Plan Review Details - Permit 18081535
Plan Review Stops For Permit 18081535
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2019-04-01 Cont ID  
Sent By rmcdouga Date 2019-04-01 Time 13:27 Rev Time 0.00
Received By pvalenti Date 2019-04-01 Time 13:27 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2019-01-24 Cont ID  
Sent By rmcdouga Date 2019-01-24 Time 19:14 Rev Time 0.00
Received By rmcdouga Date 2019-01-22 Time 17:11 Sent To  
Notes
2019-01-24 19:14:19PLAN
 REVIEW COMMENTS
 3RD REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 REVISION IS DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) COMPLIED.
  
 2) COMPLIED.
  
 3) COMPLIED
  
 4) THE ENGINEER'S REPORT REFERRED TO IN THE RESPONSE
 LETTER DATE JANURARY 7, 2019 WAS NOT FOUND WITH THE
 DOCUMENTS THAT WERE SUBMITTED. THE PLANS THAT WERE
 SUBMITTED DO NOT SHOW THE 3/4" FIRE TREATED PLYWOOD
 TAP-CONNED TO THE TOP OF THE PARAPET AS STATED IN THE
 RESPONSE LETTER. THE SIZE, LOCATION AND SPACING OF THE
 CONCRETE SCREWS WILL NEED TO BE SPECIFIED. THERE WAS
 ALSO NO MENTION OF THE SIGNS TO BE LOCATED ON THE
 PARAPET WALL WARNING AGAINST LEANING OR STANDING ON THE
 LEDGE WHICH WE HAD DISCUSSED PREVIOUSLY. FBC 107.2.1
  
 SHEETS A-3.04 SPECIFIES AN APPLIED FOAM MOULDING WITH
 STUCCO FINISH ATTACHED TO THE PARAPET. PROVIDE A DETAIL
 SHOWING MATERIALS, THICKNESSES AND ATTACHMENT METHOD.
 FOAM PLASTIC IS NOT ALLOWED ON THE EXTERIOR WALLS OF
 BUILDINGS OF TYPE I OR TYPE II CONSTRUCTION UNLESS IT
 MEETS THE REQUIREMENTS OF FBC 2603.5.1 THROUGH 2603.5.7
 NEW COMMENTS: ADDITIONAL INFORMATION IS REQUIRED. THERE
 ARE CONCERNS WITH THE PROPOSED VERTICAL AND HORIZONTAL
 FOAM MOULDINGS THAT NEED TO BE ADDRESSED. THE DRAWINGS
 INDICATE THAT THE FOAM TRIM MOULDING IS ATTACHED WITH
 AN ADHESIVE. THE FOAM TRIM AT THE TOP OF THE PARAPET
 WALL IS 6" X 11" WITH ONE INCH OF STUCCO ON THREE SIDES
 OF IT. IT EXTENDS OUT FROM THE PARAPET 12" INCLUDING
 THE INCH OF STUCCO AND THERE IS 6" OF THE FOAM ADHERED
 TO THE MASONRY PARAPET WHICH IS SUPPORTING THE STUCCO
 ENCASED FOAM. THE ONE INCH OF STUCCO THAT WILL ENCASE
 THE FOAM WILL REQUIRE WIRE LATH TO HOLD IT IN PLACE.
 THERE IS ALSO A CONCERN THAT THE TRIM MIGHT BREAK OF OR
 CRACK IF A PERSON WAS TO LEAN ON IT OR PUT WEIGHT ON
 IT. IT POSSIBLY COULD AFFECT FIRE RESCUE EFFORTS FROM
 THE ROOF OR WINDOW WASHERS, PAINTERS OR OTHER
 MAINTENANCE PERSONAL THAT MIGHT USE A BOSUNS CHAIR OR A
 SWING STAGE. THESE ITEMS SHOULD BE CONSIDERED IN YOUR
 DESIGN. IT MAY BE BETTER TO DESIGN THE TRIM USING STEEL
 FRAMING OR FORMED AND POURED CONCRETE.
 A) PROVIDE SIGNED AND SEALED WINDLOAD CALCULATIONS TO
 SHOW THAT THE ATTACHMENT OF THE FOAM TO THE BUILDING
 STRUCTURE IS CAPABLE OF RESISTING THE POSITIVE AND
 NEGATIVE PRESSURES SPECIFIED ON THE STRUCTURAL PLANS.
 FBC 1609.1
 B) THE ONE INCH OF STUCCO THAT WILL ENCASE THE FOAM
 WILL NOT BOND TO THE FOAM AND WILL REQUIRE WIRE LATH TO
 HOLD IT IN PLACE. SEE ASTM C 926. SUBMIT DETAILS FOR
 THE METAL LATH INSTALLATION THAT COMPLIES WITH ASTM
 C1063. FBC 2510.3
  
