Plan Review Details - Permit 18081197
Plan Review Stops For Permit 18081197
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2018-10-18 Cont ID  
Sent By cthroop Date 2018-10-18 Time 17:28 Rev Time 0.00
Received By cthroop Date 2018-10-18 Time 17:28 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-10-18 Cont ID  
Sent By shill Date 2018-10-18 Time 14:46 Rev Time 0.00
Received By shill Date 2018-10-18 Time 14:46 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-10-17 Cont ID  
Sent By shill Date 2018-10-17 Time 15:42 Rev Time 0.00
Received By shill Date 2018-10-17 Time 15:42 Sent To  
Notes
2018-10-17 15:43:00****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 553.79(5) 2016, THIS IS A THRESHOLD BUILDING. THE
 FOLLOWING IS REQUIRED PRIOR TO COMMENCEMENT:
  
 1. COMPLETE THE THRESHOLD / SPECIAL INSPECTOR AGREEMENT
 OF UNDERSTANDING; THIS HAS BEEN SENT VIA EMAIL TO
 CONTRACTOR.
  
 2. PROVIDE RESUMES AND COPIES OF LICENSES FOR ALL
 PROPOSED INSPECTORS OTHER THAN THE SI, IF APPLICABLE.
  
 3. ALL PLANS ARE TO INCLUDE THE THRESHOLD STATEMENT
 REQUIRED BY FS553.79(7)(D).
  
 (D)ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED TO BE
 SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF
 RECORD CONTAIN A STATEMENT THAT, TO THE BEST OF THE
 ARCHITECT?S OR ENGINEER?S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM
 BUILDING CODES AND THE APPLICABLE FIRE SAFETY STANDARDS
 AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH
 THIS CHAPTER 553 AND CHAPTER 633.
  
 EITHER REVISE PLAN/SPECIFICATION TO INCLUDE, OR ADVISE
 WHERE THIS CAN BE FOUND.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-09-26 Cont ID  
Sent By cthroop Date 2018-09-26 Time 11:10 Rev Time 0.00
Received By cthroop Date 2018-09-26 Time 06:54 Sent To  
Notes
2018-09-26 11:11:30BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. ADDRESS COMMENTS UNDER THRESHOLD REVIEW PRIOR TO
 BUILDING APPROVAL.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-10-17 Cont ID  
Sent By shill Date 2018-10-17 Time 15:43 Rev Time 0.00
Received By shill Date 2018-10-15 Time 07:41 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-09-26 Cont ID  
Sent By cthroop Date 2018-09-26 Time 11:11 Rev Time 0.00
Received By cthroop Date 2018-08-30 Time 15:52 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2018-10-18 Cont ID  
Sent By cthroop Date 2018-10-18 Time 17:28 Rev Time 0.00
Received By cthroop Date 2018-10-18 Time 17:27 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2018-10-17 Cont ID  
Sent By shill Date 2018-10-17 Time 15:43 Rev Time 0.00
Received By shill Date 2018-10-17 Time 15:43 Sent To  
Notes
2018-10-17 15:46:16ORIGINAL SIGNED AND SEALED PAPER DOCUMENTS ARE REQUIRED
 AFTER ALL PLAN REVIEWS HAVE PASSED
2018-10-12 09:57:1510/11/18 HARD COPIES ROUTED TO CTHROOP

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2018-09-26 Cont ID  
Sent By cthroop Date 2018-09-26 Time 08:11 Rev Time 0.00
Received By cthroop Date 2018-09-26 Time 06:54 Sent To  
Notes
2018-09-26 08:15:27BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. CANNOT VERIFY SIGNATURES AND SEALS ON THE FOLLOWING
 DOCUMENTS.
  
  
 A. CONCRETE REPAIR SPECIFICATIONS
 B. THRESHOLD STATEMENT
 C. SPECIAL INSPECTOR AGREEMENT
  
 UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT.

