COMMENT IS FOR ALL FIRE RATED WALLS.
 SHEET 188-AE4.01 ENLARGED FLOOR PLAN DOES SHOW WALL
 TAGS. SHEET 276-AE7.01 PROVIDES PARTITION TYPES, AND
 WALL RATINGS. WHEN YOU REFER TO THE UL FIRE RATED
 ASSEMBLIES, THERE IS NO ASSEMBLY SHOWN ON THE
 ARCHITECTURAL SHEETS FOR THE INSPECTOR TO FOLLOW, NOR
 WHEN YOU DO LOOK UP THE ASSEMBLIES THE ASSEMBLY DOES
 NOT INDICATE HOW TO TREAT THE FLOOR AND MORE IMPORTANT
 THE WALL TO DECK ABOVE. THE PLAN NOTES JUST STATE TO
 PROVIDE FR SEALANT AT THE TOP AND BOTTOM OF THE WALL.
 PLEASE PROVIDE COMPLIANCE WITH 2017 FBC-B SECTION
 715.1. JOINTS INSTALLED IN OR BETWEEN
 FIRE-RESISTANCE-RATED WALLS, FLOOR OR FLOOR/CEILING
 ASSEMBLIES AND ROOFS OR ROOF/CEILING ASSEMBLIES SHALL
 BE PROTECTED BY AN APPROVED FIRE-RESISTANT JOINT SYSTEM
 DESIGNED TO RESIST THE PASSAGE OF FIRE FOR A TIME
 PERIOD NOT LESS THAN THE REQUIRED FIRE-RESISTANCE
 RATING OF THE WALL, FLOOR OR ROOF IN OR BETWEEN WHICH
 THE SYSTEM IS INSTALLED. FIRE-RESISTANT JOINT SYSTEMS
 SHALL BE TESTED IN ACCORDANCE WITH SECTION 715.3.
  
 10C) DISCREPANCY IN PLANS. SHEETS LS1.01 LIFE SAFETY
 PLAN LEVEL VERSES 134-AE1.01 OVERALL FLOOR PLAN LEVEL
 1. ROOM 105 THE DIESEL TANK ROOM THE LIFE SAFETY PLAN
 SHOWS A 4 HOUR WALL VERSES THE ARCHITECTURAL SHEET
 SHOWING NO FIRE RATING.
  
 10D) DISCREPANCY IN PLANS. SHEETS LS1.01 LIFE SAFETY
 PLAN LEVEL VERSES 134-AE1.01 OVERALL FLOOR PLAN LEVEL
 1. ROOM # 107 THE FIRE PUMP ROOM THE WALLS ARE NOT
 SHOWN TO HAVE A FIRE RATING ON THE ARCHITECTURAL SHEET.
 THE 2017 FBC-B 913.2.1 REQUIRES 2 HOUR RATING.
  
 10E) DISCREPANCY IN PLANS. SHEETS LS1.01 LIFE SAFETY
 PLAN LEVEL VERSES 134-AE1.01 OVERALL FLOOR PLAN LEVEL
 1. ROOM 106 THE GENERATOR ROOM DOES NOT INDICATE RATING
 OF THE WALLS FOR FIRE ON THE ARCHITECTURAL SHEET.
 PLEASE SHOW COMPLIANCE WITH 403.4.8.1 OF THE 2017
 FBC-B.
  
 10F) 10E) DISCREPANCY IN PLANS. SHEETS LS1.01 LIFE
 SAFETY PLAN LEVEL VERSES 134-AE1.01 OVERALL FLOOR PLAN
 LEVEL 1. ROOMS 108 POWER ROOM AND 109 EMERGENCY
 ELECTRIC ROOM ALSO SIMILAR SITUATION, THE ARCHITECTURAL
 SHEETS DO NOT SHOW WALL RATINGS WHEREAS THE LIFE SAFETY
 PLAN SHOW A 2 HOUR FIRE RATING. PLEASE NOTE THIS IS A
 COMMON CODE VIOLATION FOR ALL OF THE 1ST FLOOR,
 ELEVATOR SHAFTS, ELEVATOR MACHINE ROOMS, STAIRWELLS,
 AND FIRE RESCUE LOBBY. 107.2.1.2 ADDITIONAL INFORMATION
 REQUIRED.
 10G) SHEETS 008-LS1.01 LIFE SAFETY PLAN LEVEL VERSES
 134-AE1.01 OVERALL FLOOR PLAN LEVEL 1.INTERIOR EXIT
 STAIRWELL 1 SHOWS A EGRESS CORRIDOR, PLEASE CORRECT ON
 BOTH SETS OF PLANS. THE VERTICAL INTERNAL EXIT STAIRWAY
 IS TO TERMINATE AT AN EXIT DISCHARGE. FBC-B 1023.3, THE
 EXCEPTION ALLOWS FOR AN EXIT PASSAGEWAY COMPLYING WITH
 1023.3.1. EXTENSION. PLEASE RENAME TO AN EXIT
 PASSAGEWAY.
 10G)(1) INTERIOR EXIT STAIRWELL 1 AND EXIT PASSAGEWAY.
 PLEASE NOTE ON THE MECHANICAL SHEET 350-M1.01 THE PLANS
 INDICATE TO BUILD A 10 INCH WIDE RATED CHASE FOR
 REFRIGERANT PIPING. THE FBC-B CODE SECTION 1023.2
 CONSTRUCTION FOR SHAFT CONSTRUCTION OF THE STAIRWELL
 FOR 4 STORIES OR MORE REQUIRES 2 HOUR CONSTRUCTION OF
 FIRE BARRIERS, VERTICAL AND HORIZONTAL. PLEASE REVIEW
 FBC-B 1023.5 PENETRATIONS AND THE LIMITATION. THERE CAN
 BE NO HORIZONTAL FIRE BARRIERS BUILT OUT OF DRYWALL,
 THERE IS NO UL LISTING FOR HORIZONTAL USAGE. PLEASE BE
 AWARE NO OTHER PLUMBING, OR ELECTRICAL PIPING CAN GO
 THROUGH THE VERTICAL EXIT NOR THE EXIT PASSAGE WAY, THE
 FPL VAULT IS JUST TO THE EAST OF THE EXIT
 PASSAGEWAY!!!!
 THE OTHER ISSUE WITH EXIT STAIRWELL 1 AND EXIT
 PASSAGEWAY, SHEET 350-M1.01 DOES INDICATE STAIR
 PRESSURIZATION FAN LOCATED ON THE MAIN ROOF, BUT THERE
 IS NO PRESSURIZATION FAN FOR THE EXIT PASSAGEWAY.
 PLEASE SHOW COMPLIANCE WITH FBC-B SECTION 1024.7
 VENTILATION.
 10H) LOADING DOCKS WOULD STILL BE CONSIDERED A S2
 OCCUPANCY AND REQUIRING SEPARATION FROM THE OTHER
 OCCUPANCIES AND ANCILLARY USES, SEE TABLE 508.4 OF THE
 FBC-B.
 10I) THE LOADING DOCKS DOES NOT INDICATE IF THIS IS TO
 BE CONSIDERED AN OPEN OR ENCLOSED PARKING GARAGE? SHOW
 COMPLIANCE WITH FBC-B 406.5 OPEN PARKING GARAGES OR
 406.6ENCLOSED PARKING GARAGES. PLEASE NOTE SHEET
 188-AE4.01 SHOWS THE WALL SEPARATING THE S2 OCCUPANCIES
 FROM MERCANTILE OR BUSINESS AS A NON-RATED WALL BUT 2
 C20 AND WALL TYPE C12 BOTH SHOW A 2 HOUR FIRE RATING.
 SE 2017 FBC-B TABLE 508.4. PLEASE ALSO SEE SHEET
 188-AE4.01 DOOR 115A, THIS DOOR DOES NOT SHOW A RATING
 BETWEEN THE S2/ M, B OCCUPANCIES. SEE OPENING
 PROTECTIVES. FBC-B 716-5. 107.2.1.2 ADDITIONAL
 INFORMATION REQUIRE.
 10J) SHEET 134-AE1.01 SHOWS A STAIR BY THE CONCRETE
 RAMP BY THE POWER ROOM 108. PLEASE NOTE THE SAME STAIR
 ON SHEET 008-LS1.01 IS NOT COMPLETE. 107.2.1.2
 ADDITIONAL INFORMATION IS REQUIRED.
 10K) ADDITIONAL INFORMATION IS REQUIRED, 107.2.1.2.
 WHEN VIEWING THE 1ST LEVEL LIFE SAFETY PLAN 008-LS1.01
 AND SHEET 134-AE1.01 THE FURTHEST EAST PROPERTY LINE
 GRID LINE 1 THRU 6 IT APPEARS TO BE A 2 HOUR FIRE RATED
 WALL ON THE 1ST LEVEL. SHEET 154-AE2.02, IN VIEWING THE
 EAST ELEVATION, GRID LINES 1-6 FOR THE 1ST FLOOR IT
 WOULD APPEAR THIS AREA HAS COLUMNS AND OPEN AREAS IN
 THE WALLS? THIS AREA IS ONLY 1 FOOT FROM THE PROPERTY
 LINE, FBC-B TABLE 705.8 0-3 FEET FROM THE PROPERTY LINE
 NO OPENINGS ARE ALLOWED.
 10L) SHEET 154-AE2.02 THE SOUTH ELEVATION & 164-AE2.19,
 PLEASE PROVIDE THE TOTAL AMOUNT OF SQUARE FOOT AREA FOR
 WALL ON THE 1ST FLOOR FROM GRID LINE F TO H. IT WOULD
 APPEAR YOU ARE OVER THE ALLOWABLE OPENING SIZE OF 45%
 OF OPENING SIZE FOR UNPROTECTED/ SPRINKLERED FOR 10 TO
 15 FOOT FIRE SEPARATION DISTANCE. I GOT A PERCENTAGE OF
 47% OPENING. 1360 SQ. FT. WALL AREA AND 643 SQ. FT.
 OPENING AREA. FBC-B TABLE 705.8.
 10M) SHEETS 008-LS1.01 LIFE SAFETY PLAN LEVEL 1 AND
 SHEET 134-AE1.01 FLOOR PLAN LEVEL 1 SHOW A ROOM JUST TO
 THE RIGHT OF ENGINEERING ROOM # 120 THAT DOES NOT HAVE
 A ROOM TAG NOR IDENTIFY THE USEAGE OF THE ROOM?
 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED.
 10N) SHEETS 008-LS1.01 LIFE SAFETY PLAN LEVEL 1 AND
 SHEET 134-AE1.01 FLOOR PLAN LEVEL 1. PLEASE NOTE THE
 FLOOR PLAN DOES IDENTIFY EACH ELEVATOR BUT DOES NOT
 INDICATE WHICH MACHINE ROOMS ARE FOR WHICH ELEVATORS?
 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED. FBC-B
 3005.1 ACCESS. AN APPROVED MEANS OF ACCESS SHALL BE
 PROVIDED TO ELEVATOR MACHINE ROOMS, CONTROL ROOMS,
 CONTROL SPACES AND MACHINERY SPACES, MACHINE ROOMS,
 CONTROL SPACES AND MACHINERY SPACES IS REQUIRED TO BE
 APPROVED BY THE BUILDING OFFICIAL. SEE ALSO 2015 IBC
 COMMENTARY. ONE CONCERN IS FOR ELEVATOR #10 A COMMON
 ELEVATOR NOT PART OF THE RETAIL TENANT SPACE, BUT TO
 ACCESS THE MACHINE ROOM FOR THIS ELEVATOR, THE MACHINE
 ROOM IS LOCATED IN THE RETAIL TENANT SPACE.
 10O) 008-LS1.01. TO UNDERSTAND THE EXITING FOR CORRIDOR
 126 YOU HAVE TO GO TO THE LIGHTING FLOOR PLAN FOUND
 UNDER 404-EL1.01. YOU FIND AN EXIT LIGHT BY GRID LINE
 B/4 FOR THIS DOOR, BUT MISSING DOOR AND EXIT LIGHT BY
 GRID LINE D/ 6.5. IT WOULD APPEAR THE DESIGNER IS
 TAKING THIS OCCUPANT LOAD TO THE FRONT LOBBY FOR
 EXITING. PLEASE CORRECT THE MISSING DOOR AND EXIT LIGHT
 ON 404-EL1.01.
 10P) SHEET 008-LS1.01 LIFE SAFETY PLAN. NOTE ON THE
 PLANS INDICATES: WHERE THE FIRE SERVICE ACCESS ELEVATOR
 SHARE THE HOISTWAY WITH ADJACENT PASSENGER ELEVATORS,
 THE ENTIRE SHAFT ENCLOSURE MUST COMPLY WITH FSAE
 HOISTWAY PROTECTION. PLEASE EXPLAIN THE NOTE. THE PLAN
 DEPICTS A SEPARATE HOISTWAY FOR THE FIRE SERVICE ACCESS
 ELEVATOR. IN THE 2017 FBC-B SECTION 3007.5 HOISTWAY
 ENCLOSURES. THE FIRE SERVICE ACCESS ELEVATOR HOISTWAY
 SHALL BE LOCATED IN A SHAFT ENCLOSURE COMPLYING WITH
 SECTION 713.
 10Q) PLEASE NOTE SHEET 188-AE4.01 ENLARGED LEVEL 1
 FLOOR PLAN AREA A. THE WALL TYPES ON ALL ELEVATOR WALLS
 CONTAINING THE ELEVATOR DOORWAY ARE IDENTIFIED AS WALL
 TYPE 2M6. SHEET 276-AE7.01 PARTITION TYPES.
 THE ENLARGED FLOOR PLAN INDICATES THE WALL TYPE AS 2M6.
 THE SHEET 276-AE7.01 PARTITION TYPES INDICATE THIS WALL
 TO BE A 6 INCH CMU AND 1 5/8 METAL FURRING AND 5/8 INCH
 GWB A 2 HOUR FIRE DESIGN UL DESIGN # U906.
 10Q)(1) PLEASE SUBMIT THE ACTUAL UL LISTED DESIGNS AS
 PART OF THE PLANS. THE ACTUAL UL DESIGN U906 SHOWS ON
 ONE SIDE OF THE BLOCK ? INCH PORTLAND CEMENT STUCCO OR
 GYPSUM PLASTER WHICH WILL ADD ? HOUR TO THE
 CLASSIFICATION. PLEASE CORRECT LISTING AND SHOW THE
 CORRECT MATERIALS NOT FURRING AND ? INCH DRYWALL.
 2017 FBC-B SHAFTS. 713.4 FIRE-RESISTANCE RATING. SHAFT
 ENCLOSURES SHALL HAVE A FIRE-RESISTANCE RATING NOT LESS
 THAN THE FLOOR ASSEMBLY PENETRATED, BUT NEED NOT EXCEED
 2 HOURS. SHAFT ENCLOSURES SHALL MEET THE REQUIREMENTS
 OF SECTION 703.2.1.
 FBC-B 703.2.1. 703.2.1 NONSYMMETRICAL WALL
 CONSTRUCTION. INTERIOR WALLS AND PARTITIONS OF
 NONSYMMETRICAL CONSTRUCTION SHALL BE TESTED WITH BOTH
 FACES EXPOSED TO THE FURNACE, AND THE ASSIGNED
 FIRE-RESISTANCE RATING SHALL BE THE SHORTEST DURATION
 OBTAINED FROM THE TWO TESTS CONDUCTED IN COMPLIANCE
 WITH ASTM E119 OR UL 263. WHERE EVIDENCE IS FURNISHED
 TO SHOW THAT THE WALL WAS TESTED WITH THE LEAST
 FIRE-RESISTANT SIDE EXPOSED TO THE FURNACE, SUBJECT TO
 ACCEPTANCE OF THE BUILDING OFFICIAL, THE WALL NEED NOT
 BE SUBJECTED TO TESTS FROM THE OPPOSITE SIDE (SEE
 SECTION 705.5 FOR EXTERIOR WALLS).
 10Q)(2) PLEASE PROVIDE A LETTER FROM THE BLOCK
 MANUFACTURER AS TO THE 6 INCH CMU MEETS THE MINIMUM
 EQUIVALENT THICKNESS FOR THE REQUIRED FIRE RATING OF
 THE ELEVATOR SHAFT WALL CONSTRUCTION SEE FBC-B TABLE
 722.3.2. THE LETTER MUST CONTAIN MANUFACTURER, THE TYPE
 OF AGGREGATE AND THE EQUIVALENT THICKNESS IN INCHES AND
 THE FIRE RATING THE BLOCK ACHIEVES. THE LETTER MUST BE
 SIGNED AND THE PERSONS POSITION IN THE COMPANY
 ATTESTING TO THIS AFFIDAVIT.
  
 10R) NEITHER THE LIFE SAFETY FOR LEVEL 1, NOR THE
 ENLARGED LEVEL 1 AREA A NOR SHEET AE4.20 ENLARGED CORE
 PLAN LEVEL 1 SHOW COMPLIANCE FOR ELEVATOR CARS TO
 ACCOMMODATE AN AMBULANCE STRETCHER AS REQUIRED BY
 SECTION 3002.4 OF THE 2017 FBC-B.
 10R)(1) FBC-B 3002.4 THE ELEVATOR CAR SHALL BE OF SUCH
 A SIZE AND ARRANGEMENT TO ACCOMMODATE AN AMBULANCE
 STRETCHER 24 INCHES BY 76 INCHES (610 MM BY 1950 MM)
 WITH NOT LESS THAN 5-INCH (127 MM) RADIUS CORNERS, IN
 THE HORIZONTAL, OPEN POSITION...
 10R)(2) FBC-B 3002.4. THE HOISTWAY DOOR FRAME SHALL BE
 IDENTIFIED BY THE INTERNATIONAL SYMBOL FOR EMERGENCY
 MEDICAL SERVICES (STAR OF LIFE). THE SYMBOL SHALL BE
 NOT LESS THAN 3 INCHES (76 MM) IN HEIGHT AND SHALL BE
 PLACED INSIDE ON BOTH SIDES OF THE HOISTWAY DOOR FRAME.
 10S) NEITHER THE LIFE SAFETY FOR LEVEL 1, NOR THE
 ENLARGED LEVEL 1 AREA A NOR SHEET AE4.20 ENLARGED CORE
 PLAN LEVEL 1 SHOW COMPLIANCE FOR:
 10S)(1) 2017 FBC-B 403.6.1 FIRE SERVICE ACCESS
 ELEVATOR. NO FEWER THAN TWO FIRE SERVICE ACCESS
 ELEVATORS SHALL BE PROVIDED IN ACCORDANCE WITH SECTION
 3007 IN BUILDINGS WITH AN OCCUPIED FLOOR MORE THAN 120
 FEET MEASURED FROM THE ELEVATION OF THE STREET LEVEL
 ACCESS.
  
