2018-09-05 09:07:59 | FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING |
| DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A |
| FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN |
| 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE |
| PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST |
| BE SUBMITTED BY EMAIL ([email protected]) OR IN WRITING |
| (FAX: 561-804-4774) AND APPROVED BY THE OFFICE OF THE |
| FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY. |
| |
| WHERE MUSIC SYSTEMS ARE BEING INSTALLED IN TENANT |
| SPACES: THE SPEAKER SYSTEM WILL NEED TO BE TESTED |
| AGAINST THE FIRE ALARM SYSTEM TO ENSURE THAT THE |
| MINIMUM REQUIRED DECIBEL LEVELS OF THE FIRE ALARM |
| SYSTEM ARE BEING MET. PENDING RESULTS OF FIELD |
| INSPECTION/FIRE ALARM TEST, ADDITIONAL REQUIREMENTS MAY |
| BE NEEDED. |
| |
| ALL TENANT SPACES FOR THE MARKETPLACE MUST BE TIED INTO |
| THE MASTER FIRE ALARM PANEL FOR THE BUILDING. EACH |
| TENANT SPACE WILL BE INTERCONNECTED AND UPON ACTIVATION |
| OF AN ALARM IN ANY ONE SPACE, ALL SPACES WILL HAVE |
| THEIR NOTIFICATION DEVICES ACTIVATE. AN FACP IN A |
| TENANT SPACES WILL HAVE THE "RESET" AND "SILENCE" |
| FUNCTIONS DEACTIVATED. RESET AND SILENCE OF AN ALARM IS |
| LIMITED TO THE MASTER PANEL FOR THE BUILDING AND MAY |
| ONLY BE DONE BY A LICENSED FIRE ALARM TECHNICIAN. |
| SHOULD IT BE FOUND THAT TENANTS ARE ACCESSING THE |
| PANELS IN THE TENANT SPACES AND/OR USING THE "RESET" OR |
| "SILENCE" FUNCTIONS, THE OFFICE OF THE FIRE MARSHAL MAY |
| REQUIRE THAT THE TENANT FACP BE REMOVED. |
| PER APPROVED MASTER PLANS: MAIN FACP FOR THIS BUILDING |
| IS TO BE THE ONLY PANEL TO NOTIFY THE FIRE DEPARMENT. |
| NOTIFICATION WILL DESIGNATE SPECIFIC ADDRESS OF TENANT |
| WHERE TROUBLE IS LOCATED. |
| |
| EACH BUILDING SHALL ALARM/EVACUATE ONLY THE SPACES IN |
| THAT BUILDING (IE AN ALARM IN "B" WILL NOT EVACUATE ANY |
| SPACE IN "A", "BII", OR "C". EACH TENANT SPACE FACP |
| SHALL BE CONNECTED TO MAIN FACP FOR THIS BUILDING VIA |
| MODULES. TENANT SYSTEM SHALL BE COMPATIBLE WITH |
| NOTIFIER OR EQUAL APPROVED MAIN FACP/HARDWARE EACH |
| FLOW/TAMPER SHALL BE ZONED SO THAT AN ALARM WILL SOUND |
| FOR EACH BUILDING SEPARATELY. |
| |