 5) PLEASE CLARIFY THE TYPES OF DECORATIVE CLADDING THAT
 WILL BE INSTALLED. I BELIEVE IT IS NATURAL STONE AND
 PORCELAIN TILES. PLEASE CLARIFY. THE ENGINEER'S
 EVALUATION REPORT FOR THE EXTERIOR STONE VENEER
 (CLADDING) AND FOAM MOLDING REFERRED TO IN THE RESPONSE
 LETTER DATE JANURARY 7, 2019 WAS NOT FOUND WITH THE
 DOCUMENTS THAT WERE SUBMITTED. I AGREE THAT PRODUCT
 APPROVALS ARE NOT REQUIRED, HOWEVER, ATTACHMENT/
 FASTENING DETAILS CAPABLE OF RESISTING THE WIND LOADS
 ARE REQUIRED. FBC 1609.1, 1405.7 & 1405.10.2
  
 PRODUCT APPROVALS AND ATTACHMENT/ FASTENING DETAILS
 WILL BE REQUIRED FOR THE STONE CLADDING.
 NEW COMMENT: NO MIAMI-DADE OF FLORIDA PRODUCT APPROVALS
 HAVE BEEN SUBMITTED AS REQUIRED BY FAC 61G20-3.001 PER
 FLORIDA STATUTE 553.842 (5)
  
 6) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 7) COMPLIED.
  
 8) COMPLIED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-11-07 Cont ID  
Sent By rmcdouga Date 2018-11-07 Time 09:18 Rev Time 0.00
Received By rmcdouga Date 2018-11-02 Time 09:16 Sent To  
Notes
2018-11-06 18:55:34PLAN
 REVIEW COMMENTS
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 REVISION IS DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) COMPLIED.
  
 2)COMPLIED.
  
 3) SHEET LS-1.21 AND LS-1.31 SPECIFY THAT PRE-FUNCTION
 ROOM 227 AND THE EXIT VESTIBULES AT THE EGRESS STAIRS
 ARE DESIGNATED AS AN AREA OF REFUGE. THE SECTIONS FOR
 AREAS OF REFUGE WAS NOT ADOPTED INTO THE 2017 FLORIDA
 BUILDING CODE FROM THE 2015 INTERNATIONAL BUILDING
 CODE. SECTION 1009.6 AREAS OF REFUGE IS RESERVED. IT IS
 GOOD THAT THESE AREAS HAVE SMOKE BARRIERS. HOWEVER,
 THEY SHOULD NOT BE DESIGNATED AS AREAS OF REFUGE AS
 THEY ARE NOT RECOGNIZED BY THE FBC AND THE REQUIREMENTS
 FOR THEM ARE NOT CODIFIED.
 NEW COMMENT: AREAS OF REFUGE NOTES ARE STILL SHOWN ON
 THE PLANS.
  
