Plan Review Details - Permit 18090102
Plan Review Stops For Permit 18090102
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-09-25 Cont ID  
Sent By jpearson Date 2018-09-25 Time 10:31 Rev Time 0.00
Received By jpearson Date 2018-09-25 Time 10:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-10-04 Cont ID  
Sent By lmarchan Date 2018-10-04 Time 15:14 Rev Time 0.00
Received By lmarchan Date 2018-09-06 Time 16:19 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-10-04 Cont ID  
Sent By ccole Date 2018-09-25 Time 14:38 Rev Time 0.00
Received By ccole Date 2018-09-25 Time 14:38 Sent To  
Notes
2018-09-25 15:25:34MECHANICAL PROVISOS:
 REVISION #18090102
 MASTER #18020252
 10/4/18
  
 1) SHEET M103, 3RD-9TH FLOORS: PROVIDE FIRE DAMPERS FOR
 THE 12X12 AND !2X10 SUPPLY DUCTS PENETRATING THE
 FIRE-RATED CORRIDOR WALLS- SECTION 607.5.3 FBC M.
  
 2) ACCORDING TO THE NARRATIVE SUBMITTED WITH THE
 REVISED PLANS, THERE ARE CHANGES TO THE DUCTWORK ON THE
 10TH FLOOR (SHEET M104), HOWEVER THE REVISED PLAN WAS
 NOT UPLOADED FOR REVIEW. PLEASE PROVIDE THE PLAN.
  
 3) M106: THERE IS NO CODE REQUIREMENT FOR SMOKE
 DETECTORS TO BE LOCATED BY THE STAIR PRESSURIZATION
 FANS IN THE INTERIOR EXIT STAIRWAYS. PLEASE PROVIDE A
 RATIONAL ANALYSIS TO CLARIFY THE FUNCTION AND CONTROLS
 OPERATION OF THE DEVICES, AND HOW THEY WILL BE
 SUPERVISED.
  
 4) M106: PROVIDE FIRE-RATED DUCTS FOR THE ELEVATOR
 PRESSURIZATION FAN SYSTEMS- SECTION 909.21.3 FBC B.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-10-04 Cont ID  
Sent By gjohnson Date 2018-10-04 Time 14:53 Rev Time 0.00
Received By tklarge Date 2018-10-04 Time 04:05 Sent To  
Notes
2018-10-04 12:54:52THE FOLLOWING ITEMS ARE PROVISOS AND MUST BE ADDRESSED
 BEFORE ANY FINAL INSPECTIONS ARE SCHEDULED FOR ANY OF
 THESE SYSTEMS.
  
 SUBMIT A DETAIL OF THE CONDENSATE DRYWELL FOR REVIEW.
 2017 FBC SEC. 107.2.1.
 SHT. P-102 - SHOW THE SQUARE FOOT AREA OF THE ROOF OF
 THE PORTE COCHERES BEING DRAINED. INCLUDE ONE-HALF OF
 THE AREA OF ANY PARAPET WALLS. 2017 FPC SEC.1106.4.
 SUBMIT SPECIFICATIONS FOR THE COMBO ROOF DRAINS.
 SHT. P-101. CLOUD AND IDENTIFY THE CHANGES MADE TO THE
 PLUMBING SYSTEM. CURRENTLY, THERE ARE NO CHANGES SHOWN
 ON THIS SHEET. CLARIFY.
 SUBMIT REVISED PIPING RISERS FOR THE SANITARY, STORM,
 AND CONDENSATE SYSTEMS THAT CLEARLY REFLECT ALL THE
 CHANGES MADE TO THESE SYSTEMS. SHOW THE LINT TRAP ON
 THE RISER AND SUBMIT A DETAIL OF THE LINT TRAP. FBC
 107.2.1.
 SUBMIT A REVISED GAS RISER WITH THE CORRECT PIPE
 SIZING.
  
 SPECIFICATION SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE
 WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2014 FUEL GAS SEC. 301.3.
  
 LOCATION, LENGTH, SIZE AND
 TERMINATION OF THE GAS VENTS PER
 FBC-2014 FUEL GAS CODE SEC. 502 THRU
 504. SUBMIT CALCULATIONS FOR
 COMBUSTION AIR PER THE FBC-2014
 FUEL GAS CODE SEC. 304. FOR BOILERS
  
 COMBUSTION AIR PER THE FBC-2014
 FUEL GAS CODE SEC. 304. FOR BOILER
 AND DRYERS
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2018-09-25 Cont ID  
Sent By jpearson Date 2018-09-25 Time 08:06 Rev Time 0.00
Received By jpearson Date 2018-09-25 Time 08:06 Sent To  
Notes
2018-09-25 08:06:17ALL SHEETS OK. WILL NEED TO CONFIRM IF RE-SUBMITTAL
 REQUIRED.