Plan Review Details - Permit 18081246
Plan Review Stops For Permit 18081246
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-02-06 Cont ID  
Sent By pvalenti Date 2019-02-06 Time 07:13 Rev Time 0.00
Received By pvalenti Date 2019-02-06 Time 07:13 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-12-17 Cont ID  
Sent By pvalenti Date 2018-12-17 Time 08:52 Rev Time 0.00
Received By pvalenti Date 2018-12-17 Time 07:37 Sent To  
Notes
2018-12-17 09:02:05****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 FBC 107. PLEASE PROVIDE MORE INFORMATION:
  
 THE SUBMITTED INFORMATION FOR THE FLOORING DOES NOT
 INCLUDE THE REQUIRED UNDERLAYMENT INFORMATION.
 THE COMMENTS FROM THE LAST REVIEW, RELATING TO FLOORING
 UNDERLAYMENT, HAVE NOT BEEN ADDRESSED.
 PLEASE REVIEW THE NOTES FROM LAST REVIEW AND PROVIDE
 THE SOUND AND FLAME SPREAD SPECIFICATIONS FROM THE
 TESTING LAB FOR THE UNDERLAYMENT.,

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-10-15 Cont ID  
Sent By cthroop Date 2018-10-15 Time 14:43 Rev Time 0.00
Received By cthroop Date 2018-10-12 Time 07:19 Sent To P
Notes
2018-10-15 14:46:29BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE FINISH SCHEDULE. SPECIFICALLY FLOORING.
 2. PROVIDE ASTM TEST REPORTS FOR FLOORING UNDERLAYMENT.
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  
 3. PROVISO - BATHROOMS SHALL COMPLY WITH FBC
 ACCESSIBILITY CODE CHPT. 6.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-12-05 Cont ID  
Sent By jpearson Date 2018-12-05 Time 08:43 Rev Time 0.00
Received By jpearson Date 2018-12-05 Time 08:43 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-09-28 Cont ID  
Sent By fgiaquin Date 2018-09-28 Time 12:51 Rev Time 0.00
Received By fgiaquin Date 2018-09-28 Time 10:12 Sent To  
Notes
2018-09-28 12:51:52ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY A LICENSED DESIGN PROFESSIONAL OR THE
 ELECTRICAL CONTRACTOR QUALIFIER. FS 471.003(2)(H);
 471.025; WPB FBC 107.2.1, 107.3.5
  
 AN ENGINEERED ELECTRICAL CEILING PLAN WAS SUBMITTED FOR
 2ND FL BATHROOMS. ONLY E0.1 AND E2.1 PAGES SUBMITTED.
 APPEARS TO BE MISSING PAGES. ARCHITECTUAL PLAN SHOWS
 ELECTRICAL WORK THROUGHOUT THE 1ST FLOOR AND 2ND FLOOR,
 NOT JUST CORRIDORS, BUT THE PERMIT APPLICATION ONLY
 SAYS "INTERIOR CORRIDOR ALTERATIONS". SUBMIT A COMPLETE
 AND ACCURATE ELECTRICAL PLAN INCLUDING ALL WORK TO BE
 PERFORMED WITH LOAD CALCULATIONS FOR REVIEW.
  
 2. PROVIDE SUBMITTALS FOR PRODUCT APPROVAL (UL OR NRTL
 LISTINGS) FOR LIGHT FIXTURES. NEC 110.3
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WPB
 [email protected]
 CELL: 561-657-1653
  
  

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2018-12-05 Cont ID  
Sent By jpearson Date 2018-12-05 Time 09:27 Rev Time 0.00
Received By jpearson Date 2018-12-05 Time 09:27 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-01-23 Cont ID  
Sent By scaldero Date 2019-01-23 Time 08:18 Rev Time 0.00
Received By scaldero Date 2019-01-23 Time 08:17 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-08-28 Cont ID  
Sent By scaldero Date 2018-08-28 Time 10:34 Rev Time 0.00
Received By scaldero Date 2018-08-28 Time 10:19 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-02-06 Cont ID  
Sent By pvalenti Date 2019-02-06 Time 07:14 Rev Time 0.00
Received By pvalenti Date 2019-01-14 Time 15:27 Sent To  
Notes
2019-01-15 15:27:24C28