 4) SHEETS A-3.04 SPECIFIES AN APPLIED FOAM MOULDING
 WITH STUCCO FINISH ATTACHED TO THE PARAPET. PROVIDE A
 DETAIL SHOWING MATERIALS, THICKNESSES AND ATTACHMENT
 METHOD. FOAM PLASTIC IS NOT ALLOWED ON THE EXTERIOR
 WALLS OF BUILDINGS OF TYPE I OR TYPE II CONSTRUCTION
 UNLESS IT MEETS THE REQUIREMENTS OF FBC 2603.5.1
 THROUGH 2603.5.7
 NEW COMMENTS: ADDITIONAL INFORMATION IS REQUIRED. THERE
 ARE CONCERNS WITH THE PROPOSED VERTICAL AND HORIZONTAL
 FOAM MOULDINGS THAT NEED TO BE ADDRESSED. THE DRAWINGS
 INDICATE THAT THE FOAM TRIM MOULDING IS ATTACHED WITH
 AN ADHESIVE. THE FOAM TRIM AT THE TOP OF THE PARAPET
 WALL IS 6" X 11" WITH ONE INCH OF STUCCO ON THREE SIDES
 OF IT. IT EXTENDS OUT FROM THE PARAPET 12" INCLUDING
 THE INCH OF STUCCO AND THERE IS 6" OF THE FOAM ADHERED
 TO THE MASONRY PARAPET WHICH IS SUPPORTING THE STUCCO
 ENCASED FOAM. THE ONE INCH OF STUCCO THAT WILL ENCASE
 THE FOAM WILL REQUIRE WIRE LATH TO HOLD IT IN PLACE.
 THERE IS ALSO A CONCERN THAT THE TRIM MIGHT BREAK OF OR
 CRACK IF A PERSON WAS TO LEAN ON IT OR PUT WEIGHT ON
 IT. IT POSSIBLY COULD AFFECT FIRE RESCUE EFFORTS FROM
 THE ROOF OR WINDOW WASHERS, PAINTERS OR OTHER
 MAINTENANCE PERSONAL THAT MIGHT USE A BOSUNS CHAIR OR A
 SWING STAGE. THESE ITEMS SHOULD BE CONSIDERED IN YOUR
 DESIGN. IT MAY BE BETTER TO DESIGN THE TRIM USING STEEL
 FRAMING OR FORMED AND POURED CONCRETE.
 A) PROVIDE SIGNED AND SEALED WINDLOAD CALCULATIONS TO
 SHOW THAT THE ATTACHMENT OF THE FOAM TO THE BUILDING
 STRUCTURE IS CAPABLE OF RESISTING THE POSITIVE AND
 NEGATIVE PRESSURES SPECIFIED ON THE STRUCTURAL PLANS.
 FBC 1609.1
 B) THE ONE INCH OF STUCCO THAT WILL ENCASE THE FOAM
 WILL NOT BOND TO THE FOAM AND WILL REQUIRE WIRE LATH TO
 HOLD IT IN PLACE. SEE ASTM C 926. SUBMIT DETAILS FOR
 THE METAL LATH INSTALLATION THAT COMPLIES WITH ASTM
 C1063. FBC 2510.3
  
 5) PRODUCT APPROVALS AND ATTACHMENT/ FASTENING DETAILS
 WILL BE REQUIRED FOR THE STONE CLADDING.
 NEW COMMENT: NO MIAMI-DADE OF FLORIDA PRODUCT APPROVALS
 HAVE BEEN SUBMITTED AS REQUIRED BY FAC 61G20-3.001 PER
 FLORIDA STATUTE 553.842 (5)
  
 6) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 7) NEW COMMENT: THE CONSTRUCTION OF THE PARAPET WALLS
 ARE BEING REVISED FROM STEEL CONSTRUCTION TO REINFORCED
 MASONRY. SUBMIT STRUCTURAL DETAILS FOR THE REDESIGNED
 PARAPET WALLS. SPECIFY THE VERTICAL AND HORIZONTAL
 REINFORCEMENTS, SIZE, SPACING, LAPS, CORNER BARS, ETC.
 ,AS WELL AS, THE REQUIREMENTS FOR DOWELING INTO THE
 CONCRETE BEAM BELOW (DEPTH AND BONDING MATERIAL). FBC
 2104.1
  
