Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-10-15 Cont ID  
Sent By rmcdouga Date 2018-10-15 Time 16:59 Rev Time 0.00
Received By rmcdouga Date 2018-10-15 Time 16:46 Sent To  
Notes
2018-10-15 16:59:11BUILDING PROVISO
  
 1) SUBMIT THE ORIGINAL DOCUMENT FROM THE ARCHITECT THAT
 SPECIFIES CHANGING THE FLOORING SOUND INSULATION
 UNDERLAYMENT TO PROFLEX 90 WITH THE ARCHITECT'S
 HANDWRITTEN SIGNATURE AS REQUIRED BY FAC 61G15-23.003
  
 2) HAVE THE PRIVATE PROVIDER IDENTIFY THE PLANS MORE
 CLEARLY. THERE ARE (2) PAGES NOT A2-1 THROUGH E2-1.
 SPECIFY THE DATE OF THE PLANS AND THE DESIGNER OF
 RECORD (ARCHITECT, JAMES A. MINGES).

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-10-15 Cont ID  
Sent By rmcdouga Date 2018-10-15 Time 13:41 Rev Time 0.00
Received By rmcdouga Date 2018-10-15 Time 13:40 Sent To  
Notes
2018-10-15 13:43:12REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE SOUND TRANSMISSION TEST REPORTS THAT WE HAVE FOR
 THE PROFLEX 90 MSC THAT YOU ARE PROPOSING TO USE,
 REQUIRES AN 8? CONCRETE FLOOR SLAB WITH A SUSPENDED
 CEILING AND 3-1/2? OF FIBERGLASS INSULATION. THIS IS
 NOT THE CONDITION THAT EXITS FOR THIS PROJECT. I WOULD
 SUGGEST THAT YOU USE PROFLEX RCU 250 IF THAT SLAB IS 8
 INCHES AND PROFLEX RCU 500 OR PROFLEX SUPER SIM 90 FOR
 A SIX INCH SLAB. FBC 1207.2, 1207.3 AND 603
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-10-03 Cont ID  
Sent By rmcdouga Date 2018-10-03 Time 07:26 Rev Time 0.00
Received By rmcdouga Date 2018-10-03 Time 07:18 Sent To I
Notes
2018-10-03 07:26:10PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1. PLEASE ADVISE, WHAT FLOORING AND UNDERLAYMENT ARE
 PROPOSED? PLEASE ADVISE VIA EMAIL. IF THE UNDERLAYMENT
 PRODUCT PROPOSED IS NOT ONE FOR WHICH WE HAVE TEST
 REPORTS ON FILE, THE FOLLOWING REPORTS ARE REQUIRED:
  
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  
 2. THIS INFORMATION MAY BE SENT VIA EMAIL. PLEASE SEND
 AN EMAIL STATING WHICH PRODUCT IS PROPOSED. IF WE HAVE
 TEST REPORTS ON FILE, THEY WILL BE PROVIDED FOR YOU. IF
 WE DO NOT HAVE TEST REPORTS ON FILE, PLEASE SEND THE
 THREE TESTS REFERENCED ABOVE.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-10-15 Cont ID  
Sent By jpearson Date 2018-10-15 Time 11:06 Rev Time 0.00
Received By jpearson Date 2018-10-15 Time 11:06 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-09-20 Cont ID  
Sent By jpearson Date 2018-09-20 Time 10:13 Rev Time 0.00
Received By jpearson Date 2018-09-20 Time 10:13 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2018-10-15 Cont ID  
Sent By pleduc Date 2018-10-15 Time   Rev Time 0.00
Received By pleduc Date 2018-10-15 Time 10:59 Sent To E
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-09-04 Cont ID  
Sent By pleduc Date 2018-09-04 Time   Rev Time 0.00
Received By pleduc Date 2018-09-04 Time 14:16 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-10-15 Cont ID  
Sent By rmcdouga Date 2018-10-15 Time 17:04 Rev Time 0.00
Received By rmcdouga Date 2018-10-05 Time 14:09 Sent To  
Notes
2018-10-11 09:28:3810/9 TO JESMITH DESK
 COPY OF PRIVATE PROVIDER PAPERWORK TO REGATHRIGHT
  
  
2018-10-09 14:09:38LIBRARY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-10-03 Cont ID  
Sent By rmcdouga Date 2018-10-03 Time 07:27 Rev Time 0.00
Received By rmcdouga Date 2018-08-30 Time 14:25 Sent To  
Notes
2018-08-31 14:25:37B23

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-10-11 Cont ID  
Sent By jesmith Date 2018-10-11 Time 09:42 Rev Time 0.00
Received By jesmith Date 2018-10-11 Time 09:41 Sent To  
Notes
2018-10-11 09:42:312ND REVIEW
 PLUMBING COMMENTS:APPROVED
  
 ARCHITECT SATISFACTORILY RESPONDED TO FIRST REVIEW.
 PROVIDED REVIEW AUDIT ONLY; NO OBVIOUS DEFICIENCIES.
 EVANS-HUGHES CODE INSPECTIONS, INC RESPONSIBLE FOR CODE
 COMPLIANCE. AUDIT INSPECTION BY CITY OF WEST PALM BEACH
 REQUIRED.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-09-27 Cont ID  
Sent By jesmith Date 2018-09-27 Time 12:58 Rev Time 0.00
Received By jesmith Date 2018-09-27 Time 12:52 Sent To  
Notes
2018-09-27 12:58:33CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 1ST REVIEW:
 PLUMBING COMMENTS: DENIED
  
 1. IS UNIT ON AN ELEVATED FLOOR? PLEASE CLARIFY. WPB
 FPC 107.2.1
 2. CLOTHES WASHER IS RELOCATED TO ANOTHER WALL. PROVIDE
 SANITARY RISER SHOWING HOW THE UNIT DRAINAGE AND
 VENTING NOTING POINTS OF CONNECTION TO EXISTING
 SYSTEMS; CLOUD NEW WORK. PROVIDE SIZE OF NEW AND
 EXISTING PIPING. IF CONNECTING TO ANY EXISTING DRAIN
 OTHER THAN THE ORIGINAL, PROVIDE LOAD CALCULATIONS OF
 EXISTING SYSTEM, NOTING TYPE (I.E. SOIL STACK, WASTE
 STACK VENT) TO CONFIRM THAT EXISTING WILL NOT BE
 OVERLOADED. WPB FPC 107.2.1
 3. IF ON ELEVATED FLOOR THEN PROVIDE PIPING MATERIALS
 TYPE & FIRE RATED ASSEMBLIES FOR NEW OR RELOCATED
 PIPING FLOOR PENETRATIONS PER WPB FBC 107.2.1
 4. PROVIDE NOTE STATING "THE VALVES FOR THE STACKABLE
 WASHING MACHINE(S) SHALL BE ACCESSIBLE." WPB FPC
 107.2.1 FBC PL 606.3
 6. PROVIDE WATER HAMMER ARRESTORS AT WATER SUPPLIES TO
 ICE LINE, DISHWASHER AND CLOTHES WASHER PER FPC PL
 604.9; INDICATE SAME ON THE PLANS PER WPB FPC 107.2.1
  
  
  
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED "VOID".
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715