Plan Review Details - Permit 18081151
Plan Review Stops For Permit 18081151
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2018-10-10 Cont ID  
Sent By shill Date 2018-10-10 Time 17:59 Rev Time 0.00
Received By shill Date 2018-10-10 Time 17:59 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-11-15 Cont ID  
Sent By jleahy Date 2018-11-15 Time 16:37 Rev Time 0.00
Received By jleahy Date 2018-11-15 Time 16:37 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-09-25 Cont ID  
Sent By jleahy Date 2018-09-25 Time 08:17 Rev Time 0.00
Received By jleahy Date 2018-09-25 Time 08:17 Sent To  
Notes
2018-09-25 08:18:04FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NEED TO SUBMIT A LOAD CALCULATION PER ARTICLE 220 OF
 THE NEC 2014 ED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2018-08-27 Cont ID  
Sent By scaldero Date 2018-08-27 Time 14:34 Rev Time 0.00
Received By scaldero Date 2018-08-27 Time 14:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-11-29 Cont ID  
Sent By gjohnson Date 2018-11-29 Time 16:50 Rev Time 0.00
Received By gjohnson Date 2018-10-26 Time 14:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-10-10 Cont ID  
Sent By shill Date 2018-10-10 Time 17:59 Rev Time 0.00
Received By shill Date 2018-08-23 Time 08:26 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-10-05 Cont ID  
Sent By ccole Date 2018-10-03 Time 07:52 Rev Time 0.00
Received By ccole Date 2018-10-03 Time 12:29 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-11-29 Cont ID  
Sent By gjohnson Date 2018-11-29 Time 16:44 Rev Time 0.00
Received By gjohnson Date 2018-11-29 Time 16:44 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-10-09 Cont ID  
Sent By gjohnson Date 2018-10-09 Time 11:06 Rev Time 0.00
Received By gjohnson Date 2018-10-06 Time 07:10 Sent To  
Notes
2018-10-09 12:06:111ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. A MIN OF 1 URINAL SHALL COMPLY WITH FBC ACC 213.3.3
 AND 605
  
 2. WHERE TOILET COMPARTMENTS ARE PROVIDED, AT LEAST ONE
 TOILET COMPARTMENT SHALL COMPLY WITH 604.8.1. IN
 ADDITION TO THE COMPARTMENT REQUIRED TO COMPLY WITH
 604.8.1, AT LEAST ONE COMPARTMENT SHALL COMPLY WITH
 604.8.2 WHERE SIX OR MORE TOILET COMPARTMENTS ARE
 PROVIDED, OR WHERE THE COMBINATION OF URINALS AND WATER
 CLOSETS TOTALS SIX OR MORE FIXTURES. THE EXISTING
 TOILET STALL MAY COMPLY WITH 604.8.1 PLEASE PROVIDE
 ENLARGED DETAIL SHOWING ALL REQUIRED DIMENSIONS. PER
 FBC ACC 213.3.1
  
 3. PLEASE PROVIDE A WATER AND SANITARY ISOMETRIC
 DRAWING. PER WPB AMEND TO FBC 107.3.5.1.3(13)
  
 4. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5
  
 5. PLEASE PROVIDE A PLUMBING FIXTURE COUNT BREAK DOWN
 WIT NEW OCCUPANT LOAD. PER WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2018-11-29 Cont ID  
Sent By gjohnson Date 2018-11-29 Time 16:48 Rev Time 0.00
Received By gjohnson Date 2018-11-29 Time 16:48 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2018-10-10 Cont ID  
Sent By shill Date 2018-10-10 Time 18:00 Rev Time 0.00
Received By shill Date 2018-10-10 Time 18:00 Sent To  
Notes
2018-10-10 18:02:53SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 THE PAGES SUBMITTED ARE NOT DIGITALLY SIGNED AND
 SEALED.
  
 BOTH ARCHITECT AND ENGINEER HAVE DIGITAL SIGNATURES.
 PLEASE PROVIDE DIGITALLY SIGNED DOCUMENTS WHEN
 RESUBMITTING. IF YOU ARE UNSURE AS TO HOW TO DETERMINE
 IF THE SHEETS ARE SIGNED, PLEASE CONTACT ME.
  
 ARCHITECT - ALAN H. POPKIN, RA
 FP, M, E, P - MICHAEL K. SULLIVAN, PE85173
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2018-08-25 Cont ID  
Sent By shill Date 2018-08-25 Time 08:38 Rev Time 0.00
Received By shill Date 2018-08-25 Time 08:38 Sent To  
Notes
2018-08-25 08:48:23SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 THE PAGES SUBMITTED ARE NOT DIGITALLY SIGNED AND
 SEALED.
  
 DO THE DESIGN PROFESSIONALS HAVE DIGITAL SEALS? IF YES,
 PLEASE CONTACT:
  
 [email protected], [email protected]
  
 UPLOAD DIGITALLY SIGNED AND SEALED PAGES **PRIOR TO
 FIRST REVIEW**.
  
 IF NOT, PLEASE SUBMIT ONE ORIGINAL SIGNED AND SEALED
 PAPER SET OF PLANS TO THE BUILDING DIVISION WITH A
 "PLAN REVIEW REQUEST FORM" AND IN THE DESCRIPTION
 INDICATE THAT THEY ARE "SIGNATURE DOCUMENTS".
  
 AS A SIGNATURE REVIEW AT THE END OF THE PROCESS ADDS A
 FEW BUSINESS DAYS TO THE PLAN REVIEW PROCESS, IT IS
 PREFERABLE THAT PAGES SIGNED AND SEALED IN ACCORDANCE
 WITH FLORIDA STATUTE 471 AND 481 ARE SUBMITTED.
  
 ARCHITECT - ALAN H. POPKIN, RA
 FP, M, E, P - MICHAEL K. SULLIVAN, PE85173
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2018-09-28 Cont ID  
Sent By aaponte Date 2018-09-28 Time 12:46 Rev Time 0.00
Received By aaponte Date 2018-09-28 Time 12:46 Sent To  
Notes
***NONE***