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2019-01-02 Cont ID  
Sent By jesmith Date 2019-01-02 Time 13:12 Rev Time 0.00
Received By jesmith Date 2018-11-05 Time 10:12 Sent To  
Notes
2018-11-07 10:12:41C26

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-10-16 Cont ID  
Sent By jesmith Date 2018-10-16 Time 09:59 Rev Time 0.00
Received By jesmith Date 2018-10-16 Time 09:59 Sent To  
Notes
2018-08-27 14:07:47C18

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2018-10-15 Cont ID  
Sent By cthroop Date 2018-10-15 Time 14:43 Rev Time 0.00
Received By cthroop Date 2018-10-12 Time 07:19 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2019-02-04 Cont ID  
Sent By ccole Date 2019-02-04 Time 08:52 Rev Time 0.00
Received By ccole Date 2019-02-04 Time 08:25 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-12-03 Cont ID  
Sent By ccole Date 2018-12-03 Time 14:55 Rev Time 0.00
Received By ccole Date 2018-12-03 Time 12:29 Sent To  
Notes
2018-12-03 15:16:541ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18081246
 12/3/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M2.1: EXHAUST VENTILATION IS REQUIRED IN THE
 KITCHEN AND RECIRCULATION OF AIR IS PROHIBITED- TABLE
 403.3.1.1 FOOTNOTE B.
  
 2) M2.1: EXHAUST GRILLS NOT LABELED OR NOT LEGIBLE IN
 THE MEN'S AND WOMEN'S SHOWER ROOMS- SECTION 107.2.1
 WPB.
  
 3) PLEASE PROVIDE A KITCHEN EQUIPMENT SCHEDULE AND
 SUBMIT MANUFACTURER'S SPECIFCATIONS FOR THE COOKING
 APPLIANCES- SECTION 917 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-10-04 Cont ID  
Sent By ccole Date 2018-10-04 Time 17:37 Rev Time 0.00
Received By ccole Date 2018-10-04 Time 17:25 Sent To  
Notes
2018-10-04 18:06:221ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18081246
 10/4/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE $28,000.00 JOB VALUE LISTED ON THE PERMIT
 APPLICATION IS UNDERVALUED FOR THE THE PROPOSED 11,937
 SF LEVEL 2 ALTERATION PLAN. PLEASE REFER TO SECTION
 109.3 WPB AND PROVIDE DETAILED ESTIMATES AND.OR BONA
 FIDE CONTRACTS FOR ALL WORK TO BE PERFORMED AS OUTLINED
 ON THE PROJECT PLANS AND SPECIFICATIONS- SHEETS G001 &
 G002. THE TOTAL VALUE SHALL INCLUDE THE COST OF LABOR
 AND MATERIALS FOR STRUCTURAL, ARCHITECTURAL,
 MECHANICAL, ELECTRICAL, PLUMBING, INTERIOR FINISH,
 ARCHITECTURAL AND DESIGN FEES, AND OVERHEAD AND PROFIT.
 ALL FIXTURES, APPLIANCES, AND EQUIPMENT SHALL BE
 INCLUDED IN THE COSTS. PLEASE NOTE AT THIS TIME THAT
 THE SUBMITTED MEP PLANS FOR THE PROJECT ARE INCOMPLETE,
 AND ONLY THE MECHANICAL AND ELECTRICAL ALTERATIONS IN
 THE EXISTING TOILET ROOMS HAVE BEEN PROVIDED.
  
