Plan Review Details - Permit 18081379
Plan Review Stops For Permit 18081379
Review Stop AIPP ART IN PUBLIC PLACES
Rev No 1 Status N Date 2018-09-01 Cont ID  
Sent By shill Date 2018-09-01 Time 18:45 Rev Time 0.00
Received By shill Date 2018-09-01 Time 18:45 Sent To  
Notes
2018-09-01 18:45:29PER EMAIL FROM SYBILLE WELTER, AIPP IS NOT REQUIRED
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-09-05 Cont ID  
Sent By shill Date 2018-09-05 Time 07:13 Rev Time 0.00
Received By shill Date 2018-09-05 Time 07:13 Sent To  
Notes
2018-09-05 07:16:02****PROVISOS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. SHEET S1, I WAS UNABLE TO LOCATE A SPECIFICATION FOR
 F5, EITHER REVISE PLAN TO INCLUDE OR DIRECT AS TO WHERE
 THIS CAN BE LOCATED.2
 6. FBC B 107.2.5, IT APPEARS THAT THIS IS LOCATED IN
 SFHA 7' NAVD88. S1 REFERS TO ARCHITECTURAL PAGES FOR
 ELEVATION; REVISE A1.1.1 TO INCLUDE (9' NAVD88 MINIMUM
 IS REQUIRED).
  
 2. FBC B 107.3.5.1.1(1), PROVIDE A "CONSTRUCTION
 DOCUMENTS" ELEVATION CERTIFICATE.
  
 3. PRIOR TO CONCRETE POUR, A "BUILDING UNDER
 CONSTRUCTION" ELEVATION CERTIFICATE WILL BE REQUIRED.
 THIS MAY BE SENT VIA EMAIL FOR PRELIMINARY REVIEW.
 PRIOR TO FINAL INSPECTION BUT AFTER ALL MECHANICAL
 EQUIPMENT HAS BEEN INSTALLED AND FINAL GRADES
 COMPLETED, A "FINISHED CONSTRUCTION" ELEVATION
 CERTIFICATE WILL BE REQUIRED. THIS MAY BE SENT VIA
 EMAIL FOR PRELIMINARY REVIEW.
  
 4. THIS PERMIT IS ISSUED AT APPLICANT'S RISK PER FBC
 105.13:
  
 PHASED PERMIT APPROVAL. AFTER SUBMITTAL OF THE
 APPROPRIATE CONSTRUCTION DOCUMENTS, THE BUILDING
 OFFICIAL IS AUTHORIZED TO ISSUE A PERMIT FOR THE
 CONSTRUCT ION OF FOUNDATIONS OR ANY OTHER PART OF A
 BUILDING OR STRUCTURE BEFORE THE CONSTRUCTION DOCUMENTS
 FOR THE WHOLE BUILDING OR STRUCTURE HAVE BEEN
 SUBMITTED. THE HOLDER OF SUCH PERMIT FOR THE FOUNDATION
 OR OTHER PARTS OF A BUILDING OR STRUCTURE SHALL PROCEED
 AT THE HOLDER'S OWN RISK WITH THE BUILDING OPERATION
 AND WITHOUT ASSURANCE THAT A PERMIT FOR THE ENTIRE
 STRUCTURE WILL BE GRANTED. CORRECTIONS MAY BE REQUIRED
 TO MEET THE REQUIREMENTS OF THE TECHNICAL CODES. THIS
 PROVISION IS ONLY FOR THE FLORIDA BUILDING CODE. ALL
 OTHER AGENCY APPROVALS NECESSARY FOR CONSTRUCTION MUST
 BE SECURED PRIOR TO THIS PROVISION BEING APPLIED.
  
 5. SEPARATE PERMITS (APPLICATIONS, PLANS, AND FEES) ARE
 REQUIRED FOR THE FOLLOWING ITEMS AS APPLICABLE:
 LIGHT POLES/SITE LIGHTING
 FIRE ALARM
 FIRE SPRINKLER
 LOW VOLTAGE
 ACCESS
 LANDSCAPING
 IRRIGATION
 ALL OTHER ITEMS OTHER THAN BMEP
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-09-01 Cont ID  
Sent By shill Date 2018-09-01 Time 18:48 Rev Time 0.00
Received By shill Date 2018-09-01 Time 18:48 Sent To  
Notes
2018-09-01 18:53:23****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. SEE FIRE COMMENTS ON PERMIT APPLICATION 18070442
 REGARDING FIRE SPRINKLERS.
  