 10S)(2) 2017 FBC-B 2017 FBC-B 403.6.1 FIRE SERVICE
 ACCESS ELEVATOR. PLEASE SHOW COMPLIANCE WITH EACH FIRE
 SERVICE ACCESS ELEVATOR SHALL HAVE A CAPACITY OF NOT
 LESS THAN 3,500 POUNDS.
 10S)(3) SHOW COMPLIANCE WITH FBC-B 3007.6.5 FIRE
 SERVICE ACCESS ELEVATOR SYMBOL.
 10S)(4) FBC-B 3007.3 WATER PROTECTION. AN APPROVED
 METHOD TO PREVENT WATER FROM INFILTRATING INTO THE
 HOISTWAY ENCLOSURE FROM THE OPERATION OF THE AUTOMATIC
 SPRINKLER SYSTEM OUTSIDE THE ENCLOSED FIRE SERVICE
 ACCESS ELEVATOR LOBBY SHALL BE PROVIDED.
 10T)(1) BOTH SHEETS 008-LS1.01 LIFE SAFETY PLAN LEVEL 1
 & SHEET 134-AE1.01SHOW A INTERSTITIAL SPACE AND A
 STAIRWELL 2, A LANDING, EGRESS CORRIDOR AND A STAIRWELL
 6. PLEASE CORRECT THE LABELING OF STAIRS AND EGRESS
 CORRIDOR. THERE SHOULD BE NO STAIR LABELED STAIR 6.
 SHEET AE3.19 DETAIL 1 OR 173-AE3.03 SHOWS THE VERTICAL
 EXIT STAIR (STAIR 2) AND THE CONTINUATION OF THIS STAIR
 BELOW LEVEL 2 TO THE INTERSTITIAL SPACE AND A
 MID-LANDING THAT CONTINUES OVER TO THE SO-CALLED STAIR
 6. THIS IS ONE CONTINUOUS STAIRWAY WHERE THE MIDLANDING
 IN THE INTERSTITIAL SPACE IS ELONGATED AND THEN
 CONTINUES TO THE 1ST FLOOR EXIT DOORWAY.
 THE 2017 FBC-B SECTION 1023.1STATES: INTERIOR EXIT
 STAIRWAYS AND RAMPS SERVING AS AN EXIT COMPONENT IN A
 MEANS OF EGRESS SYSTEM SHALL COMPLY WITH THE
 REQUIREMENTS OF THIS SECTION. INTERIOR EXIT STAIRWAYS
 AND RAMPS SHALL BE ENCLOSED AND LEAD DIRECTLY TO THE
 EXTERIOR OF THE BUILDING. THIS STAIRWELL DOES NOT MEET
 THE DEFINITION OF AN EXIT PASSAGEWAY BECAUSE THE STAIR
 IS UP OFF THE FLOOR LEVEL LOCATED IN THE INTERSTITIAL
 SPACE.
 10T)(2) PLEASE REVIEW SHEET 216-AE4.28 DETAIL 5, A CUT
 SECTION THROUGH THE 2 HOUR FIRE RATED INTERIOR EXIT
 STAIR. THE DETAIL SHOWS A 2 HOUR RATED SHAFT WALL
 ASSEMBLY. SHEET 276-AE7.01 PARTITIONS 2SW INDICATES THE
 USE OF SHAFT WALL CONSTRUCTION WITH A UL DESIGN U438.
 PLEASE INDICATE WHICH SIDE OF THE SHAFT WALL
 CONSTRUCTION IS TO BE WITHIN THE STAIRWELL SHAFT. THE
 UL DESIGN PROVIDED DOES NOT INDICATE? PLEASE ALSO
 PROVIDE THE UL DESIGN AS PART OF THE PLAN DOCUMENTS.
 107.2.1.2. ADDITIONAL INFORMATION REQUIRED TO SHOW CODE
 COMPLIANCE.
 10T)(3) SHEET 216-AE4.28 DETAIL # 5 SHOWS THE INTERIOR
 EXIT STAIRWAYS LOCATED IN THE A INTERSTITIAL SPACE WITH
 A CROSS SECTION VIEW. AS THE STATEMENT ABOVE INDICATES
 SHAFTWALL CONSTRUCTION SEPARATES THE STAIRWELL FROM THE
 REMAINDER OF THE FIRST FLOOR AREA. WHAT THIS DETAIL
 FAILS TO SHOW HOW COMPLIANCE HOW THE FIRE RESISTANCE
 RATING IS TO BE MAINTAINED FOR ALL OF THE STEEL FRAMING
 MEMBERS (STEEL ANGLES, SUPPORTS AND STEEL BEAMS) ARE TO
 BE MAINTAINED. FBC-B 707.3.2 INTERIOR EXIT STAIRWAY AND
 RAMP CONSTRUCTION. THE FIRE-RESISTANCE RATING OF THE
 FIRE BARRIER SEPARATING BUILDING AREAS FROM AN INTERIOR
 EXIT STAIRWAY OR RAMP SHALL COMPLY WITH SECTION 1023.1.
 INTERIOR EXIT STAIRWAY AND RAMP ENCLOSURES SHALL HAVE A
 FIRE-RESISTANCE RATING OF NOT LESS THAN 2 HOURS WHERE
 CONNECTING FOUR STORIES OR MORE. SHOW COMPLIANCE.
 10T)(4) 10T)(3) SHEET 216-AE4.28 DETAIL # 5 SHOWS THE
 INTERIOR EXIT STAIRWAYS LOCATED IN THE A INTERSTITIAL
 SPACE WITH A CROSS SECTION VIEW. THIS SAME DETAIL SHOWS
 A 2 HOUR FIRE RATED MASONRY WALL FROM FLOOR LEVEL OF
 THE 1ST FLOOR THAT STOPS AS DEPICTED JUST AT THE BOTTOM
 OF THE 2ND FLOOR CONCRETE PAN JOIST FLOOR SYSTEM. HOW
 WILL THE 2 HOUR FIRE RATING ACHIEVED WHERE THE TWO
 MATERIALS MAY OR MAY NOT TOUCH EACH OTHER?
 2017 FBC-B 715.1. JOINTS INSTALLED IN OR BETWEEN
 FIRE-RESISTANCE-RATED WALLS, FLOOR OR FLOOR/CEILING
 ASSEMBLIES AND ROOFS OR ROOF/CEILING ASSEMBLIES SHALL
 BE PROTECTED BY AN APPROVED FIRE-RESISTANT JOINT SYSTEM
 DESIGNED TO RESIST THE PASSAGE OF FIRE FOR A TIME
 PERIOD NOT LESS THAN THE REQUIRED FIRE-RESISTANCE
 RATING OF THE WALL, FLOOR OR ROOF IN OR BETWEEN WHICH
 THE SYSTEM IS INSTALLED. FIRE-RESISTANT JOINT SYSTEMS
 SHALL BE TESTED IN ACCORDANCE WITH SECTION 715.3.
 10T)(5) SHEET 216-AE4.28 DETAIL # 5 SHOWS THE INTERIOR
 EXIT STAIRWAYS LOCATED IN THE A INTERSTITIAL SPACE WITH
 A CROSS SECTION VIEW. SINCE THE STRUCTURAL INDEX IS
 MISSING 57 SHEETS, PLEASE PROVIDE WHERE THE STRUCTURAL
 DETAILS ARE LOCATED FOR THE STRUCTURAL MEMBERS, AND
 ATTACHMENT TO OTHER STRUCTURAL FRAMING MEMBERS. 2017
 WEST PALM BEACH AMENDMENTS 107.2.1.2. ADDITIONAL
 INFORMATION IS REQUIRED.
  
 10T)(6) SHEET 208-AE4.20 DETAIL # 3 SHOWS THE INTERIOR
 EXIT STAIRWAYS LOCATED IN THE A INTERSTITIAL SPACE WITH
 A CROSS SECTION VIEW. SHEET 215-AE4.27 DETAIL 4 SHOWS A
 CROSS SECTION OF THE STAIRWAY ON THE 1ST FLOOR A RETAIL
 AREA WITH RAMP IS SHOWN AND DIRECTLY ABOVE THE STAIR
 LANDING LOCATED IN THE A INTERSTITIAL SPACE WITH A 5
 INCH CONCRETE SLAB. PLEASE ALSO NOTE MAKING THE FIRE
 RATED WALL ON THE EDGE OF THE INTERSTITIAL LANDING IS A
 MASONRY WALL. SHEET 208-AE4.20 DETAIL 3 SHOWS THIS WALL
 BUT THE MASONRY WALL DOES NOT HAVE A WALL TAG
 IDENTIFYING THE FIRE RATING OR WALL TYPE. SEE 2017
 FBC-B 713.4. SHAFT ENCLOSURES SHALL HAVE A
 FIRE-RESISTANCE RATING OF NOT LESS THAN 2 HOURS WHERE
 CONNECTING FOUR STORIES.
 10T)(7) SHEET 216-AE4.28 DETAIL # 5 SHOWS A CROSS
 SECTION OF THE STAIRWELL IN THE INTERSTITIAL SPACE. THE
 DETAIL FAILS TO INDICATE HOW A 2 HOUR FIRE RATED FLOOR
 ASSEMBLY IS TO BE ACHIEVED? SEE SECTION 713.4 OF THE
 2017 FBC-B, SECTION SHAFT ENCLOSURES SHALL HAVE A
 FIRE-RESISTANCE RATING NOT LESS THAN THE FLOOR ASSEMBLY
 PENETRATED, BUT NEED NOT EXCEED 2 HOURS. ALSO TABLE 601
 FLOOR CONSTRUCTION.
 10T)(8) PLEASE NOTE THE STAIRWAY #2 AN INTERIOR EXIT
 STAIRWAY THAT IS CONTINUOUS TO THE EXTERIOR DOES NOT
 SHOW STAIRWELL PRESSURIZATION, SMOKEPROOF ENCLOSURES,
 IN ANY OF THE MECHANICAL PLANS, SEE 2017 FBC-B 1023.11
 SMOKEPROOF ENCLOSURES. WHERE REQUIRED BY SECTION
 403.5.4 OR 405.7.2, INTERIOR EXIT STAIRWAYS AND RAMPS
 SHALL BE SMOKEPROOF ENCLOSURES IN ACCORDANCE WITH
 SECTION 909.20.
 11) LEVEL 2: 09LS1.02, 135-AE1.02, & 190/191 AE4.02 A &
 B:
  
 11A)(1) THE LIFE SAFETY SHEET ANALYSIS, NOR LS1, NOR
 LS2 SHOW AN ANALYSIS OF THE PARKING STRUCTURE, HOW MANY
 TOTAL PARKING SPACES THERE IS OR HOW MANY ACCESSIBLE
 PARKING SPACES THERE IS OR COMPLIANCE WITH THE 2017
 FBC-ACCESSIBLE PARKING SPACES. SHOW ACCESSIBLE MATRIX.
  
 11A)(2) SHEET 135-AE1.02 THE OVERALL FLOOR PLAN FOR
 LEVEL 2 SHOWS 4 ACCESSIBLE PARKING SPACES, 3 ACCESSIBLE
 SPACES. SHOW THE ACCESSIBLE ROUTE FOR A WHEEL CHAIR TO
 BE ABLE TO GET TO AN ELEVATOR WITHOUT HAVING TO GO OUT
 INTO THE VEHICULAR TRAVEL LANE. ACCESSIBILITY CODE
 SECTION 206.2. WHERE REQUIRED. AN
 ACCESSIBLE ROUTE SHALL BE PROVIDED WHERE REQUIRED BY
 206.2.
 206.2.2 WITHIN A SITE. AT LEAST ONE ACCESSIBLE ROUTE
 SHALL CONNECT ACCESSIBLE BUILDINGS, ACCESSIBLE
 FACILITIES, ACCESSIBLE ELEMENTS, AND ACCESSIBLE SPACES
 THAT ARE ON THE SAME SITE.
  
 11B) COMMENT FOR ALL PARKING FLOORS. PLEASE ALSO SHOW
 COMPLIANCE WITH SECTION 208.2.4. VAN PARKING SPACES.
 WHERE VAN PARKING IS PROVIDED PURSUANT TO SECTION
 502.2, FOR EVERY SIX OR FRACTION OF SIX PARKING SPACES
 REQUIRED BY 208.2 TO COMPLY WITH 502, AT LEAST ONE
 SHALL BE A VAN PARKING SPACE COMPLYING WITH 502.
  
 11C) COMMENT FOR ALL PARKING FLOORS. SHEET 182-AE3.18
 BUILDING SECTION. THE PLAN SHOWS ELEVATIONS OF THE
 VARIOUS FLOOR LEVELS AND BY MEASURING BETWEEN FLOOR
 SLABS IT WOULD APPEAR THERE MAYBE ONLY 7 FEET 8 INCHES
 FROM THE BOTTOM OF THE FLOOR PRECAST AND FINISH FLOOR
 BELOW. PLEASE PROVIDE THE CLEAR HEIGHT BETWEEN FLOOR
 SLABS AND THE PRECAST FLOOR JOIST ABOVE, AND ALSO
 PROVIDE FOR THE FIRE SPRINKLERS TO HAVE A TRUE HEIGHT
 FOR THE RAMPS AND FOR THE PARKING AREAS. PLEASE SHOW
 HOW COMPLIANCE WITH 2017 FBC-ACCESSIBILITY CODE SECTION
 502.5 VERTICAL CLEARANCE. PARKING SPACES FOR VANS AND
 ACCESS AISLES AND VEHICULAR ROUTES SERVING THEM SHALL
 PROVIDE A VERTICAL CLEARANCE OF 98 INCHES MINIMUM.
  
 11D) PLEASE REVIEW SHEET 270-AE5.39 PARKING DETAILS.
 PLEASE REFER TO THE 2017 FBC-ACCESSIBILITY CODE SEE THE
 ADVISORY 502.3.3 MARKING.
 2017 ACCESSIBILITY CODE. ADVISORY 502.3.3 MARKING. THE
 METHOD AND COLOR OF MARKING ARE NOT SPECIFIED BY THESE
 REQUIREMENTS BUT MAY BE ADDRESSED BY STATE OR LOCAL
 LAWS OR REGULATIONS. BECAUSE THESE REQUIREMENTS PERMIT
 THE VAN ACCESS AISLE TO BE AS WIDE AS A PARKING SPACE,
 IT IS IMPORTANT THAT THE AISLE BE CLEARLY MARKED.
 FLORIDA LAW, S.553.5041(5)(C)1., REQUIRES DIAGONAL
 STRIPING OF ACCESS AISLES.
 PLEASE REFER TO THE WEST PALM BEACH MUNI CODE 94-485
 FOR STALL PAINTING DETAILS AND REQUIRED DOUBLE LINE
 DIMENSIONS.
  
 11E) THE 2ND LEVEL FLOOR PLAN, : 09LS1.02, 135-AE1.02,
 & 190/191 AE4.02 A & B: WILL NEED TO PROVIDE WHAT THE
 DESIGN FOR THE PARKING FLOORS, IF THESE FLOOR LEVELS
 ARE TO BE CONSIDERED AN OPEN OR ENCLOSED PARKING
 GARAGE? SHOW COMPLIANCE WITH FBC-B 406.5 OPEN PARKING
 GARAGES OR 406.6ENCLOSED PARKING GARAGES.
 IF CONSIDERED OPEN SHOW COMPLIANCE ON THE ELEVATION
 SHEETS AE2.10 THROUGH AE2.22. PLEASE SHOW THE WALL AREA
 IN SQ. FEET. THE OPENING IN SQUARE FEET, PERCENTAGE OF
 OPENING, DEDUCT FOR THE ALUMINUM ARCHITECTURAL SCREEN
 AND TAKE A SECOND DEDUCTION FOR THE BIRD SCREEN AS
 WELL. SHOW COMPLIANCE WITH 406.5.2 OPENINGS OF THE 2017
 FBC-B AND 406.5.6 FIRE SEPARATION DISTANCE CONCERNS
 WITH SOUTH WALL ON GRID LINES F-H SHEET 182AE3.18 SHOWS
 THIS AREA OF THE PARKING GARAGE EXTENDED OVER THE 1ST
 FLOOR LEVEL.
  
 11F) BOTH SHEETS 135-AE1.02 LEVEL 2 AND 190AE4.02 BOTH
 SHOW ATTENDANT BOOTHS AND A GATED ENTRANCE TO THE
 PARKING LEVELS.
  
 11F)(1) PLEASE SHOW CUT SECTIONS FOR THE ATTENDANT
 BOOTHS OF HOW THEY ARE GOING TO BE ANCHORED FOR THE
 WIND, DOES THE WIND TUNNEL TEST HAVE A PRESSURE POINT
 FOR THE BOOTHS, IF NOT HOW ARE PRESSURES TO BE DERIVED?
 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED. FBC-B
 1609.1.1 DETERMINATION OF WIND LOADS.
  
 11F)(2) ADDITIONAL INFORMATION IS REQUIRED FOR THE
 ATTENDANT BOOTHS, ARE THESE BOOTHS PRE-MANUFACTURERED
 (MODULAR) BUILDINGS UNDER FLORIDA S. 553 PART I
 MANUFACTURED BUILDINGS?
  
 11G) THE PLANS ALSO SHOW USE OF VEHICULAR GATES. IF
 THEY USE KEY CARDS THE THEY WOULD ALSO BE CONSIDERED
 AUTOMATIC VEHICULAR GATES HAVING TO COMPLY WITH: FBC-B
 3110.1 AUTOMATIC VEHICULAR GATES SHALL COMPLY WITH THE
 REQUIREMENTS OF SECTIONS 3110.2 THROUGH 3110.4 AND
 OTHER APPLICABLE SECTIONS OF THIS CODE.
  
 11H) OFFICE 202, AREA OF 5,812 SQ. FT. AND FUTURE
 RESTROOMS MAY BE AT THE OWNERS OWN RISK!!!! DEPENDING
 ON IF THE OFFICE AREA IS SUB-DIVIDED IN TO 2 TENANTS
 AND THE LARGER OF THE 2 TENANTS HAS OVER 49 OCCUPANTS
 THEN 2 EXITS WOULD BE REQUIRED. 2017 FBC-B TABLE
 1006.2.1 .SPACES WITH ONE EXIT OR EXIT ACCESS DOORWAY.
  
 11I) THIS SHEET (155-AE2.10 KEY NOTE 13 AND OTHER
 ELEVATION SHEETS) INDICATE THE USE OF COMPOSITE METAL
 PANELS. PLEASE PROVIDE DOCUMENTATION FOR CODE
 COMPLIANCE WITH FBC-B 1407.2. MCM USED AS EXTERIOR WALL
 FINISH OR AS ELEMENTS OF CLADDING OR WEATHER RESISTANCE
 SHALL COMPLY WITH SECTIONS 1407.4 THROUGH 1407.14.
 PROVIDE DOCUMENTATION FOR ALL OF THE CODE SECTIONS
 INCLUDED INCLUDING SEPARATION DISTANCE FOR FIRE.
  
 11J) SHEET 190-AE4.02 AREA A. JUST OUTSIDE OF STAIR 2
 THERE IS A MECHANICAL SHAFT THAT GOES VERTICALLY
 THROUGH THE BUILDING INCLUDING THE FUTURE SHELL OFFICE
 FLOORS. THE WALL TYPE IS NOT INDICATED WITH A WALL TAG
 IT WOULD APPEAR TO BE A 2 HOUR FIRE RATED SHAFT WALL.
 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED.
  
 12) SHEET 204-AE4.09 FLOOR PLAN & TERRACE PLAN.
  
 12A) DOORS 901A, 901B, 901C & 901D ALL ONLY HAVE 1 FOOT
 ON THE PULL SIDE OF THE DOOR LATCH. THE 2017
 FBC-ACCESSIBILITY CODE REQUIRED 18 INCHES MINIMUM. 2017
 FBC- ACCESS. CODE 404.2.4 MANEUVERING CLEARANCES.
 DOORS. DOORS 901 B & 901C BOTH HAVE ADA PUSH PLATE
 BOLLARDS, PLEASE PROVIDE DETAILS FOR AN ACCESSIBLE
 ENTRANCE. SHOW COMPLIANCE WITH 2017 ACCESSIBILITY CODE
 404.3 AUTOMATIC AND POWER-ASSISTED DOORS AND GATES.
 AUTOMATIC DOORS AND AUTOMATIC GATES SHALL COMPLY WITH
 404.3. FULL-POWERED AUTOMATIC DOORS SHALL COMPLY WITH
 ANSI/BHMA A156.10 (INCORPORATED BY REFERENCE, SEE
 ?REFERENCED STANDARDS? IN CHAPTER 1). LOW-ENERGY AND
 POWER-ASSISTED DOORS SHALL COMPLY WITH ANSI/BHMA
 A156.19 (1997 OR 2002 EDITION) (INCORPORATED BY
 REFERENCE, SEE ?REFERENCED STANDARDS? IN CHAPTER 1).
  
 12B) EGRESS DOORS THAT ARE NOT ACCESSIBLE (901A & 901D)
 WILL NEED DIRECTIONAL SIGNAGE TO WHERE THE ACCESSIBLE
 MEANS OF EGRESS IS LOCATED. SHOW COMPLIANCE WITH:
 2017 FBC-ACCESSIBILITY CODE SECTION 216.4.3 DIRECTIONAL
 SIGNS. SIGNS REQUIRED BY SECTION 1003.2.13.6 OF THE
 INTERNATIONAL BUILDING CODE (2000 EDITION) OR SECTION
 1007.7 OF THE INTERNATIONAL BUILDING CODE (2003
 EDITION) (INCORPORATED BY REFERENCE, SEE ?REFERENCED
 STANDARDS? IN CHAPTER 1) TO PROVIDE DIRECTIONS TO
 ACCESSIBLE MEANS OF EGRESS SHALL COMPLY WITH 703.5.
  
 12C) SHEET 204-AE4.09 9TH FLOOR AND TERRACE PLAN. THERE
 IS A NOTE STATING CROSSHATCHED AREA INDICATES THE
 EXTENT OF SPRAYED ON INSULATION THERMAL INSULATION
 APPLIED TO THE UNDERSIDE OF THE LEVEL OF THE 9TH FLOOR
 SLAB. SEE SECTIONS FOR ADDITIONAL INFORMATION. NEITHER
 SECTIONS 170-AE3.00 NOR 182-AE3.18 PROVIDE ANY MORE
 INFORMATION ABOUT THE SPRAY ON THERMAL INSULATION. THE
 ENERGY CALCULATIONS WILL ALSO NEED TO SHOW THE SAME
 TYPE OF INSULATION AN R-RATING. 107.2.1.2 ADDITIONAL
 INFORMATION REQUIRED. SHEET 271-AE5.40 SHOWS
 LIGHTWEIGHT INSULATING CONCRETE BEING APPLIED TO THE
 ROOF TOP STRUCTURAL DECK.
  
