Plan Review Details - Permit 18090217
Plan Review Stops For Permit 18090217
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-12-13 Cont ID  
Sent By dbattles Date 2019-12-13 Time 10:19 Rev Time 0.00
Received By dbattles Date 2019-12-13 Time 10:19 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-06-18 Cont ID  
Sent By dbattles Date 2019-06-18 Time 08:02 Rev Time 0.00
Received By dbattles Date 2019-06-17 Time 16:10 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-10-19 Cont ID  
Sent By dbattles Date 2018-10-19 Time 07:56 Rev Time 0.00
Received By dbattles Date 2018-10-19 Time 07:56 Sent To  
Notes
2018-10-19 07:57:20****CORRECTIONS****
 W.P.B. PERMIT: 18090217
 REVIEWED: OCTOBER 18, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC ENERGY = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. [FBC AMENDED 107.2.5]SUPPLY A SEPARATE PERMIT
 APPLICATION WITH SEPARATE ADDRESS FOR WEST BUILDING.
  
 2. [FBC AMENDED 107.2.5]THE PROPOSED STRUCTURE ON THE
 EAST SIDE OF PARKING AREA IS ON THE PROPERTY LINE.
 WHILE THE SAME OWNER HOLDS BOTH PARCELS, A UNITY OF
 TITLE WOULD NEED TO COMBINE THE PROPERTY INTO ONE
 PARCEL.
 SUBMIT APPLICATION TO THE ENGINEERING DEPARTMENT:
 HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR
 MS,-PERMITS-APPLICATIONS
 IF THIS HAS ALREADY BEEN DONE, PLEASE PROVIDE A COPY OF
 THE RECORDED DOCUMENT.
  
 3. [FBC AMENDED 107.2.5]SHEET S-1 HAS SECTION CUTS THAT
 REFER TO SHEET S-2. PLEASE PROVIDE SHEET S-2 TO SHOW
 THE REST OF THE STRUCTURE. I SEE FOUNDATION AND I-BEAM
 POSTS, BUT I CAN?T TELL WHAT THE POSTS ARE FOR. IS
 THERE A ROOF STRUCTURE? FULL REVIEW WILL BE COMPLETED
 UPON RECEIPT OF ALL DRAWINGS. ALSO, CO-ORDINATE WITH A
 SHEETS SO SIZES AND ELEVATIONS MATCH.
  
 4. [FBC AMENDED 107.2.5]UPDATE SHEET S-1 STRUCTURAL
 DESIGN CRITERIA AND CODE.
 D-3 PROVIDE LOADS FOR THIS PROJECT.
 D-4 THE STRUCTURES ARE NOT ENCLOSED
  
