Plan Review Details - Permit 18081425
Plan Review Stops For Permit 18081425
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-10-10 Cont ID  
Sent By cthroop Date 2018-10-10 Time 15:36 Rev Time 0.00
Received By cthroop Date 2018-10-10 Time 15:25 Sent To P
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-10-04 Cont ID  
Sent By cthroop Date 2018-10-04 Time 15:17 Rev Time 0.00
Received By cthroop Date 2018-10-02 Time 07:47 Sent To I
Notes
2018-10-04 15:55:42BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. VALUE APPEARS LOW FOR PROPOSED SCOPE OF WORK.
 THE PERMIT VALUATION AND PERMIT FEE MUST BE
 COMMENSURATE WITH THE VALUATION AND FEE THAT A LICENSED
 CONTRACTOR WOULD PROVIDE.
 YOU MAY PROVIDE A COPY OF THE CONTRACT SIGNED BY THE
 OWNER OR A LIST OF LABOR, MATERIALS AND EQUIPMENT
 RENTAL TO VERIFY VALUE.
  
 CITY OF WPB CHPT. 1 ? VALUE
 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS,
 MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED,
 QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS
 (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE
 BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION
 OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT
 VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING,
 MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK,
 ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION
 COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.),
 AS PUBLISHED BY INTERNATIONAL CODE CONGRESS.
 FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL.
  
 2. PROVIDE ASTM TEST REPORTS FOR UNDERLAYMENT TO BE
 USED UNDER HARD FLOORING.
 THE FOLLOWING INFORMATION IS REQUIRED FOR ALL FLOORING
 SUBMITTALS:
  
 1. FLOOR PLAN WITH DIMENSIONS AND LOCATION OF WORK.
 PROVIDED ON PLAN
 *DESIGNER TO PRINT NAME AND SIGN PLAN PER FBC 107 *
 PROVIDED ON PLAN
 2. TOTAL SQUARE FOOTAGE OF NEW FLOORING. PORCELAIN TILE
 AREAS - PROVIDED ON PLAN
 3. TYPE OF PROPOSED FLOORING
 (TILE/MARBLE/LAMINATE/WOOD/OTHER). PLANS SPECIFY
 PORCELAIN TILE 12 X 24
 4. STATED VALUE OF WORK. N/A THIS WILL BE INCLUDED IN
 THE TOTAL VALUE ON APPLICATION.
 5. EXISTING SITE CONDITIONS: REQUIRED
 A) THICKNESS OF SLAB. B) CEILING ASSEMBLY (OPEN
 CONCRETE/SUSPENDED GYPSUM/ACOUSTICAL)
 6. PROPOSED UNDERLAYMENT. MUST BE FOR PROPOSED
 FLOORING.
 7. TEST REPORTS FOR PROPOSED UNDERLAYMENT BASED ON
 EXISTING SITE CONDITIONS.
 8. TEST REPORTS MAY BE BASED ON THE FOLLOWING ASTM?S,
 E-84, E-90 & E-492.
 9. ALL DOCUMENTS SHALL BE SUBMITTED IN DUPLICATE.
  
 FBC 603.1 FLAME SPREAD ? ASTM E-84-09. N/A FOR TILE
  
 FBC 1207.2 AIR-BORNE SOUND. ASTM E ? 90-04 REQUIRED
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E ? 492-09
 REQUIRED
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC SPACE OR SERVICE
 AREA WITHIN THE STRUCTURE SHALL HAVE AN IMPACT
 INSULATION CLASS (IIC) RATING OF NOT LESS THAN 50 (45
 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E
 492.
  