 THERE IS A LETTER REGARDING THE INTENT TO PROVIDE FIRE
 SPRINKLERS AND PERMIT DOCUMENTS, BUT THE DOCUMENTS WERE
 NOT PROVIDED; IN PARTICULAR, HYDRAULIC CALCS. IT IS NOT
 CLEAR IF EXISTING SERVICE IS SUFFICIENT TO PROVIDE
 SPRINKLERS TO THE PROPOSED STRUCTURE.
  
 IF FIRE DOES NOT REQUIRE THIS INFORMATION FOR THE
 FOUNDATION PERMIT, PLEASE ADVISE AND THIS COMMENT WILL
 BE REMOVED.
  
 2. OK
  
 3. FBC B CHAPTER 5, 6, 7, REVISE PLAN TO INCLUDE
 BUILDING TYPE, SQUARE FOOT AREA (GARAGE AND OFFICE
 SEPARATELY), SEPARATED OR NON SEPARATED OCCUPANCIES,
 NOTE THAT IT WILL BE A FIRE SPRINKLERED BUILDING,
 BUILDING HEIGHT, NUMBER OF STORIES.
  
 4. INFORMATION GENERALLY REQUIRED FOR A FOUNDATION
 PERMIT:
  
 PERMIT APPLICATION WHICH STATES SCOPE (FOR FOUNDATION
 PERMIT, TYPICALLY FOOTINGS OR FOOTINGS AND SLAB) -
 APPLICATION IN PROJECTDOX IS BLANK
 GEOTECHNICAL REPORT - NOT SUBMITTED
 SURVEY DRAWING - OK
 STORM WATER POLLUTION PREVENTION PLAN - NOT SUBMITTED
 SITE PLAN - OK
 1ST FLOOR ARCHITECTURAL PLAN - SUBMITTED BUT LACKS
 PROPOSED DFE (ELEVATION IN NAVD88)
 ARCHITECTURAL CROSS SECTION(S) OF THE BUILDING - NOT
 PROVIDED
 FOUNDATION PLAN - OK
 FOUNDATION DETAILS AND CROSS SECTIONS - OK
 STRUCTURAL ENGINEER'S GENERAL NOTES - OK
 UNDERGROUND PLUMBING PLAN - SUBMITTED, PENDING REVIEW
 ELECTRICAL PLAN SHOWING ANY UNDERGROUND CONDUIT -
 SUBMITTED, PENDING REVIEW
 ELECTRICAL GROUNDING TO STEEL DETAIL, IF APPLICABLE (OR
 EXPLAIN WHY THIS IS NOT APPLICABLE FOR THIS PROJECT).
 IF REQUIRED, A DETAIL IS REQUIRED AS A REVIEW, PERMIT,
 AND INSPECTION ARE REQUIRED PRIOR TO CONCRETE POUR -
 SUBMITTED, PENDING REVIEW
 PLAN SHOWING UNDERGROUND FIRE LINE - SUBMITTED, PENDING
 FIRE REVIEW (BLDG OK)
 THRESHOLD INSPECTION PLAN - NA
 SI OR RESIDENT INSPECTOR AGREEMENT (AS APPLICABLE) -
 RESIDENT INSPECTOR AGREEMENT REQUIRED (4000 PSI
 CONCRETE STRUCTURAL SLAB)
 THRESHOLD STATEMENT ON PLAN (IF APPLICABLE) - N/A, NOT
 THRESHOLD (RESIDENT)
  
 5. SHEET S1, I WAS UNABLE TO LOCATE A SPECIFICATION FOR
 F5, EITHER REVISE PLAN TO INCLUDE OR DIRECT AS TO WHERE
 THIS CAN BE LOCATED.
  
 6. FBC B 107.2.5, IT APPEARS THAT THIS IS LOCATED IN
 SFHA 7' NAVD88. S1 REFERS TO ARCHITECTURAL PAGES FOR
 ELEVATION; REVISE A1.1.1 TO INCLUDE (9' NAVD88 MINIMUM
 IS REQUIRED).
  
 7. FBC B 107.3.5.1.1(1), PROVIDE A "CONSTRUCTION
 DOCUMENTS" ELEVATION CERTIFICATE.
  
 8. THIS PERMIT WILL BE ISSUED WITH PROVISO:
  
 A. PRIOR TO CONCRETE POUR, A "BUILDING UNDER
 CONSTRUCTION" ELEVATION CERTIFICATE WILL BE REQUIRED.
 THIS MAY BE SENT VIA EMAIL FOR PRELIMINARY REVIEW.
 PRIOR TO FINAL INSPECTION BUT AFTER ALL MECHANICAL
 EQUIPMENT HAS BEEN INSTALLED AND FINAL GRADES
 COMPLETED, A "FINISHED CONSTRUCTION" ELEVATION
 CERTIFICATE WILL BE REQUIRED. THIS MAY BE SENT VIA
 EMAIL FOR PRELIMINARY REVIEW.
  