 12D) SHEET 204-AE4.09 9TH FLOOR AND TERRACE PLAN SHOWS
 THE USE OF CONCRETE PEDESTAL PAVER SYSTEMS SPECIALTY
 ENGINEERED FOR APPLICABLE WIND LOAD RATING. IF THIS IS
 TO BE A DEFERRED SUBMITTAL PLEASE REQUEST IN THE
 RESPONSE NARRATIVE. 107.2.1.2 ADDITIONAL INFORMATION
 REQUIRED. DELEGATED ENGINEERING. 61G15-30.003
 ENGINEERING DOCUMENT CLASSIFICATION. FL 61G-15-30.006
 (3) THE DELEGATED ENGINEER SHALL FORWARD THE DELEGATED
 ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR
 REVIEW BEFORE BEING SUBMITTED TO THE BUILDING
 DEPARTMENT.
  
 13) SHEET 143-AE1.10 FLOOR PLAN LEVEL 18/ ROOF PLAN:
  
 13A) PLEASE PROVIDE HOW THE WINDOW WASHER EQUIPMENT
 ROOF ANCHOR WILL WORK WITHOUT INTERFERING WITH THE
 HORIZONTAL ALUMINUM METAL PANEL SYSTEM. WILL THE
 ALUMINUM METAL PANEL SYSTEM TAKE THE ADDITIONAL WEIGHT
 OF THE WINDOW WASHERS? EQUIPMENT/ SCAFFOLDING. PLEASE
 SHOW COMPLIANCE WITH 2017 FBC-B SECTIONS:
 1607.9.3 ELEMENTS SUPPORTING HOISTS FOR FA?ADE ACCESS
 EQUIPMENT. IN ADDITION TO ANY OTHER APPLICABLE LIVE
 LOADS, STRUCTURAL ELEMENTS THAT SUPPORT HOISTS FOR
 FA?ADE ACCESS EQUIPMENT SHALL BE DESIGNED FOR A LIVE
 LOAD CONSISTING OF THE LARGER OF THE RATED LOAD OF THE
 HOIST TIMES 2.5 AND THE STALL LOAD OF THE HOIST.
  
 1607.9.4 LIFELINE ANCHORAGES FOR FA?ADE ACCESS
 EQUIPMENT. IN ADDITION TO ANY OTHER APPLICABLE LIVE
 LOADS, LIFELINE ANCHORAGES AND STRUCTURAL ELEMENTS THAT
 SUPPORT LIFELINE ANCHORAGES SHALL BE DESIGNED FOR A
 LIVE LOAD OF AT LEAST 3,100 POUNDS FOR EACH ATTACHED
 LIFELINE, IN EVERY DIRECTION THAT A FALL ARREST LOAD
 MAY BE APPLIED.
  
 13B) THE OVERALL ROOF PLAN SHOWS METAL STAIRS AND METAL
 PLATFORM AND GUARDRAIL SYSTEM AT GRIDLINE D BETWEEN 3
 AND 4, PLEASE PROVIDE A CUT SECTION THROUGH THIS AREA
 TO BE ABLE TO DETERMINE CODE COMPLIANCE. 107.2.1.2.
 ADDITIONAL INFORMATION IS REQUIRED. SHEET 170-AE3.00
 SHOWS THE SAME METAL STAIR PLATFORM AND GUARDRAIL
 SYSTEM BUT NO CUT SECTIONS OR LIVE LOAD, LOADING
 CRITERIA.
  
 14) PLEASE NOTE, ONCE THE WIND TUNNEL TESTING REPORT IS
 SUBMITTED, REVIEWED AND APPROVED PRODUCT APPROVALS THEN
 CAN COME IN AFTER PERMIT ISSUANCE AS A DEFERRED
 SUBMITAL. WILL NEED A WRITTEN RESPONSE IF DEFERRED
 SUBMITTALS WILL BE USED FOR PRODUCT APPROVALS.
 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 15A) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 15B) DELEGATED ENGINEERING. 61G15-30.003 ENGINEERING
 DOCUMENT CLASSIFICATION. FL 61G-15-30.006 (3) THE
 DELEGATED ENGINEER SHALL FORWARD THE DELEGATED
 ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR
 REVIEW.
  
 16) DELEGATED ENGINEERING. 61G15-30.003 ENGINEERING
 DOCUMENT CLASSIFICATION. FL 61G-15-30.006 (3) THE
 DELEGATED ENGINEER SHALL FORWARD THE DELEGATED
 ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR
 REVIEW.
  
 17) COMPONENTS & CLADDING. 2017 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS,
 ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/
 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, LIGHTWEIGHT
 CONCRETE INSULATION, ROOF TOP VENTILATORS
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR PRE-ENGINEERED A/C STANDS AND OR CURBS
  
 18) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
  
 19) EFIS SYSTEMS: PLEASE PROVIDE THE PRODUCT APPROVAL
 FOR THE SYSTEM TO BE INSTALLED. PLEASE ALSO PROVIDE THE
 MANUFACTURERS INSTALLATION BROCHURE PROVIDING
 COMPLIANCE WITH 2017BC-B SECTIONS;
 1408.2 PERFORMANCE CHARACTERISTICS.
 1408.2 PERFORMANCE CHARACTERISTICS.
 1408.3 STRUCTURAL DESIGN.
 1408.4 WEATHER RESISTANCE.
 1408.4.1 EIFS WITH DRAINAGE.
 408.4.1.1 WATER-RESISTIVE BARRIER.
 1408.5 INSTALLATION.
  
 20) 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE CODE,
 THE CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, DESCRIBE
 AND DELINEATE THE TYPE OF ROOFING SYSTEM, MATERIALS,
 VENTING, FASTENING REQUIREMENTS, FLASHING REQUIREMENTS
 AND WIND RESISTANCE RATING THAT ARE REQUIRED TO BE
 INSTALLED. PRODUCT EVALUATION AND INSTALLATION SHALL
 INDICATE COMPLIANCE WITH THE WIND CRITERIA REQUIRED FOR
 THE SPECIFIC SITE.
  
 21) LATERAL FORCE-RESISTING SYSTEM. FOR ALL ROOF TOP
 EQUIPMENT, CURBS, FANS OR A/C STANDS, AND OR VENTS,
 DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL
 AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE.
 2017 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS.
 2017 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL
 EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO
 WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND
 PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, BUILDING.
  
 22) IMPACT FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.
 ONE SET OF PLANS WILL HAVE TO BE TAKEN (BY THE
 CONTRACTOR OR REPRESENTATIVE) TO THE PALM BEACH COUNTY
 IMPACT FEE OFFICE LOCATED AT 2300 N. JOG RD. ROOMS
 2W01-2W14 WEST PALM BEACH, FL. THE ACTUAL PERMIT SET OF
 PLANS MUST BE STAMPED BY THAT OFFICE, AND A COPY OF THE
 PAID RECEIPT ATTACHED TO THE PERMIT APPLICATION. PLEASE
 CALL (561)233-5025 FOR MORE INFORMATION.
  
 23) . FOR ELECTRONIC REVIEWS. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  
  
  
  
  
  
2018-11-01 09:54:14BUILDING PLANS EXAMINER PLEASE CHECK THE AMOUNT OF
 PENETRATION IN AND OUT OF THE STAIRWELLS FOR THE BDA
 SYSTEM SHOWN ON PAGES T5.03. JLEAHY

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2019-05-29 Cont ID  
Sent By jleahy Date 2019-05-29 Time 08:53 Rev Time 0.00
Received By jleahy Date 2019-05-29 Time 08:53 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-03-29 Cont ID  
Sent By jleahy Date 2019-03-29 Time 13:15 Rev Time 0.00
Received By jleahy Date 2019-03-29 Time 13:15 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2019-02-12 Cont ID  
Sent By jleahy Date 2019-02-12 Time 15:43 Rev Time 0.00
Received By jleahy Date 2019-02-11 Time 11:50 Sent To  
Notes
2019-02-12 15:46:30FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PAGE 446 T5.03
  
 RISER FOR FIBER OPTIC CABLE IS USING THE STAIRWELL TO
 GET TO THE UPPER FLOORS. STAIRWELL CAN NOT BE USED AS
 AMEANS TO RUN CABLE THROUGH A BUILDING
  
 FIREMAN'S COMMUNICATION SYSTEM PENETRATES THE STAIRWELL
 MORE THAN ONE TIME.
  
  
 PER FBC B1023.5 (6TH EDITION 2017) PENETRATIONS IN THE
 STAIRWELLS ARE FORBIDDEN. PLEASE VERIFY RISER WILL NOT
 BE USING STAIRWELLS AS A RACEWAY.
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-10-31 Cont ID  
Sent By jleahy Date 2018-10-31 Time 13:00 Rev Time 0.00
Received By jleahy Date 2018-10-25 Time 11:14 Sent To  
Notes
2018-10-31 15:55:50FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PAGE E8.01
  
 1) NOTE #12 STATES SEE GROUNDING RISER, COULD NOT FIND
 GROUNDING RISER IN SET.
  
 WHAT MEANS IS GOING TO BE PROVIDED TO HAVE A GEC
 AVAILABLE FOR ALL THE SEPARATELY DERIVED SYSTEMS IN
 BUILDING?
  
  
 2) FEEDER SCHEDULE: ON THE ALUMINUM SCHEDULE
  
 4000A FEEDER ONLY HAS AN AMPACITY OF 3465 AMPERES
 240.4(C)
 3200A FEEDER ONLY HAS AN AMPACITY OF 2692 AMPERES
 240.4(C)
  
 WHERE THE OVERCURRENT DEVICE IS RATED OVER 800 AMPERES,
 THE AMPACITY OF THE CONDUCTORS IT PROTECTS SHALL BE
 EQUAL TO OR GREATER THAN THE
 RATING OF THE OVERCURRENT DEVICE DEFINED IN 240.6.
  
  
 3) FIRE PUMP CONTROLER CIRCUIT IS FED THROUGH LSDP
 WHICH CANNOT HAVE OTHER LOADS THAT ARE NOT FIRE PUMP
 ASSOCIATED LOADS 695.4(B)(3)(A)(3)
  
 DISCONNECTING MEANS SUPPLIED BY ONE OF THE INDIVIDUAL
 SOURCES SPECIFIED IN 695.3(A) CANNOT BE INSTALLED IN
 DISTRIBUTION
 EQUIPMENT THAT SUPPLIES OTHER THAN FIRE PUMP LOADS.
 ?SUFFICIENTLY REMOTE? ALSO CANNOT BE INTERPRETED AS
 PERMITTING THE FIRE PUMP
 DISCONNECTING MEANS TO BE LOCATED IN A SEPARATE
 SWITCHBOARD SECTION OF EQUIPMENT THAT SUPPLIES OTHER
 THAN FIRE PUMP LOADS.
  
  
 4) TRANSFER OF POWER TO FIRE PUMP SHALL TAKE PLACE IN
 PUMP ROOM 695.3(F) NOT IN EMERGENCY ELECTRICAL ROOM AND
 PUMP ROOM.
  
 TRANSFER OF POWER. TRANSFER OF POWER TO THE FIRE PUMP
 CONTROLLER BETWEEN THE INDIVID UAL SOURCE AND ONE
 ALTERNATE SOURCE
 SHALL TAKE PLACE WITHIN THE PUMP ROOM. [20:9.6.4]
  
  
 5) A SINGLE MEANS OF DISCONNECT AND ONE ADDITIONAL
 DISCONNECT WILL BE PERMITTED BUT NOT TWO PLUS A
 TRANSFER SWITCH. 695.4(B)(1)(A,B,C)
  
 A SINGLE DISCONNECT ING MEANS AND ASSOCIATED
 OVERCURRENT PROTECTIVE DEVICE(S) SHALL BE PERMITTED TO
 BE
 INSTALLED BETWEEN THE FIRE PUMP POWER SOURCE(S) AND ONE
 OF THE FOLLOWING: [20:9.1.2]
 (1) A LISTED FIRE PUMP CONTROLLER
 (2) A LISTED FIRE PUMP POWER TRANSFER SWITCH
 (3) A LISTED COMBINATION FIRE PUMP CONTROLLER AND POWER
 TRANSFER SWITCH
  
  
 6) FEED FROM FPL TRANSFORMER TO FIRE PUMP CONTROLER TO
 ENCASED IN A MINIMUM OF 2"
  
 SERVICE CONDUCTORS AND CONDUCTORS SUPPLIED BY ON-SITE
 POWER PRODUCTION FACILITIES SHALL BE PHYSICALLY ROUTED
 OUTSIDE A BUILDING(S) AND SHALL
 BE INSTALLED AS SERVICE-ENTRANCE CONDUCTORS IN
 ACCORDANCE WITH 230.6, 230.9
  
  
 7) LOAD CALCULATION NEEDS TO BE LAYED OUT SO THE I CAN
 UNDERSTAND HOW LOADS WHERE ACHIEVED.
  
 THE CALCULATED LOAD OF A FEEDER OR S ERVICE SHALL NOT
 BE LESS THAN THE SUM OF THE LOADS ON THE BRANCH
 CIRCUITS SUPPLIED, AS DETERMINED BY
 PART II OF THIS ARTICLE, AFTER ANY APPLICABLE DEMAND
 FACTORS PERMITTED BY PART III OR IV OR REQUIRED BY PART
 V HAVE BEEN APPLIED.
 THE AMPACITY OF SERVICE-ENTRANCE CONDUCTORS SHALL NOT
 BE LESS THAN EITHER 230.42(A)(1), (A)(2), OR (A)(3).
  
  
 8) SHOW LOAD CALCULATION FOR 3200 A FEED FROM GENERATOR
 TO 4000A TRANSFER SWITCH
  
 THE CALCULATED LOAD OF A FEEDER OR S ERVICE SHALL NOT
 BE LESS THAN THE SUM OF THE LOADS ON THE BRANCH
 CIRCUITS SUPPLIED, AS DETERMINED BY
 PART II OF THIS ARTICLE, AFTER ANY APPLICABLE DEMAND
 FACTORS PERMITTED BY PART III OR IV OR REQUIRED BY PART
 V HAVE BEEN APPLIED.
  
  
 9) FAULT CURRENT CALCULATION FOR SERVICE MAINS, AND SUB
 PANELS.
  
 THE OVERCURRENT PROTECTIVE DEVICES, THE TOTAL
 IMPEDANCE, THE EQUIPMENT SHORT-CIRCUIT CURRENT RATINGS,
 AND OTHER CHARACTERISTICS
 OF THE CIRCUIT TO BE PROTECTED SHALL BE SELECTED AND
 COORDINATED TO PERMIT THE CIRCUIT PROTECTIVE DEVICES
 USED TO CLEAR A FAULT TO DO
 SO WITHOUT EXTENSIVE DAMAGE TO THE ELECTRICAL EQUIPMENT
 OF THE CIRCUIT. THIS FAULT SHALL BE ASSUMED TO BE
 EITHER BETWEEN TWO OR
 MORE OF THE CIRCUIT CONDUCTORS OR BETWEEN ANY CIRCUIT
 CONDUCTOR AND THE EQUIPMENT GROUNDING CONDUCTOR(S)
 PERMITTED IN 250.118.
 LISTED EQUIPMENT APPLIED IN ACCORDANCE WITH THEIR
 LISTING SHALL BE CONSIDERED TO MEET THE REQUIREMENTS OF
 THIS SECTION.
  
  
 10) FOR CIRCUIT BREAKERS 1200 AMPERES AND OVER ARC
 ENERGY REDUCTION REQUIRED.
  
 WHERE THE HIGHEST CONTINUOUS CURRENT TRIP SETTING FOR
 WHICH THE ACTUAL OVERCURRENT DEVICE INSTALLED IN A
 CIRCUIT BREAKER IS RATED
 OR CAN BE ADJUSTED IS 1200 A OR HIGHER, 240.87(A) AND
 (B) SHALL APPLY.
  
  
 11) ON RISERS ON PAGES E8.02, E8.03 SYMBOL OF A CIRCLE
 AND "M" IN THE MIDDLE AT ALL HIGH VOLTAGE AND LOW
 VOLTAGE PANELS?
  
  
 12) DAS SYSTEM RISER SHOWS SEVERAL PENETRATION OF THE
 STAIRWELL. THIS WILL BE REFERED OVER TO THE BUILDING
 PLANS EXAMINER FOR REVIEW.
  
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2019-02-27 Cont ID  
Sent By rrossano Date 2019-02-27 Time   Rev Time 0.00
Received By rrossano Date 2019-02-27 Time   Sent To I
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2018-11-13 Cont ID  
Sent By mgonzale Date 2018-11-13 Time   Rev Time 1.00
Received By mgonzale Date 2018-11-13 Time   Sent To I
Notes
2018-11-13 15:41:06PERMIT UNDER REVIEW AT ENGINEERING SERVICES.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2019-03-26 Cont ID  
Sent By pleduc Date 2019-03-26 Time   Rev Time 0.00
Received By pleduc Date 2019-03-26 Time 08:54 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-02-20 Cont ID  
Sent By pleduc Date 2019-02-20 Time   Rev Time 0.00
Received By pleduc Date 2019-01-25 Time 10:11 Sent To  
Notes
2019-02-07 16:17:12THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) SHEETS LS 1.06 & 1.09 INDICATE THE TERRACE OCCUPANCY
 LOAD AS BUSINESS; HOWEVER, THESE SPACES ARE ASSEMBLY
 SPACES AND SHOULD REFLECT ASSEMBLY OCCUPANCY LOADS.
  
 PLEASE CORRECT THE CALCULATIONS.
  
  
 2) NO DIMENSIONS ARE PROVIDED WITHIN THE CLEAR SPACES
 IN THESE AREAS TO CONFIRM THE SQ.FT. AND PROVIDE
 ACCURATE OCCUPANCY LOADS CALCULATIONS.
  
 PLEASE PROVIDE THE APPLICABLE DIMENSIONS.
  
  
  
 3) THE FLOOR OCCUPANCY CALCULATIONS OF THE ABOVE MAY
 NEED TO BE REVISED TO RELFECT THE CHANGES.
  
 PLEASE CORRECT AS APPLICABLE.
  
  
 4) PLEASE PROVIDE CLOUDED REVISED DRAWINGS AT AN
 APPLICABLE TIME TO REFLECT THESE CHANGES.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-10-18 Cont ID  
Sent By pleduc Date 2018-10-18 Time   Rev Time 0.00
Received By pleduc Date 2018-10-15 Time 08:46 Sent To  
Notes
2018-10-15 10:26:01THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET LS 1.01 - THERE IS NO INDICATIONS WHETHER THIS
 IS A MIXED OR SEPARATED OCCUPANCY. THERE DOES NOT
 APPEAR TO ANY RATED WALL ASSEMBLIES FOR THE CORRIDORS
 FROM THE RETAIL SPACES.
  
 PLEASE REVIEW AND CORRECT OF JUSTIFY WITH SPECIFIC CODE
 REFERNECES.
  
  
  
 2) SHEET LS 0.01 - THERE IS AN INDICATION OF SMOKE
 CONTROL HOWEVER, THERE ARE NO CLEAR INDICATIONS OF TYPE
 AND NO RATIONAL ANALYSIS SUBMITTED.
  
 PER NFPA 1, CHAPTER 10 , GENERAL SAFETY REQUIREMENTS
  
 10.14.3.4.4 ENGINEERING ANALYSIS AND CALCULATIONS. AN
 ENGINEERING ANALYSIS AND CALCULATIONS SHALL BE PROVIDED
 WITH THE
 FOLLOWING:
 (1) SMOKE PROTECTION CALCULATIONS AS FOLLOWS:
 (A) SMOKE EXHAUST AND FRESH AIR REQUIREMENTS PER NFPA
 92, STANDARD FOR SMOKE CONTROL SYSTEMS
 (B) SMOKE MAINTAINED AT A LEVEL SIX FT ABOVE THE FLOOR
 OF THE
 MEANS OF EGRESS
 (C) PROPOSED TESTING PROTOCOL FOR SMOKE SYSTEM AND
 PASS/FAIL CRITERIA
 (D) CALCULATIONS FOR PERFORMANCE-BASED DESIGN METHODS
 ACCEPTED BY THE AHJ
 (E) SMOKE AND FIRE MODELING
 (F) TIMED EGRESS ANALYSIS
 (G) ASSUMED FLOW RATES AND TRAVEL SPEED
  
 PLEASE REVIEW AND PROVIDE.
  
  
  
 3) LS 0.01 - THERE IS A COMMAND ROMM INDICATED. PLEASE
 ENSURE A GENEREATOR SWITCH AND FIRE SPRINKLER VALVE AND
 WATER FLOW PANEL ARE PROVIDED.
  
