Plan Review Details - Permit 18081117
Plan Review Stops For Permit 18081117
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2019-02-26 Cont ID  
Sent By pvalenti Date 2019-02-26 Time 13:15 Rev Time 0.00
Received By pvalenti Date 2019-02-26 Time 13:15 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-10-02 Cont ID  
Sent By rmcdouga Date 2018-10-02 Time 07:34 Rev Time 0.00
Received By rmcdouga Date 2018-10-01 Time 18:26 Sent To I
Notes
2018-10-01 19:20:14PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SPECIFY THE CLASSIFICATION OF THIS WORK ON THE
 PLANS. THIS IS A LEVEL 2 ALTERATION PER FBC EXISTING
 BUILDING SECTION 504.
  
 2) SPECIFY THE CONSTRUCTION TYPE FOR THE BUILDING ON
 THE PLANS. THIS IS A HIGH RISE BUILDING AND IS EITHER
 TYPE I OR TYPE II CONSTRUCTION.
  
 3) SPECIFY ON THE PLANS THAT THE INTERIOR NONBEARING
 WALLS AND PARTITIONS ARE REQUIRED TO BE OF
 NONCOMBUSTIBLE MATERIALS OR FIRE-RETARDANT TREATED
 WOOD. FBC 602.2
  
 4) PROVIDE THE FOLLOWING INFORMATION FOR THE PROPOSED
 FLOORING:
  
 1. TYPE OF PROPOSED HARD FLOORING (TILE, LAMINATE,
 WOOD, MARBLE, ETC.).
 2. DESCRIPTION OF EXISTING SITE CONDITIONS:
 (A) THICKNESS OF SLAB (B) FLOOR/CEILING ASSEMBLY BELOW
 (EXPOSED CONCRETE, SUSPENDED GYPSUM OR ACOUSTICAL ).
 3. PROPOSED UNDERLAYMENT.
 4. SUBMIT TEST REPORTS FOR THE PROPOSED UNDERLAYMENT
 BASED ON THE EXISTING SITE CONDITIONS.
 5. TEST REPORTS TO BE BASED ON THE FOLLOWING ASTM'S:
 E-84, E-90 & E-492.
 6. ALL DOCUMENTS SHALL BE SUBMITTED IN DUPLICATE.
  
 FBC 603.1 FLAME SPREAD - ASTM E 84-09
  
 FBC 1207.2 AIR-BORNE SOUND. ASTM E 90-04
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E 492-09
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 SUBMIT TWO COPIES OF THE TEST REPORTS FOR THE SOUND
 INSULATION INCLUDING FLAME SPREAD AND SMOKE DEVELOPED
 FOR THE APPLICABLE CONSTRUCTION CONDITIONS.
  
  
 FBC 603 COMBUSTIBLE MATERIAL IN TYPE I AND II
 CONSTRUCTION
 603.1 ALLOWABLE MATERIALS.
 COMBUSTIBLE MATERIALS SHALL BE PERMITTED IN BUILDINGS
 OF TYPE I OR II CONSTRUCTION IN THE FOLLOWING
 APPLICATIONS AND IN ACCORDANCE WITH SECTIONS 603.1.1
 THROUGH 603.1.3:
 2. THERMAL AND ACOUSTICAL INSULATION, OTHER THAN FOAM
 PLASTICS, HAVING A FLAME SPREAD INDEX OF NOT MORE THAN
 25.
 EXCEPTIONS:
 1. INSULATION PLACED BETWEEN TWO LAYERS OF
 NONCOMBUSTIBLE MATERIALS WITHOUT AN INTERVENING
 AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX
 OF NOT MORE THAN 100.
 2. INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND
 SOLID DECKING WITHOUT INTERVENING AIRSPACE SHALL BE
 ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN
 200.
  
