Plan Review Details - Permit 18090114
Plan Review Stops For Permit 18090114
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-01-14 Cont ID  
Sent By pvalenti Date 2019-01-14 Time 13:26 Rev Time 0.00
Received By pvalenti Date 2019-01-14 Time 13:24 Sent To  
Notes
2019-01-14 13:29:04PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 APPROVED WITH PROVISO:
  
 NOTE: AT TIME OF INSPECTION PLEASE PROVIDE PRODUCT
 APPROVALS FOR EXTERIOR DOORS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-01-03 Cont ID  
Sent By cthroop Date 2019-01-03 Time 13:02 Rev Time 0.00
Received By cthroop Date 2019-01-03 Time 07:07 Sent To  
Notes
2019-01-03 13:03:15PROVISO - WINDOW AND DOOR PRODUCT APPROVALS SHALL BE
 REVIEWED AND APPROVED BY DESIGNER PRIOR TO SUBMITTAL
 FOR REVIEW.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-10-25 Cont ID  
Sent By jgomez Date 2018-10-25 Time 17:52 Rev Time 0.00
Received By jgomez Date 2018-10-25 Time 10:29 Sent To  
Notes
2018-10-25 10:55:56 
 RESIDENTIAL (R3)ADDITION/ALTERATION BUILDING REVIEW
 COMMENTS.
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- IMPACT FEES - PAPER SUBMITTALS
  
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE
 PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURNED STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACT-FEES/FORMS/QUESTIONNAIRE.PDF
  
 2- ROOF FRAMING PLAN IS MISSING THE STRUCTURAL
 CONNECTORS OF ALL FRAMING MEMBERS. SEC. R301.1 FBC-
 RESIDENTIAL
  
 3- PROVIDE COMPLETE WALL SECTION AT GABLE END. CLEARLY
 SPECIFY ALL CONNECTIONS AND BRACING AS REQUIRED BY SEC.
 R802.10.3 FBC-RESIDENTIAL. ALSO, INFORMATION SHOWN ON
 THE ROOF FRAMING PLAN AND THE TRUSS ROOF FOR THE
 ADDITION DETAIL SHOWN ON SHEET A-2 DOESN'T MATCH.
 CLARIFY AND COORDINATE WITH ITEM ABOVE. SEC. 107.2.1
 CITY AMENDMENTS.
  
 4- PLANS ARE MISSING INFORMATION ABOUT THE LINTELS AS
 REQUIRED BY SEC. R606.10 FBC-RESIDENTIAL.
  
 5- TYPICAL WALL DETAIL NEW ADDITION ON SHEET A-1:
 PROVIDE COMPLETE SPECIFICATIONS FOR THE ROOF SHEATHING
 AS REQUIRED BY SEC. R803.2.3.1 FBC-RESIDENTIAL. SPECIFY
 REQUIRED TYPE OF NAIL AND NAIL SPACING FOR ALL ROOF
 ZONES INCLUDING THE GABLE END ZONE AS REQUIRED BY
 FIGURE R803.2.3.1 FBC-RESIDENTIAL. NOTE: SEE FIGURE
 R301.2.3.1 FOR MINIMUM DISTANCE TO BE CONSIDERED ZONE 3
 IN GABLE END AREAS.
  
 6- FOUNDATION PLAN ON SHEET A-1 IS MISSING
 SPECIFICATIONS FOR THE TERMITE TREATMENT AS REQUIRED BY
 SEC. R318 FBC-RESIDENTIAL.
  
 7- NEED TO SPECIFY 2 LAYERS OF WATER RESISTIVE BARRIERS
 AS REQUIRED BY SEC. R703.7.3 WATER-RESISTIVE BARRIERS
 AT THE WOOD FRAMED AREA OF THE GABLE END.
  
 8- NEED TO SPECIFY THE 7/8" MIN. STUCCO THICKNESS AS
 REQUIRED BY TABLE R702.1(1) AT THE WOOD FRAMED AREA OF
 THE GABLE END.
  
 9- REVISE DESIGN CRITERIA INFORMATION ON SHEET A-1:
 A) THIS IS ALTERATION LEVEL 3 NOT LEVEL 2 (SEC. 505
 FBC-EXISTING BUILDING). AND, ADDITION (SEC. 507
 FBC-EXISTING BUILDING). REVISE AS REQUIRED.
  
 B) SPECIFY THE BUILDING EXPOSURE AS REQUIRED BY SEC.
 R301.2.1.4 FBC-RESIDENTIAL.
  
 10- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL)
  
 A) WINDOWS (6 AND 7) AS SPECIFIED ON PLANS. NOTE: NOA
 15-0606.06 SPECIFIED ON THE WINDOW SCHEDULE DOESN'T
 EXIST. REVISE INFO IN THE WINDOW SCHEDULE AND PROVIDE
 COPIES OF PRODUCT APPROVAL.
  
 B) DOOR #2 AS SPECIFIED ON PLANS.
  
 C) ALL TRUSSES STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS. COORDINATE WITH ITEM #2 ABOVE. NOTE:
 PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL COVER PAGE
 AND PAGE SHOWING THE SPECIFIED CONNECTOR OR DESIGN
 PROFESSIONAL TO LIST THE FLORIDA PRODUCT APPROVAL
 NUMBER NEXT TO EACH SPECIFIED CONNECTOR.
  
 11- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS
 (INCLUDING ROOF SHINGLES) AS REQUIRED BY SEC. 107.3.4.1
 CITY AMENDMENTS.
  
