Plan Review Details - Permit 18081055
Plan Review Stops For Permit 18081055
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-12-17 Cont ID  
Sent By jpearson Date 2018-12-06 Time 15:45 Rev Time 0.00
Received By jpearson Date 2018-12-06 Time 15:10 Sent To  
Notes
2018-12-06 15:10:14CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
 (S)
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. REVISION APPLICATION STATES THERE IS NO INCREASE IN
 VALUE FOR THIS REVISION. HOWEVER, IT APPEARS THERE IS
 ADDITIONAL WORK. PROVIDE COPY OF CONTRACT WITH SCOPE
 AND VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR
 FOR CHANGES TO ORIGINAL PLAN. FBC 109.3 (RESPONSE
 PROVIDED DOES NOT INDICATE IF THERE IS ANY VALUE
 INCREASE IN THE REVISIONS SHOWN. VALUE INCREASE SHOULD
 INCLUDE ALL LABOR AND MATERIALS. PROVIDE AS PREVIOUSLY
 REQUESTED.)(3RD REVIEW, STILL NO DOLLAR AMOUNT PROVIDED
 FOR THE INCREASED VALUE OF THE WORK. PROVIDE AS
 PREVIOUSLY REQUESTED.)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-11-06 Cont ID  
Sent By jpearson Date 2018-11-06 Time 17:47 Rev Time 0.00
Received By jpearson Date 2018-11-06 Time 17:47 Sent To I
Notes
2018-11-06 17:47:04CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. REVISION APPLICATION STATES THERE IS NO INCREASE IN
 VALUE FOR THIS REVISION. HOWEVER, IT APPEARS THERE IS
 ADDITIONAL WORK. PROVIDE COPY OF CONTRACT WITH SCOPE
 AND VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR
 FOR CHANGES TO ORIGINAL PLAN. FBC 109.3 (RESPONSE
 PROVIDED DOES NOT INDICATE IF THERE IS ANY VALUE
 INCREASE IN THE REVISIONS SHOWN. VALUE INCREASE SHOULD
 INCLUDE ALL LABOR AND MATERIALS. PROVIDE AS PREVIOUSLY
 REQUESTED.)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-09-22 Cont ID  
Sent By jpearson Date 2018-09-22 Time 16:31 Rev Time 0.00
Received By jpearson Date 2018-09-22 Time 16:31 Sent To  
Notes
2018-09-22 16:31:07CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. REVISION APPLICATION STATES THERE IS NO INCREASE IN
 VALUE FOR THIS REVISION. HOWEVER, IT APPEARS THERE IS
 ADDITIONAL WORK. PROVIDE COPY OF CONTRACT WITH SCOPE
 AND VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR
 FOR CHANGES TO ORIGINAL PLAN. FBC 109.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2018-12-13 Time   Rev Time 0.00
Received By lmarchan Date 2018-11-14 Time 11:10 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2018-11-06 Time   Rev Time 0.00
Received By lmarchan Date 2018-10-23 Time 16:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2018-10-05 Time   Rev Time 0.00
Received By cpuell Date 2018-09-04 Time 16:20 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-12-13 Cont ID  
Sent By ccole Date 2018-12-13 Time 15:25 Rev Time 0.00
Received By ccole Date 2018-12-13 Time 12:21 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2018-10-05 Cont ID  
Sent By ccole Date 2018-10-05 Time 11:25 Rev Time 0.00
Received By ccole Date 2018-09-25 Time 17:07 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2018-12-06 Cont ID  
Sent By jpearson Date 2018-12-06 Time 15:10 Rev Time 0.00
Received By jpearson Date 2018-12-06 Time 15:10 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2018-11-06 Cont ID  
Sent By jpearson Date 2018-11-06 Time 17:43 Rev Time 0.00
Received By jpearson Date 2018-11-06 Time 17:43 Sent To  
Notes
2018-11-06 17:43:23WITH THIS SUBMISSION, ALL SHEETS WERE REPLACED. NOW,
 ALL OF THE SHEETS SHOW A SIGNATURE THAT CONTAINS
 "INCORRECT, UNRECOGNIZED, CORRUPTED, OR SUSPICIOUS
 DATA". ELECTRONIC SIGNATURES AND SEALS REQUIRED ON ALL
 PLANS. PROVIDE CORRECTION. WPB FBC 107.1, 107.2; FS
 471, 481
 IT IS RECOMMENDED THAT YOU CONTACT SAMANTHA HILL OR ONE
 OF OUR PERMIT LIBRARIANS (CAROLINE PUELL OR LAURA
 MARCHANT) FOR ASSISTANCE IN UPLOADING PLAN SHEETS.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2018-09-22 Cont ID  
Sent By jpearson Date 2018-09-22 Time 15:42 Rev Time 0.00
Received By jpearson Date 2018-09-22 Time 15:42 Sent To  
Notes
2018-10-05 11:26:27ELECTRONIC SIGNATURES AND SEALS REQUIRED ON MECH PLANS.
2018-09-22 15:42:16DIGITAL SIGNATURE CORRUPTED. PROVIDE CORRECTION. WPB
 FBC 107.1, 107.2; FS 471, 481