Plan Review Details - Permit 18090387
Plan Review Stops For Permit 18090387
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-10-12 Cont ID  
Sent By shill Date 2018-10-12 Time 12:40 Rev Time 0.00
Received By shill Date 2018-10-12 Time 12:40 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-10-30 Cont ID  
Sent By fgiaquin Date 2018-10-30 Time 05:57 Rev Time 0.00
Received By fgiaquin Date 2018-10-30 Time 05:15 Sent To I
Notes
2018-10-30 05:57:44SEPARATE ELECTRICAL PERMIT REQUIRED BY LICENSED
 ELECTRICIAN FOR INSTALLATION OF TIME CLOCK, SIGN
 CIRCUIT, AND 120V DISCONNECT. PLEASE SEE SCOPE OF WORK
 FOR ES LICENSE BELOW:
  
 SIGN CONTRACTORS F.S. 489.505 (#19) AND F.A.C.
 61G6-7.001 SPECIALTY ELECTRICAL CONTRACTORS (#2 SIGN
 SPECIALTY CONTRACTOR)
  
 THE SCOPE OF CERTIFICATION INCLUDES THE STRUCTURAL
 FABRICATION INCLUDING CONCRETE FOUNDATION, ERECTION,
 INSTALLATION, ALTERATION, REPAIR, SERVICE AND WIRING OF
 ELECTRICAL SIGNS AND OUTLINE LIGHTING. THE SCOPE OF
 CERTIFICATION SHALL NOT INCLUDE THE PROVISION OF, OR
 ANY ELECTRICAL WORK BEYOND, THE LAST DISCONNECT MEANS
 OR TERMINAL POINTS. HOWEVER, A CONTRACTOR CERTIFIED
 UNDER THIS SECTION MAY PROVIDE THE ELECTRICAL ENTRANCE
 REQUIREMENTS FOR METERING AND MAIN DISCONNECT OF REMOTE
 BILLBOARDS OR SIGNS WHICH ARE INDEPENDENT OF ANY
 STRUCTURE OR BUILDING AND WHICH REQUIRE NO MORE THAN
 TWENTY-FIVE (25) KILOWATTS AT TWO HUNDRED FIFTY (250)
 VOLTS MAXIMUM.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-10-02 Cont ID  
Sent By fgiaquin Date 2018-10-02 Time 05:50 Rev Time 0.00
Received By fgiaquin Date 2018-10-02 Time 05:34 Sent To B
Notes
2018-10-02 05:36:28ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY A LICENSED DESIGN PROFESSIONAL OR THE
 ELECTRICAL CONTRACTOR QUALIFIER. FS 471.003(2)(H);
 471.025; WPB FBC 107.2.1, 107.3.5
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WPB
 [email protected]
 CELL: 561-657-1653
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-10-30 Cont ID  
Sent By fgiaquin Date 2018-10-30 Time 05:58 Rev Time 0.00
Received By fgiaquin Date 2018-10-26 Time 15:03 Sent To  
Notes
2018-10-29 15:04:05RESUB ROUTED TO FGIAQUINTO

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-10-12 Cont ID  
Sent By shill Date 2018-10-12 Time 12:40 Rev Time 0.00
Received By shill Date 2018-09-11 Time 14:00 Sent To  
Notes
2018-09-12 14:00:15ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 1 Status P Date 2018-10-01 Cont ID  
Sent By eschneid Date 2018-10-01 Time 12:09 Rev Time 0.25
Received By eschneid Date 2018-10-01 Time 11:50 Sent To E
Notes
2018-10-01 12:06:23PASSED
  
 AN ADMINISTRATIVE WAIVER FOR A HORIZONTAL SHIFT TO THE
 SIGN ZONE WAS GRANTED AS PART OF PERMIT NO. 10100404.
  
 PERMITTED: 54 SF (SECOND STORY FRONTAGE)
 PROPOSED: 22.3 SF
  