 PER NFPA 1, CHAPTER 11, BUILDING SERVICES
  
 11.9 EMERGENCY COMMAND CENTER. WHERE REQUIRED,
 EMERGENCY
 COMMAND CENTERS SHALL COMPLY WITH SECTION 11.9.
  
 11.9.4 THE FOLLOWING SHALL BE PROVIDED IN THE EMERGENCY
 COMMAND
 CENTER:
 (1) THE FIRE DEPARTMENT COMMUNICATION UNIT
 (2) A TELEPHONE FOR FIRE DEPARTMENT USE WITH CONTROLLED
 ACCESS TO THE
 PUBLIC TELEPHONE SYSTEM
 (3) SCHEMATIC BUILDING PLANS INDICATING THE TYPICAL
 FLOOR PLAN AND
 DETAILING THE BUILDING CORE MEANS OF EGRESS, FIRE
 PROTECTION
 SYSTEMS, FIRE-FIGHTING EQUIPMENT, AND FIRE DEPARTMENT
 ACCESS
 (4) WORK TABLE
 (5) IF APPLICABLE, HAZARDOUS MATERIAL MANAGEMENT PLANS
 FOR THE
 BUILDING
 11.9.5 WHERE OTHERWISE REQUIRED, THE FOLLOWING DEVICES
 OR FUNCTIONS
 SHALL BE PROVIDED WITHIN THE EMERGENCY COMMAND CENTER:
 (1) THE EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM UNIT
 (2) FIRE DETECTION AND ALARM SYSTEM ANNUNCIATOR UNIT
 (3) ANNUNCIATOR VISUALLY INDICATING THE LOCATION OF THE
 ELEVATORS AND
 WHETHER THEY ARE OPERATIONAL
 (4) STATUS INDICATORS AND CONTROLS FOR AIR-HANDLING
 SYSTEMS
 (5) CONTROLS FOR UNLOCKING STAIRWAY DOORS
 SIMULTANEOUSLY
 (6) SPRINKLER VALVE AND WATERFLOW DETECTOR DISPLAY
 PANELS
 (7) EMERGENCY AND STANDBY POWER STATUS INDICATORS
 (8) FIRE PUMP STATUS INDICATORS
 (9) GENERATOR SUPERVISION DEVICES AND MANUAL START AND
 TRANSFER
 FEATURES
 (10) PUBLIC ADDRESS SYSTEM, WHERE SPECIFICALLY REQUIRED
 BY OTHER
 SECTIONS OF THIS CODE
 (11) CONTROLS REQUIRED FOR SMOKE CONTROL
  
 AND
  
 PER NFPA 101, CHAPTER 11, SPECIAL STRUCTURES AND HIGH
 RISE BUILDINGS
  
 11.8.6* EMERGENCY COMMAND CENTER.
 11.8.6.1 AN EMERGENCY COMMAND CENTER SHALL BE PROVIDED
 IN A
 LOCATION APPROVED BY THE FIRE DEPARTMENT.
 11.8.6.2 THE EMERGENCY COMMAND CENTER SHALL CONTAIN THE
 FOLLOWING:
 (1) VOICE FIRE ALARM SYSTEM PANELS AND CONTROLS
 (2) FIRE DEPARTMENT TWO-WAY TELEPHONE COMMUNICATION
 SERVICE
 PANELS AND CONTROLS WHERE REQUIRED BY ANOTHER SECTION
 OF THIS
 CODE
 (3) FIRE DETECTION AND FIRE ALARM SYSTEM ANNUNCIATION
 PANELS
 (4) ELEVATOR FLOOR LOCATION AND OPERATION ANNUNCIATORS
 (5) ELEVATOR FIRE RECALL SWITCH IN ACCORDANCE WITH ASME
 A17.1/CSA B44, SAFETY CODE FOR ELEVATORS AND ESCALATORS
 (6) ELEVATOR EMERGENCY POWER SELECTOR SWITCH(ES) WHERE
 PROVIDED
 IN ACCORDANCE WITH ASME A17.1/CSA B44
 (7) SPRINKLER VALVE AND WATERFLOW ANNUNCIATORS
 (8) EMERGENCY GENERATOR STATUS INDICATORS
 (9) CONTROLS FOR ANY AUTOMATIC STAIRWAY DOOR UNLOCKING
 SYSTEM
 (10) FIRE PUMP STATUS INDICATORS
 (11) TELEPHONE FOR FIRE DEPARTMENT USE WITH CONTROLLED
 ACCESS TO THE
 PUBLIC TELEPHONE SYSTEM
 (12) STAIRWAY VIDEO MONITORING EQUIPMENT AS REQUIRED BY
 11.8.8
  
  
 PLEASE REVIEW, ENSURE COMPLIANCE AND PROVIDE AN
 APPLICABLE NOTE OF ACKNOWLEDGEMENT.
  
  
  
 4 A) SHEET LS 1.09 - TWO EXITS ARE INDICATED FROM THE
 OUTSIDE SPACE INTO THE BUSINESS AREA. THESE EXITS DO
 NOT APPEAR TO HAVE THE MINIMUM EXIT SEPARATION
 REQUIRED.
  
 PER NFPA 101, CHAPTER 12 NEW ASSEMBLY OCCUPANCIES
  
 12.2.5 ARRANGEMENT OF MEANS OF EGRESS.
 12.2.5.1 GENERAL.
 12.2.5.1.1 MEANS OF EGRESS SHALL BE ARRANGED IN
 ACCORDANCE WITH
 SECTION 7.5.
  
  
 7.5.1.3 REMOTENESS SHALL BE PROVIDED IN ACCORDANCE WITH
 7.5.1.3.1
 THROUGH 7.5.1.3.7.
 7.5.1.3.1 WHERE MORE THAN ONE EXIT, EXIT ACCESS, OR
 EXIT DISCHARGE IS
 REQUIRED FROM A BUILDING OR PORTION THEREOF, SUCH
 EXITS, EXIT ACCESSES,
 OR EXIT DISCHARGES SHALL BE REMOTELY LOCATED FROM EACH
 OTHER AND BE
 ARRANGED TO MINIMIZE THE POSSIBILITY THAT MORE THAN ONE
 HAS THE
 POTENTIAL TO BE BLOCKED BY ANY ONE FIRE OR OTHER
 EMERGENCY
 CONDITION.
  
 7.5.1.3.2* WHERE TWO EXITS, EXIT ACCESSES, OR EXIT
 DISCHARGES ARE
 REQUIRED, THEY SHALL BE LOCATED AT A DISTANCE FROM ONE
 ANOTHER NOT
 LESS THAN ONE-HALF THE LENGTH OF THE MAXIMUM OVERALL
 DIAGONAL
 DIMENSION OF THE BUILDING OR AREA TO BE SERVED,
 MEASURED IN A
 STRAIGHT LINE BETWEEN THE NEAREST EDGE OF THE EXITS,
 EXIT ACCESSES, OR
 EXIT DISCHARGES, UNLESS OTHERWISE PROVIDED IN 7.5.1.3.3
 THROUGH
 7.5.1.3.5.
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE
 REFERENCES
  
  
  
  
 4 B) SHEET LS 1.09 - TWO EXITS ARE INDICATED FROM THE
 OUTSIDE SPACE INTO THE BUSINESS AREA. THESE EXITS DO
 NOT APPEAR TO HAVE THE MINIMUM EXIT SEPARATION
 REQUIRED.
  
 PER NFPA 101, CHAPTER 12 NEW ASSEMBLY OCCUPANCIES
  
 12.2.5 ARRANGEMENT OF MEANS OF EGRESS.
 12.2.5.1 GENERAL.
 12.2.5.1.1 MEANS OF EGRESS SHALL BE ARRANGED IN
 ACCORDANCE WITH
 SECTION 7.5.
  
  
 7.5.1.3 REMOTENESS SHALL BE PROVIDED IN ACCORDANCE WITH
 7.5.1.3.1
 THROUGH 7.5.1.3.7.
 7.5.1.3.1 WHERE MORE THAN ONE EXIT, EXIT ACCESS, OR
 EXIT DISCHARGE IS
 REQUIRED FROM A BUILDING OR PORTION THEREOF, SUCH
 EXITS, EXIT ACCESSES,
 OR EXIT DISCHARGES SHALL BE REMOTELY LOCATED FROM EACH
 OTHER AND BE
 ARRANGED TO MINIMIZE THE POSSIBILITY THAT MORE THAN ONE
 HAS THE
 POTENTIAL TO BE BLOCKED BY ANY ONE FIRE OR OTHER
 EMERGENCY
 CONDITION.
  
 7.5.1.3.2* WHERE TWO EXITS, EXIT ACCESSES, OR EXIT
 DISCHARGES ARE
 REQUIRED, THEY SHALL BE LOCATED AT A DISTANCE FROM ONE
 ANOTHER NOT
 LESS THAN ONE-HALF THE LENGTH OF THE MAXIMUM OVERALL
 DIAGONAL
 DIMENSION OF THE BUILDING OR AREA TO BE SERVED,
 MEASURED IN A
 STRAIGHT LINE BETWEEN THE NEAREST EDGE OF THE EXITS,
 EXIT ACCESSES, OR
 EXIT DISCHARGES, UNLESS OTHERWISE PROVIDED IN 7.5.1.3.3
 THROUGH
 7.5.1.3.5.
  
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE
 REFERENCES
  
  
  
  
  
 5) SHEET F 1.01 - THERE ARE INDICATIONS OF A FIRE PUMP
 TEST HEADER AND FIRE DEPARTMENT CONNECTION AT THE SAME
 LOCATION.
  
 PLEASE ENSURE THAT THESE ARE NOT ONE PIECE OF EQUIPMENT
 AS THEY ARE TWO DISTINCT PIECES WITH DIFFERENT
 FUNCTIONS.
  
 PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF
 ACKNOWLEDGEMENT.
  
  
  
  
 6) SHEET P 1.01 - THERE DOES NOT APPEAR TO BE ANY CLEAR
 INDICATIONS OF A FLOOR DRAIN IN THE FIRE PUMP ROOM
  
 PER NFPA 20, CHAPTER 4, GENERAL REQUIREMENTS
  
 4.12.7* DRAINAGE.
 4.12.7.1 FLOORS SHALL BE PITCHED FOR ADEQUATE DRAINAGE
 OF ESCAPING
 WATER AWAY FROM CRITICAL EQUIPMENT SUCH AS THE PUMP,
 DRIVER, CONTROLLER, AND SO FORTH.
 4.12.7.2 THE PUMP ROOM OR PUMP HOUSE SHALL BE PROVIDED
 WITH A FLOOR DRAIN THAT WILL DISCHARGE TO A FROST-FREE
 LOCATION.
  
  
  
  
 7) SHEET A 4.01 - THE IS AN INDICATION OF A FUEL TANK
 IN THE FUEL TANK ROOM; HOWEVER, THERE ARE NO DETAILS
 PROVIDED ON THE FUEL TANK.
  
 THIS FUEL TANK PROVIDE EMERGENCY POWER AND SHALL COMPLY
 WITH NFPA
  
 PER NFPA 110
  
 7.9.1.1 ALL FUEL TANKS AND SYSTEMS SHALL BE INSTALLED
 AND MAINTAINED
 IN ACCORDANCE WITH NFPA 30, FLAMMABLE AND COMBUSTIBLE
 LIQUIDS CODE; NFPA 37, STANDARD FOR THE INSTALLATION
 AND USE OF
 STATIONARY COMBUSTION ENGINES AND GAS TURBINES; NFPA
 54, NATIONAL
 FUEL GAS CODE; AND NFPA 58, LIQUEFIED PETROLEUM GAS
 CODE.
 7.9.3.1* GALVANIZED FUEL LINES SHALL NOT BE USED.
 7.9.3.2 APPROVED FLEXIBLE FUEL LINES SHALL BE USED
 BETWEEN THE
 PRIME MOVER AND THE FUEL PIPING.
  
 7.9.11 ALL MANUAL FUEL SYSTEM VALVES SHALL BE OF THE
 INDICATING
 TYPE.
 7.9.12.1 A MINIMUM CLEARANCE OF 0.9 M (36 IN.) SHALL BE
 MAINTAINED ON ALL SIDES.
  
 PLEASE PROVIDE DETAILS.
  
  
  
 8) THERE IS AN INDICATION OF A FUEL TANK WITHIN THE
 GENERATOR ROOM. THERE IS NO INDICATION IF THIS TANK IS
 DOUBLE WALLED OR THERE IS CONTAIMENT.
  
 PER NFPA 30
  
 9.13* CONTAINMENT, DRAINAGE, AND SPILL CONTROL.
 9.13.1 STORAGE AREAS SHALL BE DESIGNED AND OPERATED TO
 PREVENT
 THE DISCHARGE OF LIQUIDS TO PUBLIC WATERWAYS, PUBLIC
 SEWERS,
 OR ADJOINING PROPERTY, UNLESS SUCH DISCHARGE HAS BEEN
 SPECIFICALLY
 APPROVED.
  
 PLEASE PROVIDE SPECIFIC DETAILS FOR SPILL CONTAINMENT.
  
  
 9) SHEET A 4.01 AND M 1.01 - THERE IS AN INDICATION OF
 A GENERATOR AND EXHAUST PIPING, HOWEVER, THERE ARE NO
 DETAILS.
  
 THE INSTALLATION OF THE GENERATOR SHALL BE UNDER
 SEPARATE PERMIT APPLICATION
  
 PER NFPA 110
  
 7.10 EXHAUST SYSTEM.
 7.10.1 THE EXHAUST SYSTEM EQUIPMENT AND INSTALLATION,
 INCLUDING
 PIPING, MUFFLER, AND RELATED ACCESSORIES, SHALL BE IN
 ACCORDANCE WITH NFPA37, STANDARD FOR THE INSTALLATION
 AND USE OF
 STATIONARY COMBUSTION ENGINES AND GAS TURBINES, AND
 OTHER APPLICABLE
 STANDARDS.
 7.10.2 EXHAUST SYSTEM INSTALLATION SHALL BE GASTIGHT TO
 PREVENT
 EXHAUST GAS FUMES FROM ENTERING INHABITED ROOMS OR
 BUILDINGS
 AND TERMINATE IN SUCH A MANNER THAT TOXIC FUMES CANNOT
 REENTER A BUILDING OR STRUCTURE, PARTICULARLY THROUGH
 WINDOWS,
 AIR VENTILATION INLETS, OR THE ENGINE AIR-INTAKE
 SYSTEM.
 7.10.3* EXHAUST PIPING SHALL BE CONNECTED TO THE PRIME
 MOVER
 BY MEANS OF A FLEXIBLE CONNECTOR AND SHALL BE
 INDEPENDENTLY
 SUPPORTED THEREAFTER SO THAT NO DAMAGING WEIGHT OR
 STRESS IS
 APPLIED TO THE ENGINE EXHAUST MANIFOLD OR TURBOCHARGER.
  
 PLEASE PROVIDE SPECIFIC DETAILS AND SPEC SHEETS.
  
  
  
 10) SHEET AE 4.01 - DOORS # 115A, 115C AND 122A
 INDICATION THEIR SWING TO WHAT APPEARS TO BE AGAINST
 THE PATH OF TRAVEL.
  
 PER NFPA 101, CHAPTER 7, MEANS OF EGRESS
  
 7.2.1.4.2 DOOR LEAF SWING DIRECTION. DOOR LEAVES
 REQUIRED TO BE
 OF THE SIDE-HINGED OR PIVOTED-SWINGING TYPE SHALL SWING
 IN THE
 DIRECTION OF EGRESS TRAVEL UNDER ANY OF THE FOLLOWING
 CONDITIONS:
 (1) WHERE SERVING A ROOM OR AREA WITH AN OCCUPANT LOAD
 OF 50 OR
 MORE, EXCEPT UNDER ANY OF THE FOLLOWING CONDITIONS:
 (A) DOOR LEAVES IN HORIZONTAL EXITS SHALL NOT BE
 REQUIRED TO
 SWING IN THE DIRECTION OF EGRESS TRAVEL WHERE PERMITTED
 BY 7.2.4.3.8.1 OR 7.2.4.3.8.2.
 (B) DOOR LEAVES IN SMOKE BARRIERS SHALL NOT BE REQUIRED
 TO
 SWING IN THE DIRECTION OF EGRESS TRAVEL IN EXISTING
 HEALTH
 CARE OCCUPANCIES, AS PROVIDED IN CHAPTER 19.
 (2) WHERE THE DOOR ASSEMBLY IS USED IN AN EXIT
 ENCLOSURE, UNLESS
 THE DOOR OPENING SERVES AN INDIVIDUAL LIVING UNIT THAT
 OPENS
 DIRECTLY INTO AN EXIT ENCLOSURE
 (3) WHERE THE DOOR OPENING SERVES A HIGH HAZARD
 CONTENTS AREA
  
 PLEASE REVIEW THE OCCUPANCY LOAD CALCULATIONS AND
 POTENIAL EGRESS THRU THESE DOORS AND CORRECT OF JUSTIFY
 WITH SPECIFIC DETAILS.
  
  
  
  
  
 11) SHEET LS 1.06 - THERE IS AN OPEN/PUBLIC SPACE WITH
 AN INDICATED OCCUPANCY LOAD OF 100 SQ FT 1 OCC.
  
 THIS IS AN ASSEMBLY SPACE PER THE FFPC WITH AN
 OCCUPANCY LOAD OF 15 SQ FT/PERSON OR 106 PERSONS.
  
 BASED ON THIS NEW OCCUPANCY LOAD THE DOORS/GATES
 LEADING INTO THE GARAGE AREA SHALL SWING IN THE PATH OF
 TRAVEL.
  
 PLEASE REVIEW AND OR JUSTIFY WITH SPECIFIC CODE
 REFERENCES.
  
  
  
  
 12 A) SHEET LS 1.09 - THERE IS AN OPEN/PUBLIC SPACE
 WITH AN INDICATED OCCUPANCY LOAD OF 100 SQ FT 1 OCC. ;
 14 PERSONS
  
 THIS IS AN ASSEMBLY SPACE PER THE FFPC WITH AN
 OCCUPANCY LOAD OF 15 SQ FT/PERSON OR 89 PERSONS.
  
 BASED ON THIS NEW OCCUPANCY LOAD THE DOORS LEADING INTO
 THE OFFICE AREA SHALL SWING IN THE PATH OF TRAVEL IN
 ADDITIONAL OF MEETING THE SEPARATION REQUIRED AS PER #
 4 ABOVE.
  
 PLEASE REVIEW AND OR JUSTIFY WITH SPECIFIC CODE
 REFERENCES.
  
  
  
 12 B) SHEET LS 1.09 - THERE IS AN OPEN/PUBLIC SPACE
 WITH AN INDICATED OCCUPANCY LOAD OF 100 SQ FT 1 OCC. ;
 16 PERSONS
  
 THIS IS AN ASSEMBLY SPACE PER THE FFPC WITH AN
 OCCUPANCY LOAD OF 15 SQ FT/PERSON OR 199 PERSONS.
  
 BASED ON THIS NEW OCCUPANCY LOAD THE DOORS LEADING INTO
 THE OFFICE AREA SHALL SWING IN THE PATH OF TRAVEL IN
 ADDITIONAL OF MEETING THE SEPARATION REQUIRED AS PER #
 4 ABOVE.
  
 PLEASE REVIEW AND OR JUSTIFY WITH SPECIFIC CODE
 REFERENCES.
  
  
  
  
  
  
 13) SHEET FA 1.02 - THERE IS A PULL STATION AT STAIRWAY
 # 3 THAT IS INDICATED MORE THAN 5' FROM THE EXIT DOOR.
  
 THOUGH THIS IS NOT THE SHOP DRAWING IT NEEDS TO BE
 CALLED OUT FOR CORRECTION.
  
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 14) SHEET FA 1.02 - THERE IS NO PULL STATION LOCATED AT
 THE REAR OFFICE EXIT DOOR 201 FROM THE OFFICE AREA.
  
 THOUGH THIS IS NOT THE SHOP DRAWING IT NEEDS TO BE
 CALLED OUT FOR CORRECTION.
  
  
 PLEASE REVIEW AND CORRECT.
  
  
 15) SHEET FA 1.02 - THERE IS A PULL STATION INDICATED
 ON THE ELEVATOR WALL BY STAIRWAY # 5, SHEET AE 4.02
 DOES NOT INDICATE AND EXIT DOOR AT THAT LOCATION.
  
 THERE IS NO EXIT DOOR SHOWN ON THIS PLAN SHEET AT
 STAIRWAY # 5 AS COMPARED TO AE 4.02 WHICH INDICATES A
 COMPLETLY DIFFERENT STAIRWAY DESIGN.
  
 THOUGH THIS IS NOT THE SHOP DRAWING IT NEEDS TO BE
 CALLED OUT FOR CORRECTION.
  
  
 PLEASE REVIEW AND CORRECT
  
  
  
 16) SHEET FA 1.03 - THERE IS A PULL STATION INDICATED
 ON THE ELEVATOR WALL BY STAIRWAY # 5, SHEET AE 4.03
 DOES NOT INDICATE AND EXIT DOOR AT THAT LOCATION.
  
 THOUGH THIS IS NOT THE SHOP DRAWING IT NEEDS TO BE
 CALLED OUT FOR CORRECTION.
  
