Plan Review Details - Permit 18080814
Plan Review Stops For Permit 18080814
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2018-11-14 Cont ID  
Sent By cthroop Date 2018-11-14 Time 15:56 Rev Time 0.00
Received By cthroop Date 2018-11-14 Time 15:56 Sent To  
Notes
2018-11-14 15:58:01DEFERRED SUBMITTALS - 1. POLY FOAM ADHESIVE. 2. PEEL
 AND STICK UNDERLAYMENT. 3. EXT. DOOR NOA'S.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2018-10-26 Cont ID  
Sent By cthroop Date 2018-10-26 Time 09:21 Rev Time 0.00
Received By cthroop Date 2018-10-26 Time 08:52 Sent To  
Notes
2018-10-26 09:25:38BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. OWNER AGENT TO SIGN ENERGY SUBMITTAL.
 FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402
 SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO
 DEMONSTRATE CODE COMPLIANCE BY THIS METHOD.
  
 _ OR _
  
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 2. PROVIDE PRODUCT APPROVALS FOR NEW DOORS.
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE DOOR SUBMITTALS.
  
 3. PALM BEACH COUNTY IMPACT FEES.
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE
 PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURNED STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED AND MARK VOID.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2018-09-06 Cont ID  
Sent By cthroop Date 2018-09-06 Time 15:46 Rev Time 0.00
Received By cthroop Date 2018-09-06 Time 07:13 Sent To  
Notes
2018-09-06 16:08:11BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. ROOFING PERMIT REQUIRED.
  
 2. PALM BEACH COUNTY IMPACT FEES MAY BE REQUIRED.
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE
 PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURNED STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 3. PROVIDE SOILS REPORT PER DESIGNER OF RECORD.
 R401.4 SOIL TESTS.
 WHERE QUANTIFIABLE DATA CREATED BY ACCEPTED SOIL
 SCIENCE METHODOLOGIES INDICATE EXPANSIVE, COMPRESSIBLE,
 SHIFTING OR OTHER QUESTIONABLE SOIL CHARACTERISTICS ARE
 LIKELY TO BE PRESENT, THE BUILDING OFFICIAL SHALL
 DETERMINE WHETHER TO REQUIRE A SOIL TEST TO DETERMINE
 THE SOIL?S CHARACTERISTICS AT A PARTICULAR LOCATION.
 THIS TEST SHALL BE DONE BY AN APPROVED AGENCY USING AN
 APPROVED METHOD.
  
 4. PROVIDE PRODUCT APPROVALS FOR WINDOWS, DOORS AND
 ROOFING SYSTEM.
 FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE ROOFING, WINDOW AND DOOR
 SUBMITTALS.
  
 5. PROVIDE DESIGN WIND LOADS FOR ALL WINDOW AND DOOR
 OPENINGS. PROVIDE DESIGN PRESSURES FOR ROOF AREAS WITH
 FASTENER SCHEDULE.
 FBC 107.3.5.3 ? PROVIDE WIND DESIGN LOADS/DESIGN
 PRESSURES PURSUANT TO FBC-R301.2.
  
 R301.2.1 WIND DESIGN CRITERIA.
 BUILDINGS AND PORTIONS THEREOF SHALL BE CONSTRUCTED IN
 ACCORDANCE WITH THE WIND PROVISIONS OF THIS CODE USING
 THE BASIC WIND SPEED IN TABLE R301.2(1) AS DETERMINED
 FROM FIGURE R301.2(4). THE STRUCTURAL PROVISIONS OF
 THIS CODE FOR WIND LOADS ARE NOT PERMITTED WHERE WIND
 DESIGN IS REQUIRED AS SPECIFIED IN SECTION R301.2.1.1.
 WHERE DIFFERENT CONSTRUCTION METHODS AND STRUCTURAL
 MATERIALS ARE USED FOR VARIOUS PORTIONS OF A BUILDING,
 THE APPLICABLE REQUIREMENTS OF THIS SECTION FOR EACH
 PORTION SHALL APPLY. WHERE NOT OTHERWISE SPECIFIED, THE
 WIND LOADS LISTED IN TABLE R301.2(2) ADJUSTED FOR
 HEIGHT AND EXPOSURE USING TABLE R301.2(3) SHALL BE USED
 TO DETERMINE DESIGN LOAD PERFORMANCE REQUIREMENTS FOR
 WALL COVERINGS, CURTAIN WALLS, ROOF COVERINGS, EXTERIOR
 WINDOWS, SKYLIGHTS AND EXTERIOR DOORS (OTHER THAN
 GARAGE DOORS).
  