 8) NEW COMMENT: ON SHEET A-1.1012 THE GRAB BARS ARE NOT
 SHOWN AT THE RELOCATED TOILET. FBC ACCESSIBILITY 604.1
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-10-04 Cont ID  
Sent By rmcdouga Date 2018-10-04 Time 18:55 Rev Time 0.00
Received By rmcdouga Date 2018-10-04 Time 17:48 Sent To  
Notes
2018-10-04 18:55:33PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 REVISION IS DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THERE ARE SHEETS LISTED IN THE NARRATIVE DESCRIPTION
 OF DRAWING REVISIONS THAT ARE MISSING FROM DRAWINGS
 THAT WERE UPLOADED. SHEET LS-111A, SHEET A-3.04 AND
 SHEETS A-4.00 THROUGH A-6.06 ARE MISSING FROM THE
 DRAWINGS. PLEASE CLARIFY. FBC 107.2.1
  
 2) SHEET A-1101 IS ONE OF THE DRAWINGS UPLOADED AND IT
 IS NOT LISTED IN THE REVISION NARRATIVE. FBC 107.2.1
  
 3) SHEET LS-1.21 AND LS-1.31 SPECIFY THAT PRE-FUNCTION
 ROOM 227 AND THE EXIT VESTIBULES AT THE EGRESS STAIRS
 ARE DESIGNATED AS AN AREA OF REFUGE. THE SECTIONS FOR
 AREAS OF REFUGE WAS NOT ADOPTED INTO THE 2017 FLORIDA
 BUILDING CODE FROM THE 2015 INTERNATIONAL BUILDING
 CODE. SECTION 1009.6 AREAS OF REFUGE IS RESERVED. IT IS
 GOOD THAT THESE AREAS HAVE SMOKE BARRIERS. HOWEVER,
 THEY SHOULD NOT BE DESIGNATED AS AREAS OF REFUGE AS
 THEY ARE NOT RECOGNIZED BY THE FBC AND THE REQUIREMENTS
 FOR THEM ARE NOT CODIFIED.
  
 4) SHEETS A-3.04 SPECIFIES AN APPLIED FOAM MOLDING WITH
 STUCCO FINISH ATTACHED TO THE PARAPET. PROVIDE A DETAIL
 SHOWING MATERIALS, THICKNESSES AND ATTACHMENT METHOD.
 FOAM PLASTIC IS NOT ALLOWED ON THE EXTERIOR WALLS OF
 BUILDINGS OF TYPE I OR TYPE II CONSTRUCTION UNLESS IT
 MEETS THE REQUIREMENTS OF FBC 2603.5.1 THROUGH 2603.5.7
  
 5) PRODUCT APPROVALS AND ATTACHMENT/ FASTENING DETAILS
 WILL BE REQUIRED FOR THE STONE CLADDING.
  