  
 PLEASE REVIEW AND CORRECT
  
  
  
 17) SHEET FA 1.04 - THERE IS NO PULL STATION LOCATED AT
 THE REAR OFFICE EXIT DOOR 401 FROM THE OFFICE AREA.
  
 THOUGH THIS IS NOT THE SHOP DRAWING IT NEEDS TO BE
 CALLED OUT FOR CORRECTION.
  
  
 PLEASE REVIEW AND CORRECT.
  
  
  
  
 18) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
  
 19) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2020-05-19 Cont ID  
Sent By shill Date 2020-05-19 Time 14:49 Rev Time 0.00
Received By shill Date 2020-05-19 Time 14:49 Sent To  
Notes
2020-05-19 14:50:20GAS REVIEW WAS PASSED BY CCOLE UNDER 20031021 REVISION

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2019-02-25 Cont ID  
Sent By gjohnson Date 2019-02-25 Time 15:44 Rev Time 0.00
Received By gjohnson Date 2019-02-25 Time 15:44 Sent To  
Notes
2019-02-25 15:46:00GAS PLAN REVIEW
 A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE
 REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK.
 PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT
 SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE
 SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1.
  
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL
 GAS SEC. 301.3.
  
 A SEPARATE PERMIT AND PLANS IS REQUIRED FOR THE GAS
 INSTALLATION OR MODIFICATION OF SYSTEM.
  
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2019-06-17 Cont ID  
Sent By shill Date 2019-06-17 Time 05:54 Rev Time 0.00
Received By shill Date 2019-05-01 Time 14:43 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-04-23 Cont ID  
Sent By lmarchan Date 2019-04-23 Time 10:05 Rev Time 0.00
Received By lmarchan Date 2019-03-15 Time 11:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-02-27 Cont ID  
Sent By dbattles Date 2019-02-27 Time 14:13 Rev Time 0.00
Received By dbattles Date 2019-01-22 Time 16:00 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-12-13 Cont ID  
Sent By lmarchan Date 2018-12-13 Time 16:01 Rev Time 0.00
Received By lmarchan Date 2018-09-25 Time 16:19 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2019-08-22 Cont ID  
Sent By dbattles Date 2019-08-22 Time 09:14 Rev Time  
Received By lmarchan Date 2019-03-07 Time 10:24 Sent To  
Notes
2019-08-22 09:01:38RECEUOT 2019-0822-299 - $835,310.68 - PAID
2019-06-14 15:50:07MU-2019-008419
  
2019-03-23 10:22:36REVIEW IN PROGRESS WITH PBC IMPACT OFFICE.
2019-03-07 10:24:363/7/19 - EMAILED IMPACT FEE OFFICE. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2019-02-27 Cont ID  
Sent By dbattles Date 2019-02-27 Time 14:13 Rev Time 0.00
Received By dbattles Date 2019-02-27 Time 14:13 Sent To  
Notes
2019-02-27 14:16:04PLEASE UPLOAD PALM BEACH IMPACT FEE QUESTIONARE IN
 PREPARATION FOR PBC IMPACT FEE REVIEW.
  
 109 FBC[AMENDED] PLANS WILL BE REVIEWED BY THE PBC
 IMPACT FEE OFFICE DIGITALLY VIA PROJECTDOX UPON
 NOTIFICATION BY THIS OFFICE. NOTIFICATION MAY OCCUR
 WHEN PLANS ARE NEAREST FINAL FORM. YOU MAY COORDINATE
 WITH THE IMPACT FEE OFFICE AT (561) 233-5025 OR SIMPLY
 UPLOAD THE MUNICIPAL IMPACT FEE QUESTIONNAIRE FORM TO
 YOUR PROJECT AND NAME THE FILE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE. THE FORM CAN BE FOUND AT: HTTP://DISCOVE
 R.PBCGOV.ORG/PZB/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QU
 ESTIONNAIRE.PDF UPON APPROVAL AND FEE PAYMENT, PLEASE
 UPLOAD THE RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected]

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-12-10 Cont ID  
Sent By jwitmer Date 2018-12-10 Time 13:38 Rev Time 0.00
Received By jwitmer Date 2018-11-26 Time 10:54 Sent To  
Notes
2018-12-10 13:38:26IMPACT FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.
 ONE SET OF PLANS WILL HAVE TO BE TAKEN (BY THE
 CONTRACTOR OR REPRESENTATIVE) TO THE PALM BEACH COUNTY
 IMPACT FEE OFFICE LOCATED AT 2300 N. JOG RD. ROOMS
 2W01-2W14 WEST PALM BEACH, FL. THE ACTUAL PERMIT SET OF
 PLANS MUST BE STAMPED BY THAT OFFICE, AND A COPY OF THE
 PAID RECEIPT ATTACHED TO THE PERMIT APPLICATION. PLEASE
 CALL (561)233-5025 FOR MORE INFORMATION.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2019-05-13 Cont ID  
Sent By ccole Date 2019-05-13 Time 10:36 Rev Time 0.00
Received By ccole Date 2019-05-10 Time 15:38 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2019-04-01 Cont ID  
Sent By ccole Date 2019-04-01 Time 12:37 Rev Time 0.00
Received By ccole Date 2019-03-29 Time 10:05 Sent To  
Notes
2019-04-01 12:37:383RD REVIEW FBC-2017 MECHANICAL
 PERMIT #18090469
 360 S. ROSEMARY
 4/1/19
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 1) THE REQUEST BY TLC ENGINEERING TO ADD THE FOLLOWING
 ITEMS TO THE DEFERRED SUBMITTAL IS ACCEPTED:
 A) AC COOLING AND HEATING CALCULATIONS.
 B) MINIMUM VENTILATION CALCULATIONS FOR ALL ROOMS AND
 SPACES.
 C) COMMISSIONING PLAN: THE PLAN IS THE FIRST STEP IN
 THE PROCESS WHICH CULMINATES WITH SUBMITTAL OF A FINAL
 COMMISSIONING REPORT.
  
 2) REVISED M1.01 PLAN ERRORS AND OMISSIONS:
 A) KEYNOTE #3 IS BEING USED TO INDICATE BOTH EXHAUST AT
 THE GENERATOR ROOM AND AIR INTAKE OPENING FOR THE LOBBY
 AND CORE ROOMS AND SPACES. THE REQUESTED DAMPER AT THE
 INLET NOT SHOWN- SECTION C403.2.4.3 FBC EC.
 B) AH-DX-1-1 AND AH-DX-1-2 NOT IDENTIFIED- SECTION
 107.2.1 WPB.
 C) AH-DX-1-7 IN THE POWER ROOM NOT SHOWN- SECTION
 107.2.1 WPB.
 D) NOTE #5 INDICATES A FIRE-RATED ENCLOSURE FOR THE
 TANK ROOM MAKE UP AIR DUCT WHICH IS NOT REQUIRED,
 HOWEVER FIRE DAMPERS ARE REQUIRED AT THE DUCT
 PENETRATIONS OF FIRE-RATED WALLS- SECTION 607.5.2 FBC
 M.
 E) THE EXHAUST DUCT RUN FROM THE TANK ROOM TO THE
 EXTERIOR OF THE BUILDING IS NOT SHOWN, AND NO DUCT
 SPECIFICATIONS HAVE BEEN PROVIDED- TYPE AND SIZE OF
 DUCT, TERMINATION LOCATION AND CLEARANCES ETC- SECTION
 510 FBC M.
 F) CONSTRUCTION DETAILS FOR THE FIRE-RATED EXHAUST DUCT
 ENCLOSURE NOT PROVIDED. THE RESPONSE NARRATIVE FROM TLC
 IS CALLING THIS OUT AS AN "INTERSTITIAL WALL". NO NOTES
 ON THE PLAN PROVIDED- SECTION 713.2 FBC B.
 G) THE LETTER DAIKIN CERTIFYING THE INSTALLATIONS OF
 THE OUTDOOR CONDENSERS IN THE ENCLOSED GARAGES IS NOT
 ACCEPTED: 1) IT IS INDICATING THE UNITS ARE TO BE
 INSTALLED IN AN "OPEN GARAGE" AND NOT AN ENCLOSED
 GARAGE. 2) THE LETTER IS FROM BECAUSE A SALES MANAGER,
 AND ALTERNATE DESIGNS AND METHODS MUST BE SUBMITTED BY
 A LICENSED DESIGN PROFESSIONAL. THE MANUFACTURER'S
 TECHNICAL DEPARTMENT CAN PROVIDE INSTALLATION DETAILS
 FOR INDOOR INSTALLATIONS THAT WOULD BE ACCEPTABLE IF
 THE DETAILS BEAR A SHOP DRAWING STAMP OF APPROVAL BY
 THE ENGINEER OF RECORD FOR THE PROJECT. PLEASE NOTE
 THAT THE LETTER MUST ADDRESS ALL THE CONDENSERS ON ALL
 FLOORS THAT ARE BEING INSTALLED IN THE ENCLOSED
 GARAGES- SECTION 304.1 FBC M.
 H) RETURN AIR MISSING FROM THE ENGINEERING ROOM-
 SECTION 601.6 FBC M.
  
 3) REVISED M1.02 PLAN ERRORS AND OMISSIONS:
 A) NO O/A PRESSURIZATION PROVIDED FOR THE FIRE RESCUE
 ROOM- SECTION 404.3 FBC M.
  
 4) REVISED M1.03 PLAN ERRORS AND OMISSIONS:
 A) NO O/A PRESSURIZATION PROVIDED FOR THE FIRE RESCUE
 ROOM- SECTION 404.3 FBC M.
 B) THE PLAN APPEARS TO SHOW A 4" ROUND DUCT SUPPLYING
 660 CFMS OF CONDITIONED SUPPLY AIR TO THE FUTURE
 OFFICE, HOWEVER THE AIRFLOW ARROW SHOWN BY THE 12X10
 OPENING IS IS MOST LIKELY REVERSED. I'M ASSUMING THIS
 IS SUPPOSED TO INDICATE THE O/A SUPPLY. PLEASE CORRECT
 AND PROVIDE NOTES TO CLARIFY- SECTION 107.2.1 WPB.
 C) NO TEXT HAS BEEN PROVIDED AT KEYED NOTE #6.
  
 5) REVISED M1.04:
 A) NO O/A PRESSURIZATION PROVIDED FOR THE FIRE RESCUE
 ROOM- SECTION 404.3 FBC M.
 B) IT APPEARS THE O/A SUPPLY DUCT LAYOUT IS INCOMPLETE.
 NO INLET LOCATION IS SHOWN, NO NOTES- SECTION 107.2.1
 WPB.
  
 6) REVISED M1.05:
 A) NO O/A PRESSURIZATION PROVIDED FOR THE FIRE RESCUE
 ROOM- SECTION 404.3 FBC M.
 B) SEE COMMENT #4B ABOVE FOR SIMILAR DEFICIENCY.
  
 7) REVISED M1.06:
 A) NO O/A PRESSURIZATION PROVIDED FOR THE FIRE RESCUE
 ROOM- SECTION 404.3 FBC M.
 B) NO TEXT PROVIDED FOR NOTES #4 & 5- SECTION 107.2.1
 WPB.
  
 8) REVISED M1.07:
 A) NO O/A PRESSURIZATION PROVIDED FOR THE FIRE RESCUE
 ROOM- SECTION 404.3 FBC M.
 B) NO TEXT PROVIDED FOR NOTES #4 & 5- SECTION 107.2.1
 WPB.
  
 9) REVISED M1.08:
 A) NO O/A PRESSURIZATION PROVIDED FOR THE FIRE RESCUE
 ROOM- SECTION 404.3 FBC M.
 B) NO TEXT PROVIDED FOR NOTES #4 & 5- SECTION 107.2.1
 WPB.
  
 10) M1.09: PLACE NOTES ON THE PLAN TO SHOW THE
 LOCATIONS OF THE O/A, THE TOILET EXHAUST, AND THE SMOKE
 EXHAUST SMOKE SHAFTS-
 A) PROVIDE MOTORIZED FIRE/SMOKE DAMPERS AT THE EXHAUST
 AND AIR INLET OPENINGS AT THE SHAFTS- SECTION 607.5.5
 FBC M.
  
 PLEASE NOTE THE FOLLOWING:
 1) SEPARATE PERMITS ARE REQUIRED FOR THE FUTURE
 RESTAURANT AND OFFICES, KITCHEN EXHAUST HOODS AND FIRE
 SUPPRESSION SYSTEM, WALK IN COOLERS AND FREEZERS.
 2) DEFERRED SUBMITTALS
 REQUIRED SUBMITTALS LISTED BELOW SHALL HAVE SHOP
 DRAWING STAMPS BY THE EOR AND BE IN THE FIELD AT TIME
 OF INSPECTION.
 1) SMOKE CONTROL FANS INCLUDING SMOKE EXHAUST FANS, AND
 STAIRWELL AND ELEVATOR PRESSURIZATION FANS.
 2) FIRE DAMPERS AND FIRE/SMOKE DAMPERS.
 3) MOTORIZED AND BAROMETRIC DAMPERS
 4) DUCT SMOKE DETECTORS
 5) LOUVERS FOR EXHAUST AND OUTSIDE AIR INTAKES
 INCLUDING MANUFACTURER'S SPECIFICATIONS AND FL. PRODUCT
 APPROVALS AND/OR MIAMI-DADE NOA'S
 6) AC STAND NOA'S OR FL. PRODUCT APPROVALS
 7) C0, N02, & CO2 SENSORS, AND REFRIGERANT LEAK
 DETECTORS.
 8) COOLING TOWERS
 9) FACTORY BUILT DUCTWORK
 10) DUCT FIRE WRAPPING
 11) CLOTHES DRYERS
 12) COOKING APPLIANCES
 13) TEST AND BALANCE REPORTS
 14) SMOKE CONTROL TEST REPORTS.
  
 SUBMITTALS TO BE PROVIDED TO THE BUILDING DEPARTMENT
 FOR REVIEW.
 1) SIGNED AND SEALED STRUCTURAL ENGINEERING FOR
 INSTALLATION OF ALL EXTERIOR MECHANICAL EQUIPMENT AND
 APPLIANCES. ALTERNATELY, SIGNED AND SEALED, OR
 DELEGATED ENGINEERING MAY BE AVAILABLE ONSITE AT THE
 TIME OF INSPECTION. PLEASE NOTE THAT DELEGATED
 ENGINEERING SHALL BEAR THE SHOP DRAWING STAMP OF THE
 STRUCTURAL ENGINEER RECORD.
 2) GENERATORS AND FUEL TANKS AND ALL ASSOCIATED
 EQUIPMENT, VENT FLUES, AND FUEL OIL PIPING.
 3) BOILERS AND WATER HEATERS INCLUDING COMBUSTION AIR
 DUCTS AND VENT FLUES.
 4) COMMISSIONING REPORTS
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2019-02-25 Cont ID  
Sent By ccole Date 2019-02-25 Time 15:41 Rev Time 0.00
Received By ccole Date 2019-02-20 Time 09:48 Sent To  
Notes
2019-02-25 15:43:112ND REVIEW FBC-2017 MECHANICAL
 PERMIT #18090469
 360 S. ROSEMARY
 2/22/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED
  
 THIS 2ND MECHANICAL REVIEW WILL REFERENCE COMMENTS FROM
 THE 1ST REVIEW DATED 11/19/18
  
 1A) OK
  
 1B) REQUESTED AC CALCULATIONS NOT SUBMITTED.
  
 1C) ENERGY CALCULATIONS: A) COOLING TOWER COMPLIANCE
 DATA MISSING. B) MANY OF THE DX SYSTEMS SHOWN IN THE
 SCHEDULE ON SHEET M8.02 MISSING. C) LOBBY SYSTEMS SHOWN
 HAVE INCORRECT CAPACITIES AND EER THAT DO NOT MATCH THE
 SCHEDULE. D) THE RETAIL AND OFFICE 2-5 SYSTEMS INCLUDED
 IN THE CALCS ARE NOT SHOWN ON THE PLANS.
  
 2) OK- DEFERRED SUBMITTALS WILL BE ACCEPTED.
  
 3A) COMMENT STILL EXISTS: CO REQUIREMENT- PLEASE
 ACKNOWLEDGE A COMMISSIONING REPORT WILL BE PROVIDED.
  
 3B) COMMENT STILL EXISTS: CO REQUIREMENT- PLEASE
 ACKNOWLEDGE A SMOKE CONTROL COMMISSIONING REPORT WILL
 BE PROVIDED.
  
 4) COMMENT STILL EXISTS: PLEASE ACKNOWLEDGE SEPARATE
 PLANS AND PERMITS ARE REQUIRED FOR THE KITCHEN EXHAUST
 HOODS, FIRE SUPPRESSION SYSTEMS, AND WALK-IN COOLERS.
  
 5) COMMENT STILL EXISTS: ACCORDING TO THE RESPONSE
 NARRATIVE FROM TLC ENGINEERING, VENTILATION
 CALCULATIONS INCLUDING THE REQUIRED OUTSIDE AIR AND
 EXHAUST HAVE BEEN PLACED ON SHEET M8.03, HOWEVER ALL
 THE PRINT ON THE PLAN SHEET IS TOO FAINT TO READ EXCEPT
 FOR THE PARKING GARAGE CALCULATION SCHEDULE.
  
 7) COMMENT STILL EXISTS (SHEET M0.1): VENTILATION AIR
 NOT PROVIDED TO LOBBY 110, ELEV. LOBBY 110A, AND FIRE
 COMM. 111. THE RESUBMITTED LAYOUT PLAN DOES SHOW CFMS
 AT DIFFUSER AND RETURN AND EXHAUST GRILL LOCATIONS, AND
 AS PREVIOUSLY NOTED NO VENTILATION CALCULATIONS HAVE
 BEEN PROVIDED FOR THE MAIN CORE ROOMS AND SPACES. A)
 THE NEW OUTSIDE AIR DUCT AND EXHAUST OPENINGS NEED TO
 BE PROTECTED WITH LOUVERS THAT COMPLY WITH THE AMCA
 STANDARD 550- SECTIONS 401.5 & 501.3.2 FBC M. PLEASE
 PROVIDE SUBMITTALS INCLUDING MANUFACTURER'S PRODUCT
 SPEC SHEETS, AND FL. PRODUCT APPROVALS AND/OR
 MIAMI-DADE NOA'S FOR THE LOUVERS (MAY BE DEFERRED).
  
 8) COMMENT STILL EXISTS (M0.1): EXHAUST VENTILATION
 CALCULATIONS NOT PROVIDED WITH THE EXCEPTION OF THE
 PARKING GARAGE/LOADING DOCK AREA. PLEASE PROVIDE THE
 CONTROL SEQUENCE FOR THE SMOKE EXHAUST SYSTEM IN THE
 GARAGE/LOADING AREA, AND A SUBMITTAL FOR THE SENSORS-
 SECTION 404.2 FBC M. A) THE PLAN INDICATES EF-1-1 AND
 EF-1-2 DISCHARGING INTO THE ENCLOSED GARAGE WHICH IS
 PROHIBITED PER SECTION 501.3 FBC M.
  
 9) OK
  
 10) COMMENT STILL PARTIALLY EXISTS (M0.1): THE RESPONSE
 NARRATIVE FROM TLC INDICATES A MOTORIZED DAMPER TO BE
 INSTALLED AT THE RETAIL O/A INTAKE OPENING, HOWEVER
 NOTE #5 SPECIFIES A BACKDRAFT DAMPER.
  
 11) COMMENT HAS BEEN PARTIALLY ADDRESSED, HOWEVER THE
 DESIGN HAS THESE DEFICIENCIES (M0.1): A) A FIRE DAMPER
 CANNOT BE INSTALLED IN THE HAZARDOUS EXHAUST DUCT
 OPENING FOR THE TANK ROOM- SECTION 510..6.7 FBC M, AND
 THE EXHAUST DUCT SHALL BE ENCLOSED IN FIRE-RESISTANT
 RATED CONSTRUCTION FROM THE POINT OF PENETRATION TO THE
 OUTLET TERMINAL. B) MINIMUM 10' CLEARANCE REQUIRED FROM
 THE TANK ROOM EXHAUST DUCT OUTLET TO THE VENTILATION
 INTAKE OPENING FOR THE GENERATOR ROOM.
  
 12) OK
  
 13) OK- SMOKE CONTROL COMMISSIONING REPORT REQUIRED.
  
 14) COMMENT STILL EXISTS (M0.1): THE CONDENSING UNITS
 SHALL BE INSTALLED OUTDOORS IN ACCORDANCE WITH THEIR
 LISTING. INSTALLING THESE UNITS IN AN ENCLOSED SPACE
 WILL REQUIRE A LETTER FROM THE MANUFACTURER TO CERTIFY
 THE ALTERNATIVE INSTALLATION METHOD.
  
 15) COMMENT STILL EXISTS (M0.1): NO CONTROL SEQUENCE
 PROVIDED FOR THE EXHAUST SYSTEM IN THE ENCLOSED
 GARAGE/LOADING AREA.
  