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 2 Status P Date 2018-10-18 Cont ID  
Sent By cthroop Date 2018-10-18 Time 17:28 Rev Time 0.00
Received By cthroop Date 2018-10-18 Time 17:27 Sent To  
Notes
***NONE***

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status F Date 2018-09-26 Cont ID  
Sent By cthroop Date 2018-09-26 Time 08:15 Rev Time 0.00
Received By cthroop Date 2018-09-26 Time 06:54 Sent To  
Notes
2018-09-26 08:56:23BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. CONTRACTOR SHALL COMPLY WITH FBC CHPT 33 -
 SAFEGUARDS DURING CONSTRUCTION.
 PLEASE PROVIDE A SITE PLAN SHOWING THE PROPERTY LINES,
 CONSTRUCTION AREAS, STAGING AREAS, HOW THE OCCUPANTS OF
 THE BUILDING WILL BE SAFE GUARDED DURING THEIR ENTRY
 AND EXIT OF THE BUILDING. SHOW COMPLIANCE WITH 2017 FBC
 3306.7 ? COVERED WALKWAYS, INCLUDING LIGHTING FOR THE
 EXIT DISCHARGE. 2017 FBC 3310.2 ? MAINTENANCE OF MEANS
 OF EGRESS. REQUIRED MEANS OF EGRESS SHALL BE MAINTAINED
 AT ALL TIMES DURING CONSTRUCTION, DEMOLITION,
 REMODELING OR ALTERATIONS AND ADDITIONS TO ANY
 BUILDING.
  
 3301.1 SCOPE.
 THE PROVISIONS OF THIS CHAPTER SHALL GOVERN SAFETY
 DURING CONSTRUCTION AND THE PROTECTION OF ADJACENT
 PUBLIC AND PRIVATE PROPERTIES.
 3301.2 STORAGE AND PLACEMENT.
 CONSTRUCTION EQUIPMENT AND MATERIALS SHALL BE STORED
 AND PLACED SO AS NOT TO ENDANGER THE PUBLIC, THE
 WORKERS OR ADJOINING PROPERTY FOR THE DURATION OF THE
 CONSTRUCTION PROJECT.
  
 3302 CONSTRUCTION SAFEGUARDS
 3302.1 ALTERATIONS, REPAIRS AND ADDITIONS.
 REQUIRED EXITS, EXISTING STRUCTURAL ELEMENTS, FIRE
 PROTECTION DEVICES AND SANITARY SAFEGUARDS SHALL BE
 MAINTAINED AT ALL TIMES DURING ALTERATIONS, REPAIRS OR
 ADDITIONS TO ANY BUILDING OR STRUCTURE.
 EXCEPTIONS:
 1. WHERE SUCH REQUIRED ELEMENTS OR DEVICES ARE BEING
 ALTERED OR REPAIRED, ADEQUATE SUBSTITUTE PROVISIONS
 SHALL BE MADE.
 2. MAINTENANCE OF SUCH ELEMENTS AND DEVICES IS NOT
 REQUIRED WHEN THE EXISTING BUILDING IS NOT OCCUPIED.
 3302.2 MANNER OF REMOVAL.
 WASTE MATERIALS SHALL BE REMOVED IN A MANNER THAT
 PREVENTS INJURY OR DAMAGE TO PERSONS, ADJOINING
 PROPERTIES AND PUBLIC RIGHTS-OF-WAY.
 3302.3 FIRE SAFETY DURING CONSTRUCTION.
 FIRE SAFETY DURING CONSTRUCTION SHALL COMPLY WITH THE
 APPLICABLE REQUIREMENTS OF THIS CODE AND THE APPLICABLE
 PROVISIONS OF THE FLORIDA FIRE PREVENTION CODE.
  
 2. CANNOT VERIFY ORIGINAL SIGNATURE AND SEAL ON
 THRESHOLD STATEMENT.
 UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
  
 3. CANNOT VERIFY ORIGINAL SIGNATURE AND SEAL ON
 CONCRETE REPAIR STATEMENT.
 UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
  
 4. SPECIAL INSPECTOR AGREEMENT -
 A. FORM SUBMITTED IS OUT OF DATE. YOU MAY DOWNLOAD THE
 NEW SPECIAL INSPECTOR/RESIDENT INSPECTOR AGREEMENT FROM
 THE CITY'S WEBSITE AT WPB.ORG. COMPLETE ONLY THOSE
 SECTION THAT COMPLY WITH SPECIAL INSPECTOR FOR
 THRESHOILD BUILDINGS.
 B. CANNOT VERIFY ORIGINAL SIGNATURE AND SEALS.
 UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
  