 B. THIS PERMIT IS ISSUED AT APPLICANT'S RISK PER FBC
 105.13:
  
 PHASED PERMIT APPROVAL. AFTER SUBMITTAL OF THE
 APPROPRIATE CONSTRUCTION DOCUMENTS, THE BUILDING
 OFFICIAL IS AUTHORIZED TO ISSUE A PERMIT FOR THE
 CONSTRUCT ION OF FOUNDATIONS OR ANY OTHER PART OF A
 BUILDING OR STRUCTURE BEFORE THE CONSTRUCTION DOCUMENTS
 FOR THE WHOLE BUILDING OR STRUCTURE HAVE BEEN
 SUBMITTED. THE HOLDER OF SUCH PERMIT FOR THE FOUNDATION
 OR OTHER PARTS OF A BUILDING OR STRUCTURE SHALL PROCEED
 AT THE HOLDER'S OWN RISK WITH THE BUILDING OPERATION
 AND WITHOUT ASSURANCE THAT A PERMIT FOR THE ENTIRE
 STRUCTURE WILL BE GRANTED. CORRECTIONS MAY BE REQUIRED
 TO MEET THE REQUIREMENTS OF THE TECHNICAL CODES. THIS
 PROVISION IS ONLY FOR THE FLORIDA BUILDING CODE. ALL
 OTHER AGENCY APPROVALS NECESSARY FOR CONSTRUCTION MUST
 BE SECURED PRIOR TO THIS PROVISION BEING APPLIED.
  
 C. SEPARATE PERMITS (APPLICATIONS, PLANS, AND FEES) ARE
 REQUIRED FOR THE FOLLOWING ITEMS AS APPLICABLE:
 LIGHT POLES/SITE LIGHTING
 FIRE ALARM
 FIRE SPRINKLER
 LOW VOLTAGE
 ACCESS
 LANDSCAPING
 IRRIGATION
 ALL OTHER ITEMS OTHER THAN BMEP
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-09-02 Cont ID  
Sent By jpearson Date 2018-09-02 Time 08:46 Rev Time 0.00
Received By jpearson Date 2018-09-02 Time 08:46 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2018-09-04 Cont ID  
Sent By RRossano Date 2018-09-04 Time   Rev Time 1.00
Received By rrossano Date 2018-09-04 Time   Sent To I
Notes
2018-09-04 11:15:56PROVISO: APPLICANT MUST POST A PERFORMANCE BOND FOR
 ENGINEERING SERVICES EROSION CONTROL & LAND
 STABILIZATION BOND (ORDINANCE 4060-07). BOND SHALL BE
 INCLUSIVE OF 110% OF ENGINEER?S OPINION OF COST TO
 RESTORE SITE TO STABILIZED SODDED GRADE, GOOD FOR A
 PERIOD OF 1 YEAR, SHOWN AS:
  
 TO: CITY OF WEST PALM BEACH, A MUNICIPAL CORPORATION OF
 THE STATE OF FLORIDA, HAVING AN ADDRESS OF 401 CLEMATIS
 STREET, WEST PALM BEACH, FLORIDA, 33402.
  
 UPON SUCCESSFULLY PASSING 1ST VERTICAL INSPECTION THE
 CONTRACTOR MAY REQUEST THE BOND TO BE TERMINATED. FOR
 MORE INFORMATION YOU MAY USE THE PERFORMANCE BOND SHOWN
 ON OUR WEB PAGE, OR SUBMIT AN EQUAL INSTRUMENT DIRECTLY
 TO:
  
 MANNY GONZALEZ
 SENIOR ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-09-04 Cont ID  
Sent By pleduc Date 2018-09-04 Time   Rev Time 0.00
Received By pleduc Date 2018-08-31 Time 13:40 Sent To  
Notes
2018-09-04 11:23:01THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 APPROVED FOR FOUNDATION ONLY.
  
  
 1) THE LETTER SUBMITTED BY RBK DOES NOT SATISFY THE 61G
 REQUIREMENTS FOR FIRE SPRINKLER DESIGN.
  
  
 2) ANY WORK ON THE FIRE MAIN OR FIRE SPRINKLER SYSTEM
 IS AT RISK FOR THIS FOUNDATION AND IS NOT SPECIFICALLY
 APPROVED WITH THIS PERMIT.
  
