Plan Review Details - Permit 18081069
Plan Review Stops For Permit 18081069
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-09-22 Cont ID  
Sent By shill Date 2018-09-22 Time 12:42 Rev Time 0.00
Received By shill Date 2018-09-22 Time 12:42 Sent To  
Notes
2018-09-22 12:42:21****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC EB 301.1, THE ALTERATION, CHANGE OF OCCUPANCY IS
 TO COMPLY WITH ONE OF THE METHODS LISTED IN 301.1.1
 THROUGH 301.1.3 AS SELECTED BY APPLICANT. REVISE PLAN
 TO SPECIFY; MOST COMMON IS WORK AREA COMPLIANCE METHOD.
 IF THAT IS ELECTED, REVISE PLAN TO INCLUDE CHAPTER 10
 CHANGE OF OCCUPANCY AND LEVEL 1 OR LEVEL 2 ALTERATION
 AS APPLICABLE.
  
 SINCE THE FLOOR PLAN IS NOT LEGIBLE, WORK PROPOSED IS
 NOT CLEAR. NOTHING IS NOTED AS "EXISTING" OR "PROPOSED
 NEW". THE LATEST PERMIT PLANS ARE HELPFUL TO DOCUMENT
 EXISTING CONDITIONS BUT THE NEW PLAN NEEDS TO BE CLEAR
 AS TO WORK PROPOSED AND EXISTING TO REMAIN.
  
 2. FBC 107, REVISE PLAN TO INCLUDE THE PRINTED NAME AND
 SIGNATURE OF INDIVIDUAL TAKING RESPONSIBILITY FOR THE
 DESIGN/INFORMATION.
  
 3. FBC 107, PLAN IS NOT LEGIBLE DUE TO THE GREY OVER
 THE FLOOR PLAN. EITHER REMOVE THE GREY OR MAKE THE PLAN
 LEGIBLE IN ANOTHER MANNER. ALL ROOM DESIGNATIONS,
 SQUARE FOOT AREA, OTHER INFORMATION IS TO BE EASILY
 READABLE AND ALSO READABLE ON PAPER AND ALSO AFTER
 SCANNING.
  
 4. FBC 107, DECLARE AN OCCUPANT LOAD. PLAN STATES THAT
 THE SCHOOL IS LIMITED TO 100 STUDENTS. REVISE PLAN TO
 CLEARLY NOTE DESIGN OCCUPANT LOAD. NUMBER OF STAFF
 SHOULD BE INCLUDED.
  
 5. FBC 107, REVISE PLAN TO STATE EXISTING OCCUPANCY
 (BUSINESS), PROPOSED OCCUPANCY (EDUCATION).
  
 6. A NOTE STATES THAT THE REAR DOOR HAS PANIC BARS. SEE
 FBC EB 1005.1, FBC EB 1012.4.1, FBC B 1010.1.10.
  
 7. REVISE PLAN TO SHOW SQUARE FOOT AREA FOR EACH ROOM,
 OCCUPANT LOAD FOR EACH ROOM, FBC B 1010.1.10. SEE FBC B
 TABLE 1004.1.2, USE 20 SF NET PER PERSON. ALTHOUGH A
 REDUCED OCCUPANT LOAD FOR DETERMINING PLUMBING FIXTURES
 WAS REQUIRED, MEANS OF EGRESS TO COMPLY WITH THE TABLE.
 IF ANY ROOM HAS AN OCCUPANT LOAD OVER 50, A PANIC BAR
 IS REQUIRED AND SHOULD BE NOTED ON THE PLAN.
  
