Plan Review Details - Permit 18090178
Plan Review Stops For Permit 18090178
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-09-26 Cont ID  
Sent By rmcdouga Date 2018-09-26 Time 09:26 Rev Time 0.00
Received By rmcdouga Date 2018-09-26 Time 09:26 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-09-20 Cont ID  
Sent By fgiaquin Date 2018-09-20 Time 06:48 Rev Time 0.00
Received By fgiaquin Date 2018-09-20 Time 06:16 Sent To  
Notes
2018-09-20 06:48:28PROVIDE ACCURATE LOAD CALC FOR FINAL NOT "SIZING
 REPORT".

Review Stop G GAS REVIEW
Rev No 4 Status N Date 2018-11-30 Cont ID  
Sent By jleahy Date 2018-11-30 Time 15:16 Rev Time 0.00
Received By jleahy Date   Time   Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2018-11-15 Cont ID  
Sent By tklarge Date 2018-11-15 Time 15:14 Rev Time 0.00
Received By tklarge Date 2018-11-14 Time 14:08 Sent To I
Notes
2018-11-14 14:56:491) THERE ARE MULTIPLE COPIES OF SURVEYS THAT SHOW THE
 GENERATOR IN DIFFERENT LOCATIONS. SUBMIT TWO COPIES OF
 A CLEAN SURVEY WITHOUT ITEMS CROSSED OUT THAT CLEARLY
 SHOW THE LOCATION OF THE GENERATOR. 2017 FBC SEC.
 107.2.1. 2ND REQUEST.
 2) THIS SUBMITTAL IS DISORGANIZED AND CONFUSING. THERE
 ARE MULTIPLE COPIES OF SHEETS AND I HAVE NO IDEA WHICH
 SHEETS ARE APPLICABLE AND WHICH ARE NOT. COMPILE THE
 DOCUMENTS INTO TWO SETS OF COMPLETE PLANS FOR SUBMITTAL
 AND REVIEW. 2017 FBC SEC. 107.1. 2ND REQUEST.
 3) REMOVE ALL OLD DOCUMENTS FROM THE SUBMITTAL PACKAGE.
 2017 FBC SEC. 107.2.1. THERE ARE STILL TWO DIFFERENT
 GAS DRAWINGS IN THIS SUBMITTAL PACKAGE. 2ND REQUEST.
 4) DIFFERENT SURVEYS SHOW THE GAS METER AS NEW AND ALSO
 AS EXISTING. WHICH IS IT? CLARIFY ON THE SURVEYS. 2ND
 REQUEST.
 5) A FEW OF THE SURVEYS SHOW THE GAS METER LABELED AS
 METER #2. ARE THERE TWO GAS METERS ON THIS PROPERTY? IF
 SO, SHOW BOTH METERS ON THE SURVEY. IF NOT, DELETE THE
 LABELING ON THE SURVEY. 2017 FBC SEC. 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2018-10-25 Cont ID  
Sent By tklarge Date 2018-10-25 Time 09:39 Rev Time 0.00
Received By tklarge Date 2018-10-25 Time 06:35 Sent To I
Notes
2018-10-25 09:39:491) THE SUBMITTED GAS DRAWING SHOWS THE BTU LOAD OF THE
 GENERATOR AS 330,000 BTU'S BUT THE GENERATOR SPECS SHOW
 THE FULL BTU LOAD AS 281,000 BTU'S. CLARIFY.
 2) TWO DIFFERENT GAS DRAWINGS ARE SUBMITTED IN THIS
 APPLICATION PACKAGE. REMOVE ALL OLDD DOCUMENTS AND
 SUBMIT TWO COMPLETE SETS OF PLANS THAT CLEARLY REFLECST
 THE SCOPE OF WORK TO BE DONE. FBC 107.2.1.
 3) THERE IS A SHEET FROM ONE STOP GENERATOR SHOP THAT
 STATES THE GENERATOR WILL BE CONNECTING TO AN EXISTING
 GAS LINE BUT A GAS DRAWING HAS BEEN SUBMITTED THAT
 SHOWS A NEW GAS METER FOR THE GENERATOR. CLARIFY. AT
 THIS POINT I HAVE NO IDEA AS TO WHAT IS BEING INSTALLED
 AT THIS SITE.
 4) THERE ARE TWO SURVEYS IN THIS PERMIT APPLICATION
 PACKAGE THAT SHOW TWO DIFFERENT LOCATIONS FOR THE
 GENERATOR AND A THIRD PLAN THAT SHOWS AN ALTOGETHER
 DIFFERENT LOCATION FOR THE GENERATOR. SUBMIT TWO COPIES
 OF A LEGIBLE SURVEY THAT CLEARLY SHOWS THE LOCATION OF
 THE GENERATOR AND THE GAS METER(S). REMOVE ALL OLD
 OCCUMENTS FROM THE PERMIT PACKAGE.
 5) SUBMIT MANUFACTURER?S SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS FOR THE PRESSURE REGULATORS.
 REGULATORS INSTALLED ON THE EXTERIOR OF THE BUILDING
 SHALL BE APPROVED FOR OUTDOOR INSTALLATION. IDENTIFY ON
 THE SPECIFICATION SHEETS WHICH MODEL REGULATOR IS BEING
 INSTALLED AND THE ORIFICE SIZE TO ENSURE THE REGULATOR
 CAN ACCOMMODATE THE BTU LOAD THROUGH THE REGULATOR.2017
 FGC SEC.410.1, 2017 FBC-RES. SEC. G2421.1.
 6) THE LOCATION OF THE GENERATOR IN RELATION TO
 BUILDING OPENINGS AND OPERABLE DOORS AND WINDOWS SHALL
 COMPLY WITH THE MANUFACTURER'S INSTALLATION MANUAL. THE
 STANDARD DISTANCE IS 10 FT.BUT THE MANUAL SHALL BE
 FOLLOWED.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-09-19 Cont ID  
Sent By lcrespo Date 2018-09-19 Time 06:44 Rev Time 0.00
Received By lcrespo Date 2018-09-19 Time 06:43 Sent To  
Notes
2018-09-19 06:44:5609/19/2018 1ST GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THERE IS AN EXISTING GAS SYSTEM AND IT NEEDS TO ADD
 THE BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED
 TO THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE
 EXISTING SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE
 EXISTING SYSTEM MUST BE REDONE TO ENSURE A SAFE
 OPERATING SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM
 THAT SHOWS THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD
 OF EACH APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO
 EACH APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH
 OF PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE
 OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE
 EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE
 SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE
 REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES,
 2017 FBC FUEL GAS RES. SECS.G2412.4, G2412.8, G2413.1,
 G2413.2, G2413.3.
  