 3. FOAM PLASTICS IN ACCORDANCE WITH CHAPTER 26.
  
  
 FBC 2603 FOAM PLASTIC INSULATION
 2603.3 SURFACE-BURNING CHARACTERISTICS.
 UNLESS OTHERWISE INDICATED IN THIS SECTION, FOAM
 PLASTIC INSULATION AND FOAM PLASTIC CORES OF
 MANUFACTURED ASSEMBLIES SHALL HAVE A FLAME SPREAD INDEX
 OF NOT MORE THAN 75 AND A SMOKE-DEVELOPED INDEX OF NOT
 MORE THAN 450 WHERE TESTED IN THE MAXIMUM THICKNESS
 INTENDED FOR USE IN ACCORDANCE WITH ASTM E 84 OR UL
 723. LOOSE FILL-TYPE FOAM PLASTIC INSULATION SHALL BE
 TESTED AS BOARD STOCK FOR THE FLAME SPREAD AND
 SMOKE-DEVELOPED INDEXES.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2019-02-25 Cont ID  
Sent By jpearson Date 2019-02-25 Time 11:08 Rev Time 0.00
Received By jpearson Date 2019-02-25 Time 10:50 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-09-17 Cont ID  
Sent By jpearson Date 2018-09-17 Time 12:03 Rev Time 0.00
Received By jpearson Date 2018-09-17 Time 12:03 Sent To  
Notes
2018-09-17 12:03:18CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT,
 SINGLE-PHASE, 15- AND 20-AMPERE OUTLETS INSTALLED IN
 KITCHENS, FAMILY ROOMS, DINING ROOMS, LIVING ROOMS,
 PARLORS, LIBRARIES, DENS, BEDROOMS, SUN-ROOMS,
 RECREATIONS ROOMS, CLOSETS, HALLWAYS, LAUNDRY AREAS AND
 SIMILAR ROOMS OR AREAS SHALL BE AFCI PROTECTED. THIS
 INCLUDES LIGHTING AND POWER OUTLETS AND RECEPTACLES.
 SOME AREAS REQUIRE BOTH AFCI AND GFCI PROTECTION.
 PROVIDE CORRECTION. NEC 210.8, 210.12
 2. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5,
 408.4
 3. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC 210.8(D)
 4. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12
 5. A GFCI PROTECTED RECEPTACLE OUTLET ON A 20 AMP
 CIRCUIT IS REQUIRED WITHIN 3 FEET OF EACH BASIN.
 PROVIDE CORRECTION. NEC 210.11(C)(3), 210.52(D)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED "OLD
 SHEETS".
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2019-02-07 Cont ID  
Sent By pleduc Date 2019-02-07 Time   Rev Time 0.00
Received By pleduc Date 2019-02-07 Time 12:19 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-08-27 Cont ID  
Sent By pleduc Date 2018-08-27 Time   Rev Time 0.00
Received By pleduc Date 2018-08-27 Time 13:10 Sent To  
Notes
2018-08-27 15:42:55THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE ARE NO INDICATIONS OF WORK OR STATUS ON THE
 LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE SPRINKLERS.
  
 THE LIFE SAFETY SYSTEMS SHALL BE MAINTAINED AT ALL
 TIMES DURING CONSTRUCTION.
  
 PLEASE PROVIDE AND APPLICABLE NOTE OF ACKNOWLEDGEMENT
 AND COMPLIANCE.
  
  
  
 2) ANY WORK ON THE LIFE SAFETY SYSTEMS SHALL BE UNDER
 SEPARATE SHOP DAWINGS BY CERTIFIED LIFE SAFETY
 CONTRACTORS.
  
 PER NFPA 1
  
 1.14.5 WHEN REQUIRED BY THE AHJ, REVISED CONSTRUCTION
 DOCUMENTS OR SHOP DRAWINGS SHALL BE PREPARED AND
 SUBMITTED FOR
 REVIEW AND APPROVAL TO ILLUSTRATE CORRECTIONS OR
 MODIFICATIONS
 NECESSITATED BY FIELD CONDITIONS OR OTHER REVISIONS TO
 APPROVED
 PLANS.
  
 PLEASE PROVIDE AND APPLICABLE NOTE OF ACKNOWLEDGEMENT
 AND COMPLIANCE.
  
  
  
 3) SHEET EP 300 - THERE ARE NO INDICATION OF SMOKE
 DETECTION/ALARMS IN THE AFFECTED BEDROOM AND/OR
 HALLWAY.
  