 5. [FBC 401.4]PROVIDE COPY OF GEOTECHNICAL REFERENCED
 IN GEOTECHNICAL AND FOUNDATIONS F-1
  
 6. [FBC 1609.1]PROVIDE DETAILS OF HOW EQUIPMENT IS
 ATTACHED TO THE PAD.
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-06-19 Cont ID  
Sent By jpearson Date 2019-06-19 Time 09:30 Rev Time 0.00
Received By jpearson Date 2019-06-18 Time 15:35 Sent To  
Notes
2019-06-19 09:37:57APPROVED WITH PROVISO ON PLAN: HIGH-LEG MARKING PER NEC
 110.15.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-09-24 Cont ID  
Sent By jpearson Date 2018-09-24 Time 10:04 Rev Time 0.00
Received By jpearson Date 2018-09-24 Time 07:26 Sent To  
Notes
2018-09-24 10:04:12CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PLAN IS REQUIRED TO BE DESIGNED BY AN ELECTRICAL
 ENGINEER AS IT EXCEEDS THE VALUES PERMITTED IN FLORIDA
 STATUTE 471.003(2)(H).
 2. PLAN PROVIDED SHOWS INSTALLATIONS FOR DIFFERENT
 BUIDLINGS WHICH HAVE A DIFFERENT ADDRESS. THERE SHOULD
 BE TWO PERMIT APPLICATION, ONE FOR EACH ADDRESS.
 PROVIDE SECOND PERMIT APPLICATION WITH PERTINENT
 INFORMATION FOR EACH PROJECT. REMOVE ANY INFORMATION
 FROM THIS PACKET WHICH DOES NOT PERTAIN TO 435 SOUTHERN
 BLVD. WPB FBC 105.1
 3. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. FBC 109.3
 4. BUILDING PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH
 SCALE UPON SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE
 MEDIUM. PROVIDE CORRECTION. WPB FBC 107.2.1.3
 5. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30
 6. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY
 SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230,
 250.50, 250.94, 408.30
 7. PROVIDE PANEL SCHEDULE FOR EACH PANEL INDICATING ANY
 NEW OR ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR
 THESE CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE
 APPLICABLE TO COMPLY WITH CODE. NEC 210.8, 210.12,
 210.19, 210.20, 215.5, 408.4
 8. PROVIDE AIC RATING OF EACH PANEL. NEC 110.3, 110.9
 9. PROVIDE AIC CALCULATION FOR EACH NEW PANEL
 INSTALLED. NEC 110.10
 10. PLAN SHOWS A NEUTRAL CONDUCTOR GOING TO 80KVA
 TRANSFORMER. PROVIDE CORRECTION. NEC 250.30
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-06-19 Cont ID  
Sent By pleduc Date 2019-06-19 Time   Rev Time 0.00
Received By pleduc Date 2019-06-19 Time 14:23 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-09-17 Cont ID  
Sent By pleduc Date 2018-09-17 Time   Rev Time 0.00
Received By pleduc Date 2018-09-14 Time 11:54 Sent To  
Notes
2018-09-17 10:37:13THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THE SUBMITTED PLAN SHEETS WHERE NOT PROVIDED WITH
 ANY KIND OF ORDER AND WERE NOT ORGAINIZED OR BOUND
 TOGETHER AS SETS.
  
 PER NFPA 1
  
 1.7.11 PLANS AND SPECIFICATIONS.
  
 1.7.11.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS.
  
  
 PLEASE REVIEW AND PROVIDE COMPLETED SETS IN AN
 ORGANIZED MANNER
  
  
  
 2) THERE ARE NO INDICATIONS OF A FIRE SPRINKLER SYSTEM
 IN EITHER OF THE BUILDINGS.
  
 PER NFPA 1, CHAPTER 13, FIRE PROTECTION SYSTEMS
  
 13.3.2.28 WOODWORKING OPERATIONS. AN APPROVED AUTOMATIC
 FIRE SPRINKLER SYSTEM SHALL BE INSTALLED IN BUILDINGS
 CONTAINING
 WOODWORKING OPERATIONS EXCEEDING 2500 FT2 (232 M2) THAT
 USE
 EQUIPMENT, MACHINERY, OR APPLIANCES; THAT GENERATE
 FINELY DIVIDED
 COMBUSTIBLE WASTE; OR THAT USE FINELY DIVIDED
 COMBUSTIBLE
 MATERIALS.
  