 8. FBC EB TABLE 1012.5, SHOW COMPLIANCE FOR BUIDING
 HEIGHT AND AREA AS THIS IS A CHANGE TO A HIGHER HAZARD.
  
 9. REVISE PLAN TO INCLUDE GOVERNING CODE (FLORIDA
 BUILDING CODE 6TH EDITION).
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-09-03 Cont ID  
Sent By jpearson Date 2018-09-03 Time 09:30 Rev Time 0.00
Received By jpearson Date 2018-09-03 Time 09:30 Sent To  
Notes
2018-09-03 09:30:33CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PER THE WPB AMENDMENTS TO THE FBC, PLAN (EACH SHEET
 OF BOTH COPIES) IS REQUIRED TO BEAR THE NAME AND BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. PROVIDE CORRECTION. WPB FBC 107.1, 107.2; FS
 471, 481
 2. PROVIDE ELECTRICAL PLAN FOR REVIEW. PLAN PROVIDED
 WAS A COPY OF A PREVIOUSLY PERMITTED JOB AT THIS
 LOCATION AND DOES NOT INDICATE ANY WORK PROPOSED FOR
 THE CHANGE OF OCCUPANCY. PREVIOUS PLANS ARE NOT
 ACCEPTABLE. WPB FBC 107.2.1, 107.3.5
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD
 SHEETS?.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-08-30 Cont ID  
Sent By pleduc Date 2018-08-30 Time   Rev Time 0.00
Received By pleduc Date 2018-08-29 Time 16:18 Sent To  
Notes
2018-08-29 16:45:57THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THE SUBMITTED PLANS DO NOT INCLUDE SUFFICIENT DETAIL
 TO COMPLETE A THOROUGH PLAN REVIEW.
  
 PER NFPA 1
 1.14 PLAN REVIEW.
  
 1.14.2 THE APPLICANT SHALL BE RESPONSIBLE TO ENSURE
 THAT THE
 FOLLOWING CONDITIONS ARE MET:
 (1) THE CONSTRUCTION DOCUMENTS INCLUDE ALL OF THE FIRE
 PROTECTION
 REQUIREMENTS.
  
 THE PLAN SHEET PROVIDED ARE FROM AN OLD PLAN SET FROM
 2010.
  
 PLEASE PROVIDE CURRENT PLAN SHEETS FOR A CERTIFIED
 DESIGN PROFESSIONAL.
  
  
  
  
 2) THERE ARE NO INDICATIONS OF REVIEW OR COMPLIANCE
 WITH THE CURRENT FLORIDA LIFE SAFETY CODE.
  
 PER NFPA 101 THIS IS A NEW EDUCATIONAL OCCUPANCY AND
 SHALL COMPLY WITH THE 6TH EDITION OF THE FFPC.
  
 CHAPTER 1 ADMINISTRATION
 1.3 APPLICATION.
 1.3.1* NEW AND EXISTING BUILDINGS AND STRUCTURES. THE
 CODE SHALL
 APPLY TO BOTH NEW CONSTRUCTION AND EXISTING BUILDINGS
 AND EXISTING
 STRUCTURES.
  
 CHAPTER 14 NEW EDUCATIONAL OCCUPANCIES
 14.1 GENERAL REQUIREMENTS.
 14.1.1 APPLICATION.
 14.1.1.1 THE REQUIREMENTS OF THIS CHAPTER SHALL APPLY
 TO NEW
 BUILDINGS OR PORTIONS THEREOF USED AS EDUCATIONAL
 OCCUPANCIES.
  
 PLEASE DESCRIBE IN DETAIL THE AGE AND GRADE LEVELS AS
 WELL AS THE HOURS OF OCCUPANCY.
  
 PLEASE PROVIDE AND DOCUMENT ALL THE APPLICABLE
 REQUIREMENTS OF THE OCCUPANCY CHAPTER.
  
  
 3) THERE IS NO LIFE SAFETY PLAN FOR THIS OCCUPANCY.
  
 THIS IS A EDUCATIONAL OCCUPANCY AND A LIFE SAFETY PLAN
 IS REQUIRED.
  
 NFPA 101
  
 1.3.1.1 IF DEEMED NECESSARY BY AN AHJ FOR A COMPLETE,
 ACCURATE, AND
 THOROUGH FIRE SAFETY PLANS REVIEW OR INSPECTION, THE
 AHJ MAY REQUEST
 ASSISTANCE FROM THE BUILDING, ELECTRICAL, PLUMBING,
 MECHANICAL OR SIMILAR
 SPECIALTY INSPECTOR; HOWEVER, NOTHING IN THIS RULE
 GIVES AUTHORITY OR
 JURISDICTION TO ANY PERSON OTHER THAN A FIRE SAFETY
 INSPECTOR CERTIFIED
 UNDER SECTION 633.216, FLORIDA STATUTES, TO PERFORM
 FIRE SAFETY
 INSPECTIONS REQUIRED BY LAW, RULE, ORDINANCE, OR CODE.
  
  
 4) THERE ARE NO INDICATIONS THE CORRIDORS MEET THE
 REQUIREMENTS FOR EDUCATIONAL OCCUPANCIES.
  
 NFPA 101
  
 14.3.6 CORRIDORS. CORRIDORS SHALL BE SEPARATED FROM
 OTHER PARTS OF
 THE STORY BY WALLS HAVING A 1-HOUR FIRE RESISTANCE
 RATING IN
 ACCORDANCE WITH SECTION 8.3, UNLESS OTHERWISE PERMITTED
 BY ONE OF
 THE FOLLOWING:
 (1) CORRIDOR PROTECTION SHALL NOT BE REQUIRED WHERE ALL
 SPACES
 NORMALLY SUBJECT TO STUDENT OCCUPANCY HAVE NOT LESS
 THAN ONE
 DOOR OPENING DIRECTLY TO THE OUTSIDE OR TO AN EXTERIOR
 EXIT
 ACCESS BALCONY OR CORRIDOR IN ACCORDANCE WITH 7.5.3.
 (2) THE FOLLOWING SHALL APPLY TO BUILDINGS PROTECTED
 THROUGHOUT
 BY AN APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM
 IN
 ACCORDANCE WITH SECTION 9.7:
 (A) CORRIDOR WALLS SHALL NOT BE REQUIRED TO BE RATED,
 PROVIDED THAT SUCH WALLS FORM SMOKE PARTITIONS IN
 ACCORDANCE WITH SECTION 8.4.
 (B) THE PROVISIONS OF 8.4.3.5 SHALL NOT APPLY TO
 NORMALLY
 OCCUPIED CLASSROOMS.
 (3) WHERE THE CORRIDOR CEILING IS AN ASSEMBLY HAVING A
 1-HOUR
 FIRE RESISTANCE RATING WHERE TESTED AS A WALL, THE
 CORRIDOR
 WALLS SHALL BE PERMITTED TO TERMINATE AT THE CORRIDOR
 CEILING.
 (4) LAVATORIES SHALL NOT BE REQUIRED TO BE SEPARATED
 FROM
 CORRIDORS, PROVIDED THAT THEY ARE SEPARATED FROM ALL
 OTHER
 SPACES BY WALLS HAVING NOT LESS THAN A 1-HOUR FIRE
 RESISTANCE
 RATING IN ACCORDANCE WITH SECTION 8.3.
 (5) LAVATORIES SHALL NOT BE REQUIRED TO BE SEPARATED
 FROM
 CORRIDORS, PROVIDED THAT BOTH OF THE FOLLOWING CRITERIA
 ARE MET:
 (A) THE BUILDING IS PROTECTED THROUGHOUT BY AN
 APPROVED,
 SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE
 WITH SECTION 9.7.
 (B) THE WALLS SEPARATING THE LAVATORY FROM OTHER ROOMS
 FORM SMOKE PARTITIONS IN ACCORDANCE WITH SECTION 8.4.
  
  
 5) A FIRE ALARM SHEET IS INDICATED; HOWEVER, PLEASE
 PROVIDE DETAILS THAT IT MEETS ALL THE REQUIRMENTS OF
 EDUCATIONAL OCCUPANCIES , INCLUDING BUT NOT LIMITED TO,
  
 14.3.4.3 NOTIFICATION.
 14.3.4.3.1 OCCUPANT NOTIFICATION.
 14.3.4.3.1.1 OCCUPANT NOTIFICATION SHALL BE
 ACCOMPLISHED
 AUTOMATICALLY IN ACCORDANCE WITH 9.6.3.
 14.3.4.3.1.2 THE OCCUPANT NOTIFICATION REQUIRED BY
 14.3.4.3.1.1
 SHALL UTILIZE AN EMERGENCY VOICE/ALARM COMMUNICATION
 SYSTEM IN
 ACCORDANCE WITH 9.6.3 WHERE THE BUILDING HAS AN
 OCCUPANT LOAD OF
 MORE THAN 100.
 14.3.4.3.1.3 POSITIVE ALARM SEQUENCE SHALL BE PERMITTED
 IN
 ACCORDANCE WITH 9.6.3.4.
 14.3.4.3.1.4 IN ACCORDANCE WITH 9.6.3.10.2 THE
 EMERGENCY
 VOICE/ALARM COMMUNICATION SYSTEM SHALL BE PERMITTED TO
 BE USED
 FOR OTHER EMERGENCY SIGNALING OR FOR CLASS CHANGES.
 14.3.4.3.1.5 TO PREVENT STUDENTS FROM BEING RETURNED TO
 A BUILDING
 THAT IS BURNING, THE RECALL SIGNAL SHALL BE SEPARATE
 AND DISTINCT FROM
 ANY OTHER SIGNALS, AND SUCH SIGNAL SHALL BE PERMITTED
 TO BE GIVEN
 BY USE OF DISTINCTIVELY COLORED FLAGS OR BANNERS.
 14.3.4.3.1.6 IF THE RECALL SIGNAL REQUIRED BY
 14.3.4.3.1.5 IS ELECTRIC,
 THE PUSH BUTTONS OR OTHER CONTROLS SHALL BE KEPT UNDER
 LOCK, THE
 KEY FOR WHICH SHALL BE IN THE POSSESSION OF THE
 PRINCIPAL OR ANOTHER DESIGNATED PERSON IN ORDER TO
 PREVENT A RECALL AT A TIME
 WHEN THERE IS AN ACTUAL FIRE.
 14.3.4.3.1.7 REGARDLESS OF THE METHOD OF RECALL SIGNAL,
 THE MEANS
 OF GIVING THE RECALL SIGNAL SHALL BE KEPT UNDER LOCK.
  
  
  
 6) THERE IS NO INDICATIONS THAT WINDOWS COMPLY WITH THE
 FOLLOWING REQUIREMENT.
  
 14.2.11 SPECIAL MEANS OF EGRESS FEATURES.
 14.2.11.1* WINDOWS FOR RESCUE.
 14.2.11.1.1 EVERY ROOM OR SPACE GREATER THAN 250 FT2
 (23.2 M2)
 AND USED FOR CLASSROOM OR OTHER EDUCATIONAL PURPOSES OR
 NORMALLY
 SUBJECT TO STUDENT OCCUPANCY SHALL HAVE NOT LESS THAN
 ONE OUTSIDE
 WINDOW FOR EMERGENCY RESCUE THAT COMPLIES WITH ALL OF
 THE
 FOLLOWING, UNLESS OTHERWISE PERMITTED BY 14.2.11.1.2:
 (1) SUCH WINDOWS SHALL BE OPENABLE FROM THE INSIDE
 WITHOUT THE
 USE OF TOOLS AND SHALL PROVIDE A CLEAR OPENING OF NOT
 LESS THAN
 20 IN. (510 MM) IN WIDTH, 24 IN. (610 MM) IN HEIGHT,
 AND 5.7
 FT2 (0.5 M2) IN AREA.
 (2) THE BOTTOM OF THE OPENING SHALL BE NOT MORE THAN 44
 IN.
 (1120 MM) ABOVE THE FLOOR, AND ANY LATCHING DEVICE
 SHALL BE
 CAPABLE OF BEING OPERATED FROM NOT MORE THAN 54 IN.
 (1370
 MM) ABOVE THE FINISHED FLOOR.
 (3) THE CLEAR OPENING SHALL ALLOW A RECTANGULAR SOLID,
 WITH A
 WIDTH AND HEIGHT THAT PROVIDES NOT LESS THAN THE
 REQUIRED 5.7
 FT2 (0.5 M2) OPENING AND A DEPTH OF NOT LESS THAN 20
 IN. (510
 MM), TO PASS FULLY THROUGH THE OPENING.
 (4) SUCH WINDOWS SHALL BE ACCESSIBLE BY THE FIRE
 DEPARTMENT AND
 SHALL OPEN INTO AN AREA HAVING ACCESS TO A PUBLIC WAY.
 14.2.11.1.2 THE REQUIREMENTS OF 14.2.11.1.1 SHALL NOT
 APPLY TO ANY
 OF THE FOLLOWING:
 (1) BUILDINGS PROTECTED THROUGHOUT BY AN APPROVED,
 SUPERVISED
 AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION
 9.7
 (2) WHERE THE ROOM OR SPACE HAS A DOOR LEADING DIRECTLY
 TO AN
 EXIT OR DIRECTLY TO THE OUTSIDE OF THE BUILDING
 (3) RESERVED
 (4) ROOMS LOCATED FOUR OR MORE STORIES ABOVE THE
 FINISHED
 GROUND LEVEL
  
 PLEASE PROVIDE DETAILS OR JUSTIFY.
  