 2. I HAVE PUT AN ISOMETRIC DRAWING FOR THE PRIOR SYSTEM
 FOR REFERENCE ONLY IF YOU LIKE ME TO EMAIL YOU A COPY
 JUST EMAIL ME AND I WILL, SUBMIT AN ISOMETRIC DRAWING
 THAT CLEARLY SHOWS THE LENGTH OF ALL CUT SECTIONS OF
 PIPE PER 2017 FBC FUEL GAS RES SECS. G2413.4.1,
 G2413.4.2.
  
 3. THE BTU LOAD FOR THE GENERATOR IS LABELED AS 330,000
 BTU AND THE MANUAL SAYS OTHERWISE, PLEASE CORRECT, WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2018-11-30 Cont ID  
Sent By jleahy Date 2018-11-30 Time 15:16 Rev Time 0.00
Received By jleahy Date 2018-11-19 Time 16:13 Sent To G
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-11-14 Cont ID  
Sent By tklarge Date 2018-11-14 Time 15:15 Rev Time 0.00
Received By tklarge Date 2018-10-31 Time 15:17 Sent To  
Notes
2018-11-01 15:17:57RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-10-25 Cont ID  
Sent By cpuell Date 2018-10-25 Time 09:52 Rev Time 0.00
Received By cpuell Date 2018-10-09 Time 09:32 Sent To  
Notes
2018-10-11 09:32:29RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-09-26 Cont ID  
Sent By rmcdouga Date 2018-09-26 Time 09:26 Rev Time 0.00
Received By rmcdouga Date 2018-09-06 Time 13:21 Sent To  
Notes
2018-09-07 13:21:34ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 2 Status P Date 2018-10-18 Cont ID  
Sent By mcruz Date 2018-10-18 Time 10:40 Rev Time 0.00
Received By mcruz Date 2018-10-18 Time 10:40 Sent To PC
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2018-09-18 Cont ID  
Sent By ajones Date 2018-09-18 Time 10:55 Rev Time 0.00
Received By ajones Date 2018-09-18 Time 10:55 Sent To G
Notes
2018-09-18 11:01:499/18/18- FAILED. MAXIMUN SETBACK FOR GENENATORS IS 4
 FEET INTO ANY REQUIRED SETBACK. THE SIDE SETBACK IS 7.5
 FEET; THEREFORE, THE SETBACK FOR THE GENERATOR IS 3.5
 FEET.
  
 ANGELLA VANN, AICP
 [email protected]
 561-822-1441.