 16) COMMENTS 16A, B, C, D, & E STILL EXIST (M0.1): FUEL
 AND TANK VENT PIPING NOW SHOWN ON PLUMBING PLANS. ALL
 OTHER COMMENTS NOT ADDRESSED INCLUDING THE SUBMITTAL OF
 THE GENERATOR AND FUEL TANK SPECS. PLEASE NOTE THAT THE
 GENERATOR SHALL BE CLASSIFIED AS LEVEL 1- SEE SECTION
 4.4.1 NFPA 110. THE GENERATOR SHALL ALSO BE UL 2200
 LISTED AND LABELED, AND IN COMPLIANCE WITH NFPA 37-
 SECTION 915.1 FBC M. REFER TO NFPA 30 FOR REQUIRED
 LISTING AND LABELING OF THE FUEL TANK. A) INDICATE THE
 EPSS STANDBY LOADS AND EMERGENCY LOADS AS OUTLINED IN
 SECTIONS 403.4.8.3 AND 403.4.8.4 FBC B. B) REFER TO
 SECTIONS 4.2 AND 4.3, AND TABLES 4.1 (A) AND 4.1(B)
 NFPA 110 AND INDICATE THE CLASSIFICATION AND TYPE OF
 EPSS SYSTEM TO BE INSTALLED.
  
 17) COMMENT STILL EXISTS (M0.1 & M2.04): MINIMUM 10?
 CLEARANCE REQUIRED FROM THE TANK ROOM EXHAUST TO THE
 GENERATOR INTAKE LOUVER- SECTION 501.3.1 FBC M.
  
 18) COMMENT STILL EXISTS (M0.1): NO CLEARANCE HEIGHT
 FROM GRADE PROVIDED- 10? REQUIRED PER SECTION 501.3.1
 FBC M.
  
 19) OK
  
 20) OK- SMOKE CONTROL COMMISSIONING REPORT REQUIRED.
  
 21) COMMENT STILL EXISTS (M0.1): REQUESTED SMOKE PURGE
 CALCULATIONS NOT PROVIDED. THE SMOKE ANALYSIS PROVIDES
 ONLY THE REQUIREMENT OF AN EXHAUST AIR CHANGE EVERY 15
 MINUTES FOR THE AREA INVOLVED. HOW WERE THE FANS SIZED
 TO MEET THAT REQUIREMENT?
  
 22) COMMENT STILL EXISTS (M1.02, 1.03, 1.04, 1.05,
 1.06, 1.07, 1.08): A) NO EXHAUST CALCULATIONS PROVIDED.
 B) NO MAKEUP AIR PROVIDED FOR THE EXHAUST SYSTEMS. C)
 THE LOCATIONS OF THE EXHAUST OUTLETS DO NOT APPEAR TO
 BE LOCATED IN THE AREA OF THE HEAVIEST CONCENTRATIONS
 OF CONTAMINANTS. ADDITIONAL EXHAUST OUTLETS OR
 CIRCULATION FANS MAY HAVE TO BE PROVIDED- SECTION
 502.1.1 FBC M. D) THERE IS A NOTE ON SHEET M1.02 THAT
 STATES "IF GARAGE IS ENCLOSED, DESIGN DOESN?T WORK"
 PLEASE REMOVE OR CORRECT THE NOTE. E) M1.08: PLEASE
 CLARIFY THE NEED FOR THE DUCTS TO EXTEND BELOW THE SLAB
 AS IS NOTED ON THE PLAN.
  
 23) OK
  
 24) COMMENT STILL EXISTS ((M1.02, 1.03, 1.04, 1.05,
 1.06, 1.07, 1.08): A) NO VENTILATION AIR PROVIDED TO
 THE ELEVATOR AND GARAGE LOBBIES. B) THE EXHAUST FROM
 EF'S -2-2, 3-2, 4-2, 5-2, 6-2, 7-2, 8-2 SHALL DISCHARGE
 TO THE OUTDOORS- SECTION 501.3 FBC M.
  
 25) OK- FUTURE OFFICE SPACES UNDER SEPARATE PERMIT.
  
 26) OK
  
 27) OK
  
 28) COMMENT STILL EXISTS (M2.03 & M.401): PLEASE
 COMPLY.
  
 29) COMMENT STILL PARTIALLY EXISTS (M6.01): THE RISER
 DRAWING FOR STAIR #2 SHOWS 6 INJECTION POINTS AT 3920
 CFMS EACH, HOWEVER THE FAN HAS A TOTAL CAPACITY OF ONLY
 7920 CFMS. PLEASE SEE PAGE 1 OF THE SMOKE ANALYSIS
 WHICH INDICATES 1320 CFMS AT EACH INJECTION POINT.
  
 30 & 31) ACKNOWLEDGED THAT THE REFRIGERANT RISER AND
 THE WIND LOAD ENGINEERING WILL BE DEFERRED SUBMITTALS.
 PLEASE PROVIDE A MASTER LIST OF ALL DEFERRED SUBMITTALS
 ON THE PLANS OR AS A SEPARATELY UPLOADED DOCUMENT.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  
  
  
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-11-19 Cont ID  
Sent By ccole Date 2018-11-19 Time 10:12 Rev Time 0.00
Received By ccole Date 2018-11-13 Time 09:59 Sent To  
Notes
2018-11-19 10:19:321ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18090469
 360 S. ROSEMARY
 11/19/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 THE MECHANICAL PLANS HAVE FAILED FOR THE DEFICIENCIES
 AND OMISSIONS LISTED BELOW. PLEASE REVIEW ALL COMMENTS,
 INCLUDING THOSE LISTED FOR ADVISORY PURPOSES, AND
 RESUBMIT CORRECTED PLANS AND REQUIRED DOCUMENTS. WHEN
 RESUBMITTING, PLEASE PROVIDE A RESPONSE LETTER
 ADDRESSING EACH ITEM ALONG WITH THE CITY RE-SUBMITTAL
 FORM.
 PRIOR TO MECHANICAL PERMIT ISSUANCE, THE GENERAL
 CONTRACTOR AND MECHANICAL SUB-CONTRACTOR FOR THE
 PROJECT ARE REQUESTED TO ATTEND A MEETING AT THE WPB
 BUILDING DEPARTMENT WITH THE STAFF- CHIEF MECHANICAL
 INSPECTOR, PLANS EXAMINER, AND OTHERS- TO DISCUSS
 TIMELINES AND GUIDELINES FOR INSPECTIONS AND THE
 DOCUMENT SUBMITTAL PROCESS . FURTHER INFORMATION WILL
 FOLLOW ONCE ALL PLANS ARE APPROVED.
  
 1) THE FOLLOWING LIST OF DOCUMENTS WERE NOT SUBMITTED
 BUT ARE REQUIRED IN ORDER TO PERFORM A COMPLETE
 MECHANICAL REVIEW FOR THE PROJECT.
  
 A) SMOKE CONTROL RATIONAL ANALYSIS- SECTION 513.4 FBC
 M: A RATIONAL ANALYSIS SUPPORTING THE TYPES OF SMOKE
 CONTROL SYSTEMS TO BE EMPLOYED, THEIR METHODS OF
 OPERATION, THE SYSTEMS SUPPORTING THEM AND THE METHODS
 OF CONSTRUCTION TO BE UTILIZED SHALL ACCOMPANY THE
 SUBMITTED CONSTRUCTION DOCUMENTS AND SHALL INCLUDE, BUT
 NOT BE LIMITED TO, THE ITEMS INDICATED IN SECTIONS
 513.4.1 THROUGH 513.4.7.
  
 B) AC COOLING AND HEATING CALCULATIONS- SECTION
 C403.2.1 FBC EC: DESIGN LOADS ASSOCIATED WITH HEATING,
 VENTILATING AND AIR CONDITIONING OF THE BUILDING SHALL
 BE DETERMINED IN ACCORDANCE WITH ANSI/ASHRAE/ACCA
 STANDARD 183 OR ACCA MANUAL N OR BY AN APPROVED
 EQUIVALENT COMPUTATIONAL PROCEDURE USING THE DESIGN
 PARAMETERS SPECIFIED IN CHAPTER 3. HEATING AND COOLING
 LOADS SHALL BE ADJUSTED TO ACCOUNT FOR LOAD REDUCTIONS
 THAT ARE ACHIEVED WHERE ENERGY RECOVERY SYSTEMS ARE
 UTILIZED IN THE HVAC SYSTEM IN ACCORDANCE WITH THE
 ASHRAE HVAC SYSTEMS AND EQUIPMENT HAND-BOOK BY AN
 APPROVED EQUIVALENT COMPUTATIONAL PROCEDURE. DESIGN
 LOADS SHALL BE ATTACHED TO THE CODE COMPLIANCE FORM
 SUBMITTED TO THE BUILDING DEPARTMENT WHEN THE BUILDING
 IS PERMITTED OR, IN THE EVENT THE MECHANICAL PERMIT IS
 OBTAINED AT A LATER TIME, THE SIZING CALCULATION SHALL
 BE SUBMITTED WITH THE APPLICATION FOR THE MECHANICAL
 PERMIT.
  
 C) ENERGY EFFICIENCY COMPLIANCE REPORT- SECTION C401.2
 FBC EC.
 COMMERCIAL BUILDINGS SHALL COMPLY WITH ONE OF THE
 FOLLOWING:
 1. THE REQUIREMENTS OF ANSI/ASHRAE/IESNA 90.1,
 EXCLUDING SECTION 9.4.1.1(G) OF THE STANDARD.
 2. THE REQUIREMENTS OF SECTIONS C402 THROUGH C405. IN
 ADDITION, COMMERCIAL BUILDINGS SHALL COMPLY WITH
 SECTION C406 AND TENANT SPACES SHALL COMPLY WITH
 SECTION C406.1.1.
 3. THE REQUIREMENTS OF SECTIONS C402.5, C403.2, C404,
 C405.2, C405.3, C405.5, C405.6 AND C407. THE BUILDING
 ENERGY COST SHALL 'E EQUAL TO OR LESS THAN 85 PERCENT
 OF THE STANDARD REFERENCE DESIGN BUILDING.
 PLEASE REVIEW SECTION C101.5.1 FBC EC: THE FLORIDA
 BUILDING COMMISSION SHALL APPROVE SPECIFIC COMPUTER
 SOFTWARE. THE CODE OFFICIAL SHALL BE PERMITTED TO
 APPROVE WORKSHEETS, COMPLIANCE MANUALS AND OTHER
 SIMILAR MATERIALS THAT MEET THE INTENT OF THIS CODE.
  
 2) PRODUCT AND ENGINEERING SUBMITTAL DOCUMENTS REQUIRED
 TO PERFORM A COMPLETE MECHANICAL PLAN REVIEW, AND TO
 PERFORM COMPLETE INSPECTIONS ON THE PROJECT.
  
 A) SMOKE CONTROL FANS, DUCTS, FIRE/SMOKE DAMPERS.
  
 B) FIRE DAMPERS
  
 C) MOTORIZED AND BAROMETRIC DAMPERS
  
 D) DUCT SMOKE DETECTORS
  
 E) LOUVERS FOR EXHAUST AND OUTSIDE AIR INTAKES
 INCLUDING MANUFACTURER'S SPECIFICATIONS AND FL. PRODUCT
 APPROVALS AND/OR MIAMI-DADE NOA'S
  
 F) C0, N02, & CO2 SENSORS
  
 G) COOLING TOWERS
  
 H) GENERATOR
  
 I) ACCESS PANELS
  
 J) DUCT FIRE WRAPPING
  
 K) FIRESTOPPING AND FIRE CAULKING
  
 L) CONDENSER WATER PIPING AND PIPE INSULATION.
  
 M) WIND LOAD ENGINEERING FOR THE ROOFTOP MECHANICAL
 EQUIPMENT INCLUDING THE COOLING TOWER, OA UNIT,
 PRESSURIZATION FANS AND CURBS, CONDENSER STANDS AND
 BRACKETS, DUCTS AND DUCT SUPPORTS, HEAT EXCHANGERS,
 PUMPS AND WATER PIPING ETC. PLEASE INCLUDE FL. PRODUCT
 APPROVALS AND/OR MIAMI-DADE NOA'S FOR THE CONDENSER
 STANDS AND MOUNTING BRACKETS.
 PLEASE NOTE: ALL SUBMITTALS AND SHOP DRAWINGS SHALL
 BEAR THE APPROVAL STAMP AND SIGNATURE OF THE DESIGN
 PROFESSIONAL OF RECORD. ALL REQUIRED SUBMITTALS MAY BE
 DEFERRED IN ACCORDANCE WITH SECTION 107.3.4.1 WPB. IT
 WILL BE HELPFUL TO UPLOAD A MASTER LIST OF DEFERRED
 SUBMITTALS IN DOCUMENT FORM, OR IN THE FORM OF NOTES ON
 THE MECHANICAL PLANS.
  
 DEFERRED SUBMITTALS: FOR THE PURPOSES OF THIS SECTION,
 DEFERRED SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF
 THE DESIGN THAT ARE NOT SUBMITTED AT THE TIME OF THE
 APPLICATION AND THAT ARE TO BE SUBMITTED TO THE
 BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. DEFERRAL
 OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF
 THE BUILDING OFFICIAL. THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE
 DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS FOR
 REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE
  
 3) SUBMITTAL DOCUMENTS REQUIRED FOR FINAL MECHANICAL
 PLAN REVIEW AND INSPECTION APPROVALS, AND CO OF THE
 BUILDING.
  
 A) COMMISSIONING REPORT- COMMISSIONING OF THE
 MECHANICAL SYSTEMS, SERVICE WATER HEATING SYSTEMS, AND
 ELECTRICAL POWER AND LIGHTING SYSTEMS IS REQUIRED PER
 SECTION C408.2 FBC-17 ENERGY CONSERVATION.
 PLEASE NOTE THE FOLLOWING REQUIREMENTS LISTED BELOW.
  
 C408.2. MECHANICAL SYSTEMS AND SERVICE WATER-HEATING
 SYSTEMS COMMISSIONING AND COMPLETION REQUIREMENTS.
 PRIOR TO THE FINAL MECHANICAL AND PLUMBING INSPECTIONS,
 THE LICENSED DESIGN PROFESSIONAL, ELECTRICAL ENGINEER,
 MECHANICAL ENGINEER OR APPROVED AGENCY SHALL PROVIDE
 EVIDENCE OF MECHANICAL SYSTEMS COMMISSIONING AND
 COMPLETION IN ACCORDANCE WITH THE PROVISIONS OF THIS
 SECTION.
 CONSTRUCTION DOCUMENT NOTES SHALL CLEARLY INDICATE
 PROVISIONS FOR COMMISSIONING AND COMPLETION
 REQUIREMENTS IN ACCORDANCE WITH THIS SECTION AND ARE
 PERMITTED TO REFER TO SPECIFICATIONS FOR FURTHER
 REQUIREMENTS. COPIES OF ALL DOCUMENTATION SHALL BE
 GIVEN TO THE OWNER OR OWNER?S AUTHORIZED AGENT AND MADE
 AVAILABLE TO THE CODE OFFICIAL UPON REQUEST IN
 ACCORDANCE WITH SECTIONS C408.2.4 AND C408.2.5.
  
 C408.2.1. COMMISSIONING PLAN.
 A COMMISSIONING PLAN SHALL BE DEVELOPED BY A LICENSED
 DESIGN PROFESSIONAL, ELECTRICAL ENGINEER, MECHANICAL
 ENGINEER OR APPROVED AGENCY AND SHALL INCLUDE THE
 FOLLOWING ITEMS:
 1. A NARRATIVE DESCRIPTION OF THE ACTIVITIES THAT WILL
 BE ACCOMPLISHED DURING EACH PHASE OF COMMISSIONING,
 INCLUDING THE PERSONNEL INTENDED TO ACCOMPLISH EACH OF
 THE ACTIVITIES.
 2. A LISTING OF THE SPECIFIC EQUIPMENT, APPLIANCES OR
 SYSTEMS TO BE TESTED AND A DESCRIPTION OF THE TESTS TO
 BE PERFORMED.
 3. FUNCTIONS TO BE TESTED INCLUDING, BUT NOT LIMITED
 TO, CALIBRATIONS AND ECONOMIZER CONTROLS.
 4. CONDITIONS UNDER WHICH THE TEST WILL BE PERFORMED.
 TESTING SHALL AFFIRM WINTER AND SUMMER DESIGN
 CONDITIONS AND FULL OUTSIDE AIR CONDITIONS.
 5. MEASURABLE CRITERIA FOR PERFORMANCE'
  
 B) COMMISSIONING OF THE SMOKE CONTROL SYSTEM IS
 REQUIRED IN ACCORDANCE WITH THE PROCEDURES OUTLINED IN
 THE SLS RATIONAL ANALYSIS REPORT. PLEASE REVIEW PAGES
 28-36 OF THE REPORT. IT IS REQUIRED THAT THE SYSTEMS BE
 TESTED BY AN APPROVED SMOKE CONTROL INSPECTOR WHO IS A
 REGISTERED DESIGN PROFESSIONAL AND WHO HAS EXPERTISE IN
 FIRE PROTECTION ENGINEERING AND/OR MECHANICAL
 ENGINEERING.
 PRIOR TO COMMISSIONING THE SMOKE CONTROL SYSTEM,
 DETAILED SMOKE CONTROL TESTING SCENARIOS ARE REQUIRED
 TO BE DEVELOPED BY THE SMOKE CONTROL SPECIAL INSPECTOR
 AS REQUIRED BY SECTION 909.19.8 FBC B, AND ARE REQUIRED
 TO BE REVIEWED BY THE WPB BUILDING AND FIRE
 DEPARTMENTS.
 PAGE 36: A FINAL REPORT SHOULD BE COMPLIED BY THE
 PROJECT'S SMOKE CONTROL SPECIAL INSPECTOR AS REQUIRED
 BY SECTION 909.18.8.3 FBC B. A COPY OF THE REPORT
 SHOULD BE SUBMITTED TO THE WPB BUILDING AND FIRE
 DEPARTMENTS, AND AN IDENTICAL COPY SHOULD BE MAINTAINED
 IN AN APPROVED LOCATION (E.G. THE FIRE COMMAND CENTER)
 IN THE BUILDING.
  
 4) SEPARATE MECHANICAL PERMITS REQUIRED: SEPARATE
 PERMITS ARE REQUIRED FOR KITCHEN EXHAUST HOODS AND FIRE
 SUPPRESSION SYSTEMS, WALK-IN COOLERS AND FREEZERS.
  
 5) PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3.1.1 FBC-17 MECHANICAL.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR. IT APPEARS THAT THE
 REQUIRED CALCULATIONS WERE TO BE PLACED ON THE BLANK
 SHEET M8.03 WHICH BEARS A SMALL NOTE REFERENCING THE
 CALCULATIONS.
  
 6) SHEET M1.1: THERE ARE NO AC SYSTEMS PROVIDED FOR THE
 RETAIL AREAS. PLEASE LABEL THESE AREAS AS "FUTURE" IF
 APPLICABLE, AND NOTE THAT ALL INTERIOR SPACES INTENDED
 FOR HUMAN OCCUPANCY SHALL BE PROVIDED WITH ACTIVE OR
 PASSIVE SPACE-HEATING SYSTEMS- SECTION 309.1 FBC-M.
  
 7) M1.1: NO VENTILATION AIR (O/A) PROVIDED TO THE
 ELEVATOR LOBBIES, CORRIDOR, FIRE RESCUE, FIRE COMMAND
 AND OTHER OCCUPIED ROOMS AND SPACES- SEE SECTIONS
 401.2, 402.1, 403.1, 403.2 AND TABLE 403.3.1.1 FBC M.
 O/A. HOW WILL POSITIVE PRESSURE ME MAINTAINED IN THESE
 AREAS THAT ARE ADJACENT TO THE GARAGE AREA WHERE
 EXHAUST IS REQUIRED?
  
 8) PROVIDE EXHAUST VENTILATION CALCULATIONS AND THE
 SEQUENCE OF OPERATION FOR THE
 A) ENCLOSED GARAGE/LOADING DOCK AREA.
 B) DIESEL TANK ROOM.
 C) FIRE PUMP ROOM.
 D) SHOP.
 E) RESTROOM
 F) SMOKE PURGE SYSTEMS.
  
 9) M1.1: THE EXHAUST SYSTEMS FOR THE FIRE PUMP ROOM,
 SHOP, AND RESTROOM SHALL DISCHARGE TO THE OUTDOORS AND
 NOT THE INTERIOR GARAGE AREA- SECTION 501.3.
  
 10) M1.1: AUTOMATIC SHUT OFF DAMPERS EITHER MOTORIZED
 OR GRAVITY-TYPE ARE REQUIRED ON ALL O/A INTAKES AND
 EXHAUST OPENINGS- SECTION C403.2.4.3 FBC EC.
  