 12- THIS HOUSE IS A CONTRIBUTING HISTORIC HOUSE. ENERGY
 CALCULATIONS ARE NOT REQUIRED. IF CONTRACTOR WANTS TO
 SUBMIT THEN REVISE THE FOLLOWING. NEED OWNER/AGENT
 CERTIFICATION AT THE BOTTOM OF FORM, NEED TO COMPLETE
 TOP OF FORM (OWNER, BUILDER, PERMIT OFFICE). NUMBER OF
 BEDROOMS IS INCORRECT. CONDITIONED FLOOR AREA DOESN'T
 MATCH PLANS. NEED DOCUMENTATION SHOWING THE U-FACTOR
 AND SHGC FACTOR OF WINDOWS SHOWN ON ITEM #7. NEED TO
 SHOW COMPLIANCE WITH THE CROSS VENTILATION CREDIT TAKEN
 ON ITEM #15. NEED TO REVISE THE ATTIC VENTILATION RATIO
 ON PAGE 3 OF 5.
 SEC. 107.2.1 CITY AMENDMENTS.
  
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
  
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY
 REVIEWED DRAWINGS. DO NOT STAPLE OLD DRAWINGS TO PLANS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-12-24 Cont ID  
Sent By jpearson Date 2018-12-24 Time 11:12 Rev Time 0.00
Received By jpearson Date 2018-12-24 Time 11:11 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-10-01 Cont ID  
Sent By jpearson Date 2018-10-01 Time 10:47 Rev Time 0.00
Received By jpearson Date 2018-10-01 Time 08:25 Sent To  
Notes
2018-10-01 10:47:40CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. AFCI PROTECTION SHOWN IN NOT CODE COMPLIANT. ALL
 BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15-
 AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND
 POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH
 AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8, 210.12; FBC RE E3902; FBC EX 607.1.1 OR 801.1,
 801.2, OR 901.2 AS APPLICABLE.
 2. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10; FBC RE E3606.3
 3. PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANEL.
 NEC 110.3, 110.9; FBC RE E3603.3
 4. PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE.
 FBC EC C405.1, R404.1
 5. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT
 SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3
 6. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS. THE AC/AHU LOAD IS NOT PERMITTED TO BE INCLUDED
 IN THE GENERAL DEMAND. PROVIDE LOAD CALCULATION PER THE
 FORMAT IN THE FBC RESIDENTIAL. NEC 220; FBC RE E3602.2
 7. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12; FBC RE E4002.14
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2019-01-09 Cont ID  
Sent By fmittner Date 2019-01-09 Time 11:27 Rev Time 0.00
Received By fmittner Date 2019-01-09 Time 11:27 Sent To B
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2018-11-13 Cont ID  
Sent By fmittner Date 2018-11-13 Time 16:56 Rev Time 0.00
Received By fmittner Date 2018-11-13 Time 16:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-01-14 Cont ID  
Sent By pvalenti Date 2019-01-14 Time 13:50 Rev Time 0.00
Received By pvalenti Date 2019-01-07 Time 14:10 Sent To  
Notes
2019-01-14 09:22:411/14 TO PV DESK
  
  
2019-01-08 14:10:42RESUB ROUTED TO HISTORIC INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-01-03 Cont ID  
Sent By cthroop Date 2019-01-03 Time 13:03 Rev Time 0.00
Received By cthroop Date 2018-12-05 Time 15:25 Sent To  
Notes
2018-12-06 15:25:43R09

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-11-14 Cont ID  
Sent By cpuell Date 2018-11-14 Time 10:03 Rev Time 0.00
Received By cpuell Date 2018-09-05 Time 10:02 Sent To  
Notes
2018-11-06 08:48:2311/6 TO FM
  
2018-09-07 10:02:47R18

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2019-01-14 Cont ID  
Sent By pvalenti Date 2019-01-14 Time 13:30 Rev Time 0.00
Received By pvalenti Date 2019-01-14 Time 13:29 Sent To  
Notes
2019-01-14 13:50:01PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 APPROVED:
  
 RECEIVED THE COUNTY STAMPED SET OF PLANS AND RECEIPT
 FOR IMPACT FEES.
  
 COUNTY RECEIPT # 2019-0108-325
 COUNTY TRACKING # MU-2019-000557-0000

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-10-25 Cont ID  
Sent By jgomez Date 2018-10-25 Time 10:58 Rev Time 0.00
Received By jgomez Date 2018-10-25 Time 10:58 Sent To  
Notes
2018-10-25 10:58:42IMPACT FEES - PAPER SUBMITTALS
  
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE
 PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURNED STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-12-21 Cont ID  
Sent By cmontell Date 2018-12-21 Time 14:28 Rev Time 0.00
Received By cmontell Date 2018-12-21 Time 14:22 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-10-15 Cont ID  
Sent By cmontell Date 2018-10-15 Time 13:26 Rev Time 0.00
Received By cmontell Date 2018-10-15 Time 13:24 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-01-03 Cont ID  
Sent By cthroop Date 2019-01-03 Time 13:03 Rev Time 0.00
Received By cthroop Date 2019-01-03 Time 07:07 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-10-02 Cont ID  
Sent By lcrespo Date 2018-10-02 Time 18:30 Rev Time 0.00
Received By lcrespo Date 2018-10-02 Time 07:26 Sent To  
Notes
2018-10-02 18:31:1110/02/18 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVE PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2018-10-25 Cont ID  
Sent By jgomez Date 2018-10-25 Time 17:56 Rev Time 0.00
Received By jgomez Date 2018-10-25 Time 17:56 Sent To  
Notes
2018-10-25 17:57:12SHINGLES NOA 18-0123.06.

Review Stop Z ZONING
Rev No 1 Status P Date 2018-11-13 Cont ID  
Sent By fmittner Date 2018-11-13 Time 16:56 Rev Time 0.00
Received By fmittner Date 2018-11-13 Time 16:56 Sent To  
Notes
***NONE***