 PLEASE REVIEW AND PROVIDE FOR THE REQUIREMENT OF
 JUSTIFY,
  
  
 CHAPTER 40 DUST EXPLOSION AND FIRE PREVENTION
  
 40.1 GENERAL. EQUIPMENT, PROCESSES, AND OPERATIONS THAT
 INVOLVE
 THE MANUFACTURE, PROCESSING, BLENDING, REPACKAGING, OR
 HANDLING
 OF COMBUSTIBLE PARTICULATE SOLIDS OR COMBUSTIBLE DUSTS
 REGARDLESS
 OF CONCENTRATION OR PARTICLE SIZE SHALL BE INSTALLED
 AND MAINTAINED
 IN ACCORDANCE WITH THIS CHAPTER AND THE FOLLOWING
 STANDARDS AS
 APPLICABLE:
 (1) NFPA 61, STANDARD FOR THE PREVENTION OF FIRES AND
 DUST
 EXPLOSIONS IN AGRICULTURAL AND FOOD PROCESSING
 FACILITIES
 (2) NFPA 69, STANDARD ON EXPLOSION PREVENTION SYSTEMS
 (3) NFPA 85, BOILER AND COMBUSTION SYSTEMS HAZARDS CODE
 (4) NFPA 120, STANDARD FOR FIRE PREVENTION AND CONTROL
 IN
 COAL MINES
 (5) NFPA 484, STANDARD FOR COMBUSTIBLE METALS
 (6) NFPA 654, STANDARD FOR THE PREVENTION OF FIRE AND
 DUST
 EXPLOSIONS FROM THE MANUFACTURING, PROCESSING, AND
 HANDLING OF COMBUSTIBLE PARTICULATE SOLIDS
 (7) NFPA 655, STANDARD FOR PREVENTION OF SULFUR FIRES
 AND
 EXPLOSIONS
 (8) NFPA 664, STANDARD FOR THE PREVENTION OF FIRES AND
 EXPLOSIONS IN WOOD PROCESSING AND WOODWORKING
 FACILITIES
  
  
  
  
 3) THERE ARE NO INDICATIONS THAT THE PROPOSED PROJECT
 IS IN COMPLIANCE OR REVIEWED THROUGH THE REQUIREMENTS
 OF NFPA 664
  
 PER NFPA 1, CHAPTER 31, FOREST PRODUCTS
  
 31.1* GENERAL. THE STORAGE, MANUFACTURING, AND
 PROCESSING OF
 TIMBER, LUMBER, PLYWOOD, VENEERS, AND BY-PRODUCTS SHALL
 BE IN
 ACCORDANCE WITH THIS CHAPTER AND NFPA 664, STANDARD FOR
 THE
 PREVENTION OF FIRES AND EXPLOSIONS IN WOOD PROCESSING
 AND
 WOODWORKING FACILITIES.
  
 31.3.9 WOOD PROCESSING AND WOODWORKING FACILITIES. DUST
 CONTROL
 SHALL BE IN ACCORDANCE WITH NFPA 664 FOR COMBUSTIBLE
 DUSTPRODUCING
 OPERATIONS THAT OCCUPY AREAS OF MORE THAN 5000 FT2 (464
 M2), OR TO AREAS WHERE DUST-PRODUCING EQUIPMENT
 REQUIRES AN
 AGGREGATE DUST COLLECTION FLOW RATE OF MORE THAN 1500
 FT3/MIN (2549
 M3/HR).
  
  
 PLEASE REVIEW AND PROVIDE A NOTE OF ACKNOWLEDGEMENT OF
 COMPLIANCE OR JUSTIFY THAT IT IS NOT REQUIRED WITH
 SPECIFIC CODE REFERENCES
  
  
  
  
 4) THERE IS NO INDICATION OF A COMPLIANCE OPTION PER
 NFPA 664.
  
 4.7 COMPLIANCE OPTIONS.
 4.7.1 OPTIONS. LIFE SAFETY, PROPERTY PROTECTION, AND
 MISSION
 CONTINUITY MEETING THE GOALS AND OBJECTIVES OF SECTION
 4.1 AND
 SECTION 4.6 SHALL BE PROVIDED IN ACCORDANCE WITH EITHER
 OF THE
 FOLLOWING:
 (1) PERFORMANCE-BASED PROVISIONS PER 4.7.2
 (2) PRESCRIPTIVE-BASED PROVISIONS PER 4.7.3
  
  
 PLEASE REVIEW AND PROVIDE SPECIFIC DETAILS.
  
  
  
 5) THERE IS AN INDICATION OF A SPRAY BOOTH AS PART OF
 THIS SUBMITTAL
  
 THE SPRAY BOOTH SHALL BE SUBMITTED UNDER SEPARATE SHOP
 DRAWINGS.
  
