Plan Review Stops For Permit 18081526 |
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
|
|
|
Cont ID |
|
Sent By |
sathomas |
Date |
2018-10-26 |
Time |
00:00 |
Rev Time |
0.00 |
Received By |
|
Date |
2018-10-26 |
Time |
00:00 |
Sent To |
M |
|
Notes |
2018-10-26 10:43:02 | PROVISO: | | | | ALL WORK PER CITY CODES SUBJECT TO FIELD INSPECTOR'S | | APPROVAL. | | | | S. THOMAS | | 561-804-4728 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
F |
Date |
|
|
|
Cont ID |
|
Sent By |
sathomas |
Date |
2018-10-15 |
Time |
00:00 |
Rev Time |
0.00 |
Received By |
|
Date |
2018-10-15 |
Time |
00:00 |
Sent To |
I |
|
Notes |
2018-10-15 14:59:55 | PER FBC 904.11.1, A MANUAL ACTIVATION DEVICE SHALL BE | | LOCATED ALONG THE EGRESS PATH AND BE A MINIMUM OF 10 | | FEET AND A MAXIMUM OF 20 FEET FROM THE KITCHEN EXHAUST | | SYSTEM. THE DEVICE SHALL BE MOUNTED 42-48 INCHES ABOVE | | THE FLOOR AND SHALL CLEARLY IDENTIFY THE HAZARD | | PROTECTED. | | | | KITCHEN HOOD SUPPRESSION SYSTEM SHALL BE TIED INTO THE | | BUILDING FIRE ALARM SYSTEM TO INITIATE A GENERAL FIRE | | ALARM CONDITION. | | | | DEEP FAT FRYERS SHALL BE EQUIPPED WITH A SEPARATE | | HIGH-LIMIT CONTROL IN ADDITION TO THE ADJUSTABLE | | THERMOSTAT TO SHUT OFF FUEL OR ENERGY WHEN THE FAT | | TEMPERATURE REACHES 475F DEGREES AT 1-INCH BELOW THE | | SURFACE. | | | | PROVIDE AN 8" TALL STEEL BAFFLE OR PROVIDE 16" OF SPACE | | BETWEEN THE DEEP FAT FRYER AND SURFACE FLAMES OF THE | | ADJACENT EQUIPMENT. | | | | PER KITCHEN MISTER SYSTEM DESIGN, CYLINDER MODEL BFR-10 | | IS ALLOWED 10 MAXIMUM FLOW POINTS, WHILE PLANS SHOW 15 | | FLOW POINTS. | | | | PER KITCHEN MISTER SYSTEM DESIGN, 2W NOZZLES ARE NOT | | PERMITTED OVER THE SIX BURNER RANGE. | | | | S. THOMAS | | 561-804-4728 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
|
|
|
Cont ID |
|
Sent By |
sathomas |
Date |
2018-09-05 |
Time |
00:00 |
Rev Time |
|
Received By |
|
Date |
2018-09-05 |
Time |
00:00 |
Sent To |
M |
|
Notes |
2018-09-05 08:59:49 | INSUFFICIENT INFORMATION - PLEASE PROVIE SPECIFICATION | | SHEET FOR NOZZLES AND FUSIBLE LINKS. | | SPECIFY THE TYPE OF PLANS TO BE SUBMITTED (I.E. HOOD | | SUPPRESSION) - CURRENT PLAN JUST READS "FIRE" | | | | | | S. THOMAS | | 561-804-4728 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2018-10-30 |
Time |
|
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2018-10-17 |
Time |
13:27 |
Sent To |
|
|
Notes |
2018-10-22 13:27:37 | RESUB ROUTED TO FIRE INBOX |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2018-10-15 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2018-10-15 |
Time |
16:25 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2018-09-22 |
Time |
14:23 |
Sent To |
|
|
Notes |
2018-10-09 14:23:34 | RESUB ROUTED TO FIRE INBOX |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2018-09-21 |
Time |
|
Rev Time |
0.00 |
Received By |
lmarchan |
Date |
2018-08-30 |
Time |
14:27 |
Sent To |
|
|
Notes |
2018-08-31 14:28:01 | ROUTED TO FIRE INBOX |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2018-10-30 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2018-10-30 |
Time |
09:06 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2018-10-30 |
Time |
09:06 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2018-10-11 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2018-10-11 |
Time |
11:43 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2018-10-11 |
Time |
11:43 |
Sent To |
FIRE |
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2018-09-21 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2018-09-21 |
Time |
15:58 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2018-09-21 |
Time |
15:58 |
Sent To |
I |
|
Notes |
2018-09-21 16:02:21 | 1ST REVIEW FBC-2017 MECHANICAL | | PERMIT #18081526 | | 9/21/18 | | | | CODES IN EFFECT: | | | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | 2017 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | EDITION 2017 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) THE PLANS SHALL BEAR THE SIGNATURE OF THE LICENSED | | CONTRACTOR OR QUALIFIER WHO PREPARED THE DESIGN- | | SECTION 107.2.1 WPB. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | KEEP THEM WITH THE SUBMITTALS | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|
|