 11) M1.1: THE MAKEUP AIR OPENING AT THE DIESEL TANK
 ROOM/GARAGE WALL IS NOT PERMITTED. ALL AIR FROM THE
 GARAGE SHALL BE EXHAUSTED AND NOT TRANSFERRED OR
 RECIRCULATED INTO ADJACENT SPACES- TABLE 403.3.1.1.
 FOOTNOTE B.
  
 12) M1.1: THE LOCATION OF OPEN AIR INTAKE (TIL-1-1) BY
 THE DRIVE AREA IS NOT IN COMPLIANCE WITH SECTION 401.4
 (2) FBC M.
  
 13) M1.1: THE "EXIT PASSAGEWAY" OR "STAIRWAY EXTENSION"
 FROM STAIR #1 IS MISLABELED AS AN "EGRESS CORRIDOR".
 PLEASE SEE SECTION 202 DEFINITIONS, AND SECTION 1023
 1024 FBC B. PLEASE NOTE THAT THIS PASSAGE WAY OR
 EXTENSION IS ALSO CLASSIFIED AS A SMOKEPROOF ENCLOSURE
 AND SHALL BE PRESSURIZED EQUALLY TO THE PRESSURIZATION
 REQUIRED FOR THE STAIRWAY DURING AN EMERGENCY ALARM
 EVENT- SEE SECTION 1023.11.1 FBC B.
  
 14) M1.1: THE CONDENSING UNITS (CU'S) SHOWN IN THE
 INTERIOR GARAGE AREA ARE DESIGNED TO BE INSTALLED IN
 ACCORDANCE WITH THE CONDITIONS OF THEIR LISTING AND THE
 MANUFACTURER'S INSTALLATION INSTRUCTIONS- SECTION 304.1
 FBC M. TYPICALLY THESE UNITS MUST BE INSTALLED
 OUTDOORS.
  
 15) M1.1: AS NOTED ABOVE IN COMMENT #8, THERE IS NO
 SEQUENCE OF OPERATION FOR THE EXHAUST SYSTEM IN THE
 GARAGE AREA. PLEASE REFER TO SECTIONS 404.1 & 404.2 FBC
 M AND PROVIDE A NARRATIVE TO CLARIFY HOW THIS SYSTEM
 WILL FUNCTION, AND SUBMIT MANUFACTURER'S SPECIFICATIONS
 AND INSTALLATION INSTRUCTIONS FOR THE CO AND NO2
 SENSORS- SEE COMMENT #2 ABOVE.
  
 16) M1.1 GENERATOR/DIESEL TANK: A) SUBMIT
 MANUFACTURER'S SPECIFICATIONS FOR THE GENERATOR AND
 DIESEL TANK, FUEL AND VENT PIPES, MUFFLER, AND ALL
 OTHER ASSOCIATED SYSTEM COMPONENTS. B) SUBMIT A COPY OF
 THE UL CERTIFICATE OF COMPLIANCE FOR THE GENERATOR
 INDICATING THE UNIT MEETS THE REQUIREMENTS OF UL 2200.
 C) SHOW THE TERMINATION LOCATION OF THE ENGINE EXHAUST
 VENT PIPE. D) SHOW THE FUEL PIPING RUN FROM THE TANK TO
 THE GENERATOR AND INDICATE HOW THE PIPE PENETRATION
 WILL BE FIRESTOPPED. E) PLEASE REVIEW SECTION 7.7.1
 NFPA 110. AN AC SYSTEM MAY BE REQUIRED FOR THE
 GENERATOR ROOM IN ORDER TO LIMIT THE MAXIMUM AIR
 TEMPERATURE IN THE ROOM TO THE MAXIMUM AMBIENT AIR
 TEMPERATURE AS REQUIRED BY THE GENERATOR MANUFACTURER.
  
 17) M1.1: INDICATE THE CLEARANCE DISTANCE BETWEEN THE
 GENERATOR ROOM INTAKE AND EXHAUST LOUVERS- SECTIONS
 401.4 AND 501.3.1 FBC M.
  
 18) M1.1: INDICATE THE CLEARANCE DISTANCE HEIGHT OF THE
 PFSP-1 & 2, AND EF-1-5 EXHAUST OUTLETS TO THE ADJOINING
 GRADE- SECTION 501.3.1 (2) FBC M.
  
 19) M1.1: PROVIDE A CONDENSATE DISPOSAL PLAN FOR THE
 AIR HANDLERS- SECTION 307.2 FBC M. PLEASE NOTE THAT NO
 PIPE SIZES OR PIPE DETAILS ARE PROVIDED ON THE RISER
 DRAWING- SHEET M4.01.
  
 20) LS1.01: THE LIFE SAFETY PLAN SHOWS AN INTERSTITIAL
 SPACE WHERE STAIR #2 IS EXTENDED VIA AN EXIT PASSAGEWAY
 TO STAIR #6. PLEASE NOTE THAT THERE ARE NO MECHANICAL
 PLANS UPLOADED FOR THIS SPACE, AND THE EXIT PASSAGEWAY
 IS MISLABELED AS AN EGRESS CORRIDOR. THE PASSAGEWAY AND
 STAIR #6 ARE ALSO SMOKEPROOF ENCLOSURES THAT NEED TO BE
 PRESSURIZED DURING AN EMERGENCY ALARM- SEE COMMENTS #1A
 & #13 ABOVE AND CORRECT THE RISER DRAWINGS ON SHEET
 M6.01.
  
 21) M1.1: PROVIDE SIZING CALCULATIONS FOR THE SMOKE
 PURGE SYSTEMS- SECTION 403.4.7 FBC B.
  
 22) M1.2, 1.3, 1.4, 1.5, 1.6, 1.7, & M1.8: THE NOTES ON
 THE PLAN INDICATE THE DESIGN PROFESSIONALS HAVE NOT
 DECIDED WHETHER THE GARAGE IS DESIGNED AS "OPEN" OR
 "ENCLOSED", BUT HAVE STATED THAT THE CURRENT DESIGN
 WILL NOT WORK FOR ENCLOSED GARAGES? PLEASE CLARIFY THAT
 STATEMENT AND NOTE THAT ENCLOSED GARAGES SHALL HAVE
 MECHANICAL EXHAUST VENTILATION SYSTEMS DESIGNED IN
 ACCORDANCE WITH SECTION 404 FBC M. THE CURRENT PLAN
 SHOWS THE GARAGE EXHAUST FANS LOCATED IN ONE REMOTE
 CORNER OF THE GARAGE WHICH MAY LIMIT THEIR ABILITIES TO
 EXHAUST THE ENTIRE AREA OF THE GARAGES- PLEASE SEE
 SECTION 502.1.1 FBC M. A) THE EXHAUST FAN SCHEDULE FOR
 THE GARAGES ON M8.02 SHOWS THE FANS INTERLOCKED WITH
 CO/NO2 SENSORS. PLEASE SHOW THE SENSOR LOCATIONS ON THE
 PLAN AND PROVIDE A SEQUENCE OF OPERATION. B) PROVIDE
 EXHAUST VENTILATION CALCULATIONS FOR EACH GARAGE- TABLE
 403.3.1.1 FBC M.
  
 23) LS1.02, 1.03, 1.04, 1.05, 1.06, 1.07, 1.08, 1.09 &
 LS1.10: INTERIOR EXIT STAIRWAY ENCLOSURES (STAIR #1 &
 #2) SHALL HAVE 2-HR. FIRE-RATED WALLS, HOWEVER THE
 DRAWINGS APPEAR TO INDICATE A SMALL SECTION OF THE
 ENCLOSURE IS ONLY 1-HR. RATED AT THE LOCATIONS OF THE
 PRESSURIZATION DUCT SHAFTS. PLEASE REVIEW SECTION 1023
 FBC B.
  
 24) M1.2, 1.3, 1.4, 1.5, 1.6, 1.7, M1.8: A) NO
 VENTILATION AIR PROVIDED TO OCCUPIED ROOMS- SECTION
 401.2 B) THE EXHAUST FROM EF-2 SHALL DISCHARGE TO THE
 OUTDOORS- SECTION 501.3 FBC M. C) NO VENTILATION OR
 SPACE HEATING PROVIDED TO THE OFFICES ON THE SOUTH AND
 WEST SIDES OF THE BUILDING DESPITE NOTES ON THE M1.02 &
 M1.04 PLANS REFERENCING EQUIPMENT- SECTIONS 309.1 &
 401.2 FBC M. IT APPEARS THESE AREAS ARE SHELL SPACES TO
 BE BUILT OUT AT A FUTURE DATE. PLEASE PLACE NOTES ON
 THE PLANS TO CLARIFY, AND SHOW HOW O/A WILL BE
 PROVIDED.
  
 25) M1.09: NO VENTILATION OR SPACE HEATING PROVIDED TO
 THE OFFICES- SECTIONS 309.1 & 401.2 FBC M. IT APPEARS
 THESE AREAS ARE SHELL SPACES TO BE BUILT OUT AT A
 FUTURE DATE. PLEASE PLACE NOTES ON THE PLANS TO
 CLARIFY.
  
 26) M2.01: DUCT SMOKE DETECTORS ARE REQUIRED IN THE
 SUPPLY SYSTEM OF AC-9-1- SECTION 606.2.1 FBC M.
  
 27) M2.02: INDICATE WHICH FLOORS THIS "TYPICAL" DRAWING
 PERTAINS TO AND WHICH AC SYSTEMS. SHOW THE LOCATION OF
 THE REQUIRED DUCT SMOKE DETECTOR- SECTION 606.2.1 FBC
 M.
  
 28) M2.03 & M.401: A) PROVIDE THE CONDENSATE PIPE SIZES
 IN THE RISER DRAWING. B) INDICATE WHERE THE CONDENSATE
 BRANCH PIPES ARE DISCHARGING TO, OR HOW THEY ARE ALL
 CONNECTING INTO A MAIN STORM DRAIN. C) THE NOTE ON
 M.401 REFERENCES RISER CONTINUATIONS ON M.203. PLEASE
 NOTE THESE CONTINUATIONS ON M.203.
  
 29) M.601: PLEASE CORRECT STAIR #1 & 2 PRESSURIZATION
 RISERS IN ACCORDANCE WITH COMMENTS #1A, 13 & 20.
  
 30) PROVIDE A REFRIGERANT RISER DRAWING FOR THE DX
 SYSTEMS- SECTION 304.1 FBC M.
  
 31) PROVIDE WIND LOAD ENGINEERING FOR INSTALLATION OF
 ALL ROOFTOP MECHANICAL EQUIPMENT- SECTION 301.15 FBC M.
 THIS INFORMATION CAN BE PROVIDED WITH THE CORRECTED
 PLANS, OR AS A DEFERRED SUBMITTAL- SEE COMMENT #2.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-03-25 Cont ID  
Sent By gjohnson Date 2019-03-25 Time 15:50 Rev Time 0.00
Received By gjohnson Date 2019-03-25 Time 15:50 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-02-25 Cont ID  
Sent By gjohnson Date 2019-02-25 Time 15:36 Rev Time 0.00
Received By gjohnson Date 2019-02-20 Time 08:59 Sent To  
Notes
2019-02-25 15:36:522ND REVIEW: 18090469
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1.PLEASE SHOW ALL STACKS WITH TAGS ON THE FLOOR PLANS
 SHEETS P1.02-P1.11. PER WPB AMEND TO FBC 107.2.1
 2. THERE IS 2 P9-01 SHEETS THE SHEET FROM 1ST SUBMITTAL
 NEEDS TO BE REMOVED. PER WPB AMEND TO FBC 107.2.1
 3. THE JANITORS SINK AND WATER FOUNTAINS ON THE 18TH
 FLOOR ARE MISSING FROM THE FLOOR PLANS SHEETS P1.10 AND
 P4.11 PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
 4. PLEASE PROVIDE PIPING DETAIL FOR THE GREASE
 INTERCEPTOR. PER WPB AMEND TO FBC 107.2.1
 5. MANUFACTURE SPECIFICATIONS FOR THE FUEL OIL SYSTEM
 AND TANKS AND GENERATOR IS REQUIRED FOR APPROVAL. PER
 WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-12-10 Cont ID  
Sent By gjohnson Date 2018-12-10 Time 06:29 Rev Time 0.00
Received By gjohnson Date 2018-11-26 Time 11:02 Sent To  
Notes
2018-12-10 11:37:371ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE SHOW COMPLIANCE WITH THE FOLLOWING FBC ACC
 2017 6TH EDITION.
 A) 604.2 LOCATION.THE WATER CLOSET SHALL BE POSITIONED
 WITH A WALL OR PARTITION TO THE REAR AND TO ONE SIDE.
 THE CENTERLINE OF THE WATER CLOSET SHALL BE 16 INCHES
 MINIMUM TO 18 INCHES MAXIMUM FROM THE SIDE WALL OR
 PARTITION.
 B) 604.3.1 SIZE.CLEARANCE AROUND A WATER CLOSET SHALL
 BE 60 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE
 SIDE WALL AND 56 INCHES MINIMUM MEASURED PERPENDICULAR
 FROM THE REAR WALL. SHOW DIMENSIONS ON CLEAR FLOOR
 SPACE.
 C) 604.4 SEATS.THE SEAT HEIGHT OF A WATER CLOSET ABOVE
 THE FINISH FLOOR SHALL BE 17 INCHES MINIMUM AND 19
 INCHES MAXIMUM MEASURED TO THE TOP OF THE SEAT. SEATS
 SHALL NOT BE SPRUNG TO RETURN TO A LIFTED POSITION.
 D) 604.5.1 SIDE WALL.THE SIDE WALL GRAB BAR SHALL BE 42
 INCHES LONG MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM
 FROM THE REAR WALL AND EXTENDING 54 INCHES MINIMUM FROM
 THE REAR WALL.
 E) 604.5.2 REAR WALL.THE REAR WALL GRAB BAR SHALL BE 36
 INCHES LONG MINIMUM AND EXTEND FROM THE CENTERLINE OF
 THE WATER CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24
 INCHES MINIMUM ON THE OTHER SIDE.
 F) 609.4 POSITION OF GRAB BARS.GRAB BARS SHALL BE
 INSTALLED IN A HORIZONTAL POSITION, 33 INCHES (840 MM)
 MINIMUM AND 36 INCHES (915 MM) MAXIMUM ABOVE THE FINISH
 FLOOR MEASURED TO THE TOP OF THE GRIPPING SURFACE.
 G) 604.7 DISPENSERS.TOILET PAPER DISPENSERS SHALL
 COMPLY WITH 309.4 AND SHALL BE 7 INCHES MINIMUM AND 9
 INCHES MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE
 DISPENSER SHALL BE 15 INCHES MINIMUM AND 48 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR.
 H) 603.3 MIRRORS.MIRRORS LOCATED ABOVE LAVATORIES OR
 COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE OF
 THE REFLECTING SURFACE 40 INCHES MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND.
 I) 606.2 CLEAR FLOOR SPACE.A CLEAR FLOOR SPACE
 COMPLYING WITH 305, POSITIONED FOR A FORWARD APPROACH,
 AND KNEE AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE
 PROVIDED.
 J) 606.3 HEIGHT.LAVATORIES AND SINKS SHALL BE INSTALLED
 WITH THE FRONT OF THE HIGHER OF THE RIM OR COUNTER
 SURFACE 34 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
 K) THE SHOWER IN THE MANAGERS BATHROOM ON THE 1ST FLOOR
 SHALL COMPLY WITH ONE OF THE FOLLOWING.
 608.2.1 TRANSFER TYPE SHOWER COMPARTMENTS.TRANSFER TYPE
 SHOWER COMPARTMENTS SHALL BE 36 INCHES BY 36 INCHES
 CLEAR INSIDE DIMENSIONS MEASURED AT THE CENTER POINTS
 OF OPPOSING SIDES AND SHALL HAVE A 36 INCH WIDE MINIMUM
 ENTRY ON THE FACE OF THE SHOWER COMPARTMENT. CLEARANCE
 OF 36 INCHES WIDE MINIMUM BY 48 INCHES LONG MINIMUM
 MEASURED FROM THE CONTROL WALL SHALL BE PROVIDED.
 608.2.2 STANDARD ROLL-IN TYPE SHOWER
 COMPARTMENTS.STANDARD ROLL-IN TYPE SHOWER COMPARTMENTS
 SHALL BE 30 INCHES WIDE MINIMUM BY 60 INCHES DEEP
 MINIMUM CLEAR INSIDE DIMENSIONS MEASURED AT CENTER
 POINTS OF OPPOSING SIDES AND SHALL HAVE A 60 INCHES
 WIDE MINIMUM ENTRY ON THE FACE OF THE SHOWER
 COMPARTMENT.
 608.2.3 ALTERNATE ROLL-IN TYPE SHOWER
 COMPARTMENTS.ALTERNATE ROLL-IN TYPE SHOWER COMPARTMENTS
 SHALL BE 36 INCHES WIDE AND 60 INCHES DEEP MINIMUM
 CLEAR INSIDE DIMENSIONS MEASURED AT CENTER POINTS OF
 OPPOSING SIDES.A 36 INCH WIDE MINIMUM ENTRY SHALL BE
 PROVIDED AT ONE END OF THE LONG SIDE OF THE
 COMPARTMENT.
  
 2. PROVIDE MANUFACTURE SPECIFICATIONS FOR THE FUEL OIL
 FILL STATION, AUTOMATIC FUEL POLISHER, WATER HEATER,
 ELEVATOR SUMP PUMP, GREASE INTERCEPTOR AND DOMESTIC
 WATER BOOSTER PUMP.
  
 3. SHT. P1.01 THE BACK PREVENTER'S ON THE DOMESTIC
 WATER MAIN AND FIRE LINE MAINS SHALL BE INSTALLED AS
 CLOSE AS POSSIBLE TO THE WATER METERS. PLEASE CONTACT
 DAVE PEARSON 822-2242 WPB UTILITIES DEPT.
  
 4. PLEASE PLACE NOTES ON THE PLAN SEPARATE PERMITS ARE
 REQUIRED FOR BACKFLOWS, GREASE INTERCEPTORS. PER WPB
 AMEND TO FBC 107.2.1
  
 5. THE PLAN SHOWS 3000 GAL. GREASE INTERCEPTOR THE
 MAXIMUM SIZE ALLOWED IN WPB IS 1250 GAL. PLEASE CONTACT
 JEFFERY ODOMS 822-2172 WPB UTILITIES DEPT.
  