 PLEASE SUBMIT SEPARATE SHOP DRAWINGS FOR THE PROPOSED
 SPRAY BOOTH.
  
  
  
  
 6) THERE IS NO INDICATIONS OF FIRE PROTECTION OF THE
 PROPOSED SPRAY BOOTH.
  
 PER NFPA 1
  
 CHAPTER 43 SPRAYING, DIPPING, AND COATING USING
 FLAMMABLE OR COMBUSTIBLE MATERIALS
  
 43.1 APPLICATION.
 43.1.1* OPERATIONS INVOLVING THE SPRAY APPLICATION OF
 FLAMMABLE
 AND COMBUSTIBLE MATERIALS SHALL COMPLY WITH NFPA 33,
 STANDARD
 FOR SPRAY APPLICATION USING FLAMMABLE OR COMBUSTIBLE
 MATERIALS, AND SECTION 43.1.
  
 43.1.7 PROTECTION.
 43.1.7.1* GENERAL. SPRAY AREAS, WHICH INCLUDE BY
 DEFINITION ANY
 ASSOCIATED EXHAUST PLENUMS AND EXHAUST DUCTWORK, ANY
 PARTICULATE
 FILTERS, ANY SOLVENT CONCENTRATOR UNITS, ANY
 RECIRCULATION AIR SUPPLY
 UNITS, AND MIXING ROOMS, SHALL BE PROTECTED WITH AN
 APPROVED
 AUTOMATIC FIRE PROTECTION SYSTEM.
  
 PLEASE PROVIDE FOR THE REQUIRED PROTECTION OR JUSTIFY
 WHY NOT WITH SPECIFIC CODE REFERENCES.
  
  
  
  
 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-12-13 Cont ID  
Sent By dbattles Date 2019-12-13 Time 10:19 Rev Time 0.00
Received By dbattles Date 2019-12-06 Time 14:51 Sent To  
Notes
2019-12-09 14:51:43RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-06-23 Cont ID  
Sent By cpuell Date 2019-06-23 Time 08:52 Rev Time 0.00
Received By cpuell Date 2019-06-13 Time 15:51 Sent To  
Notes
2019-06-14 15:51:34B15

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-10-19 Cont ID  
Sent By dbattles Date 2018-10-19 Time 07:58 Rev Time 0.00
Received By dbattles Date 2018-09-07 Time 08:31 Sent To  
Notes
2018-09-12 08:31:11B18

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2019-12-12 Cont ID  
Sent By ccole Date 2019-12-12 Time 08:40 Rev Time 0.00
Received By ccole Date 2019-12-12 Time 07:28 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2019-06-17 Cont ID  
Sent By ccole Date 2019-06-17 Time 09:40 Rev Time 0.00
Received By ccole Date 2019-06-17 Time 08:15 Sent To  
Notes
2019-06-17 10:11:042ND REVIEW FBC-2017 MECHANICAL
 PERMIT #18090217
 9/27/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED
  
 THE RESULTS FROM THE 1ST REVIEW COMMENTS ARE INDICATED
 BELOW.
  
 1) OK
  
 2) OK
  
 3) STILL EXISTS- GENERAL SCOPE OF WORK NOTES ON NEW M-1
 SHEET INCLUDES THE PAINT SPRAY BOOTH. (PLEASE NOTE THAT
 A SEPARATE PERMIT IS REQUIRED FOR THE SPRAY BOOTH SO IT
 WILL NOT BE REVIEWED AT THIS TIME. THE CONTRACTOR OF
 RECORD SHALL SUBMIT A SEPARATE APPLICATION AND TWO SETS
 OF PLANS AND SPECIFICATIONS FOR REVIEW.)
  
