Plan Review Details - Permit 18080642
Plan Review Stops For Permit 18080642
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2018-08-24 Cont ID  
Sent By jleahy Date 2018-08-24 Time 07:43 Rev Time 0.00
Received By jleahy Date 2018-08-24 Time 07:42 Sent To M
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2018-08-24 Time   Rev Time 0.00
Received By lmarchan Date 2018-08-13 Time 10:17 Sent To  
Notes
2018-08-15 10:17:44REVISION ROUTED TO JLEAHY

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2018-08-30 Cont ID  
Sent By skennedy Date 2018-08-30 Time 12:42 Rev Time 0.00
Received By skennedy Date 2018-08-30 Time 12:42 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2018-08-24 Cont ID  
Sent By ccole Date 2018-08-24 Time 16:59 Rev Time 0.00
Received By ccole Date 2018-08-24 Time 16:58 Sent To I
Notes
2018-08-24 17:04:461ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17100726
 REVISION #18080642
 8/24/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) RETURN TRANSFER DUCTS SHALL BE SIZED 1-1/2 TIMES THE
 CROSS-SECTIONAL ARE OF THE SUPPLY DUCT ENTERING THE
 ROOM OR SPACE IT IS SERVING- SECTION M1602.4 (1)
 RESIDENTIAL.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  