  
  
  
 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-09-25 Cont ID  
Sent By mcruz Date 2018-09-25 Time 13:19 Rev Time 0.00
Received By mcruz Date 2018-08-22 Time 10:04 Sent To PC
Notes
2018-08-24 10:04:41C16

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-09-15 Cont ID  
Sent By shill Date 2018-09-15 Time 18:14 Rev Time 0.00
Received By shill Date 2018-09-15 Time 18:14 Sent To  
Notes
2018-09-15 18:15:28PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE
 PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURNED STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-09-13 Cont ID  
Sent By ccole Date 2018-09-13 Time 09:26 Rev Time 0.00
Received By ccole Date 2018-09-13 Time 09:25 Sent To  
Notes
2018-09-13 09:53:231ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18081069
 9/13/18
  
  
 CODES IN EFFECT:
  
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE SUBMITTED PLANS FROM 2010 ARE NOT ACCEPTABLE FOR
 REVIEW. NEW PLANS DESIGNED IN ACCORDANCE WITH THE 2017
 6TH EDITION FLORIDA BUILDING CODES ARE REQUIRED PER FS
 553.79(6) AND SECTION 107.2.1 WPB. THE SUBMITTED 2010
 PLANS MAY BE MARKED "FOR REFERENCE ONLY" AND
 RESUBMITTED WITH THE NEW PLANS.
  
 2) MINIMUM VENTILATION CALCULATIONS ARE REQUIRED FOR
 THE PROPOSED CHANGE OF OCCUPANCY. PLEASE SEE SECTION
 1009.1 FBC EX, AND TABLE 403.3.1.1 FBC M. AND PROVIDE A
 SCHEDULE SHOWING THE REQUIRED AND PROVIDED CFMS OF
 OUTDOOR AIR FOR EACH ROOM OR SPACE.
  
 3) PLEASE SEE SECTION C505.1 FBC EC AND NOTE THAT
 ENERGY CALCULATIONS AND A COMPLIANCE REPORT MAY BE
 REQUIRED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
 HTTPS://WWW.SURVEYMONKEY.COM/R/WESTPALMBEACHCONSTRUCTIO
 NSERVICES
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-09-13 Cont ID  
Sent By gjohnson Date 2018-09-13 Time 13:05 Rev Time 0.00
Received By gjohnson Date 2018-09-13 Time 10:50 Sent To  
Notes
2018-09-13 13:21:101ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
  
 1) THE SUBMITTED PLANS FROM 2010 ARE NOT ACCEPTABLE FOR
 REVIEW. NEW PLANS DESIGNED IN ACCORDANCE WITH THE 2017
 6TH EDITION FLORIDA BUILDING CODES ARE REQUIRED PER FS
 553.79(6) AND SECTION 107.2.1 WPB. THE SUBMITTED 2010
 PLANS MAY BE MARKED "FOR REFERENCE ONLY" AND
 RESUBMITTED WITH THE NEW PLANS.
  
 2. PER THE WPB AMENDMENTS TO THE FBC, PLAN (EACH SHEET
 OF BOTH COPIES) IS REQUIRED TO BEAR THE NAME AND BE
 SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE
 DESIGN. PROVIDE CORRECTION. WPB FBC 107.1, 107.2; FS
 471, 481
  
 3. FACULTY AND STAFF TOILETS SHALL BE SEPARATE FROM
 STUDENT TOILETS. PER FBC 468.3.5.3
  
 4. PROVIDE OCCUPANT LOAD FOR EDUCATION PER FBC TABLE
 1004.1.2
  
 5. THE WATER FOUNTAIN SHALL COMPLY WITH FBC 211.2
 MINIMUM NUMBER.NO FEWER THAN TWO DRINKING FOUNTAINS
 SHALL BE PROVIDED. ONE DRINKING FOUNTAIN SHALL COMPLY
 WITH 602.1 THROUGH 602.6 AND ONE DRINKING FOUNTAIN
 SHALL COMPLY WITH 602.7.
 MUST BE SHOWN ON PLAN. PER WPB AMEND TO FBC 107.2.1
  
 6. PROVIDE A SERVICE SINK OR SHOW EXISTING ON THE PLAN.
 PER FBC PL TABLE 403.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2018-09-25 Cont ID  
Sent By mcruz Date 2018-09-25 Time 13:19 Rev Time 0.00
Received By mcruz Date 2018-09-25 Time 12:31 Sent To PC
Notes
***NONE***