 6. OWNER AGENT TO SIGN ENERGY SUBMITTAL.
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 7. ALL DOCUMENTS SHALL BE SUBMITTED IN DUPLICATE.
 FBC107.1 GENERAL. SUBMITTAL DOCUMENTS CONSISTING OF
 CONSTRUCTION DOCUMENTS, STATEMENT OF SPECIAL
 INSPECTIONS, GEOTECHNICAL REPORT AND OTHER DATA SHALL
 BE SUBMITTED IN TWO OR MORE SETS WITH EACH PERMIT
 APPLICATION.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED AND MARK VOID.
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2018-11-14 Cont ID  
Sent By jpearson Date 2018-11-14 Time 15:30 Rev Time 0.00
Received By jpearson Date 2018-11-14 Time 15:30 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2018-10-15 Cont ID  
Sent By jpearson Date 2018-10-15 Time 11:01 Rev Time 0.00
Received By jpearson Date 2018-10-15 Time 07:12 Sent To  
Notes
2018-10-15 11:01:50CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. CORRECTED.
 3. CORRECTED.
 4. FEEDERS THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A
 DISCONNECTING MEANS AT THE BUILDING OR SEPARATE
 STRUCTURE SUPPLIED. PROVIDE EITHER A MAIN DISCONNECT OR
 MAIN BREAKER AT THE PANEL FOR PANEL C. NEC 225.31,
 225.32 (RISER DIAGRAM SHOWS THE REQUIRED DISCONNECT,
 BUT THE ELECTRICAL PLAN DOES NOT. PROVIDE LOCATION OF
 DISCONNECT TO CONFIRM CLEARANCES. NEC 110.26; WPB FBC
 107.2.1)
 5. BE ADVISED THAT THE GENERATOR IS NOT INCLUDED IN THE
 SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE
 INDICATING THE REQUIRED SEPARATE PERMITS AND PLAN
 SUBMITTALS FOR THIS. WPB FBC 105.1, 107.2.1 (NOTE NOT
 PROVIDED.)
 6. AFCI PROTECTION SHOWN IN NOT CODE COMPLIANT. ALL
 BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15-
 AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND
 POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH
 AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8, 210.12; FBC RE E3902 (STILL NOT COMPLIANT. THE
 NOTE PROVIDED STATES THAT RECEPTACLES SHALL BE AFCI
 PROTECTED. IT IS NOT JUST THE RECEPTACLES THAT REQUIRE
 AFCI PROTECTION. SEE NOTE ABOVE.)
 7. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS SPECIFIED IN THE FBC RESIDENTIAL EDITION. SEE
 CODE FOR PROPER FORMAT AND ALLOWABLE DEMAND FACTORS.
 NEC 220; FBC RE E3602.2 (LOAD PROVIDED NOT CORRECT.
 ONLY THE PORTION OVER 10,000 VA IS PERMITTED TO USE THE
 DEMAND FACTOR OF 40%. ADDITIONALLY, A LOAD CALCULATION
 FOR THE MAIN SERVICE IS REQUIRED TO CONFIRM THE SIZE
 SPECIFIED IS SUFFICIENT, SEE NOTE 9.)
 8. PROVIDE RISER DIAGRAM FROM MAIN HOUSE WHERE POWER
 WILL BE FED FROM, SHOWING ALL DETAILS OF SERVICE
 EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, WIRE AND
 BREAKER SIZES FOR SERVICE AND FEED TO ANY SUB-PANEL(S).
 SHOW GEC SIZE AND SYSTEM, SHOW INTERSYSTEM BONDING
 TERMINATION POINT. NEC 215.5, 230, 250.50, 250.94,
 408.30; FBC RE E3706.1, E3608.1, E3609.3; WPB FBC
 107.2.1 (RISER PROVIDED IS NOT CODE COMPLIANT. RISER
 SHOWS A 1 1/4 NIPPLE WITH THREE 4/0 WIRES FEEDING THE
 100 AMP MAIN BREAKER. THIS CONDUIT IS NOT SIZED
 APPROPRIATELY FOR THE WIRE SPECIFIED. PROVIDE
 CORRECTION. NEC ANNEX C.)
 9. PROVIDE LOAD CALCULATION FOR EXISTING SERVICE,
 INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF
 SERVICE IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE
 E3602.2 (NOT PROVIDED.)
 10. CORRECTED.
 11. CORRECTED.
 12. CORRECTED.
  