 2) AS NOTED IN COMMENT #1 ABOVE, THE MECHANICAL PLANS
 ARE INCOMPLETE. PLEASE PROVIDE COMPLETE PLANS AND
 DETAILS FOR THE WORK TO BE PERFORMED ON THE 1ST AND 2ND
 FLOORS. PLEASE NOTE THAT SEPARATE PERMITS ARE REQUIRED
 FOR KITCHEN EXHAUST HOODS, FIRE SUPRESSION SYSTEMS, AND
 WALKIN COOLERS AND FREEZERS. THE MECHANICAL PLAN REVIEW
 IS STOPED AT THIS TIME UNTIL COMPLETE PLANS ARE
 RESUBMITTED FOR REVIEW- SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
 HTTPS://WWW.SURVEYMONKEY.COM/R/WESTPALMBEACHCONSTRUCTIO
 NSERVICES
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2019-01-31 Cont ID  
Sent By jesmith Date 2019-01-31 Time 15:57 Rev Time 0.00
Received By jesmith Date 2019-01-31 Time 15:56 Sent To  
Notes
2019-01-31 15:57:06APPROVED
 1. ALL WORK PER CITY CODES SUBJECT TO FIELD INSPECTOR'S
 APPROVAL
 2. KITCHEN EQUIPMENT DISCHARGING TO GREASY WASTE IS
 EXISTING. LAYOUT IS RECONFIGURED. NO CHANGE TO THE
 DISCHARGE LOAD TO THE EXISTING GREASY WASTE.

Review Stop P PLUMBING
Rev No 2 Status F Date 2019-01-02 Cont ID  
Sent By jesmith Date 2019-01-02 Time 13:11 Rev Time 0.00
Received By jesmith Date 2019-01-02 Time 08:45 Sent To  
Notes
2019-01-02 13:11:50CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 5TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
 2ND REVIEW: DENIED
 PLUMBING COMMENTS
 1. RE: PLAN SHEET 1A-101 DATED 8/16/2018; EXISTING
 SHEET IS REDLINED. COMMENTS ARE NO LONGER APPLICABLE.
 REPLACE WITH CLEAN SIGNED AND SEALED.
 2. OCCUPANCY IS BUSINESS WITH OCCUPANT LOAD OF 262.
 THERE ARE NO DRINKING FOUNTAINS SHOWN ON THE PLAN. SHOW
 EXISTING AND, IF REQUIRED, ADD NEW DRINKING FOUNTAINS
 COMPLYING WITH FBC PL TABLE 403.1, SECTION 410 AND FBC
 ACC SECTION 211, 307 AND 602. REVISE PLUMBING PLANS AS
 REQUIRED.
 3. RE: PLAN SHEET P2.1 AND P5.1; PER CITY OF WPB
 UTILITIES DEPARTMENT, ALL KITCHEN EQUIPMENT AND
 FIXTURES SHALL DISCHARGE INTO GREASY WASTE DRAINAGE
 INTO THE GREASE INTERCEPTOR. REVISE PLUMBING PLANS TO
 SHOW COMPLIANCE. CONTACT MR. JEFFERY ODOMS, CITY OF WPB
 UTILITIES AT 561-822-2172 OR EMAIL [email protected] WITH
 ANY QUESTION OR CONCERN.
 4. PER WPB FBC 107.2.1, PROVIDE CALCULATIONS FOR NEW
 AND EXISTING EQUIPMENT AND FIXTURES DISCHARGING TO THE
 GREASE INTERCEPTOR AND PROVIDE CAPACITY OF EXISTING
 INTERCEPTOR SHOWING THAT IT WILL ACCOMMODATE THE
 INCREASED LOAD.
 5. PLAN SHEET E5.1 INDICATES A SEPARATE REFRIGERATOR
 AND SEPARATE ICE MACHINE. P5.1 INDICATES A REFRIGERATOR
 WITH ICE MAKER. PLEASE CLARIFY PER WPB FBC 107.2.1.
 6. PLAN SHEET E5.1 DOES NOT SEEM TO INDICATE A
 DISHWASHER. P5.1 INDICATES A DISHWASHER. PLEASE CLARIFY
 AND SHOW LOCATION ON THE FLOOR PLAN AND WATER RISER
 DIAGRAM PER WPB FBC 107.2.1.
 7. PER WPB FBC 107.2.1, PROVIDE SCHEDULE AND DETAIL FOR
 FIXTURE TAG SK-3
 8. THE WATER RISER DIAGRAM INDICATES BACKFLOW
 PREVENTERS FOR COFFEE MAKERS, FILTERS, ICE MAKER WATER
 SUPPLY LINES. TYPICAL PLUMBING FIXTURE CONNECTION
 SCHEDULE CALLS OUT VACUUM BREAKERS. BE SPECIFIC;
 SPECIFY BACKFLOW PREVENTER DEVICES LISTING THE ASSE,
 CSA OR AWWA STANDARD WHICH IS APPLICABLE TO THAT DEVICE
 PER WPB FBC 107.2.1.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-10-16 Cont ID  
Sent By jesmith Date 2018-10-16 Time 09:57 Rev Time 0.00
Received By jesmith Date 2018-10-16 Time 09:53 Sent To  
Notes
2018-10-16 09:57:38CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 1ST REVIEW: DENIED
  