 4) STILL EXISTS- NO CONTRACT OR DOCUMENTATION SUBMITTED
 TO VERIFY COSTS. (THE $50,000 JOB VALUE ON THE PERMIT
 APPLICATION APPEARS LOW FOR THE SCOPE OF THE PROPOSED
 PROJECT. PLEASE SUBMIT DETAILED ESTIMATES AND/OR BONA
 FIDE CONTRACTS FOR ALL PHASES OF THE PROJECT INCLUDING
 STRUCTURAL, ELECTRIC, MECHANICALL, PLUMBING, INTERIOR
 AND EXTERIOR FINISH, SITE WORK, DESIGN FEES, AND OVER
 HEAD AND PROFIT. PLEASE NOTE VALUE IS BASED ON LABOR,
 MATERIALS, AND EQUIPMENT.)
  
 5) STILL EXISTS- NEW SHEETS A-1 & A-2 SHOW THE 15000
 CFM COLLECTOR LOCATED 8'4" TO THE ROLL UP DOOR. WHETHER
 NEW OR EXISTING, PROVIDE DOCUMENTATION INDICATING THE
 DOOR IS IMPACT RESISTANT AND CAPABLE OF RESISTING THE
 CURRENT WINDSPEEDS AND PRESSURES PER THE ASCE 7-10- SEE
 SECTION 1609 FBC B. (SHEET A2: THE PLAN DOES NOT
 CLEARLY SHOW THAT THE LOCATIONS OF THE NEW COLLECTORS
 ARE IN COMPLIANCE WITH SECTION 511.1 FBC M WHICH
 REQUIRES A MINIMUM 10' CLEARANCE TO COMBUSTIBLE
 CONSTRUCTION AND ALSO UNPROTECTED OPENINGS INTO THE
 BUILDINGS.)
  
 6) STILL EXISTS- BASED ON COMMENT 35 ABOVE, A METAL
 VENT PIPE MAY BE REQUIRED TO BE LOCATED ABOVE THE
 HIGHEST ROOF LEVEL WITH A DISTANCE OF 30'- SECTION
 511.1 FBC M. (A-2, M3, & M4: THE COLLECTOR DRAWINGS ARE
 INCONSISTENT ON HOW THE COLLECTION, EXHAUST, AND RETURN
 SYSTEMS ARE FUNCTIONING. THERE ARE NO EXHAUST
 DISCHARGES SHOWN, OR LABELED FOR THE COLLECTORS,
 HOWEVER THERE APPEARS TO BE A RETURN AIR DUCT INTO THE
 BUILDING AS SHOWN ON SHEETS A2 & M3. PLEASE VERIFY
 COMPLIANCE WITH SECTION 511.1.3).
  
 7) STILL EXISTS- SPACING OF HANGERS AND ATTRACHMENT TO
 THE STRUCTURE NOT PROVIDED (PROVIDE TYPICAL DETAILS FOR
 DUCT HANGING AND SUPPORT INCLUDING SPACING OF THE
 HANGERS,).
  
 8) STILL EXISTS- NOT PROVIDED SHEETS S1 & M3: THE
 STRUCTURAL ENGINEER OF RECORD MUST PROVIDE COMPLETE
 DETAILS FOR CONSTUCTION OF THE STEEL FRAIMING AND
 SUPPORT BASES FOR THE COLLECTORS INCLUDING WIND LOAD
 ENGINEERING FOR ATTACHING THE COLLECTORS TO THE
 SUPPORTS AND THE SUPPORTS TO THE FOUNDATIONS- SECTION
 301.15 FBC M.).
  
 9) STILL EXISTS- NOT PROVIDED (A FLORIDA LICENSED
 MECHANICAL CONTRACTOR SHALL SUBMIT A SUB-PERMIT
 APPLICATION FOR INSTALLATION OF THE DUCT COLLECTORS AND
 DUCT SYSTEMS- SECTION 489.113 (I) FS.).
  
 10) NEW COMMENT: SHOW THE LOCATION OF THE REQUIRED
 EXPLOSION RELIEF VENT- SECTION 511.1.5 FBC M.
  
