Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-09-26 Cont ID  
Sent By jgomez Date 2018-09-26 Time 18:20 Rev Time 0.00
Received By jgomez Date 2018-09-26 Time 17:49 Sent To  
Notes
2018-09-26 18:08:27RESIDENTIAL (R2) SHUTTERS, SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- PROVIDE SHUTTERS COMPLETE INSTALLATION SCHEDULE AS
 REQUIRED BY CITY IMPLEMENTATION STANDARD FOR WIND-BORNE
 DEBRIS IMPACT PROTECTION FOR THE FLORIDA BUILDING CODE.
 SEE CITY SAMPLE. ALL THE COLUMNS NEED TO BE COMPLETED.
 ALTERNATIVELY, YOU MAY PROVIDE COMPLETE INSTALLATION
 SCHEDULE IN ANY OTHER FORMAT AS LONG AS ALL THE
 REQUIRED INFORMATION IS PROVIDED.
  
 RESPONSE:
 COLUMN #4 OF INSTALLATION SCHEDULE SUBMITTED IS
 INCORRECT. INSTALLATION SCHEDULE SUBMITTED NEED TO
 IDENTIFY THE SHUTTER MOUNTING CONNECTION TYPE (SEE
 COLUMN 4 OF INSTALLATION SCHEDULE). SEE SHEET 6 AND 7
 OF 20 OF ACCORDION DRAWINGS SUBMITTED. THIS IS
 IMPORTANT BECAUSE THE PROPOSED MOUNTING CONDITION AT
 THE OPENING HEADER AND SILL HAVE DIFFERENT ANCHOR
 SPACING. SEE SHEETS 13 AND 14 OF 20 OF ACCORDION
 DRAWINGS. ANCHOR SPACING WILL NEED TO BE REVISED.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-09-13 Cont ID  
Sent By jgomez Date 2018-09-13 Time 10:04 Rev Time 0.00
Received By jgomez Date 2018-09-13 Time 09:49 Sent To  
Notes
2018-09-13 10:19:49RESIDENTIAL (R2) SHUTTERS, BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- PROVIDE SHUTTERS COMPLETE INSTALLATION SCHEDULE AS
 REQUIRED BY CITY IMPLEMENTATION STANDARD FOR WIND-BORNE
 DEBRIS IMPACT PROTECTION FOR THE FLORIDA BUILDING CODE.
 SEE CITY SAMPLE. ALL THE COLUMNS NEED TO BE COMPLETED.
 ALTERNATIVELY, YOU MAY PROVIDE COMPLETE INSTALLATION
 SCHEDULE IN ANY OTHER FORMAT AS LONG AS ALL THE
 REQUIRED INFORMATION IS PROVIDED.
  
 2- THE DESIGN PRESSURES FOR OPENING #3 NEED TO BE
 REVISED. THIS OPENING IS LOCATED IN END ZONE 5 NOT
 INTERIOR ZONE 4. SEC. 1609.6.4.3 FBC.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-09-28 Cont ID  
Sent By jgomez Date 2018-09-28 Time 09:08 Rev Time 0.00
Received By jgomez Date 2018-09-27 Time 18:32 Sent To I
Notes
2018-09-27 18:32:59CONTRACTOR E-MAILED REVISED INSTALLATION SCHEDULE.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-09-26 Cont ID  
Sent By jgomez Date 2018-09-26 Time 18:31 Rev Time 0.00
Received By jgomez Date 2018-09-26 Time 17:49 Sent To  
Notes
2018-09-26 17:49:49CONTRACTOR E-MAILED INSTALLATION SCHEDULE.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-09-13 Cont ID  
Sent By jgomez Date 2018-09-13 Time 10:19 Rev Time 0.00
Received By jgomez Date 2018-09-11 Time 14:29 Sent To I
Notes
2018-09-12 14:30:19BLDG <5K


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved