Plan Review Stops For Permit 18081007 |
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2018-11-08 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2018-11-08 |
Time |
15:34 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2018-11-08 |
Time |
15:34 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2018-11-02 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2018-11-02 |
Time |
07:34 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2018-11-02 |
Time |
06:22 |
Sent To |
I |
|
Notes |
2018-11-02 07:34:16 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1. NO DISCONNECT ON PRIMARY OR SECONDARY SIDE OF NEW | | PROPOSED TRANSFORMER IN ROOM 121. PROVIDE CORRECTION | | 450.14 NEC | | | | 2. NEW PANELBOARD "RP" DOES NOT HAVE OVERCURRENT | | PROTECTION. PROVIDE CORRECTION 408.36 NEC | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | CODES IN EFFECT: | | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE 2017 6TH ED. | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | 6TH EDITION | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | V/R, | | | | FRANK GIAQUINTO III | | ELECTRICAL INSPECTOR | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | [email protected] | | CELL: 561-657-1653 | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2018-09-19 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2018-09-19 |
Time |
07:09 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2018-09-19 |
Time |
07:09 |
Sent To |
I |
|
Notes |
2018-09-19 07:09:07 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1. PROVIDE UL OR OTHER NRTL LISTING AND SPECS FOR ALL | | LIGHTING TO BE INSTALLED. 110.3B NEC | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | CODES IN EFFECT: | | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE 2017 6TH ED. | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | V/R, | | | | FRANK GIAQUINTO | | ELECTRICAL INSPECTOR | | ELECTRICAL PLANS EXAMINER | | CITY OF WPB | | [email protected] | | CELL: 561-657-1653 | | | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2018-11-08 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2018-11-08 |
Time |
15:34 |
Rev Time |
0.00 |
Received By |
jleahy |
Date |
2018-11-05 |
Time |
15:19 |
Sent To |
|
|
Notes |
2018-11-07 15:03:26 | TO LMARCHAN | 2018-11-06 15:19:13 | RESUB ROUTED TO ZONING INBOX |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2018-11-02 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2018-11-02 |
Time |
07:34 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2018-10-15 |
Time |
14:22 |
Sent To |
|
|
Notes |
2018-10-31 15:00:31 | TO LMARCHAN | 2018-10-16 14:22:25 | RESUB ROUTED TO ZONING INBOX |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2018-09-19 |
|
|
Cont ID |
|
Sent By |
fgiaquin |
Date |
2018-09-19 |
Time |
07:09 |
Rev Time |
0.00 |
Received By |
fgiaquin |
Date |
2018-08-21 |
Time |
14:29 |
Sent To |
|
|
Notes |
2018-08-22 14:29:32 | ROUTED TO ZONING INBOX |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
2018-11-07 |
|
|
Cont ID |
|
Sent By |
aaponte |
Date |
2018-11-07 |
Time |
15:02 |
Rev Time |
0.00 |
Received By |
aaponte |
Date |
2018-11-07 |
Time |
15:02 |
Sent To |
E |
|
Notes |
2018-11-07 15:03:12 | PROVISO: A MINIMUM 0.6 FOOTCANDLE SHALL BE PROVIDED AT | | THE CURB SIDE AT ONE FOOT ABOVE THE SIDEWALK GRADE | | LEVEL. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2018-10-31 |
|
|
Cont ID |
|
Sent By |
aaponte |
Date |
2018-10-31 |
Time |
14:59 |
Rev Time |
0.00 |
Received By |
aaponte |
Date |
2018-10-31 |
Time |
14:59 |
Sent To |
E |
|
Notes |
2018-10-31 15:00:15 | PROVISO: A MINIMUM 0.6 FOOTCANDLE SHALL BE PROVIDED AT | | THE CURB SIDE AT ONE FOOT ABOVE THE SIDEWALK GRADE | | LEVEL. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2018-09-17 |
|
|
Cont ID |
|
Sent By |
aaponte |
Date |
2018-09-17 |
Time |
15:40 |
Rev Time |
0.00 |
Received By |
aaponte |
Date |
2018-09-17 |
Time |
15:40 |
Sent To |
E |
|
Notes |
2018-09-17 15:41:17 | PROVISO: PERMTI SUBJECT TO FINAL APPROVAL OF | | STREETSCAPE AGREEMENT WITH THE CITY. DRAWINGS SHALL BE | | ADJUSTED TO REFLECT DRAWINGS APPROVED WITH AGREEMENT. |
|
|