 C. OWNER SECTION IS INCOMPLETE. NOTARIZED SIGNATURE
 REQUIRED.
 D. CONTRACTOR SECTION IS INCOMPLETE. NOTARIZED
 SIGNATURE REQUIRED.
 THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUESTS FOR THRESHOLD
 BUILDINGS, A SPECIAL INSPECTOR IS REQUIRED BY F.S.
 553.79 (5) TO THE MINIMUM INSPECTIONS REQUIRED BY THIS
 CODE. THE THRESHOLD INSPECTION FORMS ARE REQUIRED TO BE
 FILLED OUT BY ALL PARTIES WITH INTEREST, NOTARIZED AND
 RETURNED TO THIS OFFICE AND REVIEWED AND APPROVED
 BEFORE PERMIT ISSUANCE WILL TAKE PLACE.
  
 E. JOB INSPECTOR GUILLERMO PABRON IS NOT LICENSED PER
 FS 468 TO PERFORM STRUCTURAL INSPECTIONS. HIS
 ACTIVITIES SHALL BE LIMITED TO QUALITY CONTROL ISSUES
 ONLY.
 110.8.6 THE BUILDING DEPARTMENT MAY ALLOW A SPECIAL
 INSPECTOR TO CONDUCT THE MINIMUM STRUCTURAL INSPECTION
 OF THRESHOLD BUILDINGS REQUIRED BY THIS CODE, SECTION
 553.73, FLORIDA STATUTES, WITHOUT DUPLICATIVE
 INSPECTION BY THE BUILDING DEPARTMENT. THE BUILDING
 OFFICIAL IS RESPONSIBLE FOR ENSURING THAT ANY PERSON
 CONDUCTING INSPECTIONS IS QUALIFIED AS A BUILDING
 INSPECTOR UNDER PART XII OF CHAPTER 468, FLORIDA
 STATUTES, OR CERTIFIED AS A SPECIAL INSPECTOR
 UNDER CHAPTER 471 OR 481, FLORIDA STATUTES. INSPECTIONS
 OF THRESHOLD BUILDINGS REQUIRED BY SECTION 553.79(5),
 FLORIDA STATUTES, ARE IN ADDITION TO THE MINIMUM
 INSPECTIONS REQUIRED BY THIS CODE.
  
 110.8.4.1 THE SPECIAL INSPECTOR, UPON COMPLETION OF THE
 BUILDING AND PRIOR TO THE ISSUANCE OF A CERTIFICATE OF
 OCCUPANCY OR COMPLETION, FILE A SIGNED AND SEALED
 STATEMENT WITH THE ENFORCEMENT AGENCY IN SUBSTANTIALLY
 THE FOLLOWING FORM: ?TO THE BEST OF MY KNOWLEDGE AND
 BELIEF, THE CONSTRUCTION OF ALL STRUCTURAL LOAD-BEARING
 COMPONENTS DESCRIBED IN THE THRESHOLD INSPECTION PLAN
 COMPLIES WITH THE PERMITTED DOCUMENTS AND THE SPECIALTY
 SHORING DESIGN PROFESSIONAL ENGINEER HAS ASCERTAINED
 THAT THE SHORING AND RESHORING CONFORMS WITH THE
 SHORING AND RESHORING PLANS SUBMITTED TO THE
 ENFORCEMENT AGENCY?.
  
 NOTICE ONLY. PLEASE CALL THE CITY OF WEST PALM BEACH?S
 AUTOMATED TELEPHONE INSPECTION LINE @ (561) 805-6700
 FOR ALL BUILDING INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS. WITHOUT THIS, THE PERMIT EXPIRES IN 6
 MONTHS WHICH WILL RESULT IN ?ABANDONMENT OF JOB, NO
 INSPECTION ACTIVITY?. THE PERMIT WILL BECOME EXPIRED.
  
 CONTACT KEN CONRAD, MANAGER OF THE SPECIAL INSPECTOR
 PROGRAM AT (561) 805-6666 FOR ANY ADDITIONAL QUESTIONS
 YOU MAY HAVE.
  
  
  
  
  
  
  
  