Plan Review Details - Permit 18090013
Plan Review Stops For Permit 18090013
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-11-07 Cont ID  
Sent By jwitmer Date 2018-11-07 Time 07:29 Rev Time 0.00
Received By jwitmer Date 2018-11-07 Time 07:05 Sent To M
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date   Cont ID  
Sent By   Date   Time 11:12 Rev Time 0.00
Received By jwitmer Date 2018-10-31 Time 09:51 Sent To  
Notes
2018-10-31 10:52:402017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18090013
 ADD: 440 COLUMBIA DR. SUITE:100
 CONT: FISHER CONTRACTING CORP.
 TEL: 561-691-4716
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. OCT. 31/2018
 ACTION: DENIED
  
 1) PERMIT APPLICATION. UNDER THE HEADING OF ADDRESS AND
 SUITE, THE SUITE INDICATES 110.THE PLANS INDICATE
 SUITES 100A AND 100B IN THE RECEPTION AREAS. PLEASE
 PROVIDE IF THE PERMIT IS FOR ONLY 1 SUITE OR 2 AND THE
 SUITES NUMBERS. 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 2) SHEET A4.1.2 (A100) AND SHEET A4.14 (B100) BOTH SHOW
 A RECEPTION DESK WITH A DOUBLE TIER TOP. THE UPPER TOP
 IS AT A HEIGHT OF 42 INCHES. WITH THIS BEING A BUSINESS
 OCCUPANCY IT WOULD BE HARD TO DETERMINE IF PAYMENTS FOR
 SERVICES RENDERED WOULD BE REQUIRED, WHERE EITHER
 CHECKS AND OR CREDIT CARD TRANSACTIONS WOULD TAKE PLACE
 AND COMPLIANCE WITH THE 2017 FBC-ACCESSIBILITY CODE
 SECTIONS 902.3 AND OR 904.4.
 CHECK WRITING SURFACES. 2017 ACCESS. CODE 904.3.3 CHECK
 WRITING SURFACES.
 WHERE PROVIDED, CHECK WRITING SURFACES SHALL COMPLY
 WITH 902.3.
 902.3HEIGHT. THE TOPS OF WORK SURFACES SHALL BE 28
 INCHES (710 MM) MINIMUM AND 34 INCHES (865 MM) MAXIMUM
 ABOVE THE FINISH FLOOR OR GROUND.
 904.4 SERVICE COUNTERS. SALES COUNTERS AND SERVICE
 COUNTERS SHALL COMPLY WITH 904.4.1 OR 904.4.2. THE
 ACCESSIBLE PORTION OF THE COUNTER TOP SHALL EXTEND THE
 SAME DEPTH AS THE SALES OR SERVICE COUNTER TOP.
 THIS ADVISORY ONLY APPLIES TO EMPLOYEES!!! ADVISORY
 226.1. IN FACILITIES COVERED BY THE ADA, THIS
 REQUIREMENT DOES NOT APPLY TO WORK SURFACES USED ONLY
 BY EMPLOYEES. HOWEVER, THE ADA AND, WHERE APPLICABLE,
 SECTION 504 OF THE REHABILITATION ACT OF 1973, AS
 AMENDED, PROVIDE THAT EMPLOYEES ARE ENTITLED TO
 ?REASONABLE ACCOMMODATIONS.? WITH RESPECT TO WORK
 SURFACES, THIS MEANS THAT EMPLOYERS MAY NEED TO PROCURE
 OR ADJUST WORK STATIONS SUCH AS DESKS, LABORATORY AND
 WORK BENCHES, FUME HOODS, RECEPTION COUNTERS, TELLER
 WINDOWS, STUDY CARRELS, COMMERCIAL KITCHEN COUNTERS,
 AND CONFERENCE TABLES TO ACCOMMODATE THE INDIVIDUAL
 NEEDS OF EMPLOYEES WITH DISABILITIES ON AN ?AS NEEDED?
 BASIS. CONSIDER WORK SURFACES THAT ARE FLEXIBLE AND
 PERMIT INSTALLATION AT VARIABLE HEIGHTS AND CLEARANCES.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-10-04 Cont ID  
Sent By jpearson Date 2018-10-04 Time 08:28 Rev Time 0.00
Received By jpearson Date 2018-10-04 Time 07:21 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-09-11 Cont ID  
Sent By pleduc Date 2018-09-11 Time   Rev Time 0.00
Received By pleduc Date 2018-09-11 Time 14:43 Sent To  
Notes
2018-09-11 15:02:15THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR
 CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND
 SPRINKLER SYSTEM FOR CODE COVERAGE AND COMPLIANCE BY
 CERTIFIED LIFE SAFETY CONTRACTORS.
  
 2) ANY AND ALL WORK ON THE FIRE ALARM AND FIRE
 SPRINKLER SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP
 DRAWINGS AND BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
 3) THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
  
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-11-13 Cont ID  
Sent By ccole Date 2018-11-13 Time 13:59 Rev Time 0.00
Received By ccole Date 2018-11-07 Time 07:05 Sent To  
Notes
2018-11-07 07:16:0411/07/2018 SENT TO J. W. DESK. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-10-31 Cont ID  
Sent By cpuell Date 2018-10-31 Time 14:42 Rev Time 0.00
Received By cpuell Date 2018-09-04 Time 11:39 Sent To  
Notes
2018-09-06 11:39:42C14

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-11-13 Cont ID  
Sent By ccole Date 2018-11-13 Time 13:53 Rev Time 0.00
Received By ccole Date 2018-11-13 Time 13:53 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-10-12 Cont ID  
Sent By ccole Date 2018-10-12 Time 12:00 Rev Time 0.00
Received By ccole Date 2018-10-12 Time 12:00 Sent To  
Notes
2018-10-12 12:10:381ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18090013
 10/12/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M1.1: DUCT SMOKE DETECTORS ARE REQUIRED IN THE
 SUPPLY AIR SYSTEMS OF EACH 5-TON RTU SYSTEM PER SECTION
 606.2.1. PLEASE NOTE THAT AN EXEMPTION CAN BE APPLIED
 IF THE MANUFACTURER'S SPECIFICATIONS INDICATE SYSTEMS
 ARE NOT CAPABLE OF PRODUCING OVER 2000 CFMS OF SUPPLY
 AIR. PLEASE PROVIDE SYMBOLS ON THE PLAN TO INDICATE
 INDICATE THE DEVICE LOCATIONS.
  
 2) PROVIDE NOTES ON THE PLAN TO INDICATE THE FAN
 SHUTDOWN SEQUENCE AND HOW THE DETECTORS WILL BE
 SUPERVISED- SECTIONS 606.4 & 606.4.1 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-10-18 Cont ID  
Sent By gjohnson Date 2018-10-18 Time 11:18 Rev Time 0.00
Received By gjohnson Date 2018-10-17 Time 08:37 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2018-09-17 Cont ID  
Sent By ajones Date 2018-09-17 Time 15:13 Rev Time 0.00
Received By ajones Date 2018-09-17 Time 15:13 Sent To  
Notes
***NONE***