 NOTE: CONDOMINIUM ASSOCIATION MAY REQUIRE HIGHER DB
 VALUES. CHECK WITH PROPERTY MANAGER.
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-09-28 Cont ID  
Sent By jpearson Date 2018-09-28 Time 14:22 Rev Time 0.00
Received By jpearson Date 2018-09-28 Time 14:22 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-09-19 Cont ID  
Sent By jpearson Date 2018-09-19 Time 15:44 Rev Time 0.00
Received By jpearson Date 2018-09-19 Time 15:44 Sent To  
Notes
2018-09-19 15:44:00CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
 (S)
  
 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. FBC 109.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-09-04 Cont ID  
Sent By pleduc Date 2018-09-04 Time   Rev Time 0.00
Received By pleduc Date 2018-08-31 Time 16:07 Sent To  
Notes
2018-09-04 10:29:47THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1) ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR
 CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND
 SPRINKLER SYSTEM FOR CODE COVERAGE AND COMPLIANCE BY
 CERTIFIED LIFE SAFETY CONTRACTORS.
  
  
 2) ANY AND ALL WORK ON THE FIRE ALARM AND FIRE
 SPRINKLER SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP
 DRAWINGS AND BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
  
 3) THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
  
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-10-11 Cont ID  
Sent By jesmith Date 2018-10-11 Time 16:18 Rev Time 0.00
Received By jesmith Date 2018-10-11 Time 16:17 Sent To  
Notes
2018-10-09 14:37:08RESUB ROUTED TO CTHROOP

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-10-04 Cont ID  
Sent By cthroop Date 2018-10-04 Time 15:56 Rev Time 0.00
Received By cthroop Date 2018-08-29 Time 14:39 Sent To  
Notes
2018-08-30 14:39:41B22

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2018-10-04 Cont ID  
Sent By cthroop Date 2018-10-04 Time 15:17 Rev Time 0.00
Received By cthroop Date 2018-10-02 Time 07:47 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-09-20 Cont ID  
Sent By ccole Date 2018-09-20 Time 17:36 Rev Time 0.00
Received By ccole Date 2018-09-20 Time 17:36 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-10-11 Cont ID  
Sent By jesmith Date 2018-10-11 Time 16:17 Rev Time 0.00
Received By jesmith Date 2018-10-11 Time 16:16 Sent To  
Notes
2018-10-11 16:17:14PLUMBING COMMENTS: APPROVED
 PROVISO NOTED ON PLAN SHEETS 1A-106, 1A-306 AND BELOW
  
 1. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 LOCATED IN PUBLIC TOILET ROOMS THROUGH AN APPROVED
 WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B125.3. PER FBC PL 416.5
 2. BATHROOMS SHALL COMPLY WITH FBC ACCESSIBILITY
 CHAPTER 6.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-09-27 Cont ID  
Sent By jesmith Date 2018-09-27 Time 09:36 Rev Time 0.00
Received By jesmith Date 2018-09-27 Time 09:36 Sent To  
Notes
2018-09-27 09:36:31ODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 1ST REVIEW:
 PERMIT 18081425
 PLUMBING COMMENTS: DENIED
  
 1. PROVIDE NOTE: PER FBC PL 416.5 TEMPERED WATER SHALL
 BE DELIVERED FROM LAVATORIES AND GROUP WASH FIXTURES
 LOCATED IN PUBLIC TOILET FACILITIES PROVIDED FOR
 CUSTOMERS, PATRONS AND VISITORS. TEMPERED WATER SHALL
 BE DELIVERED THROUGH AN APPROVED WATER-TEMPERATURE
 LIMITING DEVICE THAT CONFORMS TO ASSE 1070 OR CSA
 B125.3.
 2. URINAL TO COMPLY FBC ACC 605.2 PER FBC ACC 202.4.1
 3. FLUSH CONTROL FOR WC IN ADA COMPLIANT STALL TO BE
 LOCATED ON OPEN SIDE OF FIXTURE OR SHALL BE AUTOMATIC
 OPERATION COMPLYING WITH FBC ACC 605.6 PER FBC ACC
 202.4.1
 4. PROVIDE DIMENSIONS FOR ADA COMPLIANT GRAB BARS AT
 WATER CLOSET & DIMENSIONS FOR ADA COMPLIANT TOILET
 PAPER DISPENSERS PER FBC ACC 604.5, 604.7.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED "VOID".
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715