 NEW COMMENTS:
  
 13. PLAN SHOWS A NEW SERVICE. PROVIDE AVAILABLE SHORT
 CIRCUIT CALCULATION FOR EACH PANEL INCLUDING
 INFORMATION FROM THE POWER COMPANY STATING WHAT THE
 AVAILABLE SHORT CIRCUIT CURRENT IS FOR THE SERVICE TO
 CONFIRM THE STATED AIC RATING OF THE SERVICE EQUIPMENT
 AND DOWNSTREAM PANELS IS ADEQUATE. NEC 110.9, 110.10;
 FBC RE E3606.3
 14. PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANEL.
 NEC 110.3, 110.9; FBC RE E3603.3
 15. GENERATOR TRANSFER SWITCH IS SHOWN BEHIND THE
 GENERATOR. PROVIDE CORRECTION FOR CLEARANCE. NEC
 110.26; FBC RE E3405.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD
 SHEETS?.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2018-08-29 Cont ID  
Sent By jpearson Date 2018-08-29 Time 15:42 Rev Time 0.00
Received By jpearson Date 2018-08-29 Time 06:42 Sent To  
Notes
2018-08-29 15:42:30CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ONLY ONE SERVICE PER RESIDENTIAL ADDRESS IS
 PERMITTED. PROVIDE CORRECTION. WPB FBC 107.2.1; NEC
 230.2; FBC RE E3601.2
 2. A BUILDING OR OTHER STRUCTURE THAT IS SERVED BY A
 BRANCH CIRCUIT OR FEEDER ON THE LOAD SIDE OF A SERVICE
 DISCONNECTING MEANS SHALL BE SUPPLIED BY ONLY ONE
 FEEDER OR BRANCH CIRCUIT. NEC 225.30
 3. PROVIDE GROUNDING ELECTRODE SYSTEM AS REQUIRED FOR A
 BUILDING OR STRUCTURE SUPPLIED BY A FEEDER OR BRANCH
 CIRCUIT. NEC 250.32; FBC RE3607.3
 4. FEEDERS THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A
 DISCONNECTING MEANS AT THE BUILDING OR SEPARATE
 STRUCTURE SUPPLIED. PROVIDE EITHER A MAIN DISCONNECT OR
 MAIN BREAKER AT THE PANEL FOR PANEL. NEC 225.31, 225.32
 5. BE ADVISED THAT THE GENERATOR IS NOT INCLUDED IN THE
 SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE
 INDICATING THE REQUIRED SEPARATE PERMITS AND PLAN
 SUBMITTALS FOR THIS. WPB FBC 105.1, 107.2.1
 6. AFCI PROTECTION SHOWN IN NOT CODE COMPLIANT. ALL
 BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15-
 AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND
 POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH
 AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8, 210.12; FBC RE E3902
 7. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL
 LOADS SPECIFIED IN THE FBC RESIDENTIAL EDITION. SEE
 CODE FOR PROPER FORMAT AND ALLOWABLE DEMAND FACTORS.
 NEC 220; FBC RE E3602.2
 8. PROVIDE RISER DIAGRAM FROM MAIN HOUSE WHERE POWER
 WILL BE FED FROM, SHOWING ALL DETAILS OF SERVICE
 EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, WIRE AND
 BREAKER SIZES FOR SERVICE AND FEED TO ANY SUB-PANEL(S).
 SHOW GEC SIZE AND SYSTEM, SHOW INTERSYSTEM BONDING
 TERMINATION POINT. NEC 215.5, 230, 250.50, 250.94,
 408.30; FBC RE E3706.1, E3608.1, E3609.3; WPB FBC
 107.2.1
 9. PROVIDE LOAD CALCULATION FOR EXISTING SERVICE,
 INCLUDE EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF
 SERVICE IS ADEQUATE. NEC 215.2, 220, 408.30; FBC RE
 E3602.2
 10. PROVIDE COMPLIANCE: A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS. A NOTE WILL SUFFICE.
 FBC EC C405.1, R404.1
 11. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12; FBC RE E4002.14
 12. PLAN SHOWS ONE SMALL APPLIANCE CIRCUIT FOR KITCHEN
 RECEPTACLE OUTLETS. A MINIMUM OF TWO 20 AMPERE BRANCH
 CIRCUIT SHALL BE PROVIDED TO SUPPLY KITCHEN COUNTERTOP
 RECEPTACLE OUTLET(S). PROVIDE CORRECTION. NEC
 210.11(C)(1) , FBC RE E3703.2
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD
 SHEETS?.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2018-10-23 Cont ID  
Sent By jesmith Date 2018-10-23 Time 15:43 Rev Time 0.00
Received By jesmith Date 2018-10-25 Time 08:00 Sent To  
Notes
2018-10-23 15:41:47PLAN SHEET E-1; A GAS TANKLESS WATER HEATER IS SHOWN ON
 THE PLAN.
 A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE
 REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK.
 PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT
 SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE
 SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL
 GAS SEC. 301.3.
 A SEPARATE PERMIT AND PLANS IS REQUIRED FOR THE GAS
 INSTALLATION OR MODIFICATION OF SYSTEM.
 IF THERE IS AN EXISTING SYSTEM, THE BTU LOAD OF THE
 EXISTING GAS SYSTEM MUST BE ADDED INTO THE TOTAL BTU
 LOAD ON THE SYSTEM TO ENSURE THE EXISTING SYSTEM IS
 PROPERLY SIZED. IF UNDERSIZED, THE EXISTING SYSTEM MUST
 BE REDONE TO ENSURE A SAFE OPERATING SYSTEM. SUBMIT A
 GAS PIPING RISER DIAGRAM THAT SHOWS THE TYPE OF
 EXISTING APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE
 PIPE SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND THE
 DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT
 OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD OF
 THE SECTION. NOTE: IF THE EXISTING SYSTEM IS LESS THAN
 A 2 PSI SYSTEM AND THE SYSTEM PRESSURE IS INCREASED TO
 2 PSI, A LINE PRESSURE REGULATOR IS REQUIRED AT ALL THE
 EXISTING APPLIANCES. FBCR SECS.G2412.4, G2412.8,
 G2413.1, G2413.2, G2413.3.

