Plan Review Details - Permit 18081323
Plan Review Stops For Permit 18081323
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2018-09-01 Cont ID  
Sent By pvalenti Date 2018-09-01 Time 13:46 Rev Time 0.00
Received By pvalenti Date   Time   Sent To I
Notes
2018-09-01 13:56:54PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 APPROVED PV
  
 NOTE: THE CONTRACTOR SUBMITTED THE PRODUCT APPROVAL FOR
 POLYGLASS ROOF UNDERLAYMENTS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-08-29 Cont ID  
Sent By shill Date 2018-08-29 Time 18:04 Rev Time 0.00
Received By shill Date 2018-08-29 Time 18:04 Sent To  
Notes
2018-08-29 18:05:54****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. UNDERLAYMENT PROPOSED IS NOT CLEAR.
  
 THE FRSA SPEC WAS PROVIDED AND HIGHLIGHTED. A FLORIDA
 STATE PRODUCT APPROVAL WAS ALSO PROVIDED. WHICH ONE IS
 PROPOSED? FBC R 301.
  
 THIS INFORMATION MAY BE PROVIDED VIA EMAIL.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-09-01 Cont ID  
Sent By pvalenti Date 2018-09-01 Time 13:57 Rev Time 0.00
Received By pvalenti Date 2018-08-30 Time 14:11 Sent To I
Notes
2018-08-31 14:11:57RESUB ROUTED TO SHILL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-08-29 Cont ID  
Sent By shill Date 2018-08-29 Time 18:05 Rev Time 0.00
Received By shill Date 2018-08-28 Time 13:33 Sent To  
Notes
2018-08-29 13:33:21SHILL