Plan Review Details - Permit 18081587
Plan Review Stops For Permit 18081587
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2018-10-17 Time   Rev Time 0.00
Received By lmarchan Date 2018-10-09 Time 09:18 Sent To  
Notes
2018-10-11 09:18:46RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2018-09-21 Time   Rev Time 0.00
Received By lmarchan Date 2018-09-12 Time 13:21 Sent To  
Notes
2018-09-12 13:21:10MECH <5K

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-10-17 Cont ID  
Sent By ccole Date 2018-10-17 Time 07:33 Rev Time 0.00
Received By ccole Date 2018-10-17 Time 07:29 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-09-21 Cont ID  
Sent By ccole Date 2018-09-21 Time 11:13 Rev Time 0.00
Received By ccole Date 2018-09-21 Time 11:13 Sent To I
Notes
2018-09-21 11:43:281ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18081587
 9/21/2018
  
 CODES IN EFFECT:
  
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE COMPLETE PLANS AND SPECIFICATIONS FOR THE
 NEW WALK-IN COOLER AND FREEZER INCLUDING: A) WALK-IN
 BOX CONSTRUCTION DETAILS FROM THE MANUFACTURER OR
 DESIGN PROFESSIONAL. B) REFRIGERATION EQUIPMENT
 SCHEDULES. C) CONDENSATE DISPOSAL PLANS.
  
 2) THE $5000.00 JOB COST ON THE PERMIT APPLICATION IS
 UNDERVALUED FOR THE SCOPE OF THE PROPOSED PROJECT.
 PLEASE REFER TO SECTION 109.3 WPB AMENDMENTS AND
 PROVIDE DETAILED ESTIMATES, AND/OR BONA FIDE SIGNED
 CONTRACTS FOR A COMPLETE INSTALLATION INCLUDING LABOR,
 MATERIALS, AND EQUIPMENT, PLEASE NOTE THAT THE WPB USES
 MARSHALL-SWIFT AND MEANS VALUATION PUBLICATIONS TO
 VERIFY PROJECT COSTS.
  
 3) ADVISORY: THE PLANS AND SPECIFICATIONS FOR THE
 WALK-IN BOXES AND REFRIGERATION SYSTEMS SHALL BE IN
 COMPLIANCE WITH SECTIONS C403.2.14, C403.2.15, AND
 C403.2.16 FBC EC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  