Plan Review Details - Permit 18090385
Plan Review Stops For Permit 18090385
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-12-19 Cont ID  
Sent By jduprey Date 2018-12-19 Time 15:41 Rev Time 0.00
Received By jduprey Date 2018-12-19 Time 15:41 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-09-15 Cont ID  
Sent By shill Date 2018-09-15 Time 16:06 Rev Time 0.00
Received By shill Date 2018-09-15 Time 16:06 Sent To  
Notes
2018-09-15 16:09:24****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC 107; PLEASE CLARIFY, ARE ANY EXTERIOR ELEMENTS
 AFFECTED? BUILDING ENVELOPE IS NOT CLEAR. DEMO OF
 EXTERIOR COMPONENTS (DOORS, WINDOWS) NOT PERMITTED ON
 AN INTERIOR DEMO PERMIT. THIS CAN BE CLARIFIED WITH
 EITHER A LETTER OR BY REVISING THE PLAN.
  
 2. AN ELECTRICAL SUB PERMIT IS REQUIRED. IF NO
 ELECTRICAL DEMO WORK IS PROPOSED, PLEASE ADVISE.
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-09-24 Cont ID  
Sent By jleahy Date 2018-09-24 Time 12:17 Rev Time 0.00
Received By jleahy Date 2018-09-24 Time 12:16 Sent To  
Notes
2018-09-24 12:17:54NEED ELECTRICAL PERMIT FOR DEMO ELECTRICAL WORK
 ASSOCIATED WITH THESE PLANS.
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-09-20 Cont ID  
Sent By pleduc Date 2018-09-20 Time   Rev Time 0.00
Received By pleduc Date 2018-09-19 Time 14:58 Sent To E
Notes
2018-09-20 13:12:06THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR
 CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND
 SPRINKLER SYSTEM FOR CODE COVERAGE AND COMPLIANCE BY
 CERTIFIED LIFE SAFETY CONTRACTORS.
  
 2) ANY AND ALL WORK ON THE FIRE ALARM AND FIRE
 SPRINKLER SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP
 DRAWINGS AND BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
 3) THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
  
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-12-19 Cont ID  
Sent By jduprey Date 2018-12-19 Time 15:41 Rev Time 0.00
Received By jduprey Date 2018-12-13 Time 14:28 Sent To  
Notes
2018-12-14 14:28:10RESUB ROUTED TO SHILL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-09-24 Cont ID  
Sent By jleahy Date 2018-09-24 Time 12:18 Rev Time 0.00
Received By jleahy Date 2018-09-11 Time 10:39 Sent To  
Notes
2018-09-24 11:42:349/24/2018 ROUTED TO J. L. (ELECTRIC) DESK.
2018-09-15 16:09:499/15 TO ZONING BOX
  
  
2018-09-13 10:39:49ROUTED TO SHILL

Review Stop Z ZONING
Rev No 1 Status P Date 2018-09-18 Cont ID  
Sent By eschneid Date 2018-09-18 Time 15:01 Rev Time 0.25
Received By eschneid Date 2018-09-18 Time 15:01 Sent To FIRE
Notes
***NONE***