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2018-11-13 Cont ID  
Sent By fmittner Date 2018-11-13 Time 10:39 Rev Time 0.00
Received By fmittner Date 2018-11-13 Time 10:39 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2018-08-24 Cont ID  
Sent By fmittner Date 2018-08-24 Time 15:37 Rev Time 0.00
Received By fmittner Date 2018-08-24 Time 15:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2018-11-14 Cont ID  
Sent By skennedy Date 2018-11-14 Time 16:04 Rev Time 0.00
Received By skennedy Date 2018-11-14 Time 15:07 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2018-11-13 Cont ID  
Sent By cpuell Date 2018-11-13 Time 12:57 Rev Time 0.00
Received By cpuell Date 2018-10-09 Time 09:17 Sent To  
Notes
2018-10-18 11:18:47R30
2018-10-11 09:17:31LIBRARY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2018-09-11 Cont ID  
Sent By shill Date 2018-09-11 Time 14:36 Rev Time 0.00
Received By shill Date 2018-09-11 Time 14:36 Sent To  
Notes
2018-08-16 15:56:07R21

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2018-11-19 Cont ID  
Sent By skennedy Date 2018-11-19 Time 08:37 Rev Time 0.00
Received By skennedy Date 2018-11-14 Time 16:04 Sent To  
Notes
2018-11-19 08:40:30MU2018-038700-0000 $0.00 FEE
2018-11-14 16:04:30CHECKED OUT A SET TO RUSS.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2018-10-26 Cont ID  
Sent By cthroop Date 2018-10-26 Time 08:58 Rev Time 0.00
Received By cthroop Date 2018-10-26 Time 08:58 Sent To  
Notes
2018-10-26 08:59:47BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE
 PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE
 RETURNED STAMPED AND WITH A COPY OF THE RECEIPT AS
 APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE
 QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE
 FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD
 MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2018-11-14 Cont ID  
Sent By skennedy Date 2018-11-14 Time 16:03 Rev Time 0.00
Received By skennedy Date 2018-11-14 Time 16:03 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2018-10-15 Cont ID  
Sent By cmontell Date 2018-10-15 Time 12:59 Rev Time 0.00
Received By cmontell Date 2018-10-15 Time 12:57 Sent To  
Notes
2018-10-15 12:59:42MECH PLAN REVIEW FAIL
  
 1 - 107.2.1.3 QUALITY OF BUILDING PLANS.
 BUILDING PLANS SHALL BE DRAWN TO A MINIMUM 1/8
 INCH SCALE
  
 CHRIS MONTELLO
 561-805-6733
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-09-07 Cont ID  
Sent By cmontell Date 2018-09-07 Time 15:09 Rev Time 0.00
Received By cmontell Date 2018-09-07 Time 15:02 Sent To  
Notes
2018-09-07 15:08:52MECHANICAL PLAN REVIEW FAIL
  
 1 - NEED MECHANICAL PLANS PER. FBC. SEC. [A]107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 CHRIS MONTELLO
 561-805-6733
 [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2018-11-14 Cont ID  
Sent By skennedy Date 2018-11-14 Time 15:33 Rev Time 0.00
Received By skennedy Date 2018-11-14 Time 15:33 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2018-10-25 Cont ID  
Sent By jesmith Date 2018-10-25 Time 07:59 Rev Time 0.00
Received By jesmith Date 2018-10-25 Time 08:00 Sent To  
Notes
2018-10-25 07:59:232ND REVIEW:
 PLUMBING COMMENTS: APPROVED
  