 6. PROVIDE SIZING CALCULATIONS FOR THE GREASE
 INTERCEPTORS. PER WPB AMEND TO FBC 107.2.1
  
 7. SANITARY FACILITY'S WILL BE REQUIRED FOR THE RETAIL
 SPACE ON FST FLOOR WILL THERE BE ANY ROUGH PIPING
 INSTALLED ON THIS PROJECT. PER FBC PL 403.1
  
 8. PLEASE LABEL ALL STACKS AND RISERS ON THE FLOOR
 PLANS AND ISOMETRIC DRAWINGS FOR THE SANITARY, WATER
 AND STORM DRAIN. WPB AMEND TO FBC 107.2.1
  
 9. WHAT IS THE CONDENSATE RECYCLED WATER BEING USED FOR
 PLEASE PROVIDE PIPING DIAGRAM AND SHOW PIPING ON FLOOR
 PLAN. WPB AMEND TO FBC 107.2.1
  
 10. SHTS. P-1.02 THRU P-1.10 SHOW PIPING SIZES AND
 LABEL STACKS. WPB AMEND TO FBC 107.2.1
  
 11. SHT P-1.10 SHOWS A NOTE THAT STATES 4"
 STORM/OVERFLOW FROM ABOVE BUT NO PIPING IS SHOWN PLEASE
 CLARIFY. WPB AMEND TO FBC 107.2.1
  
 12. SHT. SHT. P4.01 PLEASE CLARIFY WHAT G.C.O. STANDS
 FOR. LOCATED BETWEEN LINE F AND G. WPB AMEND TO FBC
 107.2.1
  
 13. PROVIDE PLUMBING FIXTURE BREAKDOWN PER FLOOR. WPB
 AMEND TO FBC 107.2.1
  
 14. SHT. P-4.02B A WATER FOUNTAIN IS REQUIRED FOR
 OFFICE SPACE. PER FBC PL TABLE 403.1
  
 15. THE THERMOSTATIC MIXING VALVE FOR THE TEMPERED
 WATER TO THE LAVATORY'S SHALL COMPLY WITH ASSE 1070
 PLEASE PROVIDE MANUFACTURES SPECIFICATIONS TO VERIFY
 COMPLIANCE. PER FBC PL 416.5
  
 16. SHT. P5.02 THE POLISHING SYSTEM FOR THE FUEL OILS
 NOT SHOWN AS BEING PIPED INTO THE REST OF THE SYSTEM
 PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 17. PROVIDE THE MSDS SHEETS FOR THE FUEL OIL USED BY
 GENERATOR. . PER WPB AMEND TO FBC 107.2.1
  
 18. SHT. P-9.02 SHOW ON THE PLAN THE PIPE SLOPE AND ON
 THE PIPE ITSELF SHOW THE SQFT AND OR GPM. . PER WPB
 AMEND TO FBC 107.2.1
  
 19. PROVIDE A SANITARY COLLECTION ISOMETRIC DRAWING. .
 PER WPB AMEND TO FBC 107.2.1
  
 20. PROVIDE A COMPLETE WATER ISOMETRIC DRAWING. . PER
 WPB AMEND TO FBC 107.2.1
  
 21. PROVIDE DETAIL TO SHOW COMPLIANCE WITH FBC PL
 308.6 SWAY BRACING.RIGID SUPPORT SWAY BRACING SHALL BE
 PROVIDED AT CHANGES IN DIRECTION GREATER THAN 45
 DEGREES (0.79 RAD) FOR PIPE SIZES 4 INCHES AND LARGER.
 308.7 ANCHORAGE. ANCHORAGE SHALL BE PROVIDED TO
 RESTRAIN DRAINAGE PIPING FROM AXIAL MOVEMENT.
 308.7.1 LOCATION. FOR PIPE SIZES GREATER THAN 4 INCHES
 , RESTRAINTS SHALL BE PROVIDED FOR DRAIN PIPES AT ALL
 CHANGES IN DIRECTION AND AT ALL CHANGES IN DIAMETER
 GREATER THAN TWO PIPE SIZES. BRACES, BLOCKS, RODDING
 AND OTHER SUITABLE METHODS AS SPECIFIED BY THE COUPLING
 MANUFACTURER SHALL BE UTILIZED.
 PER WPB AMEND TO FBC 107.2.1
  
 22. SHT. P-4.09 SHOW DISTANCE OF SANITARY VENTS FROM
 AIR INTAKES MUST BE MIN. OF 10'. PER FBC PL 903.5
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P-GREASE GREASE INTERCEPTOR/TRAP REVIEW
Rev No 2 Status P Date 2019-03-25 Cont ID  
Sent By gjohnson Date 2019-03-25 Time 15:50 Rev Time 0.00
Received By gjohnson Date 2019-03-25 Time 15:50 Sent To  
Notes
***NONE***

Review Stop P-GREASE GREASE INTERCEPTOR/TRAP REVIEW
Rev No 1 Status F Date 2019-02-25 Cont ID  
Sent By gjohnson Date 2019-02-25 Time 15:41 Rev Time 0.00
Received By gjohnson Date 2019-02-25 Time 15:41 Sent To  
Notes
2019-02-25 15:43:14PROVISO: 18090469
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE PROVIDE PIPING DETAIL FOR THE GREASE
 INTERCEPTOR. PER WPB AMEND TO FBC 107.2.1
 2. PROVIDE MANUFACTURE SPECIFICATIONS. PLEASE PROVIDE
 PIPING DETAIL FOR THE GREASE INTERCEPTOR. PER WPB AMEND
 TO FBC 107.2.1
 3. PLEASE PROVIDE DOCUMENTATION FROM UTILITIES
 DEPARTMENT FOR SIZE OF THE GREASE INTERCEPTOR. PER WPB
 AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status N Date 2019-03-23 Cont ID  
Sent By dbattles Date 2019-03-23 Time 10:29 Rev Time 0.00
Received By dbattles Date 2019-03-23 Time 10:29 Sent To  
Notes
2019-05-07 15:09:02SEPARATE ROOF PERMIT IS REQUIRED. PRIOR TO
 INSTALLATION, SUBMIT ROOF PERMIT APPLICATION WITH
 PRODUCT APPROVALS REVIEWED BY DESIGNER OF RECORD AND
 ENGINEERING (IF APPLICABLE).

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2019-02-27 Cont ID  
Sent By dbattles Date 2019-02-27 Time 14:16 Rev Time 0.00
Received By dbattles Date 2019-02-27 Time 14:16 Sent To  
Notes
2019-02-27 14:18:09W.P.B. PERMIT: 1901
 REVIEWED: FEBRUARY 27, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
  
 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS FOR
 ROOFING, OR INDICATE THAT YOU WOULD LIKE THEM DEFERED.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2019-03-23 Cont ID  
Sent By dbattles Date 2019-03-23 Time 10:20 Rev Time 0.00
Received By dbattles Date 2019-03-23 Time 10:03 Sent To  
Notes
2019-03-29 11:54:14NEW MECH SHEETS OK
2019-03-25 15:56:483/25/19 DIG SIG PLUMB SHT. OK/GPJ
2019-03-23 10:21:36ALL NEW SHEETS - OK
 ANY NEW SHEETS PROVIDED WILL NEED TO BE DIGITALLY
 SIGNED.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2019-02-27 Cont ID  
Sent By dbattles Date 2019-02-27 Time 14:11 Rev Time 0.00
Received By dbattles Date 2019-02-27 Time 14:11 Sent To  
Notes
2019-02-27 14:12:53SIGNATURE TO BE REVIEWED AFTER ALL SHEETS APPROVED.
2019-01-23 15:52:311/23/19 3 PAGES IN SIGNATURES FOLDER. SEE ME FOR MORE
 INFORMATION. LEM

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2018-12-12 Cont ID  
Sent By skennedy Date 2018-12-12 Time 11:24 Rev Time 0.00
Received By skennedy Date 2018-12-12 Time 11:24 Sent To  
Notes
2018-12-12 11:24:45SIGNATURES WILL BE VERIFIED BY REVIEW OF RESUBMITTED
 PLANS.

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 3 Status P Date 2019-05-06 Cont ID  
Sent By dbattles Date 2019-05-06 Time 15:56 Rev Time 0.00
Received By dbattles Date 2019-04-22 Time 09:20 Sent To  
Notes
2019-05-08 14:27:55RECEIVED THREE ORIGINALS 5/8/19
 THRESHOLD PROVISO COMPLETE-DB
2019-05-06 15:58:00THRESHOLD AGREEMENT APPROVED.
  
 PROVISO:
 PROVIDE THREE ORIGINAL COPIES AS DISCUSSED IN MEETING
 ON 5/2/19

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 2 Status F Date 2019-03-23 Cont ID  
Sent By dbattles Date 2019-03-23 Time 10:22 Rev Time 0.00
Received By dbattles Date 2019-03-23 Time 10:03 Sent To  
Notes
2019-03-23 10:23:16IN PROGRESS.
 PENDING DOCUMENTS
  
 A. PENDING - COMPLETE THE THRESHOLD / SPECIAL INSPECTOR
 AGREEMENT OF UNDERSTANDING;
  
 B. PENDING - PROVIDE RESUMES AND COPIES OF LICENSES FOR
 ALL PROPOSED INSPECTORS. PLEASE INCLUDE AS MANY
 ADDITIONAL INSPECTORS AS POSSIBLE BECAUSE THESE ARE THE
 ONLY PEOPLE THAT THE CHIEF BUILDING INSPECTOR WILL
 ALLOW TO BE ON-SITE.
  
 C. OK - STATEMENT WAS PROVIDED.
 ALL PLANS ARE TO INCLUDE THE THRESHOLD STATEMENT
 REQUIRED BY FS553.79(7)(D). ?ALL PLANS FOR THE BUILDING
 WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT?S OR ENGINEER?S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE MINIMUM BUILDING CODES AND THE APPLICABLE
 FIRE SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS CHAPTER 553 AND
 CHAPTER 633.?
  
 D. OK - SHEET S0.06 CONTAINS THRESHOLD NOTES
 THRESHOLD INSPECTION PLAN REQUIRED, FS553.79(5)A).
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status F Date 2019-02-22 Cont ID  
Sent By dbattles Date 2019-02-22 Time 08:03 Rev Time 0.00
Received By dbattles Date 2019-02-22 Time 08:03 Sent To  
Notes
2019-02-22 08:03:16THIS PROJECT MEETS THE DEFINITION OF A THRESHOLD
 BUILDING. THE FOLLOWING IS REQUIRED PRIOR TO
 COMMENCEMENT.
 STATUS = IN PROGRESS
  
 FORMS SENT TO [email protected] SAT. DEC. 01/2018 12:48
 PM/
 REPLIED: MON. DEC. 03/2018 8:37 AM
  
 A. PENDING - COMPLETE THE THRESHOLD / SPECIAL INSPECTOR
 AGREEMENT OF UNDERSTANDING;
  
 B. PENDING - PROVIDE RESUMES AND COPIES OF LICENSES FOR
 ALL PROPOSED INSPECTORS. PLEASE INCLUDE AS MANY
 ADDITIONAL INSPECTORS AS POSSIBLE BECAUSE THESE ARE THE
 ONLY PEOPLE THAT THE CHIEF BUILDING INSPECTOR WILL
 ALLOW TO BE ON-SITE.
  
 C. OK - STATEMENT WAS PROVIDED.
 ALL PLANS ARE TO INCLUDE THE THRESHOLD STATEMENT
 REQUIRED BY FS553.79(7)(D). ?ALL PLANS FOR THE BUILDING
 WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT
 THAT, TO THE BEST OF THE ARCHITECT?S OR ENGINEER?S
 KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE
 APPLICABLE MINIMUM BUILDING CODES AND THE APPLICABLE
 FIRE SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS CHAPTER 553 AND
 CHAPTER 633.?
  
 D. OK - SHEET S0.06 CONTAINS THRESHOLD NOTES
 THRESHOLD INSPECTION PLAN REQUIRED, FS553.79(5)A).
  
  
  

Review Stop Z ZONING
Rev No 5 Status P Date 2019-08-20 Cont ID  
Sent By aaponte Date 2019-08-20 Time 12:14 Rev Time 0.00
Received By aaponte Date 2019-08-20 Time 12:14 Sent To  
Notes
2019-08-20 12:17:09PROVISO: 1. BEFORE SEPTEMBER 30, 2019 APPLICANT
 SHALLPAY THE CITY $350,000 FOR THE ALLEY ABANDONMENT
 AND SHALL CLOSE ON THE PURCHASE AND SALE AGREEMENT FOR
 532 EVERNIA STREET.
 2. CANOPY AT OFFICE ENTRANCE CANNOT ENCROACH MORE THAN
 12 INTO THE ROW.
 3. FINAL DESIGN FOR TROLLEY SHELTER SHALL BE SUBMITTED
 FOR APPROVAL BY THE CITY.
 4. CURB CUT ON SE CORNER OF FERN AND ROSEMARY SHALL BE
 ADJUSTED TO ALLOW THE BIKE LANE TO CONTINUE.

Review Stop Z ZONING
Rev No 4 Status F Date 2019-06-10 Cont ID  
Sent By aaponte Date 2019-06-10 Time 14:36 Rev Time 0.00
Received By aaponte Date 2019-06-10 Time 14:36 Sent To  
Notes
2019-06-10 14:36:41BEFORE ZONING APPROVAL CAN BE GRANTED APPLICANT SHALL
 COMPLY WITH ALL THE ALLEY ABANDONMENT REQUIREMENTS AS
 PER RESOLUTION 180-18, AND THE PURCHASE AND SALE
 AGREEMENT FOR 532 EVERNIA STREET.
 ADDITIONAL COMMENTS THAT MAY BE SUBJECT TO PROVISO:
 1. CANOPY AT OFFICE ENTRANCE CANNOT ENCROACH MORE THAN
 12 INTO THE ROW.
 2. FINAL DESIGN FOR TROLLEY SHELTER SHALL BE SUBMITTED
 FOR APPROVAL BY THE CITY.
 3. CURB CUT ON SE CORNER OF FERN AND ROSEMARY SHALL BE
 ADJUSTED TO ALLOW THE BIKE LANE TO CONTINUE.
  

Review Stop Z ZONING
Rev No 3 Status F Date 2019-04-23 Cont ID  
Sent By aaponte Date 2019-04-23 Time 09:38 Rev Time 0.00
Received By aaponte Date 2019-04-23 Time 09:38 Sent To  
Notes
2019-04-23 09:46:59BEFORE ZONING APPROVAL CAN BE GRANTED APPLICANT SHALL
 COMPLY WITH ALL THE ALLEY ABANDONMENT REQUIREMENTS AS
 PER RESOLUTION 180-18, AND THE PURCHASE AND SALE
 AGREEMENT FOR 532 EVERNIA STREET.
 ADDITIONAL COMMENTS THAT MAY BE SUBJECT TO PROVISO:
 1. CANOPY AT OFFICE ENTRANCE CANNOT ENCROACH MORE THAN
 12 INTO THE ROW.
 2. FINAL DESIGN FOR TROLLEY SHELTER SHALL BE SUBMITTED
 FOR APPROVAL BY THE CITY.
 3. CURB CUT ON SE CORNER OF FERN AND ROSEMARY SHALL BE
 ADJUSTED TO ALLOW THE BIKE LANE TO CONTINUE.
  

Review Stop Z ZONING
Rev No 2 Status F Date 2019-02-26 Cont ID  
Sent By aaponte Date 2019-02-26 Time 13:07 Rev Time 0.00
Received By aaponte Date 2019-02-13 Time 15:04 Sent To  
Notes
2019-02-15 16:39:321. NOTE INCLUDED IN SHEET C5.00 WILL NOT GUARANTEE THE
 VEHICULAR ENTRANCE MAINTAINS THE SAME ELEVATION THAN
 THE SIDEWALK.PLEASE INCLUDE A DETAIL AND MORE SPECIFIC
 NOTE TO ENSURE CONSTRUCTION TEAM UNDERSTANDS THE
 INTENTION. THE SECTION SHALL BE ON THE OTHER DIRECTION
 TO SHOW THE SIDEWALK AND THE DRIVEWAY ARE AT THE SAME
 ELEVATION.
 2. PLEASE CONFIRM THERE IS NO IMPACT OF THE GAS LINE
 RUNNING ALONG FERN STREET ON THE PROPOSED LANDSCAPE.
 3. PLEASE PROVIDE SPEC SHEETS WITH DRAWINGS OF LIGHT
 FIXTURE PROPOSED. LIGHT FIXTURES ALONG EVERNIA AND FERN
 SHALL BE THE DOWNTOWN STANDARD FIXTURE. CALL OUT FOR
 LIGHT FIXTURES ON FERN AND EVERNIA HAVE DISCREPANCIES
 BETWEEN SHEET EL1.01 AND E1.01A.
 4. PLEASE CONFIRM THERE ARE NO GROUND LIGHT FIXTURES IN
 THE PUBLIC SIDEWALK. FIXTURE ADN POLE LISTED AS ELC
 DOES NOT MEET DOWNTOWN STANDARD FOR FERN ADN EVERNIA.
 PLEASE ALSO CONFIRM FIXTURE AND POLE LISTED AS ELC IS
 THE CURRENT SPEC FOR ROSEMARY AVE PHASE I.
 5. LIGHT FIXTURES ALONG ROSEMAY AVENUE SHALL BE
 RELOCATED ALONG THE CURB BETWEEN THE TREES. SHEET
 EL1.01 SHOWS THE CURB LOCATION BUT SHEET E1.01A SHOWS A
 DIFFERENT LOCATION.
 6. OFFICE ENTRANCE CANOPY IS ENCROACHING MORE THAN THE
 MAXIMUM12 FEET ALLOWED, PLEASE ADJUST. IN ADDITION, AN
 AERIAL EASEMENT WILL BE NEEDED FOR THE ENCROACHMENT UP
 TO 12 FEET.
 7. LANDSCAPE DRAWINGS SUBMITTED WITH THIS PERMIT HAVE
 BEEN REMOVED FROM THIS APPLICATION. APPLICANT SHALL
 SUBMIT A SEPARATE LANDSCAPE PERMIT.
 8. PLEASE CONFIRM COMPLIANCE WITH ALL THE CONDITIONS OF
 APPROVAL FOR THE ALLEY ABANDONMENT AS REQUIRED BY
 RESOLUTION NO. 180-18.
 9. PLEASE CONFIRM THE PURCHASE AND SALE AGREEMENT TO
 INCORPORATE THE CRA OWNED PROPERTY INTO THE PROJECT HAS
 BEEN EXECUTED.
  
 FOR ADDITIONAL INFORMAITON PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.
  
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2018-12-13 Cont ID  
Sent By aaponte Date 2018-12-13 Time 14:47 Rev Time 0.00
Received By aaponte Date 2018-12-12 Time 13:01 Sent To  
Notes
2018-12-12 14:46:231- PLEASE INCLUDE A NOTE AND DETAIL IN THE CIVIL
 DRAWINGS THAT SHOWS THAT THE SIDEWALK ELEVATION SHALL
 BE MAINTAINED ACROSS EACH OF THE GARAGE AND SERVICE
 ENTRANCES.
 2- PLEASE INDICATE ALL UTILITY CONNECTIONS AND LINES TO
 IDENTIFY ANY CONFLICTS WITH TREE PLANTINGS.
 3- THE PATTERN OF THE TERRACOTTA AND GLSSS FRAME HAS
 BEEN MODIFIED FROM THE SITE PLAN APPROVAL DRAWINGS.
 FACADE MATERIALS AND PATTERNS SHALL MATCH DAC APPROVAL
 AND SITE PLAN APPROVAL.
 4- EAST ELEVATION CALL OUT FOR "IMPACT RESISTANT
 ALUMINUM WINDOW WALL SYSTEM" ON THE EASTERNMOST GARAGE
 WALL. PLEASE CONFIRM WHAT IS BEING USED FOR THE
 ARCHITECTURAL TREATMENT ON THAT FACADE.
 5- APPROVED ELEVATIONS CALL OUT FOR TERRACOTTA
 RAINSCREEN WITH CUSTOMIZED VERTICALLY FLUTTED PROFILE,
 OR HORIZANTILLY FLUTTED PROFILE. THE PROFILE SUBMITTED
 IS DIFFERENT. PLEASE PROVIDE INFORMATION TO CONFIRM THE
 NEW PROFILE PROVIDES THE SAME EFFECT THAN THE APPROVED
 PROFILE.ALSO CLARIFY THE COLOR OF THE TERRACOTA IS AS
 APPROVED. PLEASE PROVIDE THE PROFILE DETAILS TO MATCH
 SPECIFICATIONS AND RENDERINGS APPROVED.
 6- PARKING GARAGE ENTANCE SHALL BE FINISHED (MIN. 20
 FEET FROM FACADE) WITH STUCCO OR PLASTER, FINISHED AND
 PAINTED COMPARABLE TO A HABITABLE SPACE. ALL
 MECHANICAL, ELECTRICAL, AND PLUMBING SYSTEM SHALL BE
 COVERED OR SCREENED.
 7- PROJECT IS REQUIRED TO COMPLY WITH THE ART IN PUBLIC
 PLACES ORDINANCE. PLEASE DISCUSS THE LOCATION OF THE
 PROPOSED ART AS SOON AS POSSIBLE AS THE ART DESIGN MAY
 AFFECT THE DESIGN OF THE PUBLIC OPEN SPACE.
 8- DETAILS FOR THE TROLEY SHELTER SHALL BE INCLUDED IN
 PERMIT SET.
 9- OFFICE ENTRANCE CANOPY ENCROACHES INTO THE ROW. A
 ROW AERIAL EASEMENT WILL BE REQUIRED.
 10- PLEASE INCLUDE SPECTS FOR LIGHTFIXTURES ALONG THE
 SIDEWALK.
 11. PLEASE THE SHEET WITH BUILDING FOOTPRINT
 INFORMATION, FAR INFORMATION, PARKING CALCULATIONS, AND
 PROJECT DATA.
 12. PLEASE PROVIDE A 1ST FLOOR PLAN WITH ALL THE
 EXTERIOR ELEMENTS (LANDSCAPE AND HARDSCAPE, LIGHTING,
 ETC)
 13. PLEASE INDICATE THE LOCATION OF THE EXISTING CURB
 LINE IN SITE PLAN.
 14. PLEASE INDICATE THE NUMBER OF ON-STREET PARKING
 SPACES THAT ARE GOING TO BE REMOVED BY THE PROJECT.
 PAYMENT FOR THE REMOVAL OF THE SPACES WILL BE REQUIRED
 PLESE CONTACT PARKING ADMINISTRATION.
 15- PLEASE PROVIDE LIGHT FIXTURE LEGEN AND SPEC FOR
 THOSE FIXTURES LOCATED ON THE PUBLIC REALM.
 16- PLEASE PROVIDE PHOTOMETRICS FOR PUBLIC REALM.
  
 - A SEPARATE PERMIT SHALL BE SUBMITTED FOR LANDSCAPE.
 PRELIMINARY LANDSCAPE COMMENTS ARE AS FOLLOWS:
 1.EXISTING OAKS ON ROSEMARY AVENUE SHALL BE REPLACED
 WITH NEW TREES.
 2. CLUSIA TREES ON NORTH PUBLIC OPEN SPACE DO NOT MEET
 MINIMUM TREE CANOPY REQUIRED.
  
  
  