Plan Review Details - Permit 18081526
Plan Review Stops For Permit 18081526
Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date   Cont ID  
Sent By sathomas Date 2018-10-26 Time 00:00 Rev Time 0.00
Received By   Date 2018-10-26 Time 00:00 Sent To M
Notes
2018-10-26 10:43:02PROVISO:
  
 ALL WORK PER CITY CODES SUBJECT TO FIELD INSPECTOR'S
 APPROVAL.
  
 S. THOMAS
 561-804-4728

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date   Cont ID  
Sent By sathomas Date 2018-10-15 Time 00:00 Rev Time 0.00
Received By   Date 2018-10-15 Time 00:00 Sent To I
Notes
2018-10-15 14:59:55PER FBC 904.11.1, A MANUAL ACTIVATION DEVICE SHALL BE
 LOCATED ALONG THE EGRESS PATH AND BE A MINIMUM OF 10
 FEET AND A MAXIMUM OF 20 FEET FROM THE KITCHEN EXHAUST
 SYSTEM. THE DEVICE SHALL BE MOUNTED 42-48 INCHES ABOVE
 THE FLOOR AND SHALL CLEARLY IDENTIFY THE HAZARD
 PROTECTED.
  
 KITCHEN HOOD SUPPRESSION SYSTEM SHALL BE TIED INTO THE
 BUILDING FIRE ALARM SYSTEM TO INITIATE A GENERAL FIRE
 ALARM CONDITION.
  
 DEEP FAT FRYERS SHALL BE EQUIPPED WITH A SEPARATE
 HIGH-LIMIT CONTROL IN ADDITION TO THE ADJUSTABLE
 THERMOSTAT TO SHUT OFF FUEL OR ENERGY WHEN THE FAT
 TEMPERATURE REACHES 475F DEGREES AT 1-INCH BELOW THE
 SURFACE.
  
 PROVIDE AN 8" TALL STEEL BAFFLE OR PROVIDE 16" OF SPACE
 BETWEEN THE DEEP FAT FRYER AND SURFACE FLAMES OF THE
 ADJACENT EQUIPMENT.
  
 PER KITCHEN MISTER SYSTEM DESIGN, CYLINDER MODEL BFR-10
 IS ALLOWED 10 MAXIMUM FLOW POINTS, WHILE PLANS SHOW 15
 FLOW POINTS.
  
 PER KITCHEN MISTER SYSTEM DESIGN, 2W NOZZLES ARE NOT
 PERMITTED OVER THE SIX BURNER RANGE.
  
 S. THOMAS
 561-804-4728

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date   Cont ID  
Sent By sathomas Date 2018-09-05 Time 00:00 Rev Time  
Received By   Date 2018-09-05 Time 00:00 Sent To M
Notes
2018-09-05 08:59:49INSUFFICIENT INFORMATION - PLEASE PROVIE SPECIFICATION
 SHEET FOR NOZZLES AND FUSIBLE LINKS.
 SPECIFY THE TYPE OF PLANS TO BE SUBMITTED (I.E. HOOD
 SUPPRESSION) - CURRENT PLAN JUST READS "FIRE"
  
  
 S. THOMAS
 561-804-4728

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2018-10-30 Time   Rev Time 0.00
Received By lmarchan Date 2018-10-17 Time 13:27 Sent To  
Notes
2018-10-22 13:27:37RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-10-15 Cont ID  
Sent By cpuell Date 2018-10-15 Time 16:25 Rev Time 0.00
Received By cpuell Date 2018-09-22 Time 14:23 Sent To  
Notes
2018-10-09 14:23:34RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2018-09-21 Time   Rev Time 0.00
Received By lmarchan Date 2018-08-30 Time 14:27 Sent To  
Notes
2018-08-31 14:28:01ROUTED TO FIRE INBOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2018-10-30 Cont ID  
Sent By ccole Date 2018-10-30 Time 09:06 Rev Time 0.00
Received By ccole Date 2018-10-30 Time 09:06 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-10-11 Cont ID  
Sent By ccole Date 2018-10-11 Time 11:43 Rev Time 0.00
Received By ccole Date 2018-10-11 Time 11:43 Sent To FIRE
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-09-21 Cont ID  
Sent By ccole Date 2018-09-21 Time 15:58 Rev Time 0.00
Received By ccole Date 2018-09-21 Time 15:58 Sent To I
Notes
2018-09-21 16:02:211ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18081526
 9/21/18
  
 CODES IN EFFECT:
  
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE PLANS SHALL BEAR THE SIGNATURE OF THE LICENSED
 CONTRACTOR OR QUALIFIER WHO PREPARED THE DESIGN-
 SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  