Plan Review Details - Permit 18081039
Plan Review Stops For Permit 18081039
Review Stop AIPP ART IN PUBLIC PLACES
Rev No 1 Status P Date 2019-12-12 Cont ID  
Sent By shill Date 2019-12-12 Time 17:44 Rev Time 0.00
Received By shill Date 2019-12-12 Time 17:44 Sent To  
Notes
2019-12-12 17:45:18AIPP CHECK RECEIVED PER EMAIL FROM SYBILLE WELTER,
 12/10/19
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2019-03-14 Cont ID  
Sent By dbattles Date 2019-03-14 Time 11:26 Rev Time 0.00
Received By dbattles Date 2019-03-14 Time 11:26 Sent To  
Notes
2019-03-14 11:26:30PROVISO:
 1. EXTERIOR WINDOWS, DOORS. MULLS.
 2. PANEL WALLS: STOREFRONT, CURTAIN WALL.
 3. LOUVERS
 4. EXTERIOR FINISHES: ALUMINUM COMPOSITE METAL PANEL
 SYSTEM.
 5. STUCCO AND EFIS AS APPLICABLE.
 6. ROOFING PRODUCTS INCLUDING INSULATION AND
 ENGINEERING AS REQUIRED BY PRODUCT APPROVALS.
 7. X-RAY AND PHYSICIST SHIELDING REPORT
 8. EXTERIOR SHADING SYSTEM
 9. FIRE STOPPING
 10. METAL GUARDRAIL AND HANDRAILS.
 11. ART IN PUBLIC PLACES (AIPP)
 12. IRRIGATION - SEPARATE PERMIT
 13. EXTERIOR SIGNAGE - SEPARATE PERMIT
 14. FIRE SUPRESSION SYSTEM - SEPARATE PERMIT
 15. FIRE ALARM SYSYTEM - SEPARATE PERMIT

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2019-02-05 Cont ID  
Sent By dbattles Date 2019-02-05 Time 08:36 Rev Time 0.00
Received By dbattles Date 2019-02-01 Time 13:03 Sent To  
Notes
2019-02-05 09:03:19PROVISO:
 1. EXTERIOR WINDOWS, DOORS. MULLS.
 2. PANEL WALLS: STOREFRONT, CURTAIN WALL.
 3. LOUVERS
 4. EXTERIOR FINISHES: ALUMINUM COMPOSITE METAL PANEL
 SYSTEM.
 5. STUCCO AND EFIS AS APPLICABLE.
 6. ROOFING PRODUCTS INCLUDING INSULATION AND
 ENGINEERING AS REQUIRED BY PRODUCT APPROVALS.
 7. X-RAY AND PHYSICIST SHIELDING REPORT
 8. EXTERIOR SHADING SYSTEM
 9. FIRE STOPPING
 10. METAL GUARDRAIL AND HANDRAILS.
 11. ART IN PUBLIC PLACES (AIPP)
 12. IRRIGATION - SEPARATE PERMIT
 13. EXTERIOR SIGNAGE - SEPARATE PERMIT
 14. FIRE SUPRESSION SYSTEM - SEPARATE PERMIT
 15. FIRE ALARM SYSYTEM - SEPARATE PERMIT

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-12-18 Cont ID  
Sent By dbattles Date 2018-12-18 Time 08:25 Rev Time 0.00
Received By dbattles Date 2018-12-14 Time 09:10 Sent To  
Notes
2018-12-18 08:26:39****CORRECTIONS****
 W.P.B. PERMIT: 18081039
 2ND REVIEW: DECEMBER 14, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 2017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18081039
 W. P. B. FOUN.: 18080583
 ADD: 300 PALM BEACH LAKES BLVD.
 CONT: DPR CONSTRUCTION A GENERAL PARTNERSHIP
 TEL: 561-718-2367
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. NOV. 15/2018
 ACTION: DENIED
  
 1) OK
  
 2A) OK
  
 2B) PLEASE NOTE THAT ENERGY COMPLIANCE FORMS WERE NOT
 PART OF THIS SUBMISSION. SHOW COMPLIANCE WITH THE 2017
 FBC-ENERGY CODE, SUBMIT AN ENERGY COMPLIANCE REPORT IN
 COMPLIANCE WITH EITHER C101.2, C101.5.1 AND CC401.2.
 PARTIALLY ADDRESSED:
 MECHANICAL AND ELECTRICAL COM CHECKS WERE PROVIDED.
 ADDITIONALLY, THERE SHOULD BE COMCHECK FOR THERMAL
 ENVELOPE.
 PLEASE PROVIDE, OR INDICATE IN RESPONSE WHERE THERMAL
 COMPLIANCE IS PROVIDED.
  
  
 2C) TUES. NOV. 20/18 NEW COMMENT. PLEASE NOTE MISSING
 FROM THE FILE FOLDER, THE PLANS INDICATE THE BUILDING
 IS TO BE FIRE SPRINKLERED BUT THERE IS NO HYDRAULIC
 CALCULATIONS FOR THE FLOW RATE FROM THE NEAREST FIRE
 HYDRANT.
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 FIRE HYDRANT/WATER SUPPLY/ HYDRAULIC CALCULATIONS
 THE HYDRAULIC CALCULATIONS ARE THE BASES FOR THE SIZING
 OF THE SYSTEM.
 NOT ADDRESSED:
 I COULD NOT FIND THE CALCULATIONS IN THE SUPPORTING
 DOCUMENTS.
 PLEASE UPLOAD INTO SUPPORTING DOCUMENTS OR INDICATE
 WHERE INFORMATION WAS ADDED IN PLANS.
  
 3) OK
  
 4) OK
  
 5) OK
  
 6) OK
  
 7) OK
  
 8) OK
  
 9) SHEET 002-G-001 INDEX:
 9A) OK
  
 9B) OK
  
 9C) SEE COMMENT 12B
  
 10) SHEET 057-A-001 LIFE SAFETY PLAN LEVEL 01 &
 063-A-101FIRST FLOOR PLAN:
  
 10A) OK
 ADDITIONAL COMMENT:
 IT WAS ESTABLISHED THAT A 2-HOUR SEPARATION BETWEEN S-2
 AND BUSINESS.
 HOW IS SECTION OF WALL BETWEEN GARAGE AND BANK OF
 BATHROOMS RATED AT 1 HOUR ON SHEET A-001?
  
 10B) OK
  
 10C) PLEASE ALSO REVIEW SHEET 061-A-005 SPLIT LEVEL
 PARKING FOR ALL FLOORS SHOWS OPEN EXIT STAIRS FOR THE
 UPPER AND LOWER FLOOR LEVELS FOR ALL FLOORS. PLEASE
 NOTE IT WILL DEPEND ON IF THE PARKING GARAGE IS OPEN OR
 ENCLOSED IF THE STAIRWELLS WILL NEED TO COMPLY WITH
 CHAPTER 10. SEE 406.5.7.
 ADDITIONAL COMMENT:
 I SEE ADEQUATE INFORMATION THAT THE GARAGE IS OPEN
 EXEPT FOR THE AREA ON 1ST FLOOR WHERE THERE ARE A BANK
 OF ROOMS 133, 134, 135 AND OTHER ROOMS THAT ENCLOSE
 THIS AREA ON THREE SIDES. THIS AREA DOES NOT MEET THE
 CRITERIA FOR OPENINGS DISTRUBUTED OVER TWO SIDES OR
 ALONG 40% OF PERIMETER.
 HOW WILL THIS AREA BE VENTILATED?
  
 10D) THE FIRST FLOOR PLAN INDICATES A ONE HOUR
 ENCLOSURE FOR MEDICAL GAS USE. PLEASE PROVIDE THE TYPES
 OF GASSES TO BE ENCLOSED IN THIS ROOM, QUANTITIES OF
 GAS WITHIN EACH TANK, QUANTITIES OF EACH TYPE OF GAS IN
 TANKS (IN CUBIC FEET) AND THE ACCOMPANYING MSDS SHEETS.
 2017 FBC-B TABLE 307.1(1).
 PLEASE ALSO SHOW HOW THE TANKS ARE GOING TO BE STORED,
 AND HOW THEY WILL BE SECURED WHILE IN SERVICE.
 107.2.2.1.
 MONDAY NOV. 19/18 COMMENT. 451.3.15 MEDICAL GAS. IF
 THERE IS A PIPED MEDICAL GAS INSTALLATION IN THE ASC,
 IT SHALL COMPLY WITH THE REQUIREMENTS OF NFPA 99 HEALTH
 CARE FACILITIES CODE.
 ADDITIONAL COMMENT:
 [FBC TABLE 307.1(1)]BASED ON THE AMOUNTS OF FLAMABLE
 MATERIAL BEING STORED IT WOULD BE CONSIDERED H-2.
 [FBC TABLE 508.4]H-2 REQUIRES 3-HOUR SEPARATION FROM
 S-2.
 PROVIDE DETAIL FOR 3-HOUR ASSEMBLY AT H-2 STORAGE.
  
 [F] 414.3 VENTILATION. ROOMS, AREAS OR SPACES IN WHICH
 EXPLOSIVE, CORROSIVE, COMBUSTIBLE, FLAMMABLE OR HIGHLY
 TOXIC
 DUSTS, MISTS, FUMES, VAPORS OR GASES ARE OR MAY BE
 EMITTED
 DUE TO THE PROCESSING, USE, HANDLING OR STORAGE OF
 MATERIALS
 SHALL BE MECHANICALLY VENTILATED WHERE REQUIRED BY THIS
 CODE,
 THE FLORIDA FIRE PREVENTION CODE OR THE FLORIDA
 BUILDING
 CODE, MECHANICAL.
  
 10E) OK
  
 10F) OK
  
 11) ELEVATORS:
 11A) OK
  
 11B) OK
  
 11C)(1) OK
  
 11C)(2) OK
  
 11D) OK
  
 11E) OK (SEE COMMENT 10A ADDITIONAL COMMENT)
  
 12) THE 2ND FLOOR PLANS, 058-A-002 LIFE SAFETY PLAN
 LEVEL 02 & 064-A-102:
  
 12A) OK
  
 12B) PARTIALLY ADDRESSED-SEE ADDITIONAL BELOW
 [FBC A502.5]VERTICAL CLEARANCE. PARKING SPACES FOR VANS
 AND ACCESS AISLES AND VEHICULAR ROUTES SERVING THEM
 SHALL PROVIDE A VERTICAL CLEARANCE OF 98 INCHES.
 PLEASE PROVIDE DIMENSION FOR VERTICAL CLEARANCE AT
 ENTRY TO ALLOW FOR VAN ACCESSIBLE PARKING (98 INCH
 CLEARANCE) VERTICAL CLEARANCE BE PROVIDED IF IT IS
 LOCATED IN THE PARKING GARAGE?
  
  
 12C)(1) OK
 12C)(2) ) OK
  
  
 12D) OK
  
 12E) OK
  
 12F) OK
  
 12G) OK
  
 12H) OK
  
 12I) OK
  
 13) SHEET 065-A-103 & 059-A-003:
  
 13A) OK
  
 13B) OK
  
 13H) OK
  
 13I) SEE 13B
  
 TUES. NOV. 20/18.
  
 14) 060-A-004 LIFE SAFETY PLAN & 066-A-104 FOURTH FLOOR
 PLAN:
  
 14A) ROOM 434 PATIENT TOILET DOOR SWINGS OUT INTO THE
 CORRIDOR, PLEASE SHOW COMPLIANCE WITH 2017 FBC-B
 451.3.4.1. NO DOORS SHALL SWING INTO THE CORRIDOR
 EXCEPT THOSE TO SMALL CLOSETS OR SMALL MECHANICAL OR
 ELECTRICAL ROOMS THAT CANNOT BE USEFULLY OCCUPIED WITH
 THE DOORS IN THE CLOSED POSITION.
 ADDITIONAL COMMENT:
 THE RESPONSE DOESN?T ADDRESS 451.3.4.1 THAT STATES NO
 DOOR SHALL SWING INTO CORRIDOR.
 PLEASE PROVIDE CODE SECTION FOR EXEMPTION OR ADJUST
 DOOR SWING ACCORDINGLY.
  
 14B) OK
  
 14C) OK
  
 14D) OK
  
 14E) OK
  
 14F) OK
  
 15) 070-A-108 ROOF PLAN:
  
 15A-15B) OK
  
 16) 071-A-201, 072-A-202 & 073-A-203 EXTERIOR
 ELEVATIONS:
  
 16A) PROVISO: ALUMINUM COMPOSITE METAL PANEL SYSTEM
 WILL BE ADDED TO DEFERRED SUBMITTAL LIST.
  
 16B) OK
  
 16C) OK
  
 16C)(1) OK
  
 16C)(2) OK
  
 16D) PROVISO: EXTERIOR SUNSHADE SYSTEM WILL BE ADDED TO
 DEFERRED SUBMITTAL LIST.
  
 17) OK
  
 18) OK
  
 19) SHEET 011-S-002:
 19A) OK
  
 19B) OK
  
 20A) PROVISO: DEFERRED SUBMITTAL LIST FROM G-001 WILL
 BE ADDED TO PROVISOS.
  
 20B) OK
  
 20C) OK
  
 20E) OK
  
 20F) OK
  
 20G) OK
  
 21) OK
  
 NEW COMMENTS (2ND REVIEW):
  
 22) CIVIL AND LANDSCAPE PLANS THAT ARE MULTI FILE IN
 THE SUPPORTING DOCUMENTS SHOULD BE MOVED TO DRAWING
 FOLDER. EACH DRAWING SHOULD BE DIGITALLY SIGNED AND
 [FBC 107.2.1]PLACE A DIGITALLY CREATED IMAGE OF YOUR
 SEAL AND THE FOLLOWING SENTENCES WHERE AN ORIGINAL
 SIGNATURE WOULD APPEAR IF THE ITEM WERE BEING
 PHYSICALLY SIGNED DATED AND SEALED. THE SENTENCES CAN
 BE PART OF THE DIGITAL SIGNATURE CUSTOM APPEARANCE
 AVAILABLE IN THE SIGNING TOOL, OR THEY CAN BE PLACED ON
 THE DOCUMENT OUTSIDE OF THE DIGITAL SIGNATURE BLOCK.
 THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND SEALED BY
 [LICENSEE, RA, OR LS] ON THE DATE AND/OR TIME STAMP
 SHOWN USING A DIGITAL SIGNATURE.
  
 PROVISO:
 EXTERIOR DOORS AND MULLIONS
 WINDOWS AND MULLIONS
 PANEL WALLS, STOREFRONT, CURTAIN WALLS AND LOUVERS
 EXTERIOR FINISHES (STUCCO SYSTEM)
 ALUMINUM METAL COMPOSITE PANEL SYSTEM
 ROOFING PRODUCTS AND ASSEMBLIES
 FIRE SUPPRRESSION SYSTEM
 FIRE ALARM SYSTEM
 X-RAY AND PHYSICIST SHEILDING REPORT
 EXTERIOR SUNSHADE SYSTEM
 EXTERIOR SIGNAGE
 FIRE STOPPING
 HVAC SYSTEM
 PLUMBING SYSTEM
 METAL GUARD RAILS AND HANDRAILS
 ART IN PUBLIC PLACES
 IRRIGATION
 DUMPSTER ENCLOSURE
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-11-20 Cont ID  
Sent By jwitmer Date 2018-11-20 Time 13:07 Rev Time 0.00
Received By jwitmer Date 2018-11-14 Time 07:55 Sent To  
Notes
2018-11-15 11:13:012017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18081039
 W. P. B. FOUN.: 18080583
 ADD: 300 PALM BEACH LAKES BLVD.
 CONT: DPR CONSTRUCTION A GENERAL PARTNERSHIP
 TEL: 561-718-2367
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. NOV. 15/2018
 ACTION: DENIED
  
 1) PLEASE CORRECT THE DOCUMENTS WITHIN THE FOLDER.
 EITHER REMOVE THE ARCHITECTURAL SPECIFICATION BOOK OR
 VOID ALL PAGES SINCE THE CITY DOES NOT REVIEW THESE
 DOCUMENTS PAGES 00 00 00 TAB THROUGH 32 31 21. PLEASE
 NOTE FOR FUTURE INFORMATION PLEASE REVIEW CITY OF WEST
 PALM BEACH PROJECT DOX QUICK START AS TO LOAD MULTIPLE
 PAGE DOCUMENTS OR CONTACT CAROLINE PUELL (561-805-6659)
 PLAN REVIEW LIBRARIAN OR LAURA MARCHANT (561-805-6658)
 PLAN REVIEW LIBRARIAN FOR FUTURE ASSISTANCE.
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION. 107.2.1.3 QUALITY OF BUILDING PLANS
 THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE,
 SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO
 RECORDS MANAGEMENT. ELECTRONIC MEDIA MUST BE COMPATIBLE
 WITH THE ARCHIVE REQUIREMENTS OF FLORIDA STATUTES.
  
 2A) IN THE FOLDER FOR SUPPORTING DOCUMENTS, THERE WAS
 NO PERMIT APPLICATION UPLOADED TO VERIFY CONTRACTOR
 INFORMATION. W. P. B. AMENDMENT 105.3 APPLICATION FOR
 PERMIT. TO OBTAIN A PERMIT, THE APPLICANT SHALL FIRST
 FILE AN APPLICATION THEREFORE IN WRITING ON A FORM
 FURNISHED BY THE DEPARTMENT FOR THAT PURPOSE.
  
 2B) PLEASE NOTE THAT ENERGY COMPLIANCE FORMS WERE NOT
 PART OF THIS SUBMISSION. SHOW COMPLIANCE WITH THE 2017
 FBC-ENERGY CODE, SUBMIT AN ENERGY COMPLIANCE REPORT IN
 COMPLIANCE WITH EITHER C101.2, C101.5.1 AND CC401.2.
  
 2C) TUES. NOV. 20/18 NEW COMMENT. PLEASE NOTE MISSING
 FROM THE FILE FOLDER, THE PLANS INDICATE THE BUILDING
 IS TO BE FIRE SPRINKLERED BUT THERE IS NO HYDRAULIC
 CALCULATIONS FOR THE FLOW RATE FROM THE NEAREST FIRE
 HYDRANT.
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 FIRE HYDRANT/WATER SUPPLY/ HYDRAULIC CALCULATIONS
 THE HYDRAULIC CALCULATIONS ARE THE BASES FOR THE SIZING
 OF THE SYSTEM.
  
 3) THE DOCUMENT IN THE FILE FOLDER IDENTIFIED AS 3293
 REVISED GEO LETTER IS DATED MAY 14, 2018 (REVISED).
 PLEASE UPDATE TO THE MOST CURRENT TIME OF PERMIT
 APPLICATION JUNE 27/2018 WHEREAS THE LETTER INDICATES
 WE UNDERSTAND THAT CONTINUOUS LIGHTLY LOADED FOOTINGS
 ARE BEING CONSIDERED FOR THE PERIMETER OF THE PROPOSED
 BUILDING(MOB). VIBRO-REPLACEMENT (VR) IS NOT PLANNED
 FOR THESE FOOTINGS. 107.2.1.2 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 4) THE FOUNDATION PERMIT HAS A NOTE THAT PALM BEACH
 COUNTY IMPACT FEE OFFICE, MR. SWOOPE HAS DEFERRED
 IMPACT FEES TO THE ISSUANCE OF THE BUILDING PERMIT (TO
 BE PAID BEFORE ISSUANCE). BEFORE A PERMIT TO CONSTRUCT,
 MAY BE ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH
 COUNTY. ONE SET OF PLANS WILL HAVE TO BE TAKEN (BY THE
 CONTRACTOR OR REPRESENTATIVE) TO THE PALM BEACH COUNTY
 IMPACT FEE OFFICE LOCATED AT 2300 N. JOG RD. ROOMS
 2W01-2W14 WEST PALM BEACH, FL. THE ACTUAL PERMIT SET OF
 PLANS MUST BE STAMPED BY THAT OFFICE, AND A COPY OF THE
 PAID RECEIPT ATTACHED TO THE PERMIT APPLICATION. PLEASE
 CALL (561)233-5025 FOR MORE INFORMATION.
  
 5) ART IN PUBLIC PLACES. THE CITY OF WEST PALM BEACH
 ART IN PUBLIC PLACES ORDINANCE REQUIREMENT THAT APPLIES
 TO ANY REMODEL OR NEW CONSTRUCTION PROJECT FOR WHICH
 THE PERMIT APPLICATION WAS SUBMITTED AFTER 6/29/14, AND
 THE TOTAL PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR
 GREATER THAN $750,000 WILL NEED TO COMPLY WITH THIS
 ORDINANCE.
 PER CITY OF WEST PALM BEACH ORDINANCE NO. 4504-14, AND
 CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V,
 ART IN PUBLIC PLACES, SECTION 78-123(A) AND SECTION
 78-126(A), THE ART ASSESSMENT IS 1% OF THE TOTAL
 PROJECT CONSTRUCTION COST.
 PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE
 V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND
 NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO
 THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE
 PROJECTS.
 SEC. 78-129. - PUBLIC ART ASSESSMENT FOR PRIVATE
 DEVELOPMENT.
 (A) APPLICABILITY. THE PROVISIONS OF THIS ARTICLE AND
 THE PUBLIC ART ASSESSMENT SECTION SHALL APPLY TO ALL
 PRIVATE DEVELOPMENT PROJECTS, INCLUDING NEW
 CONSTRUCTION, OR THE RENOVATION OR IMPROVEMENT OF AN
 EXISTING BUILDING, WHERE TOTAL CONSTRUCTION COSTS ARE
 EQUAL TO OR GREATER THAN $750,000.00. ALL BUILDINGS
 WITHIN NEW PLANNED DEVELOPMENTS SHALL BE ASSESSED
 CUMULATIVELY TOWARDS THIS ART IN PUBLIC PLACES
 REQUIREMENT, EVEN IF THE BUILDINGS ARE PERMITTED
 SEPARATELY OR DEVELOPED IN PHASES. THE PROVISIONS OF
 THIS SECTION APPLY TO NEW DEVELOPMENT OR NEW
 CONSTRUCTION WITHIN EXISTING PLANNED DEVELOPMENTS.
 FOR CONTACT INFORMATION PLEASE CONTACT:
 MS. SYBILLE WELTER ART IN PUBLIC PLACES COORDINATOR
 822-1515 E-MAIL: [email protected]
  
 6) SHEET 004-G-100 ACCESSIBILITY DETAILS FOR TACTILE
 SIGNAGE ABOVE FLOOR BUT THERE IS NO MENTION OF
 COMPLIANCE WITH THE 2017 FLORIDA ACCESSIBILITY CODE:
  
 BRAILLE. 703.3. BRAILLE SHALL BE CONTRASTED (GRADE 2)
 AND SHALL COMPLY WITH 703.3 AND 703.4.
  
 BRAILLE. 703.3.2 POSITION. BRAILLE SHALL BE POSITIONED
 BELOW THE CORRESPONDING TEXT. IF THE TEXT IS
 MULTI-LINED, THE BRAILLE SHALL BE BELOW THE ENTIRE
 TEXT. BRAILLE SHALL BE SEPARATED 3/8 INCH MINIMUM FROM
 ANY OTHER TACTILE CHARACTER AND 3/8 INCH MINIMUM FROM
 RAISED BORDERS AND DECORATIVE ELEMENTS.
  
 7) SHEET 005-G-400 UL ASSEMBLIES. THIS SHEET DOES SHOW
 UL ASSEMBLIES FOR RATINGS FOR WALLS AND FLOOR, FLOOR/
 CEILING ASSEMBLIES. WHAT IS MISSING ARE FIRE RATED
 THROUGH PENETRATIONS FOR HORIZONTAL FLOOR/ FLOOR
 CEILING ASSEMBLIES.
 2017 FBC-B 714.4 HORIZONTAL ASSEMBLIES. PENETRATIONS OF
 A FIRE-RESISTANCE-RATED FLOOR, FLOOR/CEILING ASSEMBLY
 OR THE CEILING MEMBRANE OF A ROOF/CEILING ASSEMBLY NOT
 REQUIRED TO BE ENCLOSED IN A SHAFT BY SECTION 712.1
 SHALL BE PROTECTED IN ACCORDANCE WITH SECTIONS 714.4.1
 THROUGH 714.4.4.
  
 8) SHEET 008-AS-110 DETAILS. PLEASE REVIEW DETAIL
 NUMBER 04 THE HANDICAPPED PARKING DETAIL.
 THE 2017 FBC-ACCESSIBILITY CODE SECTION 502.2 VEHICLE
 SPACES. EACH PARKING SPACE MUST BE AT LEAST 12 FEET
 (3658 MM) WIDE, SHALL BE MARKED TO DEFINE THE WIDTH,
 AND SHALL HAVE AN ADJACENT ACCESS AISLE COMPLYING WITH
 502.3. SEE ADVISORY 502.2.2 MARKING.
 ADVISORY 502.3.3 MARKING. THE METHOD AND COLOR OF
 MARKING ARE NOT SPECIFIED BY THESE REQUIREMENTS BUT MAY
 BE ADDRESSED BY STATE OR LOCAL LAWS OR REGULATIONS.
 THE CITY OF W. P. B. MUNI CODE SECTION CD94:276
 HANDICAPPED STALL PAINTING DETAIL INDICATES THE
 HANDICAPPED STALL LINES TO BE 4 INCHES WIDE (DOUBLE
 STRIPED) PAINTED BLUE WITH A 1 FOOT CLEAR SPACE BETWEEN
 THE DOUBLE SPACED LINES WITH THE 12 FOOT WIDE PARKING
 SPACE AS SHOWN IN THE DETAIL. PLEASE CORRECT THE 6 INCH
 WIDE STRIPING DETAIL.
  
 9) SHEET 002-G-001 INDEX:
 9A) THE INDEX SHEET IS MISSING THE SHEET A-006 LIFE
 SAFETY ROOF PLAN WITHIN THE INDEX. 107.2.2.1.
 ADDITIONAL INFORMATION IS REQUIRED.
  
 9B) HEADING BUILDING CONSTRUCTION/ USE AND OCCUPANCY IS
 A LISTING FOR GROUP S-2 PARKING GARAGE.
 THERE IS NO MENTION OF IF THE DESIGN IS FOR AN OPEN OR
 ENCLOSED PARKING GARAGE. IF OPEN THE PER CENT AGES OF
 OPEN AREA PER WALL SECTION PER FLOOR. SHEET 061-A-005
 SPLIT LEVEL
 2017 FBC-B SECTION 406.5 OPEN PARKING VERSES 406.6
 CLOSED PARKING GARAGES.
  
 9C) PLEASE PROVIDE HOW MANY PARKING SPACES ARE ON EACH
 LEVEL AND HOW MANY ACCESSIBLE SPACES ARE SHOWN. SHOW
 COMPLIANCE WITH THE 2017 FBC-ACCESSIBILITY CODE TABLE
 208.2 PARKING SPACES.
  
 10) SHEET 057-A-001 LIFE SAFETY PLAN LEVEL 01 &
 063-A-101FIRST FLOOR PLAN:
  
 10A) THE BUILDING ENTRY DOORS FROM THE GARAGE TO THE
 BUSINESS OFFICE LOBBY ARE IN A 1 HOUR RATED WALL WITH
 NOTE, UNRATED OPENING IN ONE HOUR FIRE BARRIER
 OCCUPANCY SEPARATION WALL ALLOWED PER 2017 FBC-707.6.
 PLEASE NOTE THE EXCEPTIONS LISTED 1-5 ARE STATING THE
 ALLOWABLE OPENING OF 156 SQUARE FEET CAN BE EXCEEDED.
 PLEASE REFER TO TABLE 716.5 OF THE 2017 FBC-B FOR
 OPENING PROTECTIVES FOR WALL RATING AND OPENING
 PROTECTIVE RATING.
  
 10B) PLEASE ALSO REVIEW SHEET 061-A-005 SPLIT LEVEL
 PARKING FOR ALL FLOORS. A STATEMENT FOUND ON THIS SHEET
 INDICATES UNPROTECTED SPRINKLERED OPENINGS ALLOWED IN
 EXTERIOR FIRE RATED WALL PER 706.8. AGAIN THE EXCEPTION
 2 THIS IS TAKING AWAY THE SIZE LIMITATION OF 156 SQ.
 FT. ONLY. SEE SECTION 406.5.2 OF THE 2017 FBC-B FOR
 PERCENTAGE OF AREA OPENINGS TO CLASSIFY IF THE FLOORS
 (EACH FLOOR) IN THE PARKING GARAGE QUALIFY FOR OPEN OR
 ENCLOSED. AREAS ARE TO BE TAKEN BY PER FLOOR AND WALL
 FOR WALL OPENINGS.
  
 10C) PLEASE ALSO REVIEW SHEET 061-A-005 SPLIT LEVEL
 PARKING FOR ALL FLOORS SHOWS OPEN EXIT STAIRS FOR THE
 UPPER AND LOWER FLOOR LEVELS FOR ALL FLOORS. PLEASE
 NOTE IT WILL DEPEND ON IF THE PARKING GARAGE IS OPEN OR
 ENCLOSED IF THE STAIRWELLS WILL NEED TO COMPLY WITH
 CHAPTER 10. SEE 406.5.7.
  
 10D) THE FIRST FLOOR PLAN INDICATES A ONE HOUR
 ENCLOSURE FOR MEDICAL GAS USE. PLEASE PROVIDE THE TYPES
 OF GASSES TO BE ENCLOSED IN THIS ROOM, QUANTITIES OF
 GAS WITHIN EACH TANK, QUANTITIES OF EACH TYPE OF GAS IN
 TANKS (IN CUBIC FEET) AND THE ACCOMPANYING MSDS SHEETS.
 2017 FBC-B TABLE 307.1(1).
 PLEASE ALSO SHOW HOW THE TANKS ARE GOING TO BE STORED,
 AND HOW THEY WILL BE SECURED WHILE IN SERVICE.
 107.2.2.1.
 MONDAY NOV. 19/18 COMMENT. 451.3.15 MEDICAL GAS. IF
 THERE IS A PIPED MEDICAL GAS INSTALLATION IN THE ASC,
 IT SHALL COMPLY WITH THE REQUIREMENTS OF NFPA 99 HEALTH
 CARE FACILITIES CODE.
  
 10E) THE 1ST FLOOR PLAN SHOWS THE INSTALLATION OF A MRI
 ROOM AND NEXT TO THE MRI ROOM THERE IS A LARGE ROOM AND
 NO KNOWN USAGE, PLEASE PROVIDE ADDITIONAL INFORMATION.
 107.2.2.1.
  
 10F) ELEVATORS. NEITHER FLOOR PLAN NOR SHEETS 133-A-820
 NOR 134-A821 ELEVATOR SECTIONS FOR ELEVATORS 1,2 & 3
 SHOW COMPLIANCE WITH ELEVATOR CAR TO ACCOMMODATE
 AMBULANCE STRETCHER REQUIREMENTS FOUND UNDER SECTION
 3002.4 OF THE 2017 FBC-B.
  
 11) ELEVATORS:
 11A) THE FLOOR PLAN SHEET 057-A-001 LIFE SAFETY PLAN
 LEVEL 01 & 063-A-101FIRST FLOOR PLAN SHOW THE ELEVATOR
 MACHINE ROOM AND SHEET 172-M-201 SHOW A FCU-A 14 A FAN
 COIL UNIT BUT THE SCHEDULE ON SHEET 182-M-702 LIST THE
 FAN COIL UNITS AS FCU WITH NUMBER NOT ANY LETTERS AFTER
 THE FCU. IT WOULD APPEAR COMPLIANCE WITH FBC-B 3005.2
 IS TRYING TO BE ACHIEVED BUT CLARIFICATION NEEDS TO BE
 ADDRESSED. ADDITIONAL INFORMATION IS REQUIRED FOR
 CLARIFICATION.
  
 11B) IN THE 2017 FBC-B UNDER CHAPTER 30 FOR ELEVATORS
 THE VENTING REQUIREMENT IN SECTION 3005 IS FOR MACHINE
 ROOMS ONLY. THE HOISTWAY VENTING HAS BEEN REMOVED,
 POSSIBLY RELOCATED, BUT NOT FOUND. I WOULD BELIEVE IT
 WOULD ALSO BE PART OF THE MANUFACTURES SPECIFICATION
 WHICH AT THIS TIME NO INFORMATION ABOUT THE ELEVATORS,
 HOISTWAY AND OR VENTING WAS SUBMITTED FOR THIS REVIEW.
 IF HOISTWAY VENTING IS TO OCCUR THEN WE WOULD NEED TO
 LOOK AT SHAFTS AND PROTECTED OPENINGS. SEE FBC-B 713.
 713.7.1 & 713.10.
  
 11C)(1) PLEASE CLARIFY WHAT TYPE OF DRIVE IS GOING TO
 BE USED FOR ALL OF THE ELEVATORS. ONE OF THE QUESTIONS
 IS THERE GOING TO BE HYDRAULIC CYLINDERS TO BE USED TO
 DRIVE THE ELEVATORS? IF SO THEN COMPLY WITH SECTION
 3011 OF THE 2017 FBC-B.
  
 11C)(2) THE SHEET 133-A-820 DETAILS 6 & 7 BOTH SHOW
 MACHINERY AT THE TOP OF THE 4TH FLOOR IN THE ELEVATOR
 SHAFT, IT WOULD APPEAR THE ELEVATOR ITSELF WOULD NOT
 MAKE IT TO THE 4TH FLOOR AS DEPICTED, MAYBE THIS
 EQUIPMENT AND SAFETY BEAM SHOULD BE LOCATED IN THE ROOF
 TOP PENTHOUSE? THE STRUCTURAL SHEET 029-S-151 SHOWS
 DETAILS FOR THE CONCRETE SHEER WALLS THAT SURROUND THE
 ELEVATOR SHAFT BUT THERE IS NO DESIGNATION TO THE SIZE
 NOR PLACEMENT OF THE ELEVATOR SAFETY BEAM AND IF THERE
 IS ADDITIONAL
 RE-INFORCEMENT IS REQUIRED, OR IF THERE NEEDS TO BE A
 POCKET TO SIT THE BEAM INTO NOR HOW MUCH OF THE BEAM
 NEEDS TO BE EMBEDDED INTO THE CONCRETE AND IF SO IS A
 PROTECTIVE COATING REQUIRED TO ISOLATED THE STEEL BEAM
 FROM THE LIME IN THE CONCRETE. 107.2.2.1 ADDITIONAL
 INFORMATION IS REQUIRED.
  
 11D) MONDAY. 11/19/18 COMMENT. THIS COMMENT STANDS FOR
 ALL VERTICAL EXIT DOORS ON EACH FLOOR. THE DOOR
 SCHEDULE SHEET 120-A-611 SHOWS THE VERTICAL EXIT DOORS
 WITH A LOCK SET TYPE 731R WHICH IS NOT IN THE DOOR
 SCHEDULE REMARKS AND ABBREVIATIONS. UNDER THE LOCKSETS
 THE ABBREVIATION PAN IS SHORT FOR PANIC HARDWARE.
 PLEASE SEE SECTION 1010.1.10 PANIC AND FIRE EXIT
 HARDWARE. PLEASE NOTE THE SPEC BOOK SUBMITTED DOES NOT
 GET REVIEWED, EACH AND EVERY PAGE OF THE SPEC BOOK
 NEEDS TO SHOW VOID ON EACH SHEET!!!
  
 11E) MONDAY. 11/19/18 COMMENT. THIS COMMENT IS COMMON
 TO ALL FLOORS. THE ARCHITECTURAL SHEETS FOR ALL 4
 FLOORS HAS NO WALL TYPE DESIGNATED FOR THE BLOCK WALL
 BETWEEN THE GARAGE AND THE BUSINESS OCCUPANCY. A-101.
 A-102, A-103 & A-104. SHEET 119-A-600 DOES NOT SHOW A
 FIRE RATED BLOCK WALL TYPE FOR 1 OR 2 HOUR FIRE RATING.
 PLEASE SEE 2017 FBC-B 707.3.1, 707.3.2 & TABLE
 707.3.10.
  
 12) THE 2ND FLOOR PLANS, 058-A-002 LIFE SAFETY PLAN
 LEVEL 02 & 064-A-102:
  
 12A) PLEASE NOTE THERE APPEARS TO BE A DISCREPANCY IN
 THE PLANS. IN THE LIFE SAFETY PLAN ALONG THE SOUTH WALL
 WEST OF STAIRWELL 2 THERE APPEARS TO BE A ONE HOUR FIRE
 BARRIER ALONG THE EXTERIOR WALL THAT DOES NOT APPEAR ON
 SHEET 064-A-102, 107.2.2.1 ADDITIONAL INFORMATION IS
 REQUIRED, DISCREPANCY IN PLANS.
  
 12B) ON THE 2ND LEVEL OF SHEET A-102 IS A VAN
 ACCESSIBLE PARKING SPACE. FOR HEIGHT REQUIREMENTS THAT
 ARE ASSOCIATED WITH VAN ACCESSIBLE PARKING I HAD TO GO
 TO THE BUILDING SECTIONS ON SHEET 074-A-210. ON THE
 LEFT SIDE OF THE PAGE ON LEVEL 2.3 THERE ARE 2
 ELEVATION MARKERS FOR THE 2ND FLOOR TOP AND BOTTOM OF
 SLAB TO INDICATE THE SLAB IS 8 INCHES THICK. WITH THE
 HEIGHTS GIVEN I WAS ABLE TO CALIBRATE THE FLOOR
 HEIGHTS, 1ST FLOOR HEIGHT SLAB TO SLAB 9 FOOT 3 INCHES
 (NO DEDUCTION FOR BEAMS OR FIRE SPRINKLER PIPING), RAMP
 7 FOOT 0 INCHES, AND THE 2ND FLOOR EAST SIDE 7 FOOT 8
 INCHES, NO DEDUCTION FOR FIRE SPRINKLER PIPING. SHEET
 081-A-302 WALL SECTION 10 SHOWS A HEIGHT LIMITATION BAR
 AT ENTRY PLANS INDICATE SEE SPECS. WHEN CALCULATED THE
 BAR IS AT A HEIGHT OF 7 FOOT 10 INCHES IN HEIGHT WHICH
 DOES NOT MEET THE REQUIREMENTS FOR VAN ACCESSIBILITY.
 PLEASE NOTE THESE HEIGHTS GIVEN DO NOT MEET THE VAN
 ACCESSIBILITY REQUIREMENTS FOUND UNDER:
 2017 FBC-ACCESSIBILITY CODE 502.5 VERTICAL CLEARANCE.
 PARKING SPACES FOR VANS AND ACCESS AISLES AND VEHICULAR
 ROUTES SERVING THEM SHALL PROVIDE A VERTICAL CLEARANCE
 OF 98 INCHES (2490 MM) MINIMUM.
 EVERY NONRESIDENTIAL STRUCTURE BUILT ON OR AFTER
 JANUARY 1, 1991, WHICH IS DESIGNED TO USE COVERED OR
 UNDERGROUND PARKING AS THE PRIMARY AVAILABLE PARKING
 SPACE SHALL DESIGN THE COVERED OR UNDERGROUND PARKING
 FACILITY TO MAINTAIN A MINIMUM HEIGHT FOR THE PORTION
 OF THE STREET-ACCESSIBLE LEVEL OF THE PARKING FACILITY
 DIRECTLY OVER VAN-ACCESSIBLE PARKING SPACES AND FOR
 PROVIDING INGRESS AND EGRESS TO SUCH PARKING SPACES OF
 AT LEAST 8 FEET 2 INCHES (2489 MM). SIGNS SHALL BE
 POSTED TO WARN OPERATORS OF HANDICAP-EQUIPPED VANS THAT
 THEY CANNOT PASS BEYOND A CERTAIN POINT DUE TO HEIGHT
 LIMITATIONS. IF COMPLIANCE WITH THIS MINIMUM HEIGHT
 CLEARANCE REQUIREMENT WILL CAUSE THE STRUCTURE TO
 EXCEED LOCAL HEIGHT LIMITATIONS IMPOSED BY LOCAL
 ZONING, PLANNING, OR FIRE ORDINANCES, OR WILL RESULT IN
 THE IMPOSITION OF ANY ADDITIONAL REQUIREMENTS OF SUCH
 ORDINANCES, THE STRUCTURE MAY EXCEED THE HEIGHT
 LIMITATION SPECIFIED IN THOSE PARTICULAR CODES AS
 NECESSARY TO COMPLY WITH THE REQUIREMENTS OF THIS
 SECTION AND IS EXEMPT FROM SUCH ADDITIONAL
 REQUIREMENTS. STRUCTURES FOR WHICH THE PLANS WERE
 SEALED BY AN ARCHITECT PRIOR TO JANUARY 1, 1991, ARE
 EXEMPT FROM THIS SECTION.
  
 ADVISORY 502.5 VERTICAL CLEARANCE. SIGNS PROVIDED AT
 ENTRANCES TO PARKING FACILITIES INFORMING DRIVERS OF
 CLEARANCES AND THE LOCATION OF VAN ACCESSIBLE PARKING
 SPACES CAN PROVIDE USEFUL CUSTOMER ASSISTANCE.
 FLORIDA LAW, S.553.511, F.S., REQUIRES SIGNS BE POSTED
 THAT WILL WARN HANDICAPPED-EQUIPPED VAN OPERATORS OF
 HEIGHT LIMITATIONS SO THEY WILL NOT PASS BEYOND A POINT
 WHERE THE VAN CANNOT BE MANEUVERED.
 FLORIDA LAW ALSO PREEMPTS LOCAL GOVERNMENT HEIGHT
 RESTRICTION ORDINANCES THAT WOULD PROHIBIT COMPLIANCE
 WITH THE MINIMUM HEIGHT REQUIREMENTS OF THIS SECTION.
 ALSO, ANY LOCAL OR STATE LAW OR REGULATION THAT
 PROHIBITS A COVERED ENTITY FROM COMPLYING WITH
 REQUIREMENTS OF THE ADA MAY RENDER SUCH JURISDICTION IN
 VIOLATION OF THE ADA.
  
 12C)(1) PLEASE EXPLAIN HOW ELEVATOR 1 WILL OPERATE?
 WILL THIS ELEVATOR BE ON RECALL IF FIRE ALARM OR
 SPRINKLE IS ACTIVATED? WILL THIS ELEVATOR BE CONSIDERED
 AN OCCUPANT EVACUATION ELEVATOR THAT COMPLIES WITH ALL
 OF 3008 OF THE 2017 FBC-B.
  
 12C)(2) ) MONDAY. 11/19/18 COMMENT. PLEASE SHOW
 COMPLIANCE WITH: 2017 FBC-B 451.3.5.1.
 ALL NEW AMBULATORY SURGICAL CENTERS LOCATED IN
 MULTISTORY BUILDINGS WHERE PATIENT TREATMENT AREAS ARE
 LOCATED ON OTHER THAN THE EXIT FLOOR SHALL HAVE AT
 LEAST ONE 2,500 POUND (933 KG) CAPACITY ELEVATOR THAT
 SHALL BE IN COMPLIANCE WITH THE REQUIREMENTS OF SECTION
 451.3.13.5 OF THIS CODE AND THE REQUIREMENTS OF CHAPTER
 30 OF THE CODE.
  
  
 12D) THE 2 STORAGE CLOSETS 227 AND 228 BOTH SHOW A 2
 FOOT 8 INCH DOOR. CLOSETS WHICH ARE OVER 2 FEET DEEP
 WHICH ALLOWS FOR A WHEELCHAIR TO ENTER REQUIRES A 3
 FOOT DOORWAY.
 PLEASE REVIEW THE 2017 FBC-ACCESSIBILITY CODE SECTION:
 811.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR OR
 GROUND SPACE COMPLYING WITH 305 SHALL BE PROVIDED.
 305.3 SIZE. THE CLEAR FLOOR OR GROUND SPACE SHALL BE 30
 INCHES (760 MM) MINIMUM BY 48 INCHES (1220 MM) MINIMUM.
  
 305.5 POSITION. UNLESS OTHERWISE SPECIFIED, CLEAR FLOOR
 OR GROUND SPACE SHALL BE POSITIONED FOR EITHER FORWARD
 OR PARALLEL APPROACH TO AN ELEMENT.
  
 DOORWAYS. 404.2.3 CLEAR WIDTH. DOOR OPENINGS SHALL
 PROVIDE A CLEAR WIDTH OF 32 INCHES (815 MM) MINIMUM.
 CLEAR OPENINGS OF DOORWAYS WITH SWINGING DOORS SHALL BE
 MEASURED BETWEEN THE FACE OF THE DOOR AND THE STOP,
 WITH THE DOOR OPEN 90 DEGREES. OPENINGS MORE THAN 24
 INCHES (610 MM) DEEP SHALL PROVIDE A CLEAR OPENING OF
 36 INCHES (915 MM) MINIMUM.
  
 DOORWAYS. 404.2.4 MANEUVERING CLEARANCES. MINIMUM
 MANEUVERING CLEARANCES AT DOORS AND GATES SHALL COMPLY
 WITH 404.2.4. MANEUVERING CLEARANCES SHALL EXTEND THE
 FULL WIDTH OF THE DOORWAY AND THE REQUIRED LATCH SIDE
 OR HINGE SIDE CLEARANCE.
  
 12E) ROOMS 235,236 & 237 HAVE MEASUREMENTS FOR ONE
 DIRECTION ONLY SIZE CANNOT BE CONFIRMED. SHEET
 058-A-002 2ND FLOOR LIFE SAFETY SHEET SHOWS ONLY THE
 EQUIPMENT ROOM WITH A SQUARE FOOTAGE OF ROOM, BUT
 CANNOT BE CONFIRMED. COMPLIANCE WITH TABLE 509
 INCIDENTAL USES AREAS CANNOT BE CONFIRMED.
  
 IN AMBULATORY CARE FACILITIES WASTE AND LINEN
 COLLECTION ROOMS WITH CONTAINERS THAT HAVE AN AGGREGATE
 VOLUME OF 10 CUBIC FEET OR GREATER REQUIRES 1 HOUR.
  
 IN AMBULATORY CARE FACILITIES OR GROUP I-2 OCCUPANCIES,
 STORAGE ROOMS GREATER THAN 100 SQUARE FEET, 1 HOUR.
  
 12F) STORAGE ROOM 226 IS NOT DIMENSIONED. 107.2.2.1
 ADDITIONAL INFORMATION IS REQUIRED.
  
 12G) BOTH THE MENS AND LADIES RESTROOMS SHOW THE
 INSTALLATION OF LOCKERS DEPICTED ON THIS SHEET AND
 DETAIL SHEET 100-A-102 DETAIL 03. PLEASE SHOW
 COMPLIANCE WITH: 2017 FBC- ACCESSIBILITY CODE:
  
 308 REACH RANGES. 308.2 FORWARD REACH./ 308.2.1
 UNOBSTRUCTED/ 308.2.2 OBSTRUCTED HIGH REACH.
 308.3 SIDE REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2
 OBSTRUCTED HIGH REACH.
  
 309 OPERABLE PARTS.309.3 HEIGHT. OPERABLE PARTS SHALL
 BE PLACED WITHIN ONE OR MORE OF THE REACH RANGES
 SPECIFIED IN 308.
  
 12H) MOTION ANALYSIS SHOWS WHAT APPEARS TO BE A GLASS
 WALL AND DOOR 208. THERE IS NO CUT SECTION FOR THIS
 WALL AND DOOR SHOWING COMPLIANCE WITH:
 2017 FBC-B 2406.1 HUMAN IMPACT LOADS. INDIVIDUAL GLAZED
 AREAS, INCLUDING GLASS MIRRORS, IN HAZARDOUS LOCATIONS
 AS DEFINED IN SECTION 2406.4 SHALL COMPLY WITH SECTIONS
 2406.1.1 THROUGH 2406.1.4.
  
 12I) NOTICE ONLY!!!! WHEN REFERRING FROM THE
 ARCHITECTURAL PLANS (131-A-804) TO THE STRUCTURAL
 SHEETS, THE STAIR IDENTIFIED AS S01 ON SHEET 064-A-102
 SHOWS A DETAIL BUT THERE IS NO DESIGNATION TO WHERE
 THIS CAN BE FOUND. ON VARIOUS STRUCTURAL DETAILS S-304
 DETAILS 6, 7 & 8 ALL SHOW A 7 INCH DROP BEAM AT THE
 STAIRS AND MEASURES EXACTLY AT 80 INCHES, NO CLEARANCES
 FOR DEVIATION IN LAYOUT AND FORMWORK. 2017 FBC-B
 1011.3.
  
 13) SHEET 065-A-103 & 059-A-003:
  
 13A) MONDAY. 11/19/18 COMMENT. THIS COMMENT IS COMMON
 TO ALL FLOORS. THE ARCHITECTURAL SHEETS FOR ALL 4
 FLOORS HAS NO WALL TYPE DESIGNATED FOR THE BLOCK WALL
 BETWEEN THE GARAGE AND THE BUSINESS OCCUPANCY. A-101.
 A-102, A-103 & A-104. SHEET 119-A-600 DOES NOT SHOW A
 FIRE RATED BLOCK WALL TYPE FOR 1 OR 2 HOUR FIRE RATING.
 PLEASE SEE 2017 FBC-B 707.3.1, 707.3.2 & TABLE
 707.3.10.
  
 13B) SHEET 065-A-103 SHOW 2 NEW X-RAY ROOM ROOMS 340 &
 342. THE WALL TAGS INDICATE LEAD LINED WALLS BUT THERE
 IS NO OTHER INFORMATION. THE PLANS ARE SILENT AS TO THE
 LEVEL OF RADS IN ONE HOUR COULD BE ABSORBED:
  
 HIGH RADIATION AREA. AN AREA, ACCESSIBLE TO
 INDIVIDUALS, IN WHICH RADIATION LEVELS FROM RADIATION
 SOURCES EXTERNAL TO THE BODY COULD RESULT IN AN
 INDIVIDUAL RECEIVING A DOSE EQUIVALENT IN EXCESS OF 1
 MSV (0.1 REM) IN 1 HOUR AT 30 CM FROM ANY SOURCE OF
 RADIATION OR FROM ANY SURFACE THAT THE RADIATION
 PENETRATES. FOR PURPOSES OF THIS SECTION, ROOMS OR
 AREAS IN WHICH DIAGNOSTIC X-RAY SYSTEMS ARE USED FOR
 HEALING ARTS PURPOSES ARE NOT CONSIDERED HIGH RADIATION
 AREAS.
  
  
 VERY HIGH RADIATION AREA. AN AREA, ACCESSIBLE TO
 INDIVIDUALS, IN WHICH RADIATION LEVELS FROM RADIATION
 SOURCES EXTERNAL TO THE BODY COULD RESULT IN AN
 INDIVIDUAL RECEIVING AN ABSORBED DOSE IN EXCESS TO 500
 RAD (5 GRAY) IN 1 HOUR AT 1 M FROM A SOURCE OF
 RADIATION OR FROM ANY SURFACE THAT THE RADIATION
 PENETRATES. AT VERY HIGH DOSES RECEIVED AT HIGH DOSE
 RATES, UNITS OF ABSORBED DOSE, GRAY AND RAD, ARE
 APPROPRIATE, RATHER THAN UNITS OF DOSE EQUIVALENT,
 SIEVERT AND REM.
  
 13C)CONTROL OF RADIATION HAZARD. 465.1 SCOPE. CONTROL
 OF RADIATION HAZARDS SHALL COMPLY WITH THE FOLLOWING
 DESIGN AND CONSTRUCTION STANDARDS AS DESCRIBED HEREIN.
 OTHER ADMINISTRATIVE AND PROGRAMMATIC PROVISIONS MAY
 APPLY. SEE DEPARTMENT OF HEALTH (DOH) RULE 64E-5,
 FLORIDA ADMINISTRATIVE CODE, AND CHAPTER 404, FLORIDA
 STATUTES.
  
 13D)FBC-B 465.5.1 SHIELDING. EACH X-RAY FACILITY SHALL
 HAVE PRIMARY AND SECONDARY PROTECTIVE BARRIERS AS
 NEEDED TO ASSURE THAT AN INDIVIDUAL WILL NOT RECEIVE A
 RADIATION DOSE IN EXCESS OF THE LIMITS SPECIFIED IN
 PART III OF CHAPTER 64E-5, FLORIDA ADMINISTRATIVE CODE.
 465.5.1.1. STRUCTURAL SHIELDING IN WALLS AND OTHER
 VERTICAL BARRIERS REQUIRED FOR PERSONNEL PROTECTION
 SHALL EXTEND WITHOUT BREACH FROM THE FLOOR TO A HEIGHT
 OF AT LEAST 7 FEET (2.1 M).
  
 13E) FBC-B 465.5.1.2 DOORS, DOOR FRAMES, WINDOWS AND
 WINDOW FRAMES SHALL HAVE THE SAME LEAD EQUIVALENT
 SHIELDING AS THAT REQUIRED IN THE WALL OR OTHER BARRIER
 IN WHICH THEY ARE INSTALLED.
  
 13F) FBC-B 465.5.1.3. PRIOR TO CONSTRUCTION, THE FLOOR
 PLANS AND EQUIPMENT ARRANGEMENT OF ALL NEW
 INSTALLATIONS, OR MODIFICATIONS OF EXISTING
 INSTALLATIONS, UTILIZING X-RAY ENERGIES OF 200 KEV AND
 ABOVE FOR DIAGNOSTIC OR THERAPEUTIC PURPOSES SHALL BE
 SUBMITTED TO THE DEPARTMENT OF HEALTH FOR REVIEW AND
 APPROVAL. IN COMPUTATION OF PROTECTIVE BARRIER
 REQUIREMENTS, THE MAXIMUM ANTICIPATED WORKLOAD, USE
 FACTORS, OCCUPANCY FACTORS AND THE POTENTIAL FOR
 RADIATION EXPOSURE FROM OTHER SOURCES SHALL BE TAKEN
 INTO CONSIDERATION.
  
 13G) FBC-B 465.5.1.3.1. THE PLANS SHALL SHOW, AS A
 MINIMUM, THE FOLLOWING:
  
 13G) (1) FBC-B. 465.5.1.3.1.1. THE NORMAL LOCATION OF
 THE X-RAY SYSTEM?S RADIATION PORT; THE PORT?S TRAVEL
 AND TRAVERSE LIMITS; GENERAL DIRECTION OF THE USEFUL
 BEAM; LOCATIONS OF ANY WINDOWS AND DOORS; THE LOCATION
 OF THE OPERATOR?S BOOTH; AND THE LOCATION OF THE XRAY
 CONTROL PANEL.
  
  
 13G)(2) FBC-B 465.5.1.3.1.2. THE STRUCTURAL COMPOSITION
 AND THICKNESS OR LEAD EQUIVALENT OF ALL WALLS, DOORS,
 PARTITIONS, FLOOR AND CEILING OF THE ROOM CONCERNED.
  
 13G)(2)COMPLIED. FBC-B 465.5.1.3.1.3 THE DIMENSIONS OF
 THE ROOM CONCERNED.
  
 13G)(3) FBC-B 465.5.1.3.1.4. THE TYPE OF OCCUPANCY OF
 ALL ADJACENT AREAS INCLUSIVE OF SPACE ABOVE AND BELOW
 THE ROOM CONCERNED. IF THERE IS AN EXTERIOR WALL, THE
 DISTANCE TO THE CLOSEST AREA WHERE IT IS LIKELY THAT
 INDIVIDUALS MAY BE PRESENT.
  
 13G)(4) FBC-B 465.5.1.3.1.5. THE MAKE AND MODEL OF THE
 X-RAY EQUIPMENT AND THE MAXIMUM TECHNIQUE FACTORS.
  
 13G)(5) FBC-B 465.5.1.3.1.6. THE TYPE OF EXAMINATIONS
 OR TREATMENTS WHICH WILL BE PERFORMED WITH THE
 EQUIPMENT.
  
 13H) ROOM 344 IS INDICATED AS THE ACCESSIBLE DRESSING
 ROOM. PLEASE INDICATE HOW COMPLIANCE WITH EITHER A BACK
 SUPPORT (ACCESS. CODE 903.4) OR ATTACHMENT TO THE WALL
 IN COMPLIANCE WITH ACCESSIBILITY CODE 903.6 STRUCTURAL
 STRENGTH. ALLOWABLE STRESSES SHALL NOT BE EXCEEDED FOR
 MATERIALS USED WHEN A VERTICAL OR HORIZONTAL FORCE OF
 250 POUNDS (1112 N) IS APPLIED AT ANY POINT ON THE
 SEAT, FASTENER, MOUNTING DEVICE, OR SUPPORTING
 STRUCTURE.
  
 13I) NEW COMMENT. TUES. NOV. 20/18. FOR X-RAY EQUIPMENT
 INSTALLATION DRAWINGS THEY WILL NEED TO BE REVIEWED BY
 THE ARCHITECT OF RECORD AND THEIR SHOP DRAWING STAMP OF
 APPROVAL APPLIED, EITHER REVIEWED OR REVIEWED WITH
 NOTES. FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE
 FOR SUPERVISING AND REVIEWING ALL PROJECT DATA,
 REPORTS, SHOP DRAWINGS ETC... THIS MAY ALSO BE A
 DEFERRED SUBMITTAL (AFTER PERMIT ISSUANCE).
  
 TUES. NOV. 20/18.
  
 14) 060-A-004 LIFE SAFETY PLAN & 066-A-104 FOURTH FLOOR
 PLAN:
  
 14A) ROOM 434 PATIENT TOILET DOOR SWINGS OUT INTO THE
 CORRIDOR, PLEASE SHOW COMPLIANCE WITH 2017 FBC-B
 451.3.4.1. NO DOORS SHALL SWING INTO THE CORRIDOR
 EXCEPT THOSE TO SMALL CLOSETS OR SMALL MECHANICAL OR
 ELECTRICAL ROOMS THAT CANNOT BE USEFULLY OCCUPIED WITH
 THE DOORS IN THE CLOSED POSITION.
  
 14B) SHEET 006-A-104. PLEASE EXPLAIN WHAT THE RED LINES
 REPRESENT, THE LEGEND ATOP THIS SHEET DOES NOT HAVE
 THIS AS AN EXAMPLE OF WHAT IS TO BE REPRESENTED?
 107.2.2.1. ADDITIONAL INFORMATION IS REQUIRED. THE LIFE
 SAFETY SHEET DEPICTS THE WALL AS A 1 HOUR SMOKE
 BARRIER. SHEET A-104 SHOWS THE RED LINE CROSSING AT
 DOOR 439 WHEREAS SHEET A-004 INDICATES THE 1 HOUR SMOKE
 BARRIER CONTINUING THROUGH DOOR 438-A, IS THIS A
 DISCREPANCY? 107.2.2.1. ADDITIONAL INFORMATION IS
 REQUIRED.
  
 14C) SHEET 066-A-104 THE 4TH FLOOR PLAN HAS TO DOORS
 WITH RED LINES, 415B & 460 IT WOULD APPEAR THIS MAYBE
 THE DESIGNATION FOR THE 1 HOUR SMOKE COMPARTMENT FOR
 THE SURGICAL SUITE BUT THE WALL TYPE FIRE RATINGS AND
 OPENING PROTECTIVES DOES NOT AGREE WITH SHEET 060-A-004
 4TH FLOOR LIFE SAFETY PLAN. IT WOULD APPEAR THERE IS A
 DISCREPANCY IN THE PLANS AND ALSO THE PARTITION PLAN
 119-A-600. 107.2.2.1 ADDITIONAL INFORMATION REQUIRED,
 DISCREPANCY IN PLANS.
  
 14D) THE OPERATING ROOMS HAVE NO DESIGNATION AS TO THE
 USE OF THE OPERATING ROOMS THE PROCEDURES TO OCCUR.
 PLEASE USE THE OPERATING ROOM DEFINITION FOUND IN THE
 GUIDELINES FOR DESIGN AND CONSTRUCTION OF HEALTH CARE
 FACILITIES FOR AMBULATORY OPERATING ROOMS SEE
 A3.7-3.3.1.2. 2017 FBC-B 451.2.2.
  
 14E) PLEASE EXPLAIN WHY ON THE LIFE SAFETY SHEET 004
 THE SHELL OPERATING ROOMS ARE 1 HOUR FIRE RATED WITH 45
 MINUTE OPENING PROTECTIVES WHEREAS THE OPERATING ROOMS
 1& 2 ARE NON-RATED WALLS WITH. 107.2.2.1 ADDITIONAL
 INFORMATION REQUIRED.
  
 14F) ROOM 456 THE STERILE EQUIPMENT ROOM IS SHOWN WITH
 A 1 HOUR RATED ENTRY WALL BUT THE DOOR456 IS NOT RATED
 ON THE DOOR SCHEDULE120-A-611. PLEASE REVIEW 2017 FBC-B
 TABLE 716.5 OPENING PROTECTIVES.
  
 15) 070-A-108 ROOF PLAN:
  
 15A) PLEASE NOTE THIS ROOF TOP PLAN DOES NOT SHOW ROOF
 TOP ACCESS. DETAIL PLAN 131-A-804 STAIR 04 DETAILS 06
 AND 07 DO NOT STOP AT THE ROOF TOP FOR ACCESS TO THE
 ROOF. PLEASE REVIEW 2017 FBC-B 1011.12 STAIRWAY TO THE
 ROOF.
  
 15B) ROOF TOP DRAINAGE, THIS PLAN DOES NOT SHOW
 COMPLIANCE WITH 1503.4 OF THE FBC-B. ROOF DRAINAGE
 SHALL SHOW COMPLIANCE WITH CHAPTER 11 OF THE
 FBC-PLUMING CODE FOR ROOF DRAINAGE. SHEET P-205 ALSO
 MISSING ROOF DRAINAGE INFO.
  
 15B)(1)2017 FBC-P. 1106.1. THE SIZE OF THE VERTICAL
 CONDUCTORS AND LEADERS, BUILDING STORM DRAINS, BUILDING
 STORM SEWERS AND ANY HORIZONTAL BRANCHES OF SUCH DRAINS
 OR SEWERS SHALL BE BASED ON THE 100-YEAR HOURLY
 RAINFALL RATE INDICATED IN FIGURE 1106.1 OR ON OTHER
 RAINFALL RATES DETERMINED FROM APPROVED LOCAL WEATHER
 DATA.
  
 15B)(2) 2017 FBC-P 1106.3 VERTICAL LEADER SIZING.
 VERTICAL LEADERS SHALL BE SIZED BASED ON THE FLOW RATE
 FROM HORIZONTAL GUTTERS OR THE MAXIMUM FLOW RATE
 THROUGH ROOF DRAINS. THE FLOW RATE THROUGH VERTICAL
 LEADERS SHALL NOT EXCEED THAT SPECIFIED IN TABLE
 1106.3.
  
 15B)(3) 2017 FBC-P 1106.4 VERTICAL WALLS. IN SIZING
 ROOF DRAINS AND STORM DRAINAGE PIPING, ONE-HALF OF THE
 AREA OF ANY VERTICAL WALL THAT DIVERTS RAINWATER TO THE
 ROOF SHALL BE ADDED TO THE PROJECTED ROOF AREA FOR
 INCLUSION IN CALCULATING THE REQUIRED SIZE OF VERTICAL
 CONDUCTORS, LEADERS AND HORIZONTAL STORM DRAINAGE
 PIPING.
  
 16) 071-A-201, 072-A-202 & 073-A-203 EXTERIOR
 ELEVATIONS:
  
 16A) THE PLANS INDICATE THE USE OF ALUMINUM COMPOSITE
 PANEL SYSTEMS. PLEASE SHOW COMPLIANCE WITH 2017 FBC-B
 1407.2 EXTERIOR WALL FINISH. MCM USED AS EXTERIOR WALL
 FINISH OR AS ELEMENTS OF BALCONIES AND SIMILAR
 PROJECTIONS AND BAY AND ORIEL WINDOWS TO PROVIDE
 CLADDING OR WEATHER RESISTANCE SHALL COMPLY WITH
 SECTIONS 1407.4 THROUGH 1407.14.
  
 16B) THE PLANS INDICATE THE USE OF ALUMINUM WALL PANEL
 SYSTEM AS AN EXTERIOR WALL SYSTEM. THE SHEET 071-A-201
 SHOWS THE UPRIGHTS AT 12 FOOT CENTERS, WHILE THE
 STRUCTURAL SHEET 029-S-151 SHOW THE UPRIGHTS AT 13 FOOT
 8 INCHES, DISCREPANCY IN PLANS. 107.2.2.1. ADDITIONAL
 INFORMATION IS REQUIRED.
  
 16C) NEITHER THE ROOF TOP PLAN NOR THE ELEVATION PLANS
 NOR EXTERIOR WALL SECTION PLAN 079-A-300 INDICATE HOW
 CODE COMPLIANCE WILL BE ACHIEVED FOR:
  
 16C)(1) 2017 FBC-B 1607.9.3 ELEMENTS SUPPORTING HOISTS
 FOR FA?ADE ACCESS EQUIPMENT. IN ADDITION TO ANY OTHER
 APPLICABLE LIVE LOADS, STRUCTURAL ELEMENTS THAT SUPPORT
 HOISTS FOR FA?ADE ACCESS EQUIPMENT SHALL BE DESIGNED
 FOR A LIVE LOAD CONSISTING OF THE LARGER OF THE RATED
 LOAD OF THE HOIST TIMES 2.5 AND THE STALL LOAD OF THE
 HOIST.
  
 16C)(2) 1607.9.4 LIFELINE ANCHORAGES FOR FA?ADE ACCESS
 EQUIPMENT. IN ADDITION TO ANY OTHER APPLICABLE LIVE
 LOADS, LIFELINE ANCHORAGES AND STRUCTURAL ELEMENTS THAT
 SUPPORT LIFELINE ANCHORAGES SHALL BE DESIGNED FOR A
 LIVE LOAD OF AT LEAST 3,100 POUNDS FOR EACH ATTACHED
 LIFELINE, IN EVERY DIRECTION THAT A FALL ARREST LOAD
 MAY BE APPLIED.
  
 HOW WILL CODE COMPLIANCE BE ACHIEVED WITH THE ALUMINUM
 SHADE SYSTEM OVER THE CURTAIN WALL SYSTEM, WHERE WILL
 THE ANCHORS BE ANCHORED, WALLS OR ROOF LINE?
  
 16D) PLEASE PROVIDE ENGINEERING FOR THE ALUMINUM
 SUNSHADE SYSTEM FOR THE 170 VASD WIND DESIGN. 2017
 FBC-B 1603.1.4 WIND DESIGN DATA. THIS MAYBE A DEFERRED
 SUBMITTAL PER 107.3.4.2 DEFERRED SUBMITTALS. FOR THE
 PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE
 DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT
 SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE
 TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A
 SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
  
 17) 127-A-801 STAIRWELL 501 DETAIL 05 STAIR 01, ON
 LEVEL 1 AND LEVEL 4 THERE APPEARS TO BE PIPES WITHIN
 THE STAIRWELL. PLEASE SHOW COMPLIANCE WITH 2017 FBC-B
 1023.5 PENETRATIONS.
 18) 129-A802B STAIR02 SECTION 03 IT APPEARS THERE IS A
 VERTICAL PIPE ON THE 3RD LEVEL OF THE STAIRWELL. PLEASE
 SHOW COMPLIANCE WITH 2017 FBC-B 1023.5 PENETRATIONS.
 19) SHEET 011-S-002:
 19A) A. WIND DESIGN DATA IS GIVEN BUT THERE IS NO MEAN
 ROOF HEIGHT GIVEN. FBC-B TABLE 1609.7(2) ADJUSTMENT
 FACTORS FOR HEIGHT & EXPOSURE. PROVIDE THE MEAN ROOF
 HEIGHT FOR THE BUILDING.
 19B) COMPONENTS AND CLADDING PLEASE PROVIDE A CHART FOR
 COMPONENTS AND CLADDING IN EFFECTIVE WIND AREA, 10 FT.,
 20 FT., 50 FT., & 100 FT. FOR BOTH VULT AND VASD FOR
 ALL ROOFING ZONES AS WELL AS WALL ZONES 4 & 5. ALL
 PRODUCT APPROVALS ARE LISTED IN VASD. 2017 FBC-B
 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
 20A) 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF TOP
 VENTILATORS
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) PRE-ENGINEERED A/C STANDS.
 20B) PLEASE IDENTIFY ON THE PRODUCT APPROVAL BEFORE
 SUBMITTING TO DESIGNER OF RECORD AND BEFORE SUBMISSION
 TO THE BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH
 GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT,
 TYPE OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED
 OR REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2014 FBC-B
 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
 20C) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 20D) DELEGATED ENGINEERING. 61G15-30.003 ENGINEERING
 DOCUMENT CLASSIFICATION. FL 61G-15-30.006 (3) THE
 DELEGATED ENGINEER SHALL FORWARD THE DELEGATED
 ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR
 REVIEW.
  
 20E) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
 20F) EFIS SYSTEMS: PLEASE PROVIDE THE PRODUCT APPROVAL
 FOR THE SYSTEM TO BE INSTALLED. PLEASE ALSO PROVIDE THE
 MANUFACTURERS INSTALLATION BROCHURE PROVIDING
 COMPLIANCE WITH 2014 FBC-B SECTIONS;
 1408.2 PERFORMANCE CHARACTERISTICS.
 1408.2 PERFORMANCE CHARACTERISTICS.
 1408.3 STRUCTURAL DESIGN.
 1408.4 WEATHER RESISTANCE.
 1408.4.1 EIFS WITH DRAINAGE.
 408.4.1.1 WATER-RESISTIVE BARRIER.
 1408.5 INSTALLATION.
 20G) FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY ALL
 ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES FOR
 ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL LIMITATIONS,
 IF ENHANCED FASTENING IS ALLOWED FOR ROOF ZONES 2 & 3.
 FASTENER DENSITIES SHALL BE INCREASED FOR BOTH
 INSULATION & THE BASE SHEET AS CALCULATED IN COMPLIANCE
 WITH ROOFING APPLICATION STANDARDS RAS 117. CALCULATION
 PREPARED, SIGNED AND SEALED BY A FLORIDA REGISTERED
 PROFESSIONAL ENGINEER OR REGISTERED ARCHITECT.
 1609.6.4.4.1 COMPONENTS & CLADDING.
 21) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2019-02-08 Cont ID  
Sent By jpearson Date 2019-02-08 Time 09:07 Rev Time 0.00
Received By jpearson Date 2019-02-08 Time 09:07 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2018-12-18 Cont ID  
Sent By jpearson Date 2018-12-18 Time 15:09 Rev Time 0.00
Received By jpearson Date 2018-12-18 Time 09:06 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-10-04 Cont ID  
Sent By jpearson Date 2018-10-04 Time 15:57 Rev Time 0.00
Received By jpearson Date 2018-10-04 Time 09:29 Sent To  
Notes
2018-10-04 15:57:24CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
 2. PROVIDE RECEPTACLE CONTROL REQUIRED BY ASHREA 90.1:
 8.4.2. PER THIS REQUIREMENT, THE FOLLOWING SHALL BE
 AUTOMATICALLY CONTROLLED: 1) AT LEAST 50% OF ALL
 125-VOLT, 15 AND 20 AMP RECEPTACLES, IN ALL PRIVATE
 OFFICES, CONFERENCE ROOMS, ROOMS USED PRIMARILY FOR
 PRINTING AND/OR COPYING FUNCTIONS, BREAK ROOMS,
 CLASSROOMS, AND INDIVIDUAL WORKSTATIONS. 2) AT LEASE
 25% OF BRANCH CIRCUIT FEEDERS INSTALLED FOR MODULAR
 FURNITURE NOT SHOWN ON THE CONSTRUCTION DOCUMENTS. FBC
 EC C405.6.1
 3. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES
 EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN
 RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR
 LIGHTING PROPOSED TO COMPLY WITH CODE. FBC EC C405.4.2
 4. PLEASE INDICATE ON PLANS WHICH ROOMS SHALL BE WIRED
 PER NEC 517.13 .
 5. RISER DIAGRAM DOES NOT SHOW FEEDER WIRE AND CONDUIT
 SIZES. THIS INFORMATION IS ONLY PROVIDED FOR A FEW
 CIRCUITS IN THE PANEL SCHEDULES. PROVIDE CORRECTION.
 WPB FBC 107.2.1; NEC 310.15(B)(16) AND CHAPTER 9
 TABLES.
 6. PANEL 4DPH SHOWS A DEMAND LOAD OF 692550 VA WHICH
 EQUALS APPROXIMATELY 834 AMPS. THIS PANEL IS RATED FOR
 800 AMPS. PROVIDE CORRECTION. NEC 408.30, 408.36,
 310.15, 215.2
 7. SHEET E-101 SHOWS FEED FROM GENERATOR GOING DIRECTLY
 TO PANEL EDP, BUT THE RISER DIAGRAM SHOWS THE GENERATOR
 FEED GOING TO A DUAL PURPOSE DOCKING STATION. PROVIDE
 CLARIFICATION AND/OR CORRECTION. SHOW LOCATION OF DUAL
 PURPOSE DOCKING STATION ON PLAN. PROVIDE SPEC SHEET FOR
 THIS PRODUCT. WPB FBC 107.2.1; NEC 110.3
 8. PROVIDE THE REQUIRED SERVICE AREA RECEPTACLE PER
 CODE. NEC 210.64
 9. PLAN DOES NOT SHOW THE PANEL BOARD BONDING REQUIRED.
 PROVIDE CORRECTION. NEC 517.14
 10. PLAN DOES NOT SHOW THE GFCI PROTECTION OR
 EQUIVALENT FOR HYDROTHERAPY ROOM. PROVIDE CORRECTION.
 NEC 517.20
 11. ROOMS 211 AND 215 SHOW RECEPTACLE OUTLETS WITHIN 6
 FEET OF A SINK THAT ARE NOT GFCI PROTECTED. PROVIDE
 CORRECTION. NEC 210.8(B)(5)
 12. PANELS 1P1, E1P1, 1P2, E1P2, 1P3, E1P3, 1P4, AND
 E1P4 ARE NOT SHOWN ON RISER DIAGRAM OR IN PANEL
 SCHEDULES. WHERE ARE THESE PANELS FED FROM, WHAT IS THE
 LOAD, AND IS THIS LOAD INCLUDED IN THE LOAD CALCULATION
 FOR THE SERVICE? PROVIDE CLARIFICATION AND/OR
 CORRECTION. WPB FBC 107.2.1; NEC 215.2, 215.5, 220
 13. WOMENS LOCKER ROOM (ROOM 461) AND MENS LOCKER ROOM
 (ROOM 464) SHOW RECEPTACLE OUTLETS THAT ARE NOT GFCI
 PROTECTED. PROVIDE CORRECTION. NEC 210.8(B)(7)
 14. BE ADVISED THAT FIRE ALARM, LOW VOLTAGE SYSTEMS,
 DAS, LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD
 SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND
 SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN
 THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE
 INDICATING THE REQUIRED SEPARATE PERMITS AND PLAN
 SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. WPB FBC
 105.1, 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2018-12-17 Cont ID  
Sent By RRossano Date 2018-12-17 Time   Rev Time 0.00
Received By rrossano Date 2018-12-17 Time   Sent To I
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2018-09-12 Cont ID  
Sent By RRossano Date 2018-09-12 Time   Rev Time 1.00
Received By rrossano Date 2018-09-12 Time   Sent To I
Notes
2018-09-12 14:08:13UNDER ENGINEERING REVIEW.
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
  
 RICK ROSSANO
 PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1098
 FAX: (561) 494-1116
 MOBILE: (561) 246-9525
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 MANNY GONZALEZ
 SENIOR ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2019-03-06 Cont ID  
Sent By pleduc Date 2019-03-06 Time   Rev Time 0.00
Received By pleduc Date 2019-03-06 Time 16:36 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2019-02-08 Cont ID  
Sent By pleduc Date 2019-02-08 Time   Rev Time 0.00
Received By pleduc Date 2019-01-29 Time 14:29 Sent To  
Notes
2019-01-31 10:22:55THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) ON REVIEW OF THE SUBMITTAL OF MECHANICAL COMMENTS, #
 12 INDICATES A ROOF A/C DUCT THROUGH THE EXIT
 ENCLOSURE.
  
 SHEET M 205 INDICATES THIS DUCT AT THE STAIRWELLS.
  
 THIS DUCT APPEARS TO BE IN CONFLICT WITH NFPA 101,
 CHAPTER 38, NEW BUSINESS OCCUPANCIES AND CHAPTER 7
 MEANS OF EGRESS.
  
 38.2.2.3 STAIRS.
 38.2.2.3.1 STAIRS COMPLYING WITH 7.2.2 SHALL BE
 PERMITTED.
  
  
 7.2.2.5 ENCLOSURE AND PROTECTION OF STAIRS.
 7.2.2.5.1 ENCLOSURES.
 7.2.2.5.1.1 ALL INSIDE STAIRS SERVING AS AN EXIT OR
 EXIT COMPONENT
 SHALL BE ENCLOSED IN ACCORDANCE WITH 7.1.3.2.
  
 (10) PENETRATIONS INTO, AND OPENINGS THROUGH, AN EXIT
 ENCLOSURE
 ASSEMBLY SHALL BE LIMITED TO THE FOLLOWING:
 (A) DOOR ASSEMBLIES PERMITTED BY 7.1.3.2.1(9)
 (B) *ELECTRICAL CONDUIT SERVING THE EXIT ENCLOSURE
 (C) REQUIRED EXIT DOOR OPENINGS
 (D) DUCTWORK AND EQUIPMENT NECESSARY FOR INDEPENDENT
 STAIR PRESSURIZATION
 (E) WATER OR STEAM PIPING NECESSARY FOR THE HEATING OR
 COOLING OF THE EXIT ENCLOSURE
 (F) SPRINKLER PIPING
 (G) STANDPIPES
 (H) EXISTING PENETRATIONS PROTECTED IN ACCORDANCE WITH
 8.3.5
 (I) PENETRATIONS FOR FIRE ALARM CIRCUITS, WHERE THE
 CIRCUITS
 ARE INSTALLED IN METAL CONDUIT AND THE PENETRATIONS ARE
 PROTECTED IN ACCORDANCE WITH 8.3.5
  
  
 PLEASE REVIEW, CORRECT OR JUSTIFY WITH SPECIFIC CODE
 REFERENCES.
  
  
  
 2) ADDITIONAL COMMENT ADDED 5/8/19 - THE GENERATOR ROOM
 INDICATES A 1 HOUR FIRE RATING. PER NFPA 110, EMERGENCY
 AND STANDBY POWER SYSTEMS, A 2 HOUR FIRE RATED ROOM IS
 REQUIRED.
  
 7.2 LOCATION.
 7.2.1 INDOOR EPS INSTALLATIONS. THE EPS SHALL BE
 INSTALLED IN A
 SEPARATE ROOM FOR LEVEL 1 INSTALLATIONS.
 7.2.1.1 THE EPS ROOM SHALL BE SEPARATED FROM THE REST
 OF THE
 BUILDING BY CONSTRUCTION WITH A 2-HOUR FIRE RESISTANCE
 RATING.
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE
 REFERENCES.
  
  
  
 3) ADDITIONAL COMMENT PROVIDED 5/8/19 - THE
 INSTALLATION OF THE GENERATOR SHALL BE UNDER SEPARATE
 SHOP DRAWINGS AND PERMIT.
  
 PLEASE ENSURE THAT THE REQUIRED CLASS,TYPE AND LEVEL
 PER NFPA 110 IS PROVIDED.
  
 4.2* CLASS. THE CLASS DEFINES THE MINIMUM TIME, IN
 HOURS, FOR
 WHICH THE EPSS IS DESIGNED TO OPERATE AT ITS RATED LOAD
 WITHOUT
 BEING REFUELED OR RECHARGED. [SEE TABLE 4.1(A).]
 4.3 TYPE. THE TYPE DEFINES THE MAXIMUM TIME, IN
 SECONDS,
 THAT THE EPSS WILL PERMIT THE LOAD TERMINALS OF THE
 TRANSFER
 SWITCH TO BE WITHOUT ACCEPTABLE ELECTRICAL POWER. TABLE
 4.1(B)
 PROVIDES THE TYPES DEFINED BY THIS STANDARD.
 4.4* LEVEL. THIS STANDARD RECOGNIZES TWO LEVELS OF
 EQUIPMENT
 INSTALLATION, PERFORMANCE, AND MAINTENANCE.
 4.4.1* LEVEL 1 SYSTEMS SHALL BE INSTALLED WHERE FAILURE
 OF THE
 EQUIPMENT TO PERFORM COULD RESULT IN LOSS OF HUMAN LIFE
 OR
 SERIOUS INJURIES.
 4.4.2* LEVEL 2 SYSTEMS SHALL BE INSTALLED WHERE FAILURE
 OF THE
 EPSS TO PERFORM IS LESS CRITICAL TO HUMAN LIFE AND
 SAFETY.
 4.4.3 ALL EQUIPMENT SHALL BE PERMANENTLY INSTALLED.
 4.4.4* LEVEL 1 AND LEVEL 2 SYSTEMS SHALL ENSURE THAT
 ALL LOADS
 SERVED BY THE EPSS ARE SUPPLIED WITH ALTERNATE POWER
 THAT
 MEETS ALL THE FOLLOWING CRITERIA:
 (1) OF A QUALITY WITHIN THE OPERATING LIMITS OF THE
 LOAD
 (2) FOR A DURATION SPECIFIED FOR THE CLASS AS DEFINED
 IN TABLE
 4.1(A)
 (3) WITHIN THE TIME SPECIFIED FOR THE TYPE AS DEFINED
 IN TABLE
 4.1(B)
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2018-12-17 Cont ID  
Sent By pleduc Date 2018-12-17 Time   Rev Time 0.00
Received By pleduc Date 2018-12-05 Time 10:27 Sent To  
Notes
2018-12-11 09:30:00THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) ON THE FP SHEETS THERE ARE ONLY INFDICATION OF
 STANDPIPES. THERE ARE NO INDICATIONS OF FIRE SPRINKLER
 PROTECTION DETAILS THAT ARE COMPLIANT WITH FAC 61G.
  
  
 PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004,
 FIRE PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE
 POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF
 APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT,
 CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER
 SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA)
 AND ANY PERFORMANCE BASED INFORMATION SUCH AS
 PRE-ENGINEERED SYSTEMS.
  
 FAC 61G15-32.002 DEFINES THE FIRE PROTECTION SYSTEM
 ENGINEERING DOCUMENT (5) AS WELL AS THE FIRE PROTECTION
 SYSTEM LAYOUT DOCUMENT (6). 61G15-32.003 OUTLINES THE
 COMMON REQUIREMENTS TO ALL FIRE PROTECTIONS ENGINEERING
 DOCUMENTS WITH 32.004 (2) (A-J) OUTLINING THE MINIMUM
 INFORMATION TO BE PROVIDED ON FIRE PROTECTION
 ENGINEERING DOCUMENTS FOR WATER BASED SYSTEMS. AS
 STATED IN THE DEFINITIONS, THE CONTRACTOR IS TO DEVELOP
 THE LAYOUT DOCUMENTS BASED ON THE DESIGN CRITERIA
 PROVIDED IN THE FIRE PROTECTION ENGINEERING DOCUMENTS
 BY THE ENGINEER OF RECORD FOR THE FIRE SPRINKLER
 SYSTEM. THE FIRE PROTECTION SYSTEM ENGINEERING
 DOCUMENTS ARE SUBMITTED FOR THE MASTER PERMIT (BUILDING
 PERMIT PER FBC) AND THE LAYOUT DOCUMENTS ARE SUBMITTED
 FOR THE FIRE SPRINKLER INSTALLATION PERMIT.
  
  
 61G15-32.003 COMMON REQUIREMENTS TO ALL FIRE PROTECTION
 ENGINEERING
 DOCUMENTS.
 (1) THE FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS
 SHALL PROVIDE THE ENGINEERING REQUIREMENTS TO BE USED
 IN THE PREPARATION OF THE FIRE PROTECTION SYSTEM LAYOUT
 DOCUMENTS AND TO INDICATE THE NATURE AND SCOPE OF THE
 WORK, AND TO DESCRIBE, DETAIL, DIMENSION, LABEL AND
 DEFINE THE FIRE PROTECTION COMPONENTS, SYSTEM(S),
 MATERIALS, ASSEMBLIES, EQUIPMENT AND ITS STRUCTURAL AND
 UTILITY SUPPORT SYSTEM(S), INSOFAR AS THEY INVOLVE THE
 SAFEGUARDING OF LIFE, HEALTH OR PROPERTY.
 (2) THE FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS
 SHALL SPECIFY THE APPLICABLE REQUIREMENTS FOR THE
 ACCEPTANCE TESTING OF THE FIRE PROTECTION SYSTEM AND
 COMPONENTS, WHICH SHALL BE BASED UPON APPLICABLE CODES
 AND STANDARDS, WHERE AVAILABLE.
 (3) THE OCCUPANCY OF THE AREA OR DESCRIPTION OF A
 SPECIFIC HAZARD BEING PROTECTED BY THE FIRE PROTECTION
 SYSTEM(S) SHALL BE SHOWN ON THE FIRE PROTECTION SYSTEM
 ENGINEERING DOCUMENTS.
 (4) THE APPLICABLE CODE AND STANDARD TO BE USED IN THE
 PREPARATION OF THE FIRE PROTECTION SYSTEM LAYOUT
 DOCUMENTS SHALL BE SHOWN ON THE FIRE PROTECTION SYSTEM
 ENGINEERING DOCUMENTS. WHEN CODES AND STANDARDS ARE NOT
 AVAILABLE OR APPLICABLE, AND SAID LAYOUT DOCUMENTS ARE
 TO BE BASED ON ENGINEERING JUDGMENT, ANY REASONS AND
 ASSUMPTIONS MADE TO DEVELOP THE FIRE PROTECTION CONCEPT
 SHALL BE IDENTIFIED ON THE FIRE PROTECTION SYSTEM
 ENGINEERING DOCUMENTS.
 (5) STRUCTURAL SUPPORT AND STRUCTURAL OPENINGS REQUIRED
 BY THE FIRE PROTECTION SYSTEM SHALL BE SHOWN ON THE
 FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS AND SHALL
 BE REFERENCED ON STRUCTURAL ENGINEERING DOCUMENTS.
 (6) WHEN LAYOUT DOCUMENTS CONTAIN MATERIAL DEVIATION
 FROM THE ENGINEER OF RECORD'S FIRE PROTECTION SYSTEM
 ENGINEERING DOCUMENT, SUCH LAYOUT DOCUMENTS ARE NOT
 COMPLIANT UNLESS THEY ARE ACCOMPANIED BY REVISED
 ENGINEERING DOCUMENTS MADE AND SEALED BY THE ENGINEER
 OF RECORD FOR THE FIRE PROTECTION SYSTEM.
 (7) REQUIREMENTS FOR ACTIVATION CONTROL SYSTEMS,
 SEQUENCE, OPERATING PARAMETERS, INTERLOCKS, SAFETY
 RELATED DEVICES, INDICATORS AND ALARMS, SHALL BE SHOWN
 ON THE FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS,
 UNLESS SHOWN ON OTHER RELATED DOCUMENTS.
 (8) ANY INFORMATION DEEMED APPROPRIATE BY THE ENGINEER
 OF RECORD TO ASSIST THE AUTHORITY HAVING JURISDICTION
 IN UNDERSTANDING THE OWNER?S INTENDED USE AND PROPOSED
 PROTECTION OF THE BUILDING OR FACILITY AND TO PROVIDE
 SUFFICIENT DIRECTION TO THE INSTALLATION CONTRACTOR OR
 OTHER INTERESTED PARTIES REGARDING THE LAYOUT OF THE
 SYSTEM(S), SHALL BE INCLUDED IN THE FIRE PROTECTION
 SYSTEM ENGINEERING DOCUMENTS.
 SPECIFIC AUTHORITY 471.008, 471.033(2), FS
 LAW IMPLEMENTED 471.005(7), 471.033(2), FS
 HISTORY?NEW 5-19-93, FORMERLY 21H-32.003, AMENDED
 4-2-2000, 6-26-01
  
 61G15-32.004 DESIGN OF WATER BASED FIRE PROTECTION
 SYSTEMS.
 (1) WATER BASED FIRE PROTECTION SYSTEMS INCLUDE, BUT
 ARE NOT LIMITED TO, AUTOMATIC SPRINKLER SYSTEMS OF WET,
 DRY, FINE WATER SPRAY (MIST), MANUAL, AND DELUGE VALVE
 CONTROLLED TYPES, PUMPING SYSTEMS, STANDPIPES, FIRE
 WATER MAINS AND DEDICATED FIRE PROTECTION WATER
 SOURCES.
 (2) TO ENSURE MINIMUM DESIGN QUALITY IN FIRE PROTECTION
 SYSTEM ENGINEERING DOCUMENTS, SAID DOCUMENTS SHALL
 INCLUDE AS A MINIMUM THE FOLLOWING INFORMATION WHEN
 APPLICABLE:
 (A) THE POINT OF SERVICE FOR THE FIRE PROTECTION WATER
 SUPPLY AS DEFINED BY 633.021(18) F.S.
 (B) APPLICABLE NFPA STANDARD TO BE APPLIED, OR IN THE
 CASE WHERE NO SUCH STANDARD EXISTS, THE ENGINEERING
 STUDY, JUDGMENTS, AND/OR PERFORMANCE BASED ANALYSIS AND
 CONCLUSIONS.
 (C) CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA.
 (D) DESIGN APPROACH, WHICH INCLUDES SYSTEM TYPE,
 DENSITIES, DEVICE TEMPERATURE RATING, AND SPACING FOR
 EACH SEPARATE 42 HAZARD OCCUPANCY.
 (E) CHARACTERISTICS OF WATER SUPPLY TO BE USED, SUCH AS
 MAIN SIZE AND LOCATION, WHETHER IT IS DEAD-END OR
 CIRCULATING; AND IF DEAD-END, THE DISTANCE TO THE
 NEAREST CIRCULATING MAIN, AS WELL AS ITS MINIMUM
 DURATION AND RELIABILITY FOR THE MOST HYDRAULICALLY
 DEMANDING DESIGN AREA.
 (F) WHEN PRIVATE OR PUBLIC WATER SUPPLIES ARE USED, THE
 FLOW TEST DATA, INCLUDING DATE AND TIME OF TEST, WHO
 CONDUCTED TEST OR SUPPLIED INFORMATION, TEST ELEVATION,
 STATIC GAUGE PRESSURE AT NO FLOW, FLOW RATE WITH
 RESIDUAL GAUGE PRESSURE, HYDRANT BUTT COEFFICIENT, AND
 LOCATION OF TEST IN RELATION TO THE HYDRAULIC POINT OF
 SERVICE.
 (G) VALVING AND ALARM REQUIREMENTS TO MINIMIZE
 POTENTIAL FOR IMPAIRMENTS AND UNRECOGNIZED FLOW OF
 WATER.
 (H) MICROBIAL INDUCED CORROSION (MIC). THE ENGINEER OF
 RECORD SHALL MAKE REASONABLE EFFORTS TO IDENTIFY WATER
 SUPPLIES THAT COULD LEAD TO MICROBIAL INDUCED CORROSION
 (MIC). SUCH EFFORTS MAY CONSIST OF DISCUSSIONS WITH THE
 LOCAL WATER PURVEYOR AND/OR FIRE OFFICIAL, FAMILIARITY
 WITH CONDITIONS IN THE LOCAL AREA, OR LABORATORY
 TESTING OF WATER SUPPLIES. WHEN CONDITIONS ARE FOUND
 THAT MAY RESULT IN MIC CONTAMINATION OF THE FIRE
 PROTECTION PIPING, THE ENGINEER SHALL DESIGN CORRECTIVE
 MEASURES.
 (I) BACKFLOW PREVENTION AND METERING SPECIFICATIONS AND
 DETAILS TO MEET LOCAL WATER PURVEYOR REQUIREMENTS
 INCLUDING MAXIMUM ALLOWABLE PRESSURE DROP.
 (J) QUALITY AND PERFORMANCE SPECIFICATIONS OF ALL YARD
 AND INTERIOR FIRE PROTECTION COMPONENTS.
 (3) CONTRACTOR SUBMITTALS WHICH DEVIATE FROM THE ABOVE
 MINIMUM DESIGN PARAMETERS SHALL BE CONSIDERED MATERIAL
 DEVIATIONS AND REQUIRE SUPPLEMENTAL ENGINEERING
 APPROVAL AND DOCUMENTATION.
 (4) IN THE EVENT THE ENGINEER OF RECORD PROVIDES MORE
 INFORMATION AND DIRECTION THAN IS ESTABLISHED ABOVE, HE
 OR SHE SHALL BE HELD RESPONSIBLE FOR THE TECHNICAL
 ACCURACY OF THE WORK IN ACCORDANCE WITH APPLICABLE
 CODES, STANDARDS, AND SOUND ENGINEERING PRINCIPLES.
 SPECIFIC AUTHORITY 471.008, 471.033(2), FS
 LAW IMPLEMENTED 471.005(7), 471.033(2), FS
 HISTORY?NEW 5-19-93, FORMERLY 21H-32.004, AMENDED
 4-2-2000, 6-26-01, 7-12-05
  
  
 PLEASE PROVIDE THE APPLICABLE REQUIRED 61G
 DOCUMENTATION IN EITHER WRITTEN NARRATIVE OR PLAN
 SHEETS SIGNED AND SEALED BY A STATE OF FLORIDA
 QUALIFIED PROFESSIONAL.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2018-09-24 Cont ID  
Sent By pleduc Date 2018-09-24 Time   Rev Time 0.00
Received By pleduc Date 2018-09-14 Time 17:05 Sent To  
Notes
2018-09-14 16:58:56THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 FIRE CODE REFERENCES: SHEET G 001 - THERE ARE CONFLICTS
 WITH THE CURRENT EDTIONS OF THE FIRE CODE. THE 2017
 FLORIDA FIRE PREVENTION CODE IS CORRECT; HOWEVER, THE
 CODE EDITIONS UNDER THE FFPC ARE INCORRECT. THEY ARE
 TOO NUMEROUS TO INDICATE HERE.
  
 PLEASE REVIEW THE REFERENCED NFPA EDITIOSN UNDER THE
 CURRENT FFPC AND CORRECT AND ENSURE COMPLIANCE WITH
 THOSE NEW REFERENCES.
  
  
  
  
 1) SHEET A 001 - THERE IS A COMMENT INDICATED REGARDING
 UNPROTECTED OPENINGS IN AN 1 HOUR RATED WALL WITH A
 BUILDING CODE REFERENCE.
  
 THERE IS NO SUCH REFERENCE INDICATED FROM THE FLORIDA
 FIRE PREVENTION CODE.
  
 PLEASE REVIEW AND JUSTIFY BY PROVIDING THE APPLICABLE
 FFPC REFERCE OR CORRECT.
  
  
  
 2) SHEET A002 - THERE IS A COMMENT INDICATED REGARDING
 UNPROTECTED OPENINGS IN AN 1 HOUR RATED WALL, WITH A
 BUILDING CODE REFERENCE.
  
 THERE IS NO SUCH REFERENCE INDICATED FROM THE FLORIDA
 FIRE PREVENTION CODE.
  
 PLEASE REVIEW AND JUSTIFY BY PROVIDING THE APPLICABLE
 FFPC REFERCE OR CORRECT.
  
  
  
 3) A SHEETS - A PARKING GARAGE IS INDICATED; HOWEVER,
 THERE ARE INDICATIONS IF IT IS OPEN OR CLOSED.
  
 PER NFPA 101, CHAPTER 42 AND 88A
  
 42.8 SPECIAL PROVISIONS FOR PARKING STRUCTURES.
  
 42.8.1.3 OPEN PARKING STRUCTURES. OPEN PARKING
 STRUCTURES SHALL
 COMPLY WITH 42.8.1.3.1 THROUGH 42.8.1.3.3.
 42.8.1.3.1 EACH PARKING LEVEL SHALL HAVE WALL OPENINGS
 OPEN TO THE
 ATMOSPHERE FOR AN AREA OF NOT LESS THAN 1.4 FT2 FOR
 EACH LINEAR FOOT
 (0.4 M2 FOR EACH LINEAR METER) OF ITS EXTERIOR
 PERIMETER. [88A:5.5.1]
 42.8.1.3.2 THE OPENINGS ADDRESSED IN 42.8.1.3.1 SHALL
 BE
 DISTRIBUTED OVER 40 PERCENT OF THE BUILDING PERIMETER
 OR UNIFORMLY
 OVER TWO OPPOSING SIDES. [88A: 5.5.2]
 42.8.1.3.3 INTERIOR WALL LINES AND COLUMN LINES SHALL
 BE AT LEAST 20
 PERCENT OPEN, WITH OPENINGS DISTRIBUTED TO PROVIDE
 VENTILATION.
 [88A: 5.5.3]
  
 PLEASE PROVIDE APPLICABLE GARAGELASSIFICATION AND
 SPECIFIC MATHMATICAL DETAILS SHOWIN GCOMPLIANCE THE
 REQUIREMENTS.
  
  
  
 4) A SHEETS - STAIRWELLS IN THE GARAGE MAY BE REQUIRED
 TO BE PROTECTED IF COMPLIANCE WITH OPEN GARAGE IS NOT
 MET.
  
  
  
 5) SHEET A 004 - THERE APPEARS TO BE A GLASS STRUCTURE
 WITHIN A FIRE RATED WALL IN THE AREA OF SC 1 & 2 WITH A
 COMMENT THAT IT IS NOT REQUIRED TO BE RATED.
  
 THERE IS NO SUCH REFERENCE INDICATED IN THE FLORIDA
 FIRE PREVENTION CODE TO ALLOW FOR THIS NON-RATED
 OPENING.
  
 PLEASE REVIEW AND JUSTIFY BY PROVIDING THE APPLICABLE
 FFPC REFERCE OR CORRECT.
  
  
  
 6) FP 201 - THERE ARE NO FIRE SPRINKLERS SHOWN
 THROUGHOUT THE BUILDING. THE BUILDING CODE REQUIRES A
 AUTOMATIC FIRE SPRINKLER SYSTEM.
  
 [F]903.2.11.3 BUILDINGS THREE STORIES OR MORE IN
 HEIGHT.
  
 ANY BUILDING WHICH IS OF THREE STORIES OR MORE IN
 HEIGHT SHALL BE EQUIPPED WITH AN APPROVED AUTOMATIC
 SPRINKLER SYSTEM INSTALLED IN ACCORDANCE WITH SECTION
 903.1.
  
  
  
 7) ALL STRUCTURAL SHEETS - THERE ARE INDICATIONS OF
 EACH WALL ON EACH FLOOR SEPARATING THE GARAGE AND
 BUSINESS OCCUPANCIES AS BEING 1 HOUR.
  
 PER NFPA 101, CHAPTER 38 NEW BUSINESS OCCUPANCIES
  
 38.1.3.2 COMBINED BUSINESS OCCUPANCIES AND PARKING
 STRUCTURES.
 38.1.3.2.1 THE FIRE BARRIER SEPARATING PARKING
 STRUCTURES FROM A BUILDING
 CLASSIFIED AS A BUSINESS OCCUPANCY SHALL BE A FIRE
 BARRIER HAVING A
 MINIMUM 2-HOUR FIRE RESISTANCE RATING.
 38.1.3.2.2 OPENINGS IN THE FIRE BARRIER REQUIRED BY
 38.1.3.2.1 SHALL NOT
 BE REQUIRED TO BE PROTECTED WITH FIRE PROTECTION?RATED
 OPENING
 PROTECTIVES IN ENCLOSED PARKING STRUCTURES THAT ARE
 PROTECTED THROUGHOUT
 BY AN APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM
 IN ACCORDANCE
 WITH 9.7.1.1(1), OR IN OPEN PARKING STRUCTURES,
 PROVIDED THAT ALL OF THE
 FOLLOWING CONDITIONS ARE MET:
 (1) THE OPENINGS DO NOT EXCEED 25 PERCENT OF THE AREA
 OF THE FIRE
 BARRIER IN WHICH THEY ARE LOCATED.
 (2) THE OPENINGS ARE USED AS A PUBLIC ENTRANCE AND FOR
 ASSOCIATED
 SIDELIGHT FUNCTIONS.
 (3) THE BUILDING CONTAINING THE BUSINESS OCCUPANCY IS
 PROTECTED
 THROUGHOUT BY AN APPROVED, SUPERVISED AUTOMATIC
 SPRINKLER
 SYSTEM IN ACCORDANCE WITH 9.7.1.1(1).
 (4) *MEANS ARE PROVIDED TO PREVENT SPILLED FUEL FROM
 ACCUMULATING
 ADJACENT TO THE OPENINGS AND ENTERING THE BUILDING.
  
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE
 REFERNCES
  
 8) SHEET E 001 - THERE ARE INDICATIONS/SYMBOLS UNDER
 THE FIRE ALARM SECTION LEGEND; HOWEVER, THERE ARE NO
 SYMBOLS INDICATED ON ANY ELEVTRICAL SHEETS NOT
 INDICATIONS THAT FIRE ALARM DRAWINGS SHALL BE UNDER
 SPEARATE SHOP DRAWINGS.
  
 PER NFPA 101, CHAPOTER 38, NEW BUSINESS OCCUPANCIES
  
 38.3.4 DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS.
 38.3.4.1 GENERAL. A FIRE ALARM SYSTEM IN ACCORDANCE
 WITH
 SECTION 9.6 SHALL BE PROVIDED IN ALL BUSINESS
 OCCUPANCIES
 WHERE ANY ONE OF THE FOLLOWING CONDITIONS EXISTS:
 (1) THE BUILDING IS THREE OR MORE STORIES IN HEIGHT.
 (2) THE OCCUPANCY IS SUBJECT TO 50 OR MORE OCCUPANTS
 ABOVE
 OR BELOW THE LEVEL OF EXIT DISCHARGE.
 (3) THE OCCUPANCY IS SUBJECT TO 300 OR MORE TOTAL
 OCCUPANTS.
 38.3.4.2 INITIATION. INITIATION OF THE REQUIRED FIRE
 ALARM SYSTEM
 SHALL BE BY ANY ONE OF THE FOLLOWING MEANS:
 (1) MANUAL MEANS IN ACCORDANCE WITH 9.6.2.1(1)
 (2) APPROVED AUTOMATIC FIRE DETECTION SYSTEM IN
 ACCORDANCE
 WITH 9.6.2.1(2) THAT PROVIDES PROTECTION THROUGHOUT THE
 BUILDING AND THE PROVISION OF 9.6.2.6 SHALL APPLY.
 (3) APPROVED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE
 WITH
 9.6.2.1(3) THAT PROVIDES PROTECTION THROUGHOUT THE
 BUILDING AND THE PROVISION OF 9.6.2.6 SHALL APPLY.
 38.3.4.3 OCCUPANT NOTIFICATION. DURING ALL TIMES THAT
 THE
 BUILDING IS OCCUPIED (SEE 7.2.1.1.3), THE REQUIRED FIRE
 ALARM
 SYSTEM, ONCE INITIATED, SHALL PERFORM ONE OF THE
 FOLLOWING
 FUNCTIONS:
 (1) IT SHALL ACTIVATE A GENERAL ALARM IN ACCORDANCE
 WITH 9.6.3.
 (2) A POSITIVE ALARM SEQUENCE IN ACCORDANCE WITH
 9.6.3.4
 SHALL BE PERMITTED.
 (5) PHYSICAL MEANS ARE PROVIDED TO PREVENT VEHICLES
 FROM BEING
 PARKED OR DRIVEN WITHIN 10 FT (3050 MM) OF THE
 OPENINGS.
 (6) THE OPENINGS ARE PROTECTED AS A SMOKE PARTITION IN
 ACCORDANCE
 WITH SECTION 8.4, WITH NO MINIMUM FIRE PROTECTION
 RATING REQUIRED.
  
  
 PLEASE REVIEW AND CORRECT
  
  
  
 9) LIFE SAFETY SHEETS - THERE ARE INDICATIONS THAT EXIT
 ACCESS CORRIDORS ON ANY FLOOR LEVEL ARE NOT PROTECTED
 BY 1 HOUR FIRE WALLS
  
 PER NFPA 101 -
  
 38.3.6 CORRIDORS.
 38.3.6.1* WHERE ACCESS TO EXITS IS PROVIDED BY
 CORRIDORS, SUCH
 CORRIDORS SHALL BE SEPARATED FROM USE AREAS BY FIRE
 BARRIERS IN
 ACCORDANCE WITH SECTION 8.3 HAVING A MINIMUM 1-HOUR
 FIRE
 RESISTANCE RATING, UNLESS ONE OF THE FOLLOWING
 CONDITIONS EXISTS:
 (1) *WHERE EXITS ARE AVAILABLE FROM AN OPEN FLOOR AREA
 (2) *WITHIN A SPACE OCCUPIED BY A SINGLE TENANT
 (3) WITHIN BUILDINGS PROTECTED THROUGHOUT BY AN
 APPROVED,
 SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE
 WITH
 9.7.1.1(1)
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE
 REFERNECES
  
  
  
 10) LIFE SAFETY SHEETS - IN REFERNCE TO # 9 ABOVE THE
 DOOR SCHEDULE DOES NOT INDICATED FIRE DOOR RATINGS IN
 APPLICABLE CORRIDORS.
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE
 REFERENCES.
  
  
  
 11) SHEET E 001- THERE IS AN INDICATION OF A GENERATOR
  
 THE GENERATOR INSTALLATION SHALL BE UNDER SEPARATE SHOP
 DRAWINGS AND COMPLY WITH NFPA 37 AND NFPA 110 IF
 SUPPORTING THE LIFE SAFETY SYSTEMS.
  
 PLEASE PROVIDE AN APPLICABLE NOTE OF COMPLIANCE.
  
  
  
 12) THERE ARE NUMEROUS INDICATION OF SMOKE BARRIERS AND
 SMOKE PARTITIONS, HOWEVER, THERE IS NO NARRATIVE
 COMPLYING WITH NFPA 1
  
 10.14.3.4.2 LIFE SAFETY NARRATIVE. A LIFE SAFETY
 NARRATIVE SHALL BE
 PROVIDED DESCRIBING THE FOLLOWING:
 (1) BUILDING OCCUPANCY, CONSTRUCTION TYPE, AND INTENDED
 USES AND EVENTS
 (2) BUILDING AREA AND POPULATION CAPACITY OF THE
 PROPOSED FACILITY
 (3) PRINCIPAL FIRE AND LIFE SAFETY FEATURES/STRATEGIES
 FOR THE BUILDING,
 INCLUDING THE FOLLOWING:
 (A) SPRINKLER PROTECTION
 (B) SMOKE CONTROL/PROTECTION
 (C) FIRE ALARM - VISUAL AND AUDIBLE
 (D) PA SYSTEM
 (E) EMERGENCY POWER AND LIGHTING
 (F) PROVISIONS FOR PATRONS WITH DISABILITIES
 (G) FIRE DEPARTMENT ACCESS
 (H) FIRE/EMERGENCY COMMAND CENTER
 (4) EXTERIOR CONSTRUCTION DESIGN PARAMETERS
 USED/APPLIED
  
 PLEASE PROVIDE
  
  
  
 13) SHEET A 003, A 104 & A 611 - THERE IS AN INDICATION
 OF AN ELEVATOR LOBBY ON THE 3RD AND 4TH FLOOR. THE
 HARDWARE SET FOR THESE LOBBY DOORS AND OTHER DOORS
 LEADDING TO AN EXIT COULD NOT BE FOUND TO ENSURE
 COMPLIANCE WITH THE BELOW CODE.
  
 7.4.1.6 ELEVATOR LANDING AND LOBBY EXIT ACCESS.
 7.4.1.6.1 EACH ELEVATOR LANDING AND LOBBY SHALL HAVE
 ACCESS TO AT
 LEAST ONE EXIT.
 7.4.1.6.2 THE ELEVATOR LANDING AND LOBBY EXIT ACCESS
 REQUIRED BY
 7.4.1.6.1 SHALL NOT REQUIRE THE USE OF A KEY, A TOOL,
 SPECIAL
 KNOWLEDGE, OR SPECIAL EFFORT, UNLESS PERMITTED BY
 7.4.1.6.3.
 7.4.1.6.3 DOORS SEPARATING THE ELEVATOR LOBBY FROM THE
 EXIT ACCESS
 REQUIRED BY 7.4.1.6.1 SHALL BE PERMITTED TO BE
 ELECTRONICALLY LOCKED
 IN ACCORDANCE WITH 7.2.1.6.3.
  
 PLEASE PROVIDE.
  
  
  
 14) SHEET 611 - THE HARDWARE SET IDENTIFICATION TABLE
 COULD NOT BE EASILY LOCATED OR FOUND.
  
 PLEASE CORRECT OR PROVIDE THE SHEET NUMBER FOR
 VERIFICATION PURPOSES.
  
  
  
 15) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 16) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2019-03-14 Cont ID  
Sent By gjohnson Date 2019-03-14 Time 17:49 Rev Time 0.00
Received By gjohnson Date 2019-03-14 Time 17:49 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2019-02-15 Cont ID  
Sent By gjohnson Date 2019-02-15 Time 09:57 Rev Time 0.00
Received By gjohnson Date 2019-02-15 Time 09:57 Sent To  
Notes
2019-02-15 09:58:09 
 3RD REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 FUEL GAS COMMENTS:IT APPEARS THAT THE GAS COMMENTS WERE
 NOT ADDRESSED NOT COMPLIED 3RD REQUEST
 1. PLEASE LIST THE SIZING TABLE USED IN SIZING SYSTEM.
 PER FBC FG TABLE 40204(1)-(37)
 2. SHT P-902 THERE IS A NOTE ON THE PLAN THAT STATES A
 SYSTEM PRESSURE OF 5PSI THE GAS ISOMETRIC SHOWS 0.5PSI
 SHT P-802 DETAILS #2+4 ALSO SHOW 5PSI ON ONE AND 0.5PSI
 ON THE OTHER PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
 3. SUBMIT A DETAIL SHOWING THE TYPE OF VENT, LOCATION,
 SIZE, TERMINATION POINT, HEIGHT ABOVE THE ROOF AND
 ANCHORING DETAILS OF THE GAS VENT(S) PER 2017 FBC-FUEL
 GAS SECS. 502 THRU 505 OR 2017 FBC-RES. SEC.G2426
 THROUGH G2439.
 4. SUBMIT MANUFACTURER'S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT AND
 REGULATORS TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54,
 NFPA 58, AND FBC-2017 FUEL GAS CODE SEC. 402.2, AND
 301.3 OR 2017 FBC-RES. SEC. G2404.3. GAS APPLIANCES
 SHALL BE LISTED AND LABELED. THE INSTALLATION MANUALS
 FOR ALL GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT
 THE TIME OF INSPECTION. FGC SEC.305.1, FBC-RES.
 SEC.G2408.1
 5. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC-FUEL
 GAS, SECS. 402.4.1, 402.4.2. OR 2017 FBC-RES SEC.
 G2413.4.1, G2413.4.2.
 6. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR
 EACH PIPE SIZE. WPB AMENDMENTS TO FBC SEC.107.2.1.
 7. SHT P-902 THE GAS ISOMETRIC SHOWS 3-1/" PIPE I DON?T
 THINK THAT THEY MAKE GAS PIPING IN THAT SIZE PLEASE
 SIZE THE SYSTEM PER THE SIZING TABLES IF THEY DO MAKE
 GAS PIPING IN 31/2 PLEASE PROVIDE MANUFACTURE
 SPECIFICATIONS. PER WPB AMEND TO FBC 107.2.1
 8. SHT P-802 DETAIL #2 SHOWS 1" TO THE WATER HEATERS
 THE GAS ISOMETRIC SHOWS 2-1/2" PLEASE CLARIFY. PER WPB
 AMEND TO FBC 107.2.1
 9. SHT P-802 DETAIL #4 SHOWS AN EMERGENCY GENERATOR THE
 ISOMETRIC DOES NOT SHOW A GENERATOR PLEASE CLARIFY. PER
 WPB AMEND TO FBC 107.2.1
  
 NEW COMMENT;
 1. PLEASE LABEL GAS APPLIANCES ON THE RISER DIAGRAM.
 PER WPB AMEND TO FBC 107.2.1
 2. PLEASE SHOW ALL REGULATORS, SHUT OFF VALVES AND DRIP
 LEGS AT EACH APPLIANCE. PER WPB AMEND TO FBC 107.2.1
  
  
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2018-12-20 Cont ID  
Sent By gjohnson Date 2018-12-20 Time 10:30 Rev Time 0.00
Received By gjohnson Date 2018-12-19 Time 17:00 Sent To  
Notes
2018-12-20 11:31:012ND REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 FUEL GAS COMMENTS: NOT COMPLIED 2ND REQUEST
 1. PLEASE LIST THE SIZING TABLE USED IN SIZING SYSTEM.
 PER FBC FG TABLE 40204(1)-(37)
 2. SHT P-902 THERE IS A NOTE ON THE PLAN THAT STATES A
 SYSTEM PRESSURE OF 5PSI THE GAS ISOMETRIC SHOWS 0.5PSI
 SHT P-802 DETAILS #2+4 ALSO SHOW 5PSI ON ONE AND 0.5PSI
 ON THE OTHER PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
 3. SUBMIT A DETAIL SHOWING THE TYPE OF VENT, LOCATION,
 SIZE, TERMINATION POINT, HEIGHT ABOVE THE ROOF AND
 ANCHORING DETAILS OF THE GAS VENT(S) PER 2017 FBC-FUEL
 GAS SECS. 502 THRU 505 OR 2017 FBC-RES. SEC.G2426
 THROUGH G2439.
 4. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT AND
 REGULATORS TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54,
 NFPA 58, AND FBC-2017 FUEL GAS CODE SEC. 402.2, AND
 301.3 OR 2017 FBC-RES. SEC. G2404.3. GAS APPLIANCES
 SHALL BE LISTED AND LABELED. THE INSTALLATION MANUALS
 FOR ALL GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT
 THE TIME OF INSPECTION. FGC SEC.305.1, FBC-RES.
 SEC.G2408.1
 5. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC-FUEL
 GAS, SECS. 402.4.1, 402.4.2. OR 2017 FBC-RES SEC.
 G2413.4.1, G2413.4.2.
 6. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR
 EACH PIPE SIZE. WPB AMENDMENTS TO FBC SEC.107.2.1.
 7. SHT P-902 THE GAS ISOMETRIC SHOWS 31/2? PIPE I DON?T
 THINK THAT THEY MAKE GAS PIPING IN THAT SIZE PLEASE
 SIZE THE SYSTEM PER THE SIZING TABLES IF THEY DO MAKE
 GAS PIPING IN 31/2 PLEASE PROVIDE MANUFACTURE
 SPECIFICATIONS. PER WPB AMEND TO FBC 107.2.1
 8. SHT P-802 DETAIL #2 SHOWS 1? TO THE WATER HEATERS
 THE GAS ISOMETRIC SHOWS 21/2? PLEASE CLARIFY. PER WPB
 AMEND TO FBC 107.2.1
 9. SHT P-802 DETAIL #4 SHOWS AN EMERGENCY GENERATOR THE
 ISOMETRIC DOES NOT SHOW A GENERATOR PLEASE CLARIFY. PER
 WPB AMEND TO FBC 107.2.1
  
 NEW COMMENT;
 1. PLEASE LABEL GAS APPLIANCES ON THE RISER DIAGRAM.
 PER WPB AMEND TO FBC 107.2.1
  
  
  
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2018-10-25 Cont ID  
Sent By gjohnson Date 2018-10-25 Time 12:14 Rev Time 0.00
Received By gjohnson Date 2018-10-19 Time 14:01 Sent To  
Notes
2018-10-25 12:14:471ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 FUEL GAS COMMENTS:
 1. PLEASE LIST THE SIZING TABLE USED IN SIZING SYSTEM.
 PER FBC FG TABLE 40204(1)-(37)
 2. SHT P-902 THERE IS A NOTE ON THE PLAN THAT STATES A
 SYSTEM PRESSURE OF 5PSI THE GAS ISOMETRIC SHOWS 0.5PSI
 SHT P-802 DETAILS #2+4 ALSO SHOW 5PSI ON ONE AND 0.5PSI
 ON THE OTHER PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
 3. SUBMIT A DETAIL SHOWING THE TYPE OF VENT, LOCATION,
 SIZE, TERMINATION POINT, HEIGHT ABOVE THE ROOF AND
 ANCHORING DETAILS OF THE GAS VENT(S) PER 2017 FBC-FUEL
 GAS SECS. 502 THRU 505 OR 2017 FBC-RES. SEC.G2426
 THROUGH G2439.
 4. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT AND
 REGULATORS TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54,
 NFPA 58, AND FBC-2017 FUEL GAS CODE SEC. 402.2, AND
 301.3 OR 2017 FBC-RES. SEC. G2404.3. GAS APPLIANCES
 SHALL BE LISTED AND LABELED. THE INSTALLATION MANUALS
 FOR ALL GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT
 THE TIME OF INSPECTION. FGC SEC.305.1, FBC-RES.
 SEC.G2408.1
 5. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC-FUEL
 GAS, SECS. 402.4.1, 402.4.2. OR 2017 FBC-RES SEC.
 G2413.4.1, G2413.4.2.
 6. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR
 EACH PIPE SIZE. WPB AMENDMENTS TO FBC SEC.107.2.1.
 7. SHT P-902 THE GAS ISOMETRIC SHOWS 31/2? PIPE I DON?T
 THINK THAT THEY MAKE GAS PIING IN THAT SIZE PLEASE SIZE
 THE SYSTEM PER THE SIZING TABLES IF THEY DO MAKE GAS
 PIPING IN 31/2 PLEASE PROVIDE MANUFACTURE
 SPECIFICATIONS. PER WPB AMEND TO FBC 107.2.1
 8. SHT P-802 DETAIL #2 SHOWS 1? TO THE WATER HEATERS
 THE GAS ISOMETRIC SHOWS 21/2? PLEASE CLARIFY. PER WPB
 AMEND TO FBC 107.2.1
 9. SHT P-802 DETAIL #4 SHOWS AN EMERGENCY GENERATOR THE
 ISOMETRIC DOES NOT SHOW A GENERATOR PLEASE CLARIFY. PER
 WPB AMEND TO FBC 107.2.1
  
  
  
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status F Date   Cont ID  
Sent By   Date 2019-03-15 Time   Rev Time 0.00
Received By lmarchan Date 2019-02-28 Time 13:32 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2019-02-15 Cont ID  
Sent By gjohnson Date 2019-02-15 Time 14:12 Rev Time 0.00
Received By gjohnson Date 2019-01-16 Time 08:25 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-12-27 Cont ID  
Sent By shill Date 2018-12-27 Time 12:53 Rev Time 0.00
Received By shill Date 2018-11-30 Time 12:50 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-11-25 Cont ID  
Sent By cpuell Date 2018-11-25 Time 11:07 Rev Time 0.00
Received By cpuell Date 2018-09-05 Time 10:12 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2019-01-28 Cont ID  
Sent By lmarchan Date 2019-01-28 Time 09:17 Rev Time 0.00
Received By lmarchan Date 2019-01-23 Time 08:58 Sent To  
Notes
2019-06-14 11:36:22IMPACT FEE TRACKING MU-2019-002339-0000
2019-01-28 09:17:57RECEIPT - MU2019-0128-277 $80,913.15
2019-01-23 08:58:281/23/19 IMPACT FEE REVIEW OFFICE NOTIFIED. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-11-09 Cont ID  
Sent By rmcdouga Date 2018-11-09 Time 16:42 Rev Time 0.00
Received By jwitmer Date 2018-11-09 Time 16:42 Sent To  
Notes
2018-11-09 16:48:30IMPACT FEES - DIGITAL SUBMITTALS
  
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2019-03-15 Cont ID  
Sent By ccole Date 2019-03-15 Time 13:09 Rev Time 0.00
Received By ccole Date 2019-03-15 Time 11:43 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2019-02-06 Cont ID  
Sent By ccole Date 2019-02-06 Time 17:24 Rev Time 0.00
Received By ccole Date 2019-02-06 Time 10:55 Sent To  
Notes
2019-02-06 17:38:403RD REVIEW FBC-2017 MECHANICAL
 PERMIT #18081039
 2/7/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
 GUIDELINES FOR DESIGN AND CONSTRUCTION OF HEALTH CARE
 FACILITIES
 ASHRAE 170-2008.
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) COMCHECK ENERGY COMPLIANCE RESUBMITTED REPORT:
  
 A) THE BTUH COOLING CAPACITIES FOR AHU- 1& 2 AND THE
 DOAS- 1 & 2 DO NOT MATCH THE CAPACITIES SHOWN IN TH
 SCHEDULE ON SHEET M-701.
 B) REFERENCE IS MADE TO IPLV RATINGS CH-1 & 2 THAT ARE
 NOT SHOWN IN THE SCHEDULES- SEE TABLE C403.2.3(7) FBC
 EC.
 C) COOLING AND HEATING CAPACITIES FOR FCU 1-7, 1-8, &
 1-9 ARE REVERSED.
 D) HEATING CAPACITIES FOR MANY OF THE FCU'S DO NOT
 MATCH THE CAPACITIES IN THE SCHEDULE.
  
 2) SHEET M-703: THE VENTILATION CALCULATIONS FOR (OR'S
 # 442, 443, 444, & 445), & (ROOMS 451,453, 457, 458)
 AND THE FOURTH FLOOR POST-OP AND PRE-OP ROOMS ARE NOT
 SHOWN IN THE SCHEDULE. AS PREVIOUSLY NOTED THE SCHEDULE
 IS NOT IN COMPLIANCE WITH TABLE 7-1 ASHRAE-170 WHICH
 REQUIRES MINIMUM OUTDOOR AIR CHANGES AND MINIMUM TOTAL
 SUIPPLY AIR CHANGES AND PRESSURE RELATIONSHIPS TO BE
 SHOWN FOR ALL ROOMS AND SPACES. ALSO IT IS NOT CLEAR
 HOW THE PRESSURE RELATIONSHIPS WILL BE MONITORED. WILL
 SENSORS BE INSTALLED?
  
 3) M-201: THE SUBMITTED SPECIFICATIONS FOR THE CUMMINGS
 EMERGENCY GENERATOR INDICATE THE UNIT IS A LEVEL 2
 SYSTEM , HOWEVER THE AMBULATORY SURGICAL CENTER
 REQUIRES A LEVEL 1 SYSTEM- SEE SECTION 451.3.13 FBC B
 AND SECTIONS 4.4.1 & NFPA 110. THE GENERATOR SHALL ALSO
 BE UL 2200 LISTED AND LABELED, AND IN COMPLIANCE WITH
 NFPA 37- SECTION 915.1 FBC M.
  
 4) M-201: COMMENT #5 FROM THE PREVIOUS REVIEW STILL
 EXISTS : THE REQUESTED MANUFACTURER'S SPECIFICATIONS
 FOR THE GENERATOR AND ASSOCIATED EQUIPMENT INCLUDING
 THE VENT PIPING WERE NOT SUBMITTED. THE EXHAUST FLUE
 TERMINATION REQUIRED CLEARANCE MEASUREMENTS NOT
 PROVIDED ON THE PLAN.
 A) PROVIDE AN EXHAUST FLUE DIAGRAM THAT INCLUDES THE
 TOTAL RUN LENGTH, AND INDICATE HOW THE PIPE WILL BE
 SUPPORTED.
 B) VERIFY THE EXHAUST SYSTEM INCLUDING SILENCER COMPLY
 WITH THE GENERATOR ENGINE'S MAX BACKPRESSURE- PLEASE
 PROVIDE A CALCULATION.
 C) CLARIFY HOW THE RADIATOR EXHAUST AT THE TOP OF THE
 GENERATOR WILL BE VENTED TO THE OUTDOORS.THE GENERATOR
 ROOM IS ONLY OPEN ON ONE SIDE AND MAY BE SUBJECT TO
 POSITIVE PRESSURE WHICH WOULD TRAP THE EXHAUST IN THE
 ROOM. PLEAS NOTE THAT SECTION 7.7.4.2 NFPA 110 REQUIRES
 THE RADIATOR DISCHARGE TO BE DUCTED OUTDOORS OR TO AN
 EXTERIOR OPENING BY A 2-HOUR FIRE RATED AIR TRANSFER
 SYSTEM.
 D) SHOW ALL REQUIRED VENT PIPING RUNS, AND TERMINATION
 LOCATIONS. INDICATE THE TYPE AND SIZE OF THE PIPING.
  
 5) A-001 & M-201: REFER TO SECTION 7.2.1.1: THE EPS
 (GENERATOR) ROOM SHALL BE SEPARATED FROM THE REST OF
 THE BUILDING BY 2-HR FIRE RESISTANCE RATED
 CONSTRUCTION. THE PLANS ARE INDICATING 1-HR FIRE RATED
 WALLS ENCLOSING THE ROOM. PLEASE NOTE THE FLOOR/CEILING
 ASSEMBLY ABOVE THE ROOM MUSTL ALSO BE 2-HR. FIRE-RATED
 - PLEASE CORRECT THE PLANS.
  
 6) M-201: REFER TO SECTIONS 7.7.1 & 7.7.7 NFPA 110 AND
 PROVIDE VERIFICATION FROM THE GENERATOR MANUFACTURER
 THAT THE VENTILATION SYSTEM, AS CURRENTLY DESIGNED,
 WILL LIMIT THE MAXIMUM AMBIENT AIR TEMPERATURE IN THE
 ENCLOSURE TO THE MAXIMUM AIR TEMNPERATURE REQUIRED BY
 THE MANUFACTURER.
  
 7) REFER TO SECTION 451.3.13.1 FBC B AND PROVIDE A
 NARRATIVE THAT VERIFIES THAT A TYPE 1 ESSENTIAL
 ELECTRICAL SYSTEM HAS BEEN PROVIDED FOR THE FACILITY AS
 DESCRIBED BY NFPA 99
  
 8) M-201 & M-703: THE ARE NO EXHAUST AIR FLOW CHANGES
 SHOWN IN THE SCHEDULE FOR THE FUTURE MRI ROOMS, HOWEVER
 EXHAUST IS SHOWN ON THE PLAN.
  
 9) M-201: PLEASE CLARIFY IF THE LOCATION OF THE
 CRYOGENIC EXHAUST DUCT TERMINATION IS LOCATED IN A
 VENTILATED SOFFIT, AND INDICATE THE TYPE AND SIZE OF
 EXHAUST DUCT MATERIAL- SECTIONS 510.9 FBC M.
  
 10) M-201: THE EXHAUST DUCT FROM THE MEDGAS ROOM SHALL
 BE ENCLOSED IN 2-HR FIRE-RATED CONSTRUCTION IN
 ACCORDANCE WITH SECTION 510.7.3 FBC M. A) PLEASE
 PROVIDE DETAILS AND PROTECTION FOR THE EF-4 OPENING
 FROM WIND PRESSURE AND WIND BORNE DEBRIS- SECTION
 301.15 FBC M. B) INDICTE THE TYPE OF DUCTWORK TO BE
 INSTALLED- SECTION 510.9 FBC M.
  
 11) M-201: IT APPEARS THAT THE EF-4 EXHAUST OUTLET IS
 LESS THAN THE 10' REQUIRED CLEARANCE DISTANCE TO THE
 DOOR OPENING- SECTION 501.3.1 (2) FBC M. A) THE GARAGE
 EXHAUST DUCT ALSO APPEARS TO BE WITHIN THE REQUIRED 3'
 CLEARANCE PER 501.3.1 (3).
  
 12) M-201: INDICATE HOW MAKEUP AIR IS BEING PROVIDED
 FOR THE MEDGAS ROOM EXHAUST, AND PROVIDE A SEQUENCE OF
 OPERATION FOR THE FAN- SEE SECTION 510.6.5 FBC M AND
 60.3.2.5.3 FFPC- 2017. A) CLARIFY HOW EF-4 WAS SIZED
 AND PROVIDE AN EXHAUST VENTILATION CALCULATION.
  
 13) M-201: RETURN AIR CANNOT BE TAKEN FROM THE MEP ROOM
 101- SECTION 601.5 (7) FBC M.
  
 14) M-201, 202, 203: PROVIDE DETAILS OR NOTES ON THE
 PLAN TO VERIFY COMPLIANCE WITH ONE OF THE THREE
 EXCEPTIONS FOR REQUIRED DUCT SMOKE DETECTORS LISTED
 UNDER SECTION 606.2.2: COMMON SUPPLY SYSTEMS.
 WHERE MULTIPLE AIR-HANDLING SYSTEMS SHARE COMMON SUPPLY
 WITH A COMBINED DESIGN CAPACITY GREATER THAN 2,000 CFM
 (0.9 M3/S), EACH SUPPLY AIR SYSTEM SHALL BE PROVIDED
 WITH SMOKE DETECTORS IN ACCORDANCE WITH SECTION
 606.2.1.
  
 EXCEPTION: INDIVIDUAL SMOKE DETECTORS SHALL NOT BE
 REQUIRED FOR EACH FAN-POWERED TERMINAL UNIT, PROVIDED
 THAT SUCH UNITS DO NOT HAVE AN INDIVIDUAL DESIGN
 CAPACITY GREATER THAN 2,000 CFM (0.9 M3/S) AND WILL BE
 SHUT DOWN BY ACTIVATION OF ONE OF THE FOLLOWING:
 1.SMOKE DETECTORS REQUIRED BY SECTIONS 606.2.1 AND
 606.2.3.
 2.AN APPROVED AREA SMOKE DETECTOR SYSTEM LOCATED IN THE
 RETURN AIR PLENUM SERVING SUCH UNITS.
 3.AN AREA SMOKE DETECTOR SYSTEM AS PRESCRIBED IN THE
 EXCEPTION TO SECTION 606.2.1.
  
 15) M-201 ENCLOSED GARAGE:
 A) SHOW THE LOCATIONS OF THE CO/NO2 SENSORS.
 B) PROVIDE AN EXHAUST VENTILATION CALCULATION TO VERIFY
 FAN SIZING- SECTION 404.2 FBC M.
 C) THE SPECS FOR THE SENSORS DO NOT INDICATE THE
 SENSORS ARE LISTED OR HAVE BEEN TESTED IN ACCORDANCE
 WITH ANY STANDARD- SECTION 304.1 FBC M. D) REFER TO
 SECTION 502.1.1:
 D) IT DOES NOT APPEAR THAT THE LOCATION OF THAT THE
 LOCATION OF THE GARAGE EXHAUST INLET (R3) IS LOCATED IN
 THE AREA OF THE HEAVIEST CONCENTRATION OF CONTAMINANTS.
 E) PROVIDE SUPPORT AND HANGING DETAILS FOR RF-4 AND
 DUCTWORK, AND SHOW THE CLEARANCE HEIGHTS FOR THE FAN
 AND DUCTWORK FROM THE FINISHED GARAGE FLOOR- SECTION
 304.6 FBC M.
 F) PLEASE LABEL R3 AND RF-4 USING THE "E" SYMBOL FOR
 EXHAUST- SECTION 107.2.1 WPB.
  
 16) REPEAT COMMENT #11 FROM THE 1ST REVIEW: M-204:
 PROVIDE A DUCT SMOKE DETECTOR IN THE SUPPLY SYSTEMS OF
 AHU- 1 & 2, AND DOAS- 1 & 2 PER SECTION 606.2.1 FBC M.
 A) PLEASE REFER TO SECTIONS 606.4 AND 606.4.1 FBC M AND
 PROVIDE FAN SHUTDOWN SEQUENCES. ( IN REPONSE TO THIIS
 COMMENT, THE ENGINEER INDICATES IN THE NARRATIVE THAT
 THE DETECTORS ARE ON ELECTRICAL PLAN SHEETS, HOWEVER
 THIS IS A MECHANICAL CODE REQUIRMENT AND THEY MUST BE
 SHOWN ON THE MECHANICAL PLANS FOR PLAN REVIEW
 COMPLIANCE, AND TO AVOID CONFLICTS IN THE FIELD).
  
 17) THE ENGINEER IS INDICATING IN THE COMMENT RESPONSE
 NARRATIVE THAT THE REQUESTED WIND LOAD ENGINEERING FOR
 THE ROOFTOP AND OTHER EXTERIOR MECHANICAL EQUIPMENT IS
 PROVIDED BY THE MANUFACTURER AND THE NOA'S. A) THE
 SUBMITTED NOA FOR THE DOAS IS MISSING THE INSTALLATION
 PAGES. B) NO ENGINEERING HAS BEEN PROVIDED BY THE
 MANUFACTURER'S OF THE AIR HANDLERS, THE CHILLERS, THE
 FANS, ROOFTOP DUCTWORK AND SUPPORTS ETC. PLEASE NOTE
 THAT SITE SPECIFIC ENGINEERING IS REQUIRED PER SECTION
 301.15 FBC M, AND 1609 FBC B.
  
 18) M-701 & M-703: AN ERV IS REQUIRED DUE TO THE FACT
 THAT EF-1 HAS AN EXHAUST RATE OF 7600 CFMS WHICH
 EXCEEDS THE 4597 CFM SUPPLY AIRFLOW RATE- SEE SECTION
 C403.2.7 FBC EC.
  
 19) M-201: INDICATE HOW ACCESS WILL BE PROVIDED FOR
 SERVICE AND REPLACEMENT OF FCU-1-14 & RF-1- SECTION
 306.1 FBC M
  
 20) M-202: MANY FCU'S ARE INSTALLED ABOVE HARD CEILINGS
 THAT REQUIRE ACCESS PANELS- SECTION 306.1 FBC M.
  
 21) REQUIRED SUBMITTALS TO APPROVED BY THE EOR: PLEASE
 NOTE THAT THE SUBMITTALS LISTED BELOW AND THE WIND LOAD
 ENGINEERING MAY BE DEFERRED BY REQUEST.
  
 A) FIRE SMOKE DAMPERS
 B) FIRE DAMPERS
 C) MOTORIZED DAMPERS
 D) DUCT SMOKE DETECTORS
 E) WATER HEATERS AND VENT PIPING
 F) O/A AND EXHAUST LOUVERS INCLUDING FL. PRODUCT
 APPROVALS AND/OR MIAMI-DADE NOA'S
 G) OR DUCTS & MRI DUCTS AND EXHAUST FANS
 H) PIPE AND DUCT INSULATIONS
  
 PLEASE NOTE THAT ADDITIONAL COMMENTS MAY OCCUR WHEN
 CORRECTED PLANS AND SPECIFICATIONS ARE RESUBMITTED.
 WHEN RESUBMITTING PLEASE PROVIDE A RESPONSE LETTER
 ADDRESSING EACH ITEM ALONG WITH THE CITY RE-SUBMITTAL
 FORM. ADDITIONALLY, PLEASE INSERT CORRECTED PLAN SHEETS
 INTO THE SETS, REMOVE THE PREVIOUSLY REVIEWED SHEETS
 AND MARK VOID ON THEM, AND KEEP THEM WITH THE
 SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-12-18 Cont ID  
Sent By ccole Date 2018-12-18 Time 15:19 Rev Time 0.00
Received By ccole Date 2018-12-17 Time 16:28 Sent To  
Notes
2018-12-18 15:19:532ND REVIEW FBC-2017 MECHANICAL
 PERMIT #18081039
 12/18/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
 GUIDELINES FOR DESIGN AND CONSTRUCTION OF HEALTH CARE
 FACILITIES
 ASHRAE 170-2008.
  
 PLAN REVIEW RESULTS: DENIED.
  
 AN INCOMPLETE RESPONSE NARRATIVE TO MECHANICAL COMMENTS
 THAT ENDED AT COMMENT #17 WAS UPLOADED WITH THE
 CORRECTED PLANS. MISSING FROM THE NARRATIVE ARE
 RESPONSES TO COMMENTS #18- 32.
  
 1) THE COMCHECK COMPLIANCE REPORT IS MISSING DATA FOR
 THE CHILLERS AND THE FAN COIL UNITS. PLEASE NOTE THAT
 THE 8.78 EER FOR CH-1 SHOWN IN THE EQUIPMENT SCHEDULE
 DOES NOT MEET COMPLIANCE WITH TABLE C403.2.3(7) FBC EC.
  
 2) SHEET M-701: PLEASE LIST THE COOLING AND HEATING
 CAPACITIES OF THE AHU 1 & 2, AND DOAS 1 & 2 IN THE
 EQUIPMENT SCHEDULES- SECTION C403.2.1 FBC EC.
  
 3) PLEASE VERIFY THAT COMMISSIONING OF THE MECHANICAL,
 AND ELECTRICAL POWER AND LIGHTING SYSTEMS WILL BE
 ACCOMPLISHED BY EITHER PROVIDING A NOTE OR AN OUTLINE
 ON THE PLAN.
  
 4) M-703: THE ASHRAE 170 VENTILATION RATE SCHEDULE IS
 INCOMPLETE. PLEASE REFER TO TABLE 7-1 ASHRAE 170-2008
 AND PROVIDE COMPLETE DESIGN PARAMETERS THAT INCLUDE
 PRESSURE RELATIONSHIPS TO ADJACENT AREAS, MINIMUM TOTAL
 ACH, EXHAUST AND RECIRCULATION AIR, RELATIVE HUMIDITY,
 AND TEMPERATURE. ALSO MISSING FROM THE SCHEDULE ARE THE
 DESIGN PARAMETERS FOR THE SOILED AND CLEAN HOLDING AND
 UTILITY ROOMS, AND THE HAZARDOUS STORAGE ROOM. INDICATE
 HOW THE PRESSURE RELATIONSHIPS WILL BE MONITORED. WILL
 SENSORS BE INSTALLED?
  
 5) M-201: THE REQUESTED MANUFACTURER'S SPECIFICATIONS
 FOR THE GENERATOR AND ASSOCIATED EQUIPMENT INCLUDING
 THE VENT PIPING WERE NOT SUBMITTED. THE EXHAUST FLUE
 TERMINATION REQUIRED CLEARANCE MEASUREMENTS NOT
 PROVIDED ON THE PLAN. A) PROVIDE AN EXHAUST FLUE
 DIAGRAM THAT INCLUDES THE TOTAL RUN LENGTH, AND
 INDICATE HOW THE PIPE WILL BE SUPPORTED. B) VERIFY THE
 EXHAUST SYSTEM INCLUDING SILENCER COMPLY WITH THE
 GENERATOR ENGINE'S MAX BACKPRESSURE- PLEASE PROVIDE A
 CALCULATION. C) CLARIFY HOW THE RADIATOR EXHAUST AT THE
 TOP OF THE GENERATOR WILL BE VENTED TO THE OUTDOORS.
 THE GENERATOR ROOM IS ONLY OPEN ON ONE SIDE AND MAY BE
 SUBJECT TO POSITIVE PRESSURE WHICH WOULD TRAP THE
 EXHAUST IN THE ROOM.
  
 6) M-201 & M-703: PROVIDE THE DESIGN PARAMETERS AND
 EXHAUST CALCULATIONS FOR THE MRI ROOMS ON THE PLANS AND
 IN THE VENTILATION SCHEDULE. B) PROVIDE A DETAIL
 SHOWING THE LOCATION OF THE CRYOGENIC EXHAUST PIPE
 TERMINATIONS WITH ALL REQUIRED CLEARANCE DISTANCES
 NOTED- SEE SECTION 501.3.1 FBC M.
  
 7) M-201: PLEASE REVISE THE PLANS TO SHOW THE REQUIRED
 MECHANICAL VENTILATION SYSTEM FOR THE MED GAS ROOM IN
 ACCORDANCE WITH SECTION 510.1 AND 510.2 FBC M AND 414.3
 FBC B. THE EXHAUST SYSTEM SHALL BE SIZED TO OPERATE
 CONTINUOUSLY AT A RATE OF 1.0 CFM PER SQ. FT.- SECTION
 60.3.2.5.3 FFPC-2017, AND THE DUCT SYSTEM SHALL EXTEND
 DIRECTLY TO THE EXTERIOR OF THE BUILDING. PLEASE NOTE
 THAT HAZARDOUS EXHAUST DUCTS THAT PENETRATE FIRE-RATED
 WALL ASSEMBLIES SHALL BE ENCLOSED IN FIRE-RESISTANT
 RATED CONSTRUCTION FROM THE POINT OF PENETRATION TO THE
 OUTLET TERMINAL- SECTION 510.7.3 FBC M.
  
 8) REPEAT COMMENT #10 FROM THE 1ST REVIEW: M-201, 202 &
 203: DUCT SMOKE DETECTORS ARE REQUIRED IN THE SUPPLY
 AIR SYSTEMS OF EACH FCU IN COMPLIANCE WITH SECTION
 606.2.2 FBC M. PLEASE PROVIDE A SYMBOL AT EACH FCU TO
 VERIFY COMPLIANCE.
  
 9) REPEAT COMMENT #11 FROM THE 1ST REVIEW: M-204:
 PROVIDE A DUCT SMOKE DETECTOR IN THE SUPPLY SYSTEMS OF
 AHU- 1 & 2, AND DOAS- 1 & 2 PER SECTION 606.2.1 FBC M.
 A) PLEASE REFER TO SECTIONS 606.4 AND 606.4.1 FBC M AND
 PROVIDE FAN SHUTDOWN SEQUENCES.
  
 10) REFER TO SECTIONS 406.5.2 AND 406.6.2 FBC B: THE
 EAST SECTION OF THE PARKING GARAGE THAT IS BOUNDED BY
 INTERIOR WALLS AND A CEILING IS CLASSIFIED AS ENCLOSED
 AND REQUIRES MECHANICAL VENTILATION IN COMPLIANCE WITH
 SECTIONS 404 AND 502.13 FBC M. PLEASE REVISE THE PLANS
 ACCORDINGLY.
  
 11) M-203: SECOND REQUEST FOR RETURN DUCT SIZES FOR
 FCU-5 & 10.
  
 12) THE DUCTLESS FAN COIL UNITS ARE NOT PERMITTED FOR
 INSTALLATION IN THE INTERIOR EXIT STAIRWAYS IN
 COMPLIANCE WITH SECTION 1023.5 & 1023.6 FBC B.
  
 PRINTED BELOW ARE COMMENTS 22-31 FROM THE 1ST REVIEW
 THAT HAVE NOT BEEN ADDRESSED IN THE RESPONSE NARRATIVE
 AND THE PLANS.
  
 22) M-205: PROVIDE WIND LOAD ENGINEERING FOR
 INSTALLATION OF ALL ROOFTOP MECHANICAL EQUIPMENT
 INCLUDING THE CHILLERS, DOAS?S UNITS, AHU- 1 & 2, EF-1
 &2, H-1 & 2, VENT FLUES, AND THE CHILLED WATER PIPE
 SUPPORTS- SECTION 301.15 FBC M.
  
 23) M-701: PROVIDE EFFICIENCY RATINGS FOR THE DOAS-1 &
 2 UNITS IN THE SCHEDULE- TABLE C403.2.3(1) FBC EC.
  
 24) M-701: THE EFFICIENCY RATING OF CH-1 AT 8.78 EER IS
 DEFICIENT ACCORDING TO TABLE C403.2.3(7) FBC EC.
  
 25) M-701: NO EFFICIENCY RATINGS HAVE BEEN PROVIDED FOR
 THE MRI CH-2- TABLE C403.2.3(7) FBC EC.
  
 26) M-701: ALTHOUGH VENTILATION CALCULATIONS HAVE NOT
 BEEN PROVIDED, IT APPEARS BY THE EXHAUST RATE OF EF-1
 THAT AN ERV WILL BE REQUIRED FOR THE SYSTEM- SEE
 SECTION C403.2.7 FBC EC.
  
 27) CLARIFY IF THE ELEVATOR HOISTWAYS WILL BE VENTED
 AND PROVIDE DETAILS.
  
 28) PROVIDE UL TESTED AND APPROVED FIRESTOPPING
 ASSEMBLIES FOR THE CHILLED WATER PIPING, CONDENSATE
 PIPING, AND DUCTWORK.
  
 29) INDICATE THE R-VALUE AND THICKNESS OF THE CHILLED
 WATER PIPING INSULATION IN THE BUILDING AND ABOVE THE
 ROOF- TABLE C403.2.10 FBC EC.
  
 30) REQUIRED SUBMITTALS TO APPROVED BY THE EOR:
  
 A) FIRE SMOKE DAMPERS
 B) FIRE DAMPERS
 C) MOTORIZED DAMPERS
 D) DUCT SMOKE DETECTORS
 E) GENERATOR
 F) PRE- MANUFACTURED ACCESS PANELS FOR AC UNITS AND
 DAMPERS
 G) WATER HEATERS AND VENT PIPING
 H) O/A AND EXHAUST LOUVERS INCLUDING FL. PRODUCT
 APPROVALS AND/OR MIAMI-DADE NOA'S
 I) OR DUCTS & DIFFUSERS, & MRI DUCTS AND EXHAUST FANS
 J) PIPE AND DUCT INSULATIONS
  
 31) REFER TO SECTION 451.1.1- 451.1.5 AND CLARIFY IF
 THE PROPOSED PLANS FOR THE AMBULATORY SURGICAL CENTER
 HAS BEEN REVIEWED AND APPROVED BY ACHA.
  
 PLEASE NOTE THAT ADDITIONAL COMMENTS MAY OCCUR WHEN
 CORRECTED PLANS AND SPECIFICATIONS ARE RESUBMITTED.
 WHEN RESUBMITTING PLEASE PROVIDE A RESPONSE LETTER
 ADDRESSING EACH ITEM ALONG WITH THE CITY RE-SUBMITTAL
 FORM. ADDITIONALLY, PLEASE INSERT CORRECTED PLAN SHEETS
 INTO THE SETS, REMOVE THE PREVIOUSLY REVIEWED SHEETS
 AND MARK VOID ON THEM, AND KEEP THEM WITH THE
 SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  
  
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-10-16 Cont ID  
Sent By ccole Date 2018-10-16 Time 14:48 Rev Time 0.00
Received By ccole Date 2018-10-16 Time 14:47 Sent To  
Notes
2018-10-16 18:09:11 
 1ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18081039
 10/16/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
 GUIDELINES FOR DESIGN AND CONSTRUCTION OF HEALTH CARE
 FACILITIES
 ASHRAE 170-2008.
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SUBMIT AN ENERGY COMPLIANCE REPORT FOR THE NEW
 BUILDING- SEE SECTIONS C101.2, C101.5.1 AND C401.2 FBC
 EC.
  
 2) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR ALL
 THE NEW SYSTEMS SHOWN ON SHEET IN ACCORDANCE WITH
 SECTION C403.2.1 FBC EC.
  
 3) COMMISSIONING OF THE MECHANICAL, SERVICE AND
 ELECTRICAL POWER AND LIGHTING SYSTEMS IS REQUIRED PER
 SECTIONS C408.1 AND C408.2 FBC-17 ENERGY CONSERVATION.
 PLEASE REVIEW:
  
 SYSTEM COMMISSIONING
 C408.1GENERAL.
 THIS SECTION COVERS THE COMMISSIONING OF THE BUILDING
 MECHANICAL SYSTEMS IN SECTION C403 AND ELECTRICAL POWER
 AND LIGHTING SYSTEMS IN SECTION C405.
 C408.2 MECHANICAL SYSTEMS AND SERVICE WATER-HEATING
 SYSTEMS COMMISSIONING AND COMPLETION REQUIREMENTS.
 PRIOR TO THE FINAL MECHANICAL AND PLUMBING INSPECTIONS,
 THE LICENSED DESIGN PROFESSIONAL, ELECTRICAL ENGINEER,
 MECHANICAL ENGINEER OR APPROVED AGENCY SHALL PROVIDE
 EVIDENCE OF MECHANICAL SYSTEMS COMMISSIONING AND
 COMPLETION IN ACCORDANCE WITH THE PROVISIONS OF THIS
 SECTION.
 CONSTRUCTION DOCUMENT NOTES SHALL CLEARLY INDICATE
 PROVISIONS FOR COMMISSIONING AND COMPLETION
 REQUIREMENTS IN ACCORDANCE WITH THIS SECTION AND ARE
 PERMITTED TO REFER TO SPECIFICATIONS FOR FURTHER
 REQUIREMENTS. COPIES OF ALL DOCUMENTATION SHALL BE
 GIVEN TO THE OWNER OR OWNER?S AUTHORIZED AGENT AND MADE
 AVAILABLE TO THE CODE OFFICIAL UPON REQUEST IN
 ACCORDANCE WITH SECTIONS C408.2.4 AND C408.2.5.
  
 PLEASE NOTE ISSUANCE OF THE CO FOR THE OCCUPANCY IS
 CONTINGENT ON RECEIPT OF A COPY OF THE COMMISSIONING
 REPORT AND RECEIPT OF A LETTER FROM THE OWNERSHIP TO
 VERIFY THEY HAVE RECEIVED A COPY.
  
 4) REFER TO TABLE 7-1 ASHRAE 170-2008 AND PROVIDE THE
 VENTILATION DESIGN PARAMETERS FOR ALL ROOMS AND SPACES
 DESIGNATED FOR MEDICAL USE INCLUDING THE MRI ROOMS
 (NOTE: SEE COMMENT #8).
  
 5) REFER TO TABLE 403.3.1.1 FBC M AND PROVIDE MINIMUM
 VENTILATION RATES FOR ALL ROOMS AND SPACES NOT
 DESIGNATED FOR MEDICAL SUCH AS ADMINISTRATIVE OFFICES,
 EMPLOYEE AREAS, RECEPTION/LOBBY ROOMS, TOILET AND
 LOCKER ROOMS ETC.
  
 6) SHEET M-201: PROVIDE AN ENLARGED DRAWING OF THE
 GENERATOR AND GENERATOR ROOM, AND SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE UNIT AND ALL ASSOCIATED
 EQUIPMENT- SECTION 915.1 FBC M. SHOW THE ENGINE EXHAUST
 VENT PIPE RUN AND TERMINATION LOCATION, SHOW THE
 LOCATION OF THE RADIATOR EXHAUST, AND SHOW HOW THE ROOM
 IS BEING VENTILATED AND HOW MAKEUP AIR IS BEING
 PROVIDED. PLEASE INCLUDE CLEARANCE DISTANCE
 MEASUREMENTS FOR THE EXHAUST TERMINATIONS. THE
 GENERATOR AND ALL ASSOCIATED SPECS SHALL BEAR THE
 APPROVAL STAMP BY THE EOR.
  
 7) M-201: PROVIDE EXHAUST VENTILATION CALCULATIONS FOR
 THE MRI 1 (RM 130-1) EMERGENCY EXHAUST SYSTEM (EF-3)
 AND CLARIFY WHY NO EMERGENCY SYSTEM IS BEING PROVIDED
 FOR MRI-1 (RM 132-1).
  
 8) M-201: CLARIFY HOW THE VENTILATION SYSTEMS AND
 CRYOGENIC EXHAUST SYSTEMS IN THE MRI ROOMS WERE
 CALCULATED AND DESIGNED. INDICATE THE TYPE OF DUCTWORK
 TO BE USED FOR THE SYSTEMS AND SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE MRI EQUIPMENT WITH APPROVAL
 STAMPS BY THE EOR. PLEASE NOTE THAT AIR FROM THE ROOMS
 MAY BE RESTRICTED PER MANUFACTURER'S SPECIFICATIONS.
  
 9) M-201: REFER TO TABLE 7-1 ASHRAE 170-2008 AND
 PROVIDE EXHAUST VENTILATION FOR THE MED GAS STORAGE
 ROOM. SEE ALSO SECTION 9.3.6.5.3 NFPA 99 AND ALL
 SUBSECTIONS FOR MECHANICAL VENTILATION SYSTEM DESIGN
 REQUIREMENTS. BASED ON THE CURRENT PLAN SUBMITTAL AN
 INDOOR STORAGE LOCATION IS ASSUMED. PLEASE NOTE THE
 FOLLOWING: A) FIRE DAMPERS ARE REQUIRED FOR THE
 LOUVERED OPENINGS SHOWN IN THE ROOM- SECTION 607.5.2
 FBC M. B) ALL EXHAUST SHALL DISCHARGE TO THE OUTDOORS-
 SECTION 501.3 FBC M.
  
 10) M-201, 202 & 203: DUCT SMOKE DETECTORS ARE REQUIRED
 IN THE SUPPLY AIR SYSTEMS OF EACH FCU IN COMPLIANCE
 WITH SECTION 606.2.2 FBC M. PLEASE PROVIDE A SYMBOL AT
 EACH FCU TO VERIFY COMPLIANCE.
  
 11) M-204: PROVIDE A DUCT SMOKE DETECTOR IN THE SUPPLY
 SYSTEMS OF AHU- 1 & 2 PER SECTION 606.2.1 FBC M. A)
 PLEASE REFER TO SECTIONS 606.4 AND 606.4.1 FBC M AND
 PROVIDE FAN SHUITDOWN SEQUENCES.
  
 12) M-201, 202, 203, & 204: INDICATE THE TYPE OF
 SHUTOFF DAMPERS TO BE PROVIDED FOR THE O/A DUCTS- SEE
 SECTION C403.2.4.3 FBC EC.
  
 13) PARKING GARAGE: THE PLANS DO NOT INDICATE WHETHER
 THE PARKING GARAGE IS AN OPEN OR ENCLOSED GARAGE- SEE
 SECTIONS 406.4, 406.5, AND 406.6 FBC B. FOR ENCLOSED
 GARAGES MECHANICAL VENTILATION IS REQUIRED PER SECTIONS
 404.1, 404.2, AND 404.1 FBC M. IF HOWEVER THE GARAGE IS
 CLASSIFIED AS AN "OPEN GARAGE", AND MEETS THE
 REQUIREMENTS OF SECTION 406.5.2 THEN MECHANICAL EXHAUST
 VENTILATION SHALL NOT BE REQUIRED.
  
 14) M-202: MISSING FIRE DAMPER FOR THE 36X24" RELIEF
 AIR OPENING AT THE HYDRO THERAPY ROOM- SECTION 607.5.2
 FBC M.
  
 15) M-202: INDICATE HOW ACCESS WILL BE PROVIDED TO THE
 FAN COIL UNITS LOCATED ABOVE GYPSUM CEILINGS INCLUDING
 FCU 2-1, 2-2, 2-3, 2-4, 2-5, 2-11, AND PU-1- SEE
 SECTION 306.1 FBC M.
  
 16) M-203: MAIN RETURN DUCT SIZES FOR FCU 3-05, 3-09, &
 3-10 NOT SHOWN , AND MANY MISSING O/A BRANCH DUCT
 SIZES.- PLEASE REVIEW THE LAYOUT AND CORRECT.
  
 17) M-404: PLEASE SEE SECTION 451.3.6.2 FBC B: THE VAV
 AND VRH SYSTEMS ARE NOT PERMITTED TO BE USED IN THE
 SURGICAL ROOMS AND THE RECOVERY ROOMS.
  
 18) M-404: MISSING FIRE DAMPERS FOR DUCTS PENETRATING
 FIRE-RATED WALLS TRASH/MAT MAN, SUB-STERILE/STERILIZER
 EQUIP, CORR/EQUIP STORAGE.
  
 19) M-404: THERE IS A VAV IN THE EQUIP STORAGE ROOM NOT
 LABELED.
  
 20) M-404: THE DUCTWORK TO BE USED IN THE OR'S AND
 RECOVERY ROOMS (POST OP) SHALL BE IN COMPLIANCE WITH
 FBC CODE SECTIONS LISTED BELOW. PLEASE REVIEW AND
 VERIFY COMPLIANCE BY SUBMITTING PRODUCT SPECIFICATIONS
 AITH APPROVAL STAMPS BY THE EOR.
  
 451.3.6.3
 FRIABLE DUCT LININGS EXPOSED TO AIR MOVEMENT SHALL NOT
 BE USED IN DUCTS, TERMINAL BOXES OR OTHER SYSTEMS
 SUPPLYING OPERATING ROOMS AND RECOVERY ROOMS, UNLESS
 TERMINAL FILTERS OF AT LEAST 90-PERCENT EFFICIENCY ARE
 INSTALLED DOWNSTREAM OF LININGS. FLEXIBLE DUCT WORK
 SHALL HAVE A CONTINUOUS METAL INNER LINER ENCASED BY
 INSULATING MATERIAL WITH AN OUTER VAPOR JACKET
 CONFORMING TO UL 181 UNLESS THE FLEXIBLE DUCT MEETS THE
 FOLLOWING CRITERIA:
  
 451.3.6.3.1
 THE DUCT CONFORMS TO UL CLASS 1 AIR DUCT, STANDARD 181
 WITH MINIMUM RATED AIR VELOCITY OF 4,000 FEET PER
 MINUTE, AND IS PRESSURE RATED FOR A MINIMUM OF 4-INCHES
 WATER GAGE POSITIVE PRESSURE AND 1-INCH WATER GAGE
 NEGATIVE PRESSURE.
  
 451.3.6.3.2
 THE INNER CORE OF THE DUCT IS CONSTRUCTED OF
 CHLORINATED POLYETHYLENE (CPE) MATERIAL ENCIRCLING A
 STEEL HELIX BONDED TO THE CPE.
  
 451.3.6.3.3
 THE DUCT HAS A FIRE-RETARDANT METALIZED VAPOR BARRIER
 THAT IS REINFORCED WITH CROSSHATCHED FIBERGLASS SCRIM
 HAVING A PERMANENCE OF NOT GREATER THAN 0.05 PERMS WHEN
 TESTED IN ACCORDANCE WITH ASTM E96 PROCEDURE A.
  
 451.3.6.3.4
 THE DUCT HAS PASSED AN IMPACT TEST SIMILAR TO THE UL181
 STANDARD, CONDUCTED BY A NATIONALLY RECOGNIZED TESTING
 LABORATORY (NRTL) EXCEPT IT SHALL USE A 25-POUND WEIGHT
 DROPPED FROM A HEIGHT OF 10 FEET. AS A RESULT OF THE
 TEST, THE INNER AND OUTER SURFACES OF THE SAMPLE SHALL
 NOT HAVE RUPTURED, BROKEN, TORN, RIPPED, COLLAPSED OR
 SEPARATED IN ORDER FOR THE DUCT TO PASS THE TEST. IN
 ADDITION, THE HELIX SHALL REBOUND TO A CROSS-SECTIONAL
 ELLIPTICAL AREA NOT LESS THAN 80 PERCENT OF THE
 ORIGINAL TEST SAMPLE DIAMETER. THE USE OF FLEXIBLE DUCT
 SHALL BE LIMITED TO FLEXIBLE AIR CONNECTOR
 APPLICATIONS.
  
 451.3.6.4
 FILTER HOUSING FRAME BLANK-OFF PANELS SHALL BE
 PERMANENTLY ATTACHED TO THE FRAME, CONSTRUCTED OF RIGID
 MATERIALS AND HAVE SEALING SURFACES EQUAL TO OR GREATER
 THAN THE FILTER MEDIA INSTALLED IN THE FILTER FRAME.
 ALL JOINTS BETWEEN THE BLANK-OFF PANELS, FILTER HOUSING
 FRAMES AND FILTER SUPPORT STRUCTURE SHALL BE CAULKED
 AIR TIGHT.
  
 451.3.6.5
 AIR DUCTS AND EXHAUST SYSTEMS SHALL NOT BE CONSTRUCTED
 OF FIBERGLASS DUCT BOARD.
  
 21) M-205: PROVIDE CONDENSATE DISPOSAL DRAWINGS AND
 DETAILS THAT SHOW THE TYPE AND SIZES OF PIPES, PIPE
 RUNS, PIPE SUPPORTS AND SPACINGS OF SUPPORT, AND PIPE
 DISCHARGE LOCATIONS- SECTION 307. PLEASE PROVIDE A
 RISER DRAWING.
  
 22) M-205: PROVIDE WIND LOAD ENGINEERING FOR
 INSTALLATION OF ALL ROOFTOP MECHANICAL EQUIPMENT
 INCLUDING THE CHILLERS, DOAS SUNITS, AHU- 1 & 2, EF-1
 &2, H-1 & 2, VENT FLUES, AND THE CHILLED WATER PIPE
 SUPPORTS- SECTION 301.15 FBC M.
  
 23) M-701: PROVIDE EFFICIENCY RATINGS FOR THE DOAS-1 &
 2 UNITS IN THE SCHEDULE- TABLE C403.2.3(1) FBC EC.
  
 24) M-701: THE EFFICENCY RATING OF CH-1 AT 8.78 EER IS
 DEFICIENT ACCORDING TO TABLE C403.2.3(7) FBC EC.
  
 25) M-701: NO EFFICENCY RATINGS HAVE BEEN PROVIDED FOR
 THE MRI CH-2- TABLE C403.2.3(7) FBC EC.
  
 26) M-701: ALTHOUGH VENTILATION CALCULATIONS HAVE NOT
 BEEN PROVIDED, IT APPEARS BY THE EXHAUST RATE OF EF-1
 THAT AN ERV WILL BE REQUIRED FOR THE SYSTEM- SEE
 SECTION C403.2.7 FBC EC.
  
 27) CLARIFY IF THE ELEVATOR HOISTWAYS WILL BE VENTED
 AND PROVIDE DETAILS.
  
 28) PROVIDE UL TSTED AND APPROVED FIRESTOPPING
 ASSEMBLIES FOR THE CHILLED WATER PIPING, CONDENSATE
 PIPING, AND DUCTWORK.
  
 29) INDICATE THE R-VALUE AND THICKNESS OF THE CHILLED
 WATER PIPING INSULATION IN THE BUILDING AND ABOVE THE
 ROOF- TABLE C403.2.10 FBC EC.
  
 30) REQUIRED SUBMITTALS TO APPROVED BY THE EOR:
  
 A) FIRE SMOKE DAMPERS
 B) FIRE DAMPERS
 C) MOTORIZED DAMPERS
 D) DUCT SMOKE DETECTORS
 E) GENERATOR
 F) PRE- MANUFACTURED ACCESS PANELS FOR AC UNITS AND
 DAMPERS
 G) WATER HEATERS AND VENT PIPING
 H) O/A AND EXHAUST LOUVERS INCLUDING FL. PRODUCT
 APPROVALS AND/OR MIAMI-DADE NOA'S
 I) OR DUCTS & MRI DUCTS AND EXHAUST FANS
 J) MRI
 K) PIPE AND DUCT INSULATIONS
  
 31) REFER TO SECTION 451.1.1- 451.1.5 AND CLARIFY IF
 THE PROPOSED PLANS FOR THE AMBULATORY SURGICAL CENTER
 HAS BEEN REVIEWED AND APPROVED BY ACHA.
  
 32) NO PERMIT APPLICATION FOR THE PROPOSED [PROJECT WAS
 UPLOADED INTO THE DOCUMENTS. PLEASE PROVIDE A COMPLETE
 APPLICATION THAT INCLUDES THE TOTAL VALUE OF THE
 PROJECT PER SECTION 109.3 WPB.
  
 PLEASE NOTE THAT ADDITIONAL COMMENTS MAY OCCUR WHEN
 CORRECTED PLANS AND SPECIFICATIONS ARE RESUBMITTED.
 WHEN RESUBMITTING PLEASE PROVIDE A RESPONSE LETTER
 ADDRESSING EACH ITEM ALONG WITH THE CITY RE-SUBMITTAL
 FORM. ADDITIONALLY, PLEASE INSERT CORRECTED PLAN SHEETS
 INTO THE SETS, REMOVE THE PREVIOUSLY REVIEWED SHEETS
 AND MARK VOID ON THEM, AND KEEP THEM WITH THE
 SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop MEDGAS MEDICAL GAS
Rev No 3 Status P Date 2019-02-14 Cont ID  
Sent By gjohnson Date 2019-02-14 Time 08:16 Rev Time 0.00
Received By gjohnson Date 2019-02-14 Time 08:16 Sent To  
Notes
***NONE***

Review Stop MEDGAS MEDICAL GAS
Rev No 2 Status F Date 2018-12-21 Cont ID  
Sent By gjohnson Date 2018-12-21 Time 07:32 Rev Time 0.00
Received By gjohnson Date 2018-12-21 Time 07:32 Sent To  
Notes
2018-12-21 07:32:582ND REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PREVIOUS MED GAS COMMENTS: 2ND REQUEST
 1. NOT COMPLIED: PROVIDE A SCHEDULE FOR ALL MED GAS
 EQUIPMENT. PER WPB AMEND TO FBC 107.2.1
 2. NOT COMPLIED: PROVIDE MANUFACTURE SPECIFICATIONS AND
 INSTALLATION GUIDES FOR ALL MED GAS EQUIPMENT INCLUDING
 THE TANKS AND VALVES. PER WPB AMEND TO FBC 107.2.1
 3. COMPLIED
 4. NOT COMPLIED: SHT. P-903 ON THE ISOMETRIC WHEN A
 PIPE IS CROSSING ANOTHER PIPE IT SHOULD HAVE A GAP AS
 THEY LOOK NOW A NUMBER OF PIPES APPEAR TO BE CONNECTED
 TOGETHER IT IS DIFFICULT TO DETERMINE WHICH SYSTEMS IS
 WHICH PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
 ISOMETRIC IS STILL TO CONGESTED TO READ PLEASE EXPAND.
 5. NOT COMPLIED: PLEASE PROVIDE DETAIL OF THE STRAPPING
 OF THE MED GAS STORAGE TANKS. PER WPB AMEND TO FBC
 107.2.1
 6. NOT COMPLIED: A SEPARATE PERMIT IS REQUIRED FOR MED
 GAS, ALONG WITH THE APPLICATION PROOF OF MED GAS
 CERTIFICATION FOR THE CONTRACTOR AND INSTALLER IS
 REQUIRED. PER FAC 61G4-15.031(1) (4) (A) (B) PLEASE
 PLACE NOTE ON PLAN.
 7. COMPLIED
 8. COMPLIED
 NEW COMMENTS:
 1. PLEASE PROVIDE DETAILS FOR THE MED GAS ZONE VALVES 5
 PORTS AND 2 PORTS. PER WPB AMEND TO FBC 107.2.1
 2. THE VACUUM EXHAUST PIPE ON SHEET P-802 DETAIL #4
 SHOWS THE PIPING AT 2" THE NOTE STATES IT 1-1/2" SHEET
 P-205 KEY NOTE #2 STATES IT AT STATES IT AT 3" PLEASE
 CHECK ALL NOTES DETAILS AND ISOMETRIC AND SIZE THE
 SYSTEM THE SAME PER THE MANUFACTURE SPECIFICATIONS. PER
 WPB AMEND TO FBC 107.2.1
 3. SHEET P-903 THE MED GAS ISOMETRIC IS SHOWING THE
 VACUUM EXHAUST PIPING LABELED AS MV PRESSURE RELIEF
 VENT IT SHALL BE LABELED TO MATCH THE REST OF THE PLAN
 AND THE TEXT IN THE CODE AS VACUUM EXHAUST PIPING. PER
 NFPA 99
 4. PLEASE STATE ON THE PLAN WHAT CATEGORY THE MED GAS
 SYSTEM IS DESIGNED TO BE. PER NFPA 99 CHAPTER 4
 5. THE LIFE SAFETY SHEETS SHOWS A MED GAS STORAGE
 SCHEDULE PLEASE INCLUDE THIS ON THE MED GAS PLAN
 SHEETS. PER WPB AMEND TO FBC 107.2.1
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop MEDGAS MEDICAL GAS
Rev No 1 Status F Date 2018-10-25 Cont ID  
Sent By gjohnson Date 2018-10-25 Time 11:04 Rev Time 0.00
Received By gjohnson Date 2018-10-24 Time 07:05 Sent To  
Notes
2018-10-25 11:05:041ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 MED GAS COMMENTS:
 1. PROVIDE A SCHEDULE FOR ALL MED GAS EQUIPMENT. PER
 WPB AMEND TO FBC 107.2.1
 2. PROVIDE MANUFACTURE SPECIFICATIONS AND INSTALLATION
 GUIDES FOR ALL MED GAS EQUIPMENT INCLUDING THE TANKS
 AND VALVES. PER WPB AMEND TO FBC 107.2.1
 3. SHT. P-801 DETAIL #4 SHOWS VACUUM EXHAUST
 DISCHARGING THROUGH THE EXTERIOR WALL IT SHALL
 DISCHARGE THROUGH ROOF. PER FBC PL 713.6 AND NFPA 99/
 5.1.3.7.7
 4. SHT. P-903 ON THE ISOMETRIC WHEN A PIPE IS CROSSING
 ANOTHER PIPE IT SHOULD HAVE A GAP AS THEY LOOK NOW A
 NUMBER OF PIPES APPEAR TO BE CONNECTED TOGETHER IT IS
 DIFFICULT TO DETERMINE WHICH SYSTEMS IS WHICH PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
 5. PLEASE PROVIDE DETAIL OF THE STRAPPING OF THE MED
 GAS STORAGE TANKS. PER WPB AMEND TO FBC 107.2.1
 6. A SEPARATE PERMIT IS REQUIRED FOR MED GAS, ALONG
 WITH THE APPLICATION PROOF OF MED GAS CERTIFICATION FOR
 THE CONTRACTOR AND INSTALLER IS REQUIRED. PER FAC
 61G4-15.031(1)(4)(A)(B)
 7. PROVIDE A RISER DIAGRAM FOR THE VACUUM EXHAUST AND
 THE PRESSURE RELIEF LINES FOR THE MED GAS SYSTEM. PER
 WPB AMEND TO FBC 107.2.1 AND NFPA 99/ 5.1.3.7.7,
 5.1.3.5.6
 8. CLEARLY SHOW THE TERMINATION POINTE OF THE VACUUM
 EXHAUST AND RELIEF PIPING ON THE ROOF PLAN. PER WPB
 AMEND TO FBC 107.2.1 AND NFPA 99/ 5.1.3.7.7, 5.1.3.5.6
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 5 Status P Date 2019-03-14 Cont ID  
Sent By gjohnson Date 2019-03-14 Time 17:49 Rev Time 0.00
Received By gjohnson Date 2019-03-14 Time 13:31 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status F Date 2019-02-15 Cont ID  
Sent By gjohnson Date 2019-02-15 Time 09:58 Rev Time 0.00
Received By gjohnson Date 2019-02-12 Time 08:22 Sent To  
Notes
2019-02-15 14:12:323RD REVIEW: 18081039
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. P-402 REMOVE FIXTURES FROM ISOMETRIC DRAWING
 THEY OBSTRUCT THE VIEW OF PIPING. PER WPB AMEND TO FBC
 107.2.1
 2. SHT. P-402 SHOW ALL VENTS REVENTS AND TEG END OF
 PIPING AS TO WHERE IT CONTINUES. PER WPB AMEND TO FBC
 107.2.1
 3. PROVIDE PIPING DETAIL AND MANUFACTURE SPECIFICATIONS
 FOR HYDRO THERAPY TUB. PER WPB AMEND TO FBC 107.2.1
 4. SHT P-403 PLEASE CLEARLY LABEL THE HOT, COLD AND
 RETURN RISERS ALSO SHOW DIRECTION OF FLOW ON THE HOT
 WATER RETURN SYSTEM. PER WPB AMEND TO FBC 107.2.1
 5. SHT.P-803 DETAIL #3 SHOW PIPE SIZE TYPE OF GAS AND
 FLOW DIRECTION. PER WPB AMEND TO FBC 107.2.1
 6. PREVIOUS COMMENT: ENLARGE STORM ISOMETRIC. PER WPB
 AMEND TO FBC 107.2.1
 7. P-403 PLEASE SHOW DIRECTION OF FLOW. PER WPB AMEND
 TO FBC 107.2.1
 8. PREVIOUS COMMENT: MANUFACTURE SPECIFICATIONS AND
 INSTILLATION GUIDES FOR ALL EQUIPMENT SHALL BE
 SUBMITTED AND APPROVED BY PLAN REVIEW PRIOR TO
 INSPECTIONS. PER WPB AMEND TO FBC 107.2.1
 9. SHT. P-904 DETAIL #6 LABEL PIPE WITH THE SQFT OR
 GPM. PER WPB AMEND TO FBC 107.2.1
 10. SHT. P-904 PLEASE LABEL ALL PIPE TERMINATION AND
 CONTINUATION POINTS ON THE ISOMETRIC. PER WPB AMEND TO
 FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop P PLUMBING
Rev No 3 Status F Date 2018-12-20 Cont ID  
Sent By gjohnson Date 2018-12-20 Time 10:17 Rev Time 0.00
Received By gjohnson Date 2018-12-19 Time 17:00 Sent To  
Notes
2018-12-20 10:17:532ND REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 I BELEAVE A MEETING IS GOING TO HELP EXPEDITE THE
 APPROVAL OF THIS PLAN PLEASE CONTACT ME TO SCHEDULE
 ONE.
  
 PROVISO: FROM FOUNDATION PERMIT SHALL COMPLY BEFORE
 PLUMBING PERMIT WILL BE ISSUED.
 1. PARTIALLY COMPLIED: PROVIDE A SANITARY ISOMETRIC
 DRAWING THAT SHOWS ONLY THE UNDERGROUND PIPING AND
 EXPAND IT LARGE ENOUGH SO THAT NONE OF THE PIPES
 OVERLAP AND SHOW SIZING, DFU LOAD AND THE PITCH THE
 PIPE WILL BE INSTALLED. PER WPB AMEND TO FBC
 107.3.5.1.3(13) PLEASE ENLARGE ISOMETRIC AND SHOW DFU
 LOAD, SLOPE OF PIPE. I SUGGEST SEPARATING THE FLOORS
 FOR CLARITY.
 2. PARTIALLY COMPLIED: PROVIDE A STORM DRAIN ISOMETRIC
 DRAWING THAT SHOWS ONLY THE UNDERGROUND PIPING AND
 EXPAND IT LARGE ENOUGH SO THAT NONE OF THE PIPES
 OVERLAP AND SHOW SIZING. . PER WPB AMEND TO FBC
 107.3.5.1.3(13) PLEASE ENLARGE ISOMETRIC DRAWING ON
 SHEET P-401 AND SHOW SQFT ON 8" + 10" PIPE, SLOPE OF
 PIPE.
  
  
 PREVIOUS PLUMBING COMMENTS:
 1. NOT COMPLIED: PLEASE PROVIDE A PLUMBING FIXTURE
 COUNT BREAK DOWN BASED ON OCCUPANT LOAD. RESPONSE
 LETTER STATED THEY ARE OM SHT P-001 I COULD NOT LOCATE
 THAT SHEET.
 2. NOT COMPLIED: SHT. A-500 PROVIDE MANUFACTURE
 SPECIFICATIONS FOR THE WATERPROOF MEMBRANE FOR SHOWER
 PAN. PER WPB AMEND TO FBC 107.2.1
 3. NOT COMPLIED: SHT. A-500 PROVIDE SHOWER SEAT DETAIL
 SHOWING HEIGHT. PER FBC ACC 610.3
 4. NOT COMPLIED: PROVIDE STRUCTURAL DETAIL FOR ELEVATOR
 SUMP PIT. PER WPB AMEND TO FBC 107.2.1
 5. NOT COMPLIED: PROVIDE MANUFACTURE SPECIFICATIONS FOR
 THE WATER SOFTENER, BOOSTER PUMP, AND ELEVATOR SUMP
 PUMP. PER WPB AMEND TO FBC 107.2.1 PLACE NOT ON PLAN TO
 BE ON JOBSITE FOR INSPECTION.
 6. COMPLIED
 7. COMPLIED
 8. COMPLIED
 9. PARTIALLY COMPLIED: SHT. P-901 PLEASE TAG THE PIPE
 ENDINGS TO IDENTIFY WHERE THEY CONNECT TO THE STACKS
 ALSO TAG THE BRANCHES ON THE SANITARY RISERS TO MATCH
 THE ENLARGE ISOMETRICS. PER WPB AMEND TO FBC 107.2.1
 PLEASE TAG THE ISOMETRICS TO CORRELATE TO THE TAGS ON
 THE RISERS.
 10. COMPLIED
 11. COMPLIED
 12. COMPLIED
 NEW PLUMBING COMMENTS:
 1. TRAP PRIMERS ARE REQUIRED ON ALL FLOOR DRAINS PLEASE
 PLACE NOT ON ISOMETRIC DRAWING. PER FBC PL 1002.4.1
 2. SHT P-802 DETAIL #9 SHOWS A DEEP SEAL TRAP ON A
 FLOOR DRAIN THIS IS NOT A COMPLIANT INSTILLATION PLEASE
 REMOVE. PER FBC PL 1002.4.2
 3. A HOT WATER RECIRCULATION SYSTEM IS REQUIRED ON HOT
 WATER SYSTEMS WITH A TOTAL DEVELOPED LENGTH OF GREATER
 THAN 50' FROM THE SOURCE OF HOT WATER. PER FBC PL 607.2
 4. PLEASE PROVIDE A COMPLETE ISOMETRIC DRAWING FOR THE
 WATER SYSTEM. PER WPB AMEND TO FBC 107.3.5.1.3(13)
 5. ON SHT P-904 YOU PROVIDE DETAILED ISOMETRICS FOR THE
 BATHROOMS PLEASE PROVIDE DETAILS FOR THE OTHER PLUMBING
 FIXTURE AND TAG THEM TO CORRELATE TO THE RISER TAGS.
 PER WPB AMEND TO FBC 107.3.5.1.3(13)
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2018-10-25 Cont ID  
Sent By gjohnson Date 2018-10-25 Time 08:32 Rev Time 0.00
Received By gjohnson Date 2018-10-25 Time 08:32 Sent To  
Notes
2018-10-25 08:48:291ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PROVISO: FROM FOUNDATION PERMIT SHALL COMPLY BEFORE
 PLUMBING PERMIT WILL BE ISSUED.
 1. PROVIDE A SANITARY ISOMETRIC DRAWING THAT SHOWS ONLY
 THE UNDERGROUND PIPING AND EXPAND IT LARGE ENOUGH SO
 THAT NONE OF THE PIPES OVERLAP AND SHOW SIZING, DFU
 LOAD AND THE PITCH THE PIPE WILL BE INSTALLED. PER WPB
 AMEND TO FBC 107.3.5.1.3(13)
 2. PROVIDE A STORM DRAIN ISOMETRIC DRAWING THAT SHOWS
 ONLY THE UNDERGROUND PIPING AND EXPAND IT LARGE ENOUGH
 SO THAT NONE OF THE PIPES OVERLAP AND SHOW SIZING. .
 PER WPB AMEND TO FBC 107.3.5.1.3(13)
 3. PROVIDE A SANITARY FLOOR PLAN. PER WPB AMEND TO FBC
 107.2.1
 4. PROVIDE A SEPARATE STORM DRAIN FLOOR PLAN. PER WPB
 AMEND TO FBC 107.2.1
 5. SHALL COMPLY WITH PROVISO PRIOR TO PLUMBING PERMIT
 BEING ISSUED.
  
 NEW PLUMBING COMMENTS:
 1. PLEASE PROVIDE A PLUMBING FIXTURE COUNT BREAK DOWN
 BASED ON OCCUPANT LOAD.
 2. SHT. A-500 PROVIDE MANUFACTURE SPECIFICATIONS FOR
 THE WATERPROOF MEMBRANE FOR SHOWER PAN. PER WPB AMEND
 TO FBC 107.2.1
 3. SHT. A-500 PROVIDE SHOWER SEAT DETAIL SHOWING
 HEIGHT. PER FBC ACC 610.3
 4. PROVIDE STRUCTURAL DETAIL FOR ELEVATOR SUMP PIT. PER
 WPB AMEND TO FBC 107.2.1
 5. PROVIDE MANUFACTURE SPECIFICATIONS FOR THE WATER
 SOFTENER, BOOSTER PUMP, AND ELEVATOR SUMP PUMP. PER WPB
 AMEND TO FBC 107.2.1
 6. SHT. P-205 THE SANITARY VENT TERMINATION THAT IS
 LOCATED ON THE EAST SIDE OF AHU2 APPEARS TO BE WITH THE
 10? CLEARANCES FROM AN AIR INTAKE PLEASE CLARIFY. FBC
 PL 903.5
 7. PLEASE PROVIDE A COLLECTION ISOMETRIC FOR THE
 SANITARY WITH ONLY THE UNDERGROUND PLUMBING. PER WPB
 AMEND TO FBC 107.3.5.1.3(13)
 8. SHT P-901 PLEASE ENLARGE THE ISOMETRICS; ALSO
 SEPARATE THE WATER FROM THE SANITARY AS THEY ARE NOW IT
 IS DIFFICULT TO DETERMINE CODE COMPLIANCE. PER WPB
 AMEND TO FBC 107.2.1
 9. SHT. P-901 PLEASE TAG THE PIPE ENDINGS TO IDENTIFY
 WHERE THEY CONNECT TO THE STACKS ALSO TAG THE BRANCHES
 ON THE SANITARY RISERS TO MATCH THE ENLARGE ISOMETRICS.
 PER WPB AMEND TO FBC 107.2.1
 10. PROVIDE A STORM DRAIN ISOMETRIC. PER WPB AMEND TO
 FBC 107.3.5.1.3(13)
 11. SHT M-301 KEY NOTE #10 STATES CONDENSATE
 DISCHARGING TO FLOOR DRAIN CONDENSATE SHALL NOT
 DISCHARGE TO THE SANITARY SYSTEM. PER WPB CODE OF
 ORDINANCES SEC. 90-126.
 12. PLEASE PROVIDE A CONDENSATE RISER DIAGRAM. PER WPB
 AMEND TO FBC 107.3.5.1.3(13)
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-10-25 Cont ID  
Sent By gjohnson Date 2018-10-25 Time 11:36 Rev Time 0.00
Received By gjohnson Date 2018-10-25 Time 11:36 Sent To  
Notes
2018-10-25 11:36:571ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PROVISO: FROM FOUNDATION PERMIT SHALL COMPLY BEFORE
 PLUMBING PERMIT WILL BE ISSUED.
 1. PROVIDE A SANITARY ISOMETRIC DRAWING THAT SHOWS ONLY
 THE UNDERGROUND PIPING AND EXPAND IT LARGE ENOUGH SO
 THAT NONE OF THE PIPES OVERLAP AND SHOW SIZING, DFU
 LOAD AND THE PITCH THE PIPE WILL BE INSTALLED. PER WPB
 AMEND TO FBC 107.3.5.1.3(13)
 2. PROVIDE A STORM DRAIN ISOMETRIC DRAWING THAT SHOWS
 ONLY THE UNDERGROUND PIPING AND EXPAND IT LARGE ENOUGH
 SO THAT NONE OF THE PIPES OVERLAP AND SHOW SIZING. .
 PER WPB AMEND TO FBC 107.3.5.1.3(13)
 3. PROVIDE A SANITARY FLOOR PLAN. PER WPB AMEND TO FBC
 107.2.1
 4. PROVIDE A SEPARATE STORM DRAIN FLOOR PLAN. PER WPB
 AMEND TO FBC 107.2.1
 5. SHALL COMPLY WITH PROVISO PRIOR TO PLUMBING PERMIT
 BEING ISSUED.
  
 NEW PLUMBING COMMENTS:
 1. PLEASE PROVIDE A PLUMBING FIXTURE COUNT BREAK DOWN
 BASED ON OCCUPANT LOAD.
 2. SHT. A-500 PROVIDE MANUFACTURE SPECIFICATIONS FOR
 THE WATERPROOF MEMBRANE FOR SHOWER PAN. PER WPB AMEND
 TO FBC 107.2.1
 3. SHT. A-500 PROVIDE SHOWER SEAT DETAIL SHOWING
 HEIGHT. PER FBC ACC 610.3
 4. PROVIDE STRUCTURAL DETAIL FOR ELEVATOR SUMP PIT. PER
 WPB AMEND TO FBC 107.2.1
 5. PROVIDE MANUFACTURE SPECIFICATIONS FOR THE WATER
 SOFTENER, BOOSTER PUMP, AND ELEVATOR SUMP PUMP. PER WPB
 AMEND TO FBC 107.2.1
 6. SHT. P-205 THE SANITARY VENT TERMINATION THAT IS
 LOCATED ON THE EAST SIDE OF AHU2 APPEARS TO BE WITH THE
 10? CLEARANCES FROM AN AIR INTAKE PLEASE CLARIFY. FBC
 PL 903.5
 7. PLEASE PROVIDE A COLLECTION ISOMETRIC FOR THE
 SANITARY WITH ONLY THE UNDERGROUND PLUMBING. PER WPB
 AMEND TO FBC 107.3.5.1.3(13)
 8. SHT P-901 PLEASE ENLARGE THE ISOMETRICS; ALSO
 SEPARATE THE WATER FROM THE SANITARY AS THEY ARE NOW IT
 IS DIFFICULT TO DETERMINE CODE COMPLIANCE. PER WPB
 AMEND TO FBC 107.2.1
 9. SHT. P-901 PLEASE TAG THE PIPE ENDINGS TO IDENTIFY
 WHERE THEY CONNECT TO THE STACKS ALSO TAG THE BRANCHES
 ON THE SANITARY RISERS TO MATCH THE ENLARGE ISOMETRICS.
 PER WPB AMEND TO FBC 107.2.1
 10. PROVIDE A STORM DRAIN ISOMETRIC. PER WPB AMEND TO
 FBC 107.3.5.1.3(13)
 11. SHT M-301 KEY NOTE #10 STATES CONDENSATE
 DISCHARGING TO FLOOR DRAIN CONDENSATE SHALL NOT
 DISCHARGE TO THE SANITARY SYSTEM. PER WPB CODE OF
 ORDINANCES SEC. 90-126.
 12. PLEASE PROVIDE A CONDENSATE RISER DIAGRAM. PER WPB
 AMEND TO FBC 107.3.5.1.3(13)
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2019-02-04 Cont ID  
Sent By dbattles Date 2019-02-04 Time 11:35 Rev Time 0.00
Received By dbattles Date 2019-02-04 Time 11:35 Sent To  
Notes
2019-02-04 11:39:23ROOFING SUBMITTAL AND PRODUCT APPROVALS DUE WITH SUB
 PERMIT.
 SEE ENERGY COMPLIANCE REPORT THAT STATES INSULATION TO
 BE R-25 AND ABOVE ROOF DECK ONLY.
 INSULATION ATTACHMENT WILL BE REQUIRED.
 ALSO, ENERGY COMPLIANCE REQUIRES HIGH ALBEDO ROOF FOR
 THE ENTIRE 16304 SQUARE FEET.
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2019-03-14 Cont ID  
Sent By dbattles Date 2019-03-14 Time 11:31 Rev Time 0.00
Received By dbattles Date 2019-03-14 Time 11:27 Sent To  
Notes
2019-03-14 11:32:45OK - ALL SHEETS FOR 4TH REVIEW.
 IF ANY ADDITIONAL SHEETS PROVIDED, THEY WILL NEED
 DIGITAL SIGNATURE.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2019-02-05 Cont ID  
Sent By dbattles Date 2019-02-05 Time 08:36 Rev Time 0.00
Received By dbattles Date 2019-02-02 Time 09:24 Sent To  
Notes
2019-02-05 08:38:19ALL SHEETS GOOD FOR 3RD REVIEW.
 ANY ADDITIONAL SHEETS WILL NEED DIGITAL SIGNATURE.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2018-12-14 Cont ID  
Sent By dbattles Date 2018-12-14 Time 09:52 Rev Time 0.00
Received By dbattles Date 2018-12-14 Time 09:10 Sent To  
Notes
2018-12-14 09:53:452ND REVIEW ALL SHEETS DIGITALLY SIGNED.
 ANY ADDITIONAL SHEETS WILL NEEDT TO BE CHECKED
2018-10-04 09:28:22ELECTRICAL SHEETS OK.

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status P Date 2018-11-14 Cont ID  
Sent By jwitmer Date 2018-11-14 Time 07:56 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2018-11-14 07:57:53FOR THRESHOLD DOCUMENTS PLEASE SEE FOUNDATION PERMIT
 18080583.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 2019-02-04 Cont ID  
Sent By elevesqu Date 2019-02-04 Time 14:38 Rev Time 0.00
Received By elevesqu Date 2019-02-04 Time 14:38 Sent To  
Notes
2019-02-04 14:38:39PROVISOS REMAINING FROM PREVIOUS SUBMITTAL APPROVAL:
  
 1. APPLICANT SHALL CHECK CONDITION OF EXISTING TREE
 GRATES OF OLIVE AVENUE AND REPAIR OR ADJUST IF
 NECESSARY.
 2. LIGHT FIXTURE AND POLE DETAILS TO BE INCLUDED IN
 DRAWINGS WITHIN 60 DAYS.
 3. FIRST PARKING SPACE IN PARKING GARAGE FROM PALM
 BEACH LAKES BOULEVARD ENTRANCE SHALL BE REMOVED.
 4. APPLICANT SHALL REMAIN IN CONTACT WITH SYBILLE
 WELTER FOR ART IN PUBLIC PLACES REQUIREMENT.
 [email protected]
 5. THE FUTURE LEVEL TO THE PARKING IS NOT INCLUDED WITH
 THIS SITE PLAN APPROVAL. A MINOR APPROVAL WOULD BE
 NEEDED IF FUTURE LEVELS ARE TO BE ADDED.
 6. UTILITY BOXES, POLES, FIRE DEPARTMENT CONNECTIONS,
 AND OTHER UTILITIES ARE TO BE LOCATED AS TO NOT BLOCK
 PEDESTRIAN TRAVEL AND PROPERLY SCREENED.
 7. APPLICANT SHALL WORK WITH UTILITY COMPANIES TO
 RELOCATE POLES THAT ARE BLOCKING PEDESTRIAN AND ADA
 ACCESS ALONG SIDEWALKS.
 8. PHOTOMETRICS INCLUDING EXISTING LIGHT POLES SHALL BE
 INCLUDED IN PLANS WITHIN 60 DAYS.
 9. A LANDSCAPE PERMIT SHALL BE SUBMITTED WITHIN 60
 DAYS.
  
 LIZ LEVESQUE, URBAN DESIGN PLANNER
 [email protected]
 561 822 1426
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2018-12-27 Cont ID  
Sent By elevesqu Date 2018-12-27 Time 09:46 Rev Time 0.00
Received By elevesqu Date 2018-12-27 Time 08:26 Sent To  
Notes
2018-12-27 09:45:41PROVISO:
  
 1. APPLICANT SHALL CHECK CONDITION OF EXISTING TREE
 GRATES OF OLIVE AVENUE AND REPAIR OR ADJUST IF
 NECESSARY.
 2. LIGHT FIXTURE AND POLE DETAILS TO BE INCLUDED IN
 DRAWINGS WITHIN 60 DAYS.
 3. FIRST PARKING SPACE IN PARKING GARAGE FROM PALM
 BEACH LAKES BOULEVARD ENTRANCE SHALL BE REMOVED.
 4. APPLICANT SHALL REMAIN IN CONTACT WITH SYBILLE
 WELTER FOR ART IN PUBLIC PLACES REQUIREMENT.
 [email protected]
 5. THE FUTURE LEVEL TO THE PARKING IS NOT INCLUDED WITH
 THIS SITE PLAN APPROVAL. A MINOR APPROVAL WOULD BE
 NEEDED IF FUTURE LEVELS ARE TO BE ADDED.
 6. UTILITY BOXES, POLES, FIRE DEPARTMENT CONNECTIONS,
 AND OTHER UTILITIES ARE TO BE LOCATED AS TO NOT BLOCK
 PEDESTRIAN TRAVEL AND PROPERLY SCREENED.
 7. APPLICANT SHALL WORK WITH UTILITY COMPANIES TO
 RELOCATE POLES THAT ARE BLOCKING PEDESTRIAN AND ADA
 ACCESS ALONG SIDEWALKS.
 8. PHOTOMETRICS INCLUDING EXISTING LIGHT POLES SHALL BE
 INCLUDED IN PLANS WITHIN 60 DAYS.
 9. A LANDSCAPE PERMIT SHALL BE SUBMITTED WITHIN 60
 DAYS.
  
 LIZ LEVESQUE, URBAN DESIGN PLANNER
 [email protected]
 561 822 1426
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 2018-11-06 Cont ID  
Sent By aaponte Date 2018-11-06 Time 14:28 Rev Time 0.00
Received By elevesqu Date 2018-11-06 Time 14:15 Sent To  
Notes
2018-11-06 14:28:561. PLEASE CHANGE/ADD THE FOLLOWING TO THE SITE PLAN,
 SHEET AS101:
 A. REPLACE THE ROOF PLAN WITH THE 1ST FLOOR PLAN.
 B. SHOW SIDEWALK AND PATHWAY DIMENSIONS.
 C. ENSURE THAT INDICATED TREES MATCH LANDSCAPE PLAN.
 D. SHOW THE PROPERTY LINES.
 E. INDICATE BUILDING SETBACK DIMENSIONS ON THE SITE
 PLAN.
 F. SHOW LOCATION OF THE PARKING GARAGE ENTRANCE WIDTH.
 A CONDITION OF APPROVAL FOR THE PROJECT REQUIRED THAT
 THE PARKING GARAGE ENTRANCE BE REDUCED TO 20 FEET.
 G. INCLUDE THE UPDATED SITE PROJECT DATA AND ZONING
 DATA, IN THE FORMAT THAT WAS ON THE APPROVED COVER
 SHEET A.0.0 PREPARED BY ALFONSO HERNANDEZ ARCHITECT
 LLC.
 H. INCLUDE REQUIRED AND PROPOSED BICYCLE PARKING DATA
 WITH THE PARKING DATA. THE REQUIRED BICYCLE PARKING FOR
 THE PROJECT IS AS FOLLOWS:
 I. SECURE BIKE RACKS AND/OR STORAGE AT A RATIO OF ONE
 BICYCLE PARKING SPACE PER EVERY 15 REQUIRED PARKING
 SPACES (INTERNAL TO BUILDING)
 II. PUBLIC BICYCLE PARKING AT A RATE OF ONE SPACE PER
 EVERY 100 FEET OF STREET FRONTAGE.
 2. PLEASE MARK THE FLOOR PLANS WITH ELEVATIONS FOR
 UNDERSTANDING OF ELEVATION CHANGES BETWEEN PARKING
 GARAGE AND OFFICE.
 3. REQUIRED PARKING IS BASED ON NET INTERIOR AREA,
 DEFINED AS: THE TOTAL FLOOR AREA, LESS AREAS DEDICATED
 TO PUBLIC LOBBIES AND CORRIDORS, EXTERIOR WALL
 ASSEMBLIES, STAIRWELLS, ELEVATOR SHAFTS, MECHANICAL,
 ELECTRICAL AND TRASH ROOMS. PLEASE PROVIDE PARKING
 CALCULATIONS BASED ON THIS DEFINITION.
 4. PLEASE INCLUDE A HARDSCAPE PLAN THAT INCLUDES
 BICYCLE RACKS, BOLLARDS, PAVERS, TREE GRATES, STREET
 LIGHTS, ETC. THE CITY-APPROVED BICYCLE RACK DETAIL CAN
 BE REQUESTED FROM CITY STAFF. PLEASE NOTE, THE BICYCLE
 RACK ON "L2&L2 PARKING", SHEET A2.2 IS NOT AN
 ACCEPTABLE RACK TYPE.
 5. PLEASE INCLUDE SITE PHOTOMETRIC PLANS WITH
 RESUBMITTAL.
 6. PLEASE INCLUDE AN UPDATED PLAN (SHEET A0.2 OF SITE
 PLAN APPROVAL SET) THAT SHOWS THE NEW BREAKDOWN OF
 F.A.R. WITH MODIFICATIONS TO THE FLOOR PLAN SINCE SITE
 PLAN APPROVAL.
 7. PLEASE ENCLOSE THE CRAWL SPACE OR USE A DIFFERENT
 FENCE THAN THE PROPOSED CHAIN LINK FENCE TO ENCLOSE THE
 VISIBLE NON-ACTIVE USE.
 8. PLEASE ADD SCORING LINES OR OTHER FENESTRATION TO
 WEST ELEVATION TO REDUCE AMOUNT OF EXPOSED BLANK WALL
 THAT WILL BE VISIBLE BEYOND THE ADJACENT ONE-STORY
 STRUCTURE.
 9. SOME BUILDING ARTICULATION WAS LOST ALONG THE TOP OF
 THE NORTH ELEVATION WITH THE REMOVAL OF THE EXPOSED
 PARKING DECK. PLEASE INCLUDE SOME ARTICULATION ALONG
 THIS FA?ADE.
 10. PLEASE ADD SCORING LINES OR FENESTRATION ALONG 6'3"
 TALL BLANK WALL ALONG THE NORTH FA?ADE (NEXT TO
 PROPOSED CHAIN LINK FENCE).
 11. APPLICANT SHALL SUBMIT A SEPARATE LANDSCAPE PERMIT.
 12. PLEASE INCLUDE CIVIL PLANS WITH RESUBMITTAL.
 13. PLEASE INCLUDE DIMENSIONS OF REGULAR AND ADA
 PARKING SPACES.
 14. PLEASE INCLUDE STRIPING DETAIL FOR PARKING SPACES,
 MEETING THE REQUIREMENTS OF SECTION 94-485 GENERAL
 PROVISIONS.
 15. PLEASE SHOW REQUIRED 1 FOOT EXTRA SPACE IN BETWEEN
 SOLID WALLS/RAMPS AND PARKING SPACE.
 16. PLEASE LABEL THE PARKING RAMPS "TO FLOOR 2.3" OR
 "TO FLOOR 1.6" TO CLARIFY RAMP LOCATIONS.
 17. PLEASE CLARIFY IF STRIPED PARKING SPACE ON FIRST
 FLOOR IS INTENDED TO BE A BACK UP SPACE AS IT IS AT THE
 TERMINUS OF A PARKING ROW. PLEASE INCLUDE BACK UP TURN
 RADIUS ON PLAN.
 18. PLEASE REMOVE THE FIRST PARKING SPACE AT THE
 NORTHERN ENTRANCE TO THE PARKING GARAGE FOR QUEUING AND
 VISIBILITY PURPOSES.
 19. PLEASE PROVIDE ADDITIONAL SCORING OR ARCHITECTURAL
 TREATMENT ALONG THE SOUTH EXTERIOR ELEVATION
 (SPECIFICALLY ALONG THE PARKING GARAGE).
 20. PLEASE SUBMIT A PLAN THAT SHOWS THE TREATMENT OF
 THE INTERIOR PORTION OF THE GARAGE ENTRY.
 21. THE SECOND FLOOR PLAN AND LEVEL 1.6 ON THE SPLIT
 LEVEL PLANS DO NOT APPEARS TO MATCH (BICYCLE PARKING
 DOES NOT ALIGN). PLEASE REVISE ACCORDINGLY.
 22. PLEASE INCLUDE STEPS OR A PATHWAY FROM THE
 ON-STREET PARKING TO THE PORTE COCHERE AREA.
 PEDESTRIANS HAVE TO NAVIGATE TO OTHER ENDS OF THE
 SIDEWALK TO REACH THE PATHWAY CONNECTIONS TO THE
 BUILDING AND WILL CUT THROUGH/DAMAGE LANDSCAPING.
 23. PLEASE CLARIFY IF SOUTHERN GARAGE EXIT IS INTENDED
 TO BE RIGHT-TURN OUT ONLY GOING INTO THE BI-DIRECTIONAL
 ALLEYWAY.
 24. THE PROPOSED TRANSFORMER PAD SHALL NEED TO BE
 PROPERLY SCREENED PER SECTION 94-315. PLEASE CONSIDER
 AN ALTERNATIVE LOCATION FOR THE TRANSFORMER TO NOT BE
 IN ADJACENT TO THE PUBLIC ROW AND SIDEWALK.
 25. PLEASE INCLUDE THE BICYCLE RACK LOCATION ON THE
 NORTH ELEVATION.
 26. CONSIDER THE REMOVAL OF THE SCREENING PANEL ALONG
 THE EXTERIOR CORRIDOR FROM THE PARKING GARAGE TO THE
 BUILDING (AREAS NOT PART OF THE PARKING GARAGE) TO
 CREATE AN OPEN AIR CORRIDOR.
 27. PLEASE CONTACT SYBILLE WELTER [email protected] 561
 822 1521 FOR ART IN PUBLIC PLACES REQUIREMENT.
  
  
 CONTACT LIZ LEVESQUE, URBAN DESIGN PLANNER WITH ANY
 QUESTIONS
 561 822 1426
 [email protected]
  