 PLUMBING COMMENTS:
 1. THERE ARE NO PLUMBING PLANS. PLUMBING PLANS ARTE NOT
 REQUIRED BASED ON THE SCOPE OF WORK INDICATED ON THE
 EXISTING PLANS. THE PLUMBING WORK IS NOTED ON PLAN
 SHEETS A1-101, ID-101 AND CONSISTS OF REMOVAL OF
 EXISTING CORRIDOR TOILET ROOM FIXTURES AND TEMPORARILY
 CAPPING EXISTING PLUMBING SERVICE CONNECTIONS TO ALLOW
 NEW WALL AND FLOOR FINISHES TO BE PUT IN PLACE. THE
 ORIGINAL WATER CLOSETS AND URINALS WILL BE REINSTALLED.
 NEW LAVATORIES WILL BE INSTALLED IN NEW VANITIES (SEE
 PLAN SHEET 1A-700; BATHROOM EQUIPMENT SPECS). ALL WILL
 BE RECONNECTED TO EXISTING PLUMBING SERVICE
 CONNECTIONS.
 A) RE: PLAN SHEET G002 ; 22000 PLUMBING, SUMMARY NOTE
 1.REPLACE THE WORDS "BUILDING PLUMBING DRAWINGS" WITH
 THE WORDS "PLAN SHEET A1-700".
 B) RE: PLAN SHEET ID-101; ADD DEMOLITION KEYED NOTE 12
 ?CAP EXISTING PLUMBING SERVICE CONNECTIONS? AND NOTE
 SAME ON FLOOR PLAN WHEREVER NOTES 5 AND 11 ARE
 DESIGNATED PER WPB FBC 107.2.1
 2. BASED ON CONVERSATIONS WITH THE APPLICANT, THE SCOPE
 OF WORK IS LIMITED TO THE CORRIDOR TOILET ROOMS ON THE
 FIRST AND SECOND FLOOR ONLY, AND IS REINFORCED BY PLAN
 SHEET 1A-101: DETAIL 1; A1-1A-700 WITH NOTE STATING
 "LIMITS OF ALTERATION LEVEL 1" . THE FIRST FLOOR LOBBY
 AREA NOTED ON PLAN SHEET A1-101: DETAIL 1; A1-702 AND
 PLAN SHEET A1-702 IS NOT INCLUDED IN THE SCOPE OF WORK.
 A) PLEASE REMOVE FROM PERMIT PLANS SHEETS AND DETAILS
 THAT INDICATE WORK IN THE FIRST FLOOR LOBBY INCLUDING
 PLAN SHEET A1-702, 1A-801, AND DETAILS ON PLAN SHEET
 A1-851 THAT DO NOT SPECIFICALLY ADDRESS THE CORRIDOR
 TOILET ROOMS, OR
 I. CLARIFY ON PLAN SHEET A1-101 THAT THIS AREA IS
 INCLUDED IN THE "LIMITS OF ALTERATION LEVEL 1", ADD TO
 PLAN SHEET G002 ; 22000 PLUMBING, SUMMARY NOTE 1. ADD
 THE WORDS "AND PLAN SHEET A1-702" AFTER THE WORDS "PLAN
 SHEET A1-700" AND ADJUST VALUE OF WORK ON PERMIT
 APPLICATION TO REFLECT SUCH PER WPB FBC 107.2.1
 3. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 LOCATED IN PUBLIC TOILET ROOMS THROUGH AN APPROVED
 WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B125.3 PER FBC PL 416.5. PLEASE NOTE ON
 PLAN SHEET 1A-700; BATHROOM EQUIPMENT SPECS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  