Plan Review Details - Permit 18081502
Plan Review Stops For Permit 18081502
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-10-22 Cont ID  
Sent By jleahy Date 2018-10-22 Time 09:34 Rev Time 0.00
Received By jleahy Date 2018-10-22 Time 09:34 Sent To  
Notes
2018-10-22 09:34:50SLAB REVIEW DONE UNDER THE ELECTRICAL REVIEW JLEAHY

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-09-26 Cont ID  
Sent By rmcdouga Date 2018-09-26 Time 16:34 Rev Time 0.00
Received By rmcdouga Date 2018-09-26 Time 16:34 Sent To I
Notes
2018-09-26 16:42:17PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE GENERATOR PAD DRAWINGS ARE REQUIRED TO HAVE THE
 ENGINEER'S ORIGINAL HAND WRITTEN SIGNATURE AND SEAL.
 61G15-23.003 PROCEDURES FOR PHYSICALLY SIGNING AND
 SEALING PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS.
 ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS WHICH MUST BE SIGNED, DATED AND SEALED IN
 ACCORDANCE WITH THE PROVISIONS OF SECTION 471.025,
 F.S., AND RULE 61G15-23.001, F.A.C. MUST BE PHYSICALLY
 SIGNED, DATED AND SEALED AS PROVIDED HEREIN BY THE
 PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE.
 (1) THE LICENSEE SHALL SIGN BY HAND AN ORIGINAL OF THE
 LICENSEE?S SIGNATURE ON EACH PAGE REQUIRED TO BE
 SEALED. A SCANNED, FACSIMILE, DIGITALLY CREATED OR
 COPIED IMAGE OF THE LICENSEE?S SIGNATURE SHALL NOT BE
 USED.
 (2) THE LICENSEE MUST THEN USE A WET SEAL, A DIGITALLY
 CREATED SEAL, OR AN EMBOSSING SEAL PLACED PARTIALLY
 OVERLAPPING THE LICENSEE?S SIGNATURE ON EACH PAGE
 REQUIRED TO BE SEALED. THE PLACEMENT OF THE SEAL SHALL
 NOT RENDER THE SIGNATURE ILLEGIBLE.
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-10-22 Cont ID  
Sent By jleahy Date 2018-10-22 Time 09:35 Rev Time 0.00
Received By jleahy Date 2018-10-22 Time 09:34 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-09-17 Cont ID  
Sent By fgiaquin Date 2018-09-17 Time 06:51 Rev Time 0.00
Received By fgiaquin Date 2018-09-17 Time 06:46 Sent To  
Notes
2018-09-17 06:51:07ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. NO WIRE SIZES ANNOTATED FOR FEEDER FROM MAIN TO ATS
 OR ATS TO EXISITNG SUB-PANEL, ALSO INDICATE SIZE OF
 SUB-PANEL ON PLANS. FBC 107.2.1
  
 2. ELECTRICAL PLAN IS REQUIRED TO BE SIGNED BY THE
 ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE CORRECTION. FS
 471.003(2)(H); 471.025; WPB FBC 107.1
  
 3. ADDRESS IS REQUIRED TO BE ON PLAN. FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WPB
 [email protected]
 CELL: 561-657-1653
  

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2018-09-14 Cont ID  
Sent By lcrespo Date 2018-09-14 Time 18:50 Rev Time 0.00
Received By lcrespo Date 2018-09-14 Time 18:50 Sent To  
Notes
2018-09-14 18:51:2309/14/18 REVIEWED FOR CODE COMPLIANCE (GAS)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVE PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-10-22 Cont ID  
Sent By jleahy Date 2018-10-22 Time 09:35 Rev Time 0.00
Received By jleahy Date 2018-10-18 Time 15:03 Sent To  
Notes
2018-10-19 15:03:17RESUB ROUTED TO FGIAQUINTO

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-09-26 Cont ID  
Sent By rmcdouga Date 2018-09-26 Time 16:34 Rev Time 0.00
Received By rmcdouga Date 2018-08-30 Time 11:40 Sent To  
Notes
2018-08-31 11:41:02ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 1 Status P Date 2018-09-11 Cont ID  
Sent By mcruz Date 2018-09-11 Time 07:56 Rev Time 0.00
Received By mcruz Date 2018-09-11 Time 07:49 Sent To B
Notes
2018-09-11 07:57:17ZONING PASSED WITH PROVISO: GENERATOR SHALL BE AT LEAST
 1' FROM SIDE PROPERTY LINE.
  
 MAGGIE CRUZ
 ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: 561-822-1442
 E-MAIL: [email protected]
  