Plan Review Details - Permit 18090310
Plan Review Stops For Permit 18090310
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-11-02 Cont ID  
Sent By dbattles Date 2018-11-02 Time 16:45 Rev Time 0.00
Received By dbattles Date 2018-11-02 Time 16:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-10-11 Cont ID  
Sent By dbattles Date 2018-10-11 Time 08:25 Rev Time 0.00
Received By dbattles Date 2018-10-11 Time 08:25 Sent To  
Notes
2018-10-11 08:26:22****CORRECTIONS****
 W.P.B. PERMIT: 18090310
 REVIEWED: OCTOBER 11, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
  
 1. [FBC 107.2.5]PROVIDE TABLE TO SHOW EXISTING PARKING
 SPACES AND PARKING FOR ADA, AND SHOW ADJUSTED TABLE FOR
 ADJUSTED LAYOUT.
  
 2. [FBC 107.2.5]PLEASE CLARIFY THE LAYOUT OF PARKING
 LOT. SHEETS C100 TO C501 SHOW PARKING AS EXISTING AND
 SHEETS C502 TO C507 SHOW A NEW LAYOUT AND THE SITE
 DOESN?T SEEM TO MATCH THE ADDRESS.
  
 3. [FBC 107.2.5]WHY ARE THESE SHEETS INCLUDED?
 IF NO CHANGES ARE BEING MADE THAN COMMENT 1 WON?T
 APPLY, BUT SHEETS THAT DON?T APPLY TO THIS SITE SHOULD
 BE REMOVED.
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2018-11-01 Cont ID  
Sent By rrossano Date 2018-11-01 Time   Rev Time 0.00
Received By rrossano Date 2018-11-01 Time   Sent To B
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2018-09-27 Cont ID  
Sent By rrossano Date 2018-09-27 Time   Rev Time 0.50
Received By rrossano Date 2018-09-27 Time   Sent To B
Notes
2018-09-27 11:22:59PASSED WITH PROVISOS:
 1) CORRECT THE STREET ADRESS AS LABELED ON THE PLANS;
 PLANS SHOW 7295, ADDRESS SHOULD BE 4295.
 2) THERE IS AN 8" CITY OF WPB SANITARY SEWER LINE ON
 SITE RUNNING EAST/WEST BETWEEN MCDONALDS AND THE GAS
 STATION IN THE VICINITY OF THIS PROJECT. PER CHAPTER
 556 OF THE FLORIDA STATE STATUTES, YOU MUST CALL 811
 FOR UTILITY LOCATES AT LEAST TWO FULL BUSINESS DAYS IN
 ADVANCE OF ANY CONSTRUCTION OR DEMOLITION WORK. MORE
 INFORMATION CAN BE FOUND HERE:
 HTTP://WWW.SUNSHINE811.COM/

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-11-02 Cont ID  
Sent By dbattles Date 2018-11-02 Time 16:46 Rev Time 0.00
Received By dbattles Date 2018-10-18 Time 15:23 Sent To  
Notes
2018-10-19 15:23:15RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-10-11 Cont ID  
Sent By dbattles Date 2018-10-11 Time 08:26 Rev Time 0.00
Received By dbattles Date 2018-09-11 Time 13:58 Sent To  
Notes
2018-09-12 13:58:41ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 2 Status P Date 2018-10-30 Cont ID  
Sent By mcruz Date 2018-10-30 Time 16:50 Rev Time 0.00
Received By mcruz Date 2018-10-30 Time 16:49 Sent To ENG
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2018-09-25 Cont ID  
Sent By mcruz Date 2018-09-25 Time 14:46 Rev Time 0.00
Received By mcruz Date 2018-09-25 Time 14:45 Sent To ENG
Notes
2018-09-25 14:46:10ZONING AND LANDSCAPING APPROVED, PROPOSED WORK DOES NOT
 AFFECT PARKING SPACES OR LANDSCAPING.