 11) NEW COMMENT, SHEET M-3: MUCH OF THE PRINT IN THE
 MAXI-FILTER DETAILS IS TOO FAINT TO READ AND SCAN INTO
 THE CITY'S COMPUTER FILES- SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-09-27 Cont ID  
Sent By ccole Date 2018-09-27 Time 17:54 Rev Time 0.00
Received By ccole Date 2018-09-27 Time 17:54 Sent To  
Notes
2018-09-27 18:26:541ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18090217
 9/27/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) DESIGN CRITERIA: PROVIDE A LIST OF CURRENT CODES AND
 STANDARDS USED IN THE DESIGN OF THE PROJECT- SECTION
 107.2.1 WPB.
  
 2) PROVIDE ON THE PLAN THE LEVEL OF ALTERATION AS
 OUTLINED IN CHAPTER 5 FBC EX.
  
 3) PLEASE NOTE THAT A SEPARATE PERMIT IS REQUIRED FOR
 THE SPRAY BOOTH SO IT WILL NOT BE REVIEWED AT THIS
 TIME. THE CONTRACTOR OF RECORD SHALL SUBMIT A SEPARATE
 APPLICATION AND TWO SETS OF PLANS AND SPECIFICATIONS
 FOR REVIEW.
  
 4) THE $50,000 JOB VALUE ON THE PERMIT APPLICATION
 APPEARS LOW FOR THE SCOPE OF THE PROPOSED PROJECT.
 PLEASE SUBMIT DETAILED ESTIMATES AND/OR BONA FIDE
 CONTRACTS FOR ALL PHASES OF THE PROJECT INCLUDING
 STRUCTURAL, ELECTRIC, MECHANICALL, PLUMBING, INTERIOR
 AND EXTERIOR FINISH, SITE WORK, DESIGN FEES, AND OVER
 HEAD AND PROFIT. PLEASE NOTE VALUE IS BASED ON LABOR,
 MATERIALS, AND EQUIPMENT.
  
 5) SHEET A2: THE PLAN DOES NOT CLEARLY SHOW THAT THE
 LOCATIONS OF THE NEW COLLECTORS ARE IN COMPLIANCE WITH
 SECTION 511.1 FBC M WHICH REQUIRES A MINIMUM 10'
 CLEARANCE TO COMBUSTIBLE CONSTRUCTION AND ALSO
 UNPROTECTED OPENINGS INTO THE BUILDINGS.
  
 6) A-2, M3, & M4: THE COLLECTOR DRAWINGS ARE
 INCONSISTENT ON HOW THE COLLECTION, EXHAUST, AND RETURN
 SYSTEMS ARE FUNCTIONING. THERE ARE NO EXHAUST
 DISCHARGES SHOWN, OR LABELED FOR THE COLLECTORS,
 HOWEVER THERE APPEARS TO BE A RETURN AIR DUCT INTO THE
 BUILDING AS SHOWN ON SHEETS A2 & M3. PLEASE VERIFY
 COMPLIANCE WITH SECTION 511.1.3:
  
 511.1.3 CONVEYING SYSTEMS EXHAUST DISCHARGE.
 AN EXHAUST SYSTEM SHALL DISCHARGE TO THE OUTSIDE OF THE
 BUILDING EITHER DIRECTLY BY FLUE OR INDIRECTLY THROUGH
 THE BIN OR VAULT INTO WHICH THE SYSTEM DISCHARGES
 EXCEPT WHERE THE CONTAMINANTS HAVE BEEN REMOVED.
 EXHAUST SYSTEM DISCHARGE SHALL BE PERMITTED TO BE
 RECIRCULATED PROVIDED THAT THE SOLID PARTICULATE HAS
 BEEN REMOVED AT A MINIMUM EFFICIENCY OF 99.9 PERCENT AT
 10 MICRONS (10.01 MM), VAPOR CONCENTRATIONS ARE LESS
 THAN 25 PERCENT OF THE LFL, AND APPROVED EQUIPMENT IS
 USED TO MONITOR THE VAPOR CONCENTRATION.
  
