Plan Review Details - Permit 18081007
Plan Review Stops For Permit 18081007
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-11-08 Cont ID  
Sent By jleahy Date 2018-11-08 Time 15:34 Rev Time 0.00
Received By jleahy Date 2018-11-08 Time 15:34 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-11-02 Cont ID  
Sent By fgiaquin Date 2018-11-02 Time 07:34 Rev Time 0.00
Received By fgiaquin Date 2018-11-02 Time 06:22 Sent To I
Notes
2018-11-02 07:34:16ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. NO DISCONNECT ON PRIMARY OR SECONDARY SIDE OF NEW
 PROPOSED TRANSFORMER IN ROOM 121. PROVIDE CORRECTION
 450.14 NEC
  
 2. NEW PANELBOARD "RP" DOES NOT HAVE OVERCURRENT
 PROTECTION. PROVIDE CORRECTION 408.36 NEC
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-09-19 Cont ID  
Sent By fgiaquin Date 2018-09-19 Time 07:09 Rev Time 0.00
Received By fgiaquin Date 2018-09-19 Time 07:09 Sent To I
Notes
2018-09-19 07:09:07ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE UL OR OTHER NRTL LISTING AND SPECS FOR ALL
 LIGHTING TO BE INSTALLED. 110.3B NEC
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WPB
 [email protected]
 CELL: 561-657-1653
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-11-08 Cont ID  
Sent By jleahy Date 2018-11-08 Time 15:34 Rev Time 0.00
Received By jleahy Date 2018-11-05 Time 15:19 Sent To  
Notes
2018-11-07 15:03:26TO LMARCHAN
2018-11-06 15:19:13RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-11-02 Cont ID  
Sent By fgiaquin Date 2018-11-02 Time 07:34 Rev Time 0.00
Received By fgiaquin Date 2018-10-15 Time 14:22 Sent To  
Notes
2018-10-31 15:00:31TO LMARCHAN
2018-10-16 14:22:25RESUB ROUTED TO ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-09-19 Cont ID  
Sent By fgiaquin Date 2018-09-19 Time 07:09 Rev Time 0.00
Received By fgiaquin Date 2018-08-21 Time 14:29 Sent To  
Notes
2018-08-22 14:29:32ROUTED TO ZONING INBOX

Review Stop Z ZONING
Rev No 3 Status P Date 2018-11-07 Cont ID  
Sent By aaponte Date 2018-11-07 Time 15:02 Rev Time 0.00
Received By aaponte Date 2018-11-07 Time 15:02 Sent To E
Notes
2018-11-07 15:03:12PROVISO: A MINIMUM 0.6 FOOTCANDLE SHALL BE PROVIDED AT
 THE CURB SIDE AT ONE FOOT ABOVE THE SIDEWALK GRADE
 LEVEL.

Review Stop Z ZONING
Rev No 2 Status P Date 2018-10-31 Cont ID  
Sent By aaponte Date 2018-10-31 Time 14:59 Rev Time 0.00
Received By aaponte Date 2018-10-31 Time 14:59 Sent To E
Notes
2018-10-31 15:00:15PROVISO: A MINIMUM 0.6 FOOTCANDLE SHALL BE PROVIDED AT
 THE CURB SIDE AT ONE FOOT ABOVE THE SIDEWALK GRADE
 LEVEL.

Review Stop Z ZONING
Rev No 1 Status P Date 2018-09-17 Cont ID  
Sent By aaponte Date 2018-09-17 Time 15:40 Rev Time 0.00
Received By aaponte Date 2018-09-17 Time 15:40 Sent To E
Notes
2018-09-17 15:41:17PROVISO: PERMTI SUBJECT TO FINAL APPROVAL OF
 STREETSCAPE AGREEMENT WITH THE CITY. DRAWINGS SHALL BE
 ADJUSTED TO REFLECT DRAWINGS APPROVED WITH AGREEMENT.