 PER NFPA 101
  
 31.3.4.5 SMOKE ALARMS.
 31.3.4.5.1* IN BUILDINGS OTHER THAN THOSE EQUIPPED
 THROUGHOUT WITH AN
 EXISTING, COMPLETE AUTOMATIC SMOKE DETECTION SYSTEM,
 SMOKE ALARMS
 SHALL BE INSTALLED IN ACCORDANCE WITH 9.6.2.10, AS
 MODIFIED BY 31.3.4.5.2,
 OUTSIDE EVERY SLEEPING AREA IN THE IMMEDIATE VICINITY
 OF THE BEDROOMS
 AND ON ALL LEVELS OF THE DWELLING UNIT, INCLUDING
 BASEMENTS.
 31.3.4.5.2 SMOKE ALARMS REQUIRED BY 31.3.4.5.1 SHALL
 NOT BE REQUIRED TO
 BE PROVIDED WITH A SECONDARY (STANDBY) POWER SOURCE.
  
 PLEASE PROVIDE APPLICABLE DETAILS.
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status P Date 2019-02-26 Cont ID  
Sent By pvalenti Date 2019-02-26 Time 13:16 Rev Time 0.00
Received By pvalenti Date 2019-02-04 Time 14:56 Sent To  
Notes
2019-02-05 14:56:42B24

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-10-02 Cont ID  
Sent By rmcdouga Date 2018-10-02 Time 07:34 Rev Time 0.00
Received By rmcdouga Date 2018-08-22 Time 09:54 Sent To  
Notes
2018-08-24 09:54:39B21

Review Stop P PLUMBING
Rev No 2 Status P Date 2019-02-21 Cont ID  
Sent By jesmith Date 2019-02-21 Time 12:58 Rev Time 0.00
Received By jesmith Date 2019-02-21 Time 12:57 Sent To  
Notes
2019-02-21 12:58:04APPROVED
 PLUMBING PROVISO
 1. ALL WORK PER CITY CODES SUBJECT TO FIELD INSPECTOR'S
 APPROVAL
 2. NO NEW SHOWER FLOOR PER JOHNSTON GROUP?S COMMENTS
 DATED 2/4/19

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-09-19 Cont ID  
Sent By shill Date 2018-09-19 Time 12:53 Rev Time 0.00
Received By jesmith Date 2018-09-19 Time 12:49 Sent To  
Notes
2018-09-19 12:53:02CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 1ST REVIEW:
 PERMIT 18081117
 PLUMBING COMMENTS: DENIED
  
 1. PROVIDE NOTE D/W AND REF ICE LINE STATING "WATER
 HAMMER ARRESTOR TO BE INSTALLED IN ACCORDANCE WITH FBC
 RES P2903.5"
 2. PROVIDE NOTE AT SHOWER STATING "SHOWER CONTROL
 VALVE(S) SHALL BE PRESSURE BALANCED PB,THERMOSTATIC
 MIXING (TM) OR COMBINATION PB/TM VALVE TYPES WITH HIGH
 TEMPERATURE LIMITING STOP." FBC RES P2708.4
 3. WILL THERE BE A HAND HELD SHOWER? PLEASE CLARIFY ON
 PLAN. IF SO, PROVIDE NOTE STATING "HAND HELD SHOWER
 REQUIRES AN ATMOSPHERIC VACUUM BREAKER AT SHOWER ARM
 OUTLET." FBC RES P2708.5
 4. THE NOTE CONCERNING THE "NEW RAINSHOWER HEAD WITH
 SEPARATE CONTROLS" INDICATES THAT THERE WILL BE NEW
 TILE WORK. IF SO, SUCH NEW WORK SHOULD BE INDICATED ON
 THE PLANS. ADDITIONALLY IF THE SHOWER FLOOR IS INVOLVED
 A CURRENT CODE COMPLIANT SHOWER PAN MAY BE REQUIRED.
  
  
 NOTE OF INTEREST
 RE: LAVATORY DRAIN; ONE SINGLE TRAP SERVICING TWO
 LAVATORIES AS NOTED AND SHOWN IS PERMITTED PER FBC RES
 P3201.6 SO LONG AS THE DISTANCE BETWEEN THE TWO OUTLETS
 DOES NOT EXCEED 30".
 HOWEVER, FOR A FEASIBLE ALTERNATIVE INSTALLATION,
 PLEASE REFER TO FBC RES P3107.2 COMMON VENT, ALLOWING
 FOR INSTALLATION OF INDIVIDUAL TRAP FOR EACH LAV AND
 CONNECT FIXTURE DRAINS TO SINGLE BRANCH STUBBED OUT
 UNDER COUNTER. IF THIS METHOD IS TO BE USED, THEN NOTE
 AND SHOW ON PLAN.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED "VOID".
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6715
  