 6) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2019-01-11 Cont ID  
Sent By scaldero Date 2019-01-11 Time 13:14 Rev Time 0.00
Received By scaldero Date 2019-01-11 Time 13:13 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-10-24 Cont ID  
Sent By scaldero Date 2018-10-24 Time 11:40 Rev Time 0.00
Received By scaldero Date 2018-10-24 Time 11:35 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-09-13 Cont ID  
Sent By pleduc Date 2018-09-13 Time 14:47 Rev Time 0.00
Received By scaldero Date 2018-09-11 Time 14:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status P Date 2019-04-01 Cont ID  
Sent By pvalenti Date 2019-04-01 Time 13:27 Rev Time 0.00
Received By pvalenti Date 2019-03-12 Time 09:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-01-28 Cont ID  
Sent By gjohnson Date 2019-01-28 Time 14:49 Rev Time 0.00
Received By gjohnson Date 2019-01-10 Time 14:57 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-11-14 Cont ID  
Sent By gjohnson Date 2018-11-14 Time 12:38 Rev Time 0.00
Received By gjohnson Date 2018-10-18 Time 10:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-10-18 Cont ID  
Sent By lmarchan Date 2018-10-18 Time 11:16 Rev Time 0.00
Received By lmarchan Date 2018-09-06 Time 09:24 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-01-28 Cont ID  
Sent By gjohnson Date 2019-01-28 Time 14:49 Rev Time 0.00
Received By gjohnson Date 2019-01-28 Time 14:49 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-11-14 Cont ID  
Sent By gjohnson Date 2018-11-14 Time 12:27 Rev Time 0.00
Received By gjohnson Date 2018-11-14 Time 12:27 Sent To  
Notes
2018-11-14 12:37:441ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. A-400 THE ADA BATHROOM SHALL COMPLY WITH FBC
 ACC
 604.7 DISPENSERS. TOILET PAPER DISPENSERS SHALL COMPLY
 WITH 309.4 AND SHALL BE 7 INCHES MINIMUM AND 9 INCHES
 MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO THE
 CENTERLINE OF THE DISPENSER.
 604.3.1 SIZE. CLEARANCE AROUND A WATER CLOSET SHALL BE
 60 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE SIDE
 WALL AND 56 INCHES MINIMUM MEASURED PERPENDICULAR FROM
 THE REAR WALL.
 604.2 LOCATION.THE WATER CLOSET SHALL BE POSITIONED
 WITH A WALL OR PARTITION TO THE REAR AND TO ONE SIDE.
 THE CENTERLINE OF THE WATER CLOSET SHALL BE 16 INCHES
 MINIMUM TO 18 INCHES MAXIMUM FROM THE SIDE WALL OR
 PARTITION
  
 2. THE REVISION NARRATIVE LIST SHT. A-4.18 IT IS NOT
 INCLUDED IN PLAN SHEETS SUBMITTED/. PLEASE CLARIFY WPB
 AMEND TO FBC 107.2.1
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2019-04-01 Cont ID  
Sent By pvalenti Date 2019-04-01 Time 13:27 Rev Time 0.00
Received By pvalenti Date 2019-04-01 Time 13:26 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2019-01-24 Cont ID  
Sent By rmcdouga Date 2019-01-24 Time 19:15 Rev Time 0.00
Received By rmcdouga Date 2019-01-24 Time 19:15 Sent To  
Notes
2019-01-24 19:15:27SIGNATURES WILL BE VERIFIED WHEN DOCUMENTS HAVE BEEN
 APPROVED.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2018-11-07 Cont ID  
Sent By rmcdouga Date 2018-11-07 Time 09:18 Rev Time 0.00
Received By rmcdouga Date 2018-11-07 Time 09:18 Sent To  
Notes
2018-11-07 09:19:08SIGNATURES WILL BE VERIFIED WHEN DOCUMENTS HAVE BEEN
 APPROVED.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2018-10-04 Cont ID  
Sent By rmcdouga Date 2018-10-04 Time 18:56 Rev Time 0.00
Received By rmcdouga Date 2018-10-04 Time 18:56 Sent To  
Notes
2018-10-04 18:57:06SIGNATURES WILL BE VERIFIED WHEN DOCUMENTS HAVE BEEN
 APPROVED.

Review Stop Z ZONING
Rev No 2 Status P Date 2018-10-29 Cont ID  
Sent By ajones Date 2018-10-29 Time 11:54 Rev Time 0.00
Received By rmcdouga Date 2018-11-02 Time 09:16 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2018-10-17 Cont ID  
Sent By ajones Date 2018-10-17 Time 16:46 Rev Time 0.00
Received By ajones Date 2018-10-17 Time 16:46 Sent To  
Notes
***NONE***