Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2018-09-24 Cont ID  
Sent By bwoods Date 2018-09-24 Time 08:59 Rev Time 0.00
Received By bwoods Date 2018-09-21 Time 00:00 Sent To I
Notes
2018-09-24 08:59:47THE PROPOSED PROJECT INDICATES THE USE OF FLEX DROP
 PIPING. THE EXISTING SYSTEM APPEARS TO A TYPICAL ARM
 OVER.
 FLEX DROPS TYPICALLY HAVE A HIGHER FRICTION LOSS THAN
 THE DESIGNED ARM OVER SYSTEM.
 THERE IS NO HYDRAULIC CALCULATION SHEET SUBMITTED THAT
 SHOWS THAT THE NEW FLEX DROPS WILL BE SUPPORTED BY THE
 EXISTING SYSTEM DESIGN TO PROVIDE THE REQUIRED WATER
 FLOW.
 PLEASE PROVIDE CALCULATIONS DETAILS.
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-09-14 Cont ID  
Sent By bwoods Date 2018-09-14 Time 00:00 Rev Time 0.00
Received By bwoods Date 2018-09-14 Time 00:00 Sent To M
Notes
2018-09-14 14:05:531.)THE PROPOSED PROJECT INDICATES THE USE OF FLEX DROP
 PIPING. THE EXISTING SYSTEM APPEARS TO A TYPICAL ARM
 OVER.
 FLEX DROPS TYPICALLY HAVE A HIGHER FRICTION LOSS THAN
 THE DESIGNED ARM OVER SYSTEM.
 THERE IS NO HYDRAULIC CALCULATION SHEET SUBMITTED THAT
 SHOWS THAT THE NEW FLEX DROPS WILL BE SUPPORTED BY THE
 EXISTING SYSTEM DESIGN TO PROVIDE THE REQUIRED WATER
 FLOW.
 PLEASE PROVIDE CALCULATIONS DETAILS OR USE THE SAME
 TYPE OF ARM OVER THAT MATCHES THE EXISTING SYSTEM
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-10-05 Cont ID  
Sent By cpuell Date 2018-10-05 Time 12:40 Rev Time 0.00
Received By cpuell Date 2018-09-26 Time 10:12 Sent To  
Notes
2018-09-28 10:12:28ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-09-24 Cont ID  
Sent By cpuell Date 2018-09-24 Time 15:55 Rev Time 0.00
Received By cpuell Date 2018-09-17 Time 14:33 Sent To  
Notes
2018-09-18 14:33:52RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-09-14 Cont ID  
Sent By cpuell Date 2018-09-14 Time 16:28 Rev Time 0.00
Received By cpuell Date 2018-08-27 Time 13:50 Sent To  
Notes
2018-08-28 13:51:09ROUTED TO FIRE INBOX


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved