Plan Review Details - Permit 18081036
Plan Review Stops For Permit 18081036
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-12-11 Cont ID  
Sent By fgiaquin Date 2018-12-11 Time 06:06 Rev Time 0.00
Received By fgiaquin Date 2018-12-11 Time 05:21 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-10-24 Cont ID  
Sent By fgiaquin Date 2018-10-24 Time 05:37 Rev Time 0.00
Received By fgiaquin Date 2018-10-24 Time 05:21 Sent To M
Notes
2018-10-24 05:40:331. SATISFY NOTES FROM FIRE DEPARTMENT.
  
 2. 120V DEDICATED CIRCUIT TO FACP MUST BE INSTALLED BY
 A LICENSED ELECTRICIAN. A NOTE INDICATING THE
 ELECTRICIAN ON-SITE FOR THE REMODEL, REFERENCING THEIR
 PERMIT NUMBER WILL SUFFICE. F.S. 489.505, FBC 105.1,
 FBC 107.2.1

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-09-20 Cont ID  
Sent By fgiaquin Date 2018-09-20 Time 05:23 Rev Time 0.00
Received By fgiaquin Date 2018-09-20 Time 05:15 Sent To M
Notes
2018-09-20 05:15:47FAIL- SEE NOTES FROM FIRE DEPARTMENT

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2018-12-10 Cont ID  
Sent By sathomas Date 2018-12-10 Time 00:00 Rev Time 0.00
Received By   Date 2018-12-10 Time 00:00 Sent To E
Notes
2018-12-10 08:49:02PROVISO:
 24 HOUR BATTERY TEST IS REQUIRED.
  
 S. THOMAS
 561-804-4728

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date   Cont ID  
Sent By sathomas Date 2018-10-22 Time 00:00 Rev Time 0.00
Received By   Date 2018-10-22 Time 00:00 Sent To E
Notes
2018-10-22 08:57:01PER NFPA 101, CHAPTER 7 EXISTING OCCUPANCY
  
 37.1.2.2 SUBCLASSIFICATION OF OCCUPANCY.
 37.1.2.2.1 MERCANTILE OCCUPANCIES SHALL BE
 SUBCLASSIFIED AS
 FOLLOWS:
 (1) CLASS A, ALL MERCANTILE OCCUPANCIES HAVING AN
 AGGREGATE
 GROSS AREA OF MORE THAN 30,000 FT2 (2800 M) OR
 OCCUPYING
 MORE THAN THREE STORIES FOR SALES PURPOSES
  
 37.1.3 MULTIPLE OCCUPANCIES.
 37.1.3.1 GENERAL.
 37.1.3.1.1 ALL MULTIPLE OCCUPANCIES SHALL BE IN
 ACCORDANCE WITH
 6.1.14 AND 37.1.3.
 37.1.3.1.2 WHERE THERE ARE DIFFERENCES IN THE SPECIFIC
 REQUIREMENTS
 IN THIS CHAPTER AND PROVISIONS FOR MIXED OCCUPANCIES OR
 SEPARATED
 OCCUPANCIES AS SPECIFIED IN 6.1.14.3 AND 6.1.14.4, THE
 REQUIREMENTS OF THIS CHAPTER SHALL APPLY.
  
 37.3.4 DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS.
 37.3.4.1 GENERAL. CLASS A MERCANTILE OCCUPANCIES SHALL
 BE
 PROVIDED WITH A FIRE ALARM SYSTEM IN ACCORDANCE WITH
 SECTION 9.6.
  
 NFPA 101, CHAPTER 6, OCCUPANCY CLASSIFICATION
  
 6.1.14.2 DEFINITIONS.
 6.1.14.2.1 MULTIPLE OCCUPANCY. A BUILDING OR STRUCTURE
 IN WHICH TWO
 OR MORE CLASSES OF OCCUPANCY EXIST.
 6.1.14.2.2 MIXED OCCUPANCY. A MULTIPLE OCCUPANCY WHERE
 THE
 OCCUPANCIES ARE INTERMINGLED.
 6.1.14.2.3 SEPARATED OCCUPANCY. A MULTIPLE OCCUPANCY
 WHERE THE
 OCCUPANCIES ARE SEPARATED BY FIRE RESISTANCE.RATED
 ASSEMBLIES.
 6.1.14.3 MIXED OCCUPANCIES.
 6.1.14.3.1 EACH PORTION OF THE BUILDING SHALL BE
 CLASSIFIED AS TO ITS USE IN
 ACCORDANCE WITH SECTION 6.1.
 6.1.14.3.2* THE BUILDING SHALL COMPLY WITH THE MOST
 RESTRICTIVE
 REQUIREMENTS OF THE OCCUPANCIES INVOLVED, UNLESS
 SEPARATE SAFEGUARDS
 ARE APPROVED.
  
 6.1.14.4 SEPARATED OCCUPANCIES. (SEE ALSO 6.1.14.1.2.)
 6.1.14.4.1 WHERE SEPARATED OCCUPANCIES ARE PROVIDED,
 EACH PART OF THE
 BUILDING COMPRISING A DISTINCT OCCUPANCY, AS DESCRIBED
 IN THIS CHAPTER,
 SHALL BE COMPLETELY SEPARATED FROM OTHER OCCUPANCIES BY
 FIRE-RESISTIVE
 ASSEMBLIES, AS SPECIFIED IN 6.1.14.4.2, 6.1.14.4.3,
 TABLE 6.1.14.4.1(A),
 AND TABLE 6.1.14.4.1(B), UNLESS SEPARATION IS PROVIDED
 BY APPROVED
 EXISTING SEPARATIONS OR AS OTHERWISE PERMITTED BY
 6.1.14.4.6.
  
 SHOULD YOU CHOOSE TO BE A SEPARATED OCCUPANCY, YOUR
 OCCUPANCY SHALL BE THE SEPARATION REQUIRMENTS WHICH IS
 2 HOURS ACCORDING TO THE TABLE.
 PLEASE PROVIDE SPECIFIC DETAILS RELATING TO YOUR
 SPECIFIC WALLS THAT SEPARATE YOUR OCCUPANCY AND THOSE
 ON EACH SIDE.
  
  
 S. THOMAS
 561-804-4728

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date   Cont ID  
Sent By sathomas Date 2018-08-30 Time 00:00 Rev Time  
Received By   Date 2018-08-30 Time 00:00 Sent To E
Notes
2018-08-30 15:13:10INCLUDE EXISTING FIRE ALARM SYSTEM DRAWINGS TO BE
 REMOVED AS THIS BUILDING CURRENTLY HAS A FULL FIRE
 ALARM SYSTEM INSTALLED.
  
 S. THOMAS
 561-804-4728

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-12-11 Cont ID  
Sent By hmoser Date 2018-12-11 Time 14:05 Rev Time 0.00
Received By hmoser Date 2018-11-28 Time 14:16 Sent To  
Notes
2018-11-29 14:17:10RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-10-24 Cont ID  
Sent By hmoser Date 2018-10-24 Time 10:49 Rev Time 0.00
Received By hmoser Date 2018-10-17 Time 15:42 Sent To  
Notes
2018-10-18 15:42:16RESUB ROUTED TO FIRE INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-09-20 Cont ID  
Sent By hmoser Date 2018-09-20 Time 15:03 Rev Time 0.00
Received By hmoser Date 2018-08-21 Time 10:41 Sent To  
Notes
2018-08-22 10:42:06ROUTED TO FIRE INBOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2018-12-11 Cont ID  
Sent By hmoser Date 2018-12-11 Time 14:04 Rev Time 0.00
Received By hmoser Date 2018-12-11 Time 13:54 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-10-24 Cont ID  
Sent By hmoser Date 2018-10-24 Time 10:43 Rev Time 0.00
Received By hmoser Date 2018-10-24 Time 09:05 Sent To I
Notes
2018-10-24 10:48:55PLAN DENIED
 REFER TO SECTION 602.2.1 WHERE REQUIRED
 INSTALL DUCT DETECTORS ON THE SUPPLY SIDE OF
 EQUIPMENT. 2017 FBC (M).
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805- 6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-09-20 Cont ID  
Sent By hmoser Date 2018-09-20 Time 15:03 Rev Time 0.00
Received By hmoser Date 2018-09-20 Time 15:01 Sent To I
Notes
2018-09-20 15:02:57PLAN DENIED
 SEE FIRE COMMENTS