 7) PROVIDE TYPICAL DETAILS FOR DUCT HANGING AND SUPPORT
 INCLUDING SPACING OF THE HANGERS,
  
 8) SHEETS S1 & M3: THE STRUCTURAL ENGINEER OF RECORD
 MUST PROVIDE COMPLETE DETAILS FOR CONSTUCTION OF THE
 STEEL FRAIMING AND SUPPORT BASES FOR THE COLLECTORS
 INCLUDING WIND LOAD ENGINEERING FOR ATTACHING THE
 COLLECTORS TO THE SUPPORTS AND THE SUPPORTS TO THE
 FOUNDATIONS- SECTION 301.15 FBC M.
  
 9) A FLORIDA LICENSED MECHANICAL CONTRACTOR SHALL
 SUBMIT A SUB-PERMIT APPLICATION FOR INSTALLATION OF THE
 DUCT COLLECTORS AND DUCT SYSTEMS- SECTION 489.113 (I)
 FS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
2018-09-27 17:55:35 
  
  
  
  
  
  
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2019-06-21 Cont ID  
Sent By llouie Date 2019-06-21 Time   Rev Time 0.00
Received By llouie Date 2019-06-21 Time   Sent To  
Notes
2019-06-21 16:31:19ZONING PROVISOS:
  
 1.) OPAQUE SCREEN REQUIRED FOR THE WEST DUST COLLECTION
 SYSTEM FACING THE STREET SIDE PRIOR TO FINAL
 INSPECTION. SEPARATE PERMIT WILL BE REQUIRED FOR THE
 SCREEN.
  
 2.) PARKING LOT STRIPING SHALL COMPLY WITH THE STRIPING
 REQUIREMENTS OF ZLDR S.94-485.
  
 (REFERENCE: ZBA 3329)
  
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2018-09-18 Cont ID  
Sent By llouie Date 2018-09-18 Time   Rev Time  
Received By llouie Date 2018-09-18 Time   Sent To  
Notes
2018-09-18 16:06:11** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) THE USE ON THE PROPERTY WAS GRANTED A CLASS B
 SPECIAL USE PERMIT (SUBJECT TO CONDITIONS) ON JANUARY
 7, 2016. AS PART OF THE USE APPROVAL, SEVERAL
 CONDITIONS HAD TO BE MET PRIOR TO THE OPERATION OF THE
 PROPERTY AS A WOOD KITCHEN CABINET MANUFACTURING
 BUSINESS. TO DATE, NOT ALL CONDITIONS HAVE BEEN MET. IF
 THE PROPERTY OWNER FAILS TO SATISFY ALL CONDITIONS
 PRIOR TO THE EXPIRATION OF THE CLASS B PERMIT, THE
 CLASS B PERMIT WILL BE REVOKED AND THE USE SHALL CEASE.
 THE OWNER OF THE BUSINESS SHOULD BE REMINDED TO ADDRESS
 ALL CONDITIONS OF APPROVAL.
  
 2.) EXISTING PARKING WILL BE ELIMINATED WITH THE
 ADDITION OF THE DUST COLLECTION SYSTEM LOCATED NEXT TO
 THE EXISTING ONE-STORY INDUSTRIAL BUILDING. PLEASE
 DEMONSTRATE THAT SUFFICIENT PARKING WILL REMAIN FOR THE
 USE WITH THE ELIMINATION OF PARKING STALLS BY PROVIDING
 PARKING CALCULATIONS IN THE PLAN (EXISTING VS.
 PROPOSED).
  
  
 PROVISO: THE REQUIRED LANDSCAPE IMPROVEMENTS AS PART OF
 THE CLASS B APPROVAL SHALL BE INSTALLED PRIOR TO FINAL
 INSPECTION OF THE DUST COLLECTION SYSTEMS. A SEPARATE
 PERMIT FOR LANDSCAPING WILL BE REQUIRED.
  
 NOTES:
  
 REFERENCE: ZBA FINAL ORDER 3329
  
 * REVISION MAY RESULT IN ADDITIONAL COMMENTS.
  
 * ZONE: I
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  