Plan Review Details - Permit 18090102
Plan Review Stops For Permit 18090102 |
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2018-09-25 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2018-09-25 |
Time |
10:31 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2018-09-25 |
Time |
10:31 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2018-10-04 |
|
|
Cont ID |
|
Sent By |
lmarchan |
Date |
2018-10-04 |
Time |
15:14 |
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2018-09-06 |
Time |
16:19 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2018-10-04 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2018-09-25 |
Time |
14:38 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2018-09-25 |
Time |
14:38 |
Sent To |
|
|
Notes |
2018-09-25 15:25:34 | MECHANICAL PROVISOS: | | REVISION #18090102 | | MASTER #18020252 | | 10/4/18 | | | | 1) SHEET M103, 3RD-9TH FLOORS: PROVIDE FIRE DAMPERS FOR | | THE 12X12 AND !2X10 SUPPLY DUCTS PENETRATING THE | | FIRE-RATED CORRIDOR WALLS- SECTION 607.5.3 FBC M. | | | | 2) ACCORDING TO THE NARRATIVE SUBMITTED WITH THE | | REVISED PLANS, THERE ARE CHANGES TO THE DUCTWORK ON THE | | 10TH FLOOR (SHEET M104), HOWEVER THE REVISED PLAN WAS | | NOT UPLOADED FOR REVIEW. PLEASE PROVIDE THE PLAN. | | | | 3) M106: THERE IS NO CODE REQUIREMENT FOR SMOKE | | DETECTORS TO BE LOCATED BY THE STAIR PRESSURIZATION | | FANS IN THE INTERIOR EXIT STAIRWAYS. PLEASE PROVIDE A | | RATIONAL ANALYSIS TO CLARIFY THE FUNCTION AND CONTROLS | | OPERATION OF THE DEVICES, AND HOW THEY WILL BE | | SUPERVISED. | | | | 4) M106: PROVIDE FIRE-RATED DUCTS FOR THE ELEVATOR | | PRESSURIZATION FAN SYSTEMS- SECTION 909.21.3 FBC B. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2018-10-04 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2018-10-04 |
Time |
14:53 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2018-10-04 |
Time |
04:05 |
Sent To |
|
|
Notes |
2018-10-04 12:54:52 | THE FOLLOWING ITEMS ARE PROVISOS AND MUST BE ADDRESSED | | BEFORE ANY FINAL INSPECTIONS ARE SCHEDULED FOR ANY OF | | THESE SYSTEMS. | | | | SUBMIT A DETAIL OF THE CONDENSATE DRYWELL FOR REVIEW. | | 2017 FBC SEC. 107.2.1. | | SHT. P-102 - SHOW THE SQUARE FOOT AREA OF THE ROOF OF | | THE PORTE COCHERES BEING DRAINED. INCLUDE ONE-HALF OF | | THE AREA OF ANY PARAPET WALLS. 2017 FPC SEC.1106.4. | | SUBMIT SPECIFICATIONS FOR THE COMBO ROOF DRAINS. | | SHT. P-101. CLOUD AND IDENTIFY THE CHANGES MADE TO THE | | PLUMBING SYSTEM. CURRENTLY, THERE ARE NO CHANGES SHOWN | | ON THIS SHEET. CLARIFY. | | SUBMIT REVISED PIPING RISERS FOR THE SANITARY, STORM, | | AND CONDENSATE SYSTEMS THAT CLEARLY REFLECT ALL THE | | CHANGES MADE TO THESE SYSTEMS. SHOW THE LINT TRAP ON | | THE RISER AND SUBMIT A DETAIL OF THE LINT TRAP. FBC | | 107.2.1. | | SUBMIT A REVISED GAS RISER WITH THE CORRECT PIPE | | SIZING. | | | | SPECIFICATION SHEETS FOR ALL GAS | | EQUIPMENT TO VERIFY COMPLIANCE | | WITH STANDARDS NFPA 54, NFPA 58, AND | | FBC-2014 FUEL GAS SEC. 301.3. | | | | LOCATION, LENGTH, SIZE AND | | TERMINATION OF THE GAS VENTS PER | | FBC-2014 FUEL GAS CODE SEC. 502 THRU | | 504. SUBMIT CALCULATIONS FOR | | COMBUSTION AIR PER THE FBC-2014 | | FUEL GAS CODE SEC. 304. FOR BOILERS | | | | COMBUSTION AIR PER THE FBC-2014 | | FUEL GAS CODE SEC. 304. FOR BOILER | | AND DRYERS | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | | | |
|
|
Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
Rev No |
1 |
Status |
P |
Date |
2018-09-25 |
|
|
Cont ID |
|
Sent By |
jpearson |
Date |
2018-09-25 |
Time |
08:06 |
Rev Time |
0.00 |
Received By |
jpearson |
Date |
2018-09-25 |
Time |
08:06 |
Sent To |
|
|
Notes |
2018-09-25 08:06:17 | ALL SHEETS OK. WILL NEED TO CONFIRM IF RE-SUBMITTAL | | REQUIRED. |
|
|
|