  
 3) THE REQUIRED 61G FIRE SPRINKLER DESIGN DOCUMENTATION
 SHALL BE SUBMITTED WITH THE REMAINING BUIDLING PERMIT
 SUBMITTAL.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-09-06 Cont ID  
Sent By cpuell Date 2018-09-06 Time 11:03 Rev Time 0.00
Received By cpuell Date 2018-08-28 Time 16:15 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status P Date 2018-09-02 Cont ID  
Sent By shill Date 2018-09-01 Time 18:55 Rev Time 0.00
Received By shill Date 2018-09-01 Time 18:55 Sent To  
Notes
2018-09-01 18:55:50SEE IMPACT FEE STAMP AND QUESTIONNAIRE WITH BUILDING
 PERMIT APPLICATION 18070442
 $0 DUE

Review Stop P PLUMBING
Rev No 1 Status P Date 2018-09-06 Cont ID  
Sent By tklarge Date 2018-09-06 Time 10:40 Rev Time 0.00
Received By tklarge Date 2018-09-06 Time 03:54 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2018-09-06 Cont ID  
Sent By shill Date 2018-09-06 Time 12:18 Rev Time 0.00
Received By shill Date 2018-09-06 Time 12:18 Sent To  
Notes
2018-09-06 12:18:55PROVISO: PROVIDE S&S CIVILS, SOILS REPORT
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2018-08-29 Cont ID  
Sent By shill Date 2018-08-29 Time 18:09 Rev Time 0.00
Received By shill Date 2018-08-29 Time 18:09 Sent To  
Notes
2018-09-01 18:13:47****CORRECTIONS****
 REVISED 9/4/18
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 SIGNATURES FOR PLAN PAGES A, S, E, P ARE OK
  
 CIVIL PAGES ARE NOT SIGNED - DOCUMENTS PREPARED BY AN
 ENGINEER (MICHAEL SPRUCE, PE) AND SUBMITTED FOR PUBLIC
 RECORD ARE TO BE SIGNED, SEALED, DATED ORIGINALS FS471.
 IF THE ENGINEER DOES NOT HAVE A DIGITAL SIGNATURE, HE
 CAN PROVIDE ONE ORIGINAL PAPER SIGNED AND SEALED
 DOCUMENT AFTER ALL OTHER PLAN REVIEWS HAVE PASSED.
  
 SOILS REPORT NOT SIGNED - PROVIDE ONE PAPER ORIGINAL
  
  
  
  
  
2018-08-29 18:10:20SIGNATURES OK, BUT PLANS HAVE NOT ADDRESSED COMMENTS
 FROM BUILDING PERMIT REVIEW
 ADVISED APPLICANT; NEW PAGES WILL LIKELY BE UPLOADED
 PRIOR TO FIRST REVIEW
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 3 Status P Date 2018-09-22 Cont ID  
Sent By shill Date 2018-09-22 Time 11:38 Rev Time 0.00
Received By shill Date 2018-09-22 Time 11:38 Sent To  
Notes
2018-09-22 11:41:29AGREEMENT SUBMITTED UNDER SUBMITTAL #18090636
 THRESHOLD INSPECTION CONSULTING ENGINEERS, LLC (TICE)
 J.F. DESNOYERS, PE
 JENNINGS L. HILL, BN 3142
 DAVID ANTOINE, BN 7367
 BURTON SILVER, BN 2171
 AUTOBUILDERS, INC.
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 2 Status P Date 2018-09-06 Cont ID  
Sent By shill Date 2018-09-06 Time 12:19 Rev Time 0.00
Received By shill Date 2018-09-06 Time 12:19 Sent To  
Notes
2018-09-06 12:20:22PROVISO:
 ALL PARTIES ARE THE SAME AS THE BRISTOL
 PER KC, PROVIDE AGREEMENT PRIOR TO FIRST INSPECTION
 INSPECTION FIRM: TICE THRESHOLD INSPECTION ENGINEERS
  
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status F Date 2018-09-01 Cont ID  
Sent By shill Date 2018-09-01 Time 18:53 Rev Time 0.00
Received By shill Date 2018-09-01 Time 18:53 Sent To  
Notes
2018-09-01 18:54:59****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. RESIDENT INSPECTOR AGREEMENT SIGNED BY ALL PARTIES
 REQUIRED.
  
 2. PROVIDE RESUMES FOR THE SI, PROPOSED INSPECTORS.
  
 3. PROVIDE COPIES OF THE LICENSES FOR THE SI, PROPOSED
 INSPECTORS.
  
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2018-09-06 Cont ID  
Sent By jroach Date 2018-09-06 Time 09:20 Rev Time 0.00
Received By jroach Date 2018-09-06 Time 09:17 Sent To  
Notes
***NONE***