 PROVISO
 1. TUB/SHOWER CONTROL VALVE(S) SHALL BE ANTI-SCALD TYPE
 WITH HIGH TEMPERATURE LIMITING STOP. FBC RES P2708.4
 2. PROVIDE WATER HAMMER ARRESTORS AT WATER SUPPLY TO
 ICE LINE. FBC RES P2903.5
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715

Review Stop P PLUMBING
Rev No 1 Status F Date 2018-09-11 Cont ID  
Sent By shill Date 2018-09-11 Time 14:34 Rev Time 0.00
Received By jesmith Date 2018-09-11 Time 14:15 Sent To  
Notes
2018-09-11 14:34:081ST REVIEW: FBC 2017 6TH EDITION
 PERMIT 180814
 PLUMBING COMMENTS:
  
 1. RE: PLAN SHEET E-1; SHOW TRAP ON ALL UNDERFLOOR
 FIXTURE DRAINS, IE. BATHTUBS AND SHOWERS, UNLESS
 FIXTURE IS INTEGRALLY TRAPPED, IE. WATER CLOSETS. FBC
 WPB AMEND 107.2.1, FBC RES P3201.2B. CIRCLE SYMBOLS AT
 END OF HORIZONTAL PIPING FOR WATER CLOSETS ARE
 CONFUSING. PROVIDE VERTICAL EXTENSION AT END OF WATER
 CLOSET HORIZONTAL AND PLACE OVAL SYMBOL AT TOP PER FBC
 WPB AMEND 107.2.1.
 2. RE: PLAN SHEET E-1; SHOWS SHOWER AND WATER CLOSET
 FIXTURE DRAINS SHOWN CONNECTING TO EACH OTHER BEFORE
 CONNECTING TO(WET)VENT. MUST CONNECT INDEPENDENTLY TO
 VENT FBC RES 3108.1; FIXTURE DRAIN LENGTH TRAP TO VENT
 TO BE IN ACCORDANCE WITH FBC RES TABLE P3105.1.
 3. ADD PLUMBING NOTE: SHOWER CONTROL VALVE(S) SHALL BE
 PRESSURE BALANCED PB,THERMOSTATIC MIXING (TM) OR
 COMBINATION PB/TM VALVE TYPES WITH HIGH TEMPERATURE
 LIMITING STOP. 2017 FBC RES 2708.4
 4. RE: PLAN SHEET E-1; A GAS TANKLESS WATER HEATER IS
 SHOWN ON THE PLAN.
 A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL
 PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT
 THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE
 REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK.
 PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT
 SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE
 SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL
 GAS SEC. 301.3.
 A SEPARATE PERMIT AND PLANS IS REQUIRED FOR THE GAS
 INSTALLATION OR MODIFICATION OF SYSTEM.
 IF THERE IS AN EXISTING SYSTEM, THE BTU LOAD OF THE
 EXISTING GAS SYSTEM MUST BE ADDED INTO THE TOTAL BTU
 LOAD ON THE SYSTEM TO ENSURE THE EXISTING SYSTEM IS
 PROPERLY SIZED. IF UNDERSIZED, THE EXISTING SYSTEM MUST
 BE REDONE TO ENSURE A SAFE OPERATING SYSTEM. SUBMIT A
 GAS PIPING RISER DIAGRAM THAT SHOWS THE TYPE OF
 EXISTING APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE
 PIPE SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND THE
 DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT
 OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD OF
 THE SECTION. NOTE: IF THE EXISTING SYSTEM IS LESS THAN
 A 2 PSI SYSTEM AND THE SYSTEM PRESSURE IS INCREASED TO
 2 PSI, A LINE PRESSURE REGULATOR IS REQUIRED AT ALL THE
 EXISTING APPLIANCES. FBCR SECS.G2412.4, G2412.8,
 G2413.1, G2413.2, G2413.3.
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6715

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2018-10-26 Cont ID  
Sent By cthroop Date 2018-10-26 Time 09:00 Rev Time 0.00
Received By cthroop Date 2018-10-26 Time 09:00 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2018-11-13 Cont ID  
Sent By fmittner Date 2018-11-13 Time 10:39 Rev Time 0.00
Received By fmittner Date 2018-11-13 Time 10:39 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2018-08-24 Cont ID  
Sent By fmittner Date 2018-08-24 Time 15:37 Rev Time 0.00
Received By fmittner Date 2018-08-24 Time 